1MRS 750404-MBG
Issued: April 1999
Status: Updated
Version: B/8.11.2001
Data subject to change without notice
Features • Two-stage residual overvoltage relay mod- • The undervoltage stage U< can be given
ule containing a low-set residual overvolt- definite time characteristic or inverse time
age stage U0> and a high-set residual characteristic while the undervoltage stage
overvoltage stage U0>> 3U<< has a definite time characteristic only
• Both residual overvoltage stages feature • Numerical display of setting values, cur-
definite time characteristic and wide setting rently measured values, fault values, oper-
ranges ate times, event messages, etc.
• Two-stage undervoltage relay module con- • Serial interface for connection of the relay
taining a higher undervoltage stage U< and to the serial bus and a substation level
a lower undervoltage stage 3U<< communication and reporting system and/
or a remote control system
• The three-phase undervoltage stage U<
starts if one or more of the phase-to-phase • High system reliability and availability
voltages fall below the set start level through integrated self-supervision system
with auto-diagnostic capabilities in the
• The three-phase undervoltage stage 3U<<
relay modules
starts if all three phase-to-phase voltages
fall below the set start level • Member of the SPACOM product family
and ABB’s Substation Automation system
• CE marking according to the EC directive
for EMC
Application The voltage relay SPAU 331 C is intended for The relay can also be used in other applica-
the supervision of the substation busbar volt- tions requiring undervoltage protection and
ages in distribution networks. The relay mea- residual voltage supervision, e.g. for the pro-
sures the phase-to-phase voltage and the tection of large motors.
residual voltage and provides three-phase
undervoltage protection and residual over-
voltage protection.
1
Voltage relay SPAU 331 C
1MRS 750404-MBG
Design The voltage relay forms an integrated protec- the relay can be connected to the fibre-optic
tion scheme which includes a residual over- SPA bus. The bus connection module type
voltage relay module, an undervoltage relay SPA-ZC 21 is powered from the host relay,
module and a disturbance recorder module. whereas the bus connection module SPA-
The relay is provided with one control input ZC 17 is provided with a built-in power unit,
for an external control signal such as a block- which can be fed from an external secured
ing signal. Further, the voltage relay is power source. The relay communicates with
equipped with six output relays for CB con- higher-level data acquisition and control sys-
trol, signalling, etc. tems over the SPA bus.
2
Voltage relay SPAU 331 C
1MRS 750404-MBG
7DEOH2XWSXWFRQWDFWUDWLQJV
Type of contact Tripping Signalling
Terminals 65-66 67-68-69, 70-71-72,
73-74-75, 76-77-78,
79-80-81
Rated voltage 250 V ac/dc
Thermal withstand Carry continuously 5A 5A
capability Make and carry for 0.5 s 30 A 10 A
Make and carry for 3 s 15 A 8A
Breaking capacity for dc, 220 V dc 1A 0.15 A
when the control/ 110 V dc 3A 0.25 A
signalling circuit time
48 V dc 5A 1A
constant L/R ≤ 40 ms, at
the control voltages
Contact material AgCdO2
7DEOH&RQWUROLQSXWFRPPXQLFDWLRQDQGSRZHUVXSSO\
External control input Terminals 10-11
Control voltage level 18…265 V dc or
80…265 V ac
Power consumption when input activated 2…20 mA
Data communication Transmission mode Fibre optic serial bus
Data code ASCII
Selectable data transfer rates 300, 1200, 2400, 4800 or
9600 Bd
Fibre optic bus for plastic fibre cables SPA-ZC 21BB
connection module, for glass fibre cables SPA-ZC 21MM
powered from the host
relay
Fibre optic bus for plastic fibre cables SPA-ZC 17BB
connection module with for glass fibre cables SPA-ZC 17MM
a built-in power supply
unit
Auxiliary supply modules Power supply and I/O SPGU 240A1 80…265 V ac/dc
modules and voltage SPGU 48B2 18…80 V dc
ranges
Power consumption under quiescent ~10 W
conditions
under operating ~15 W
conditions
3
Voltage relay SPAU 331 C
1MRS 750404-MBG
7DEOH8QGHUYROWDJHUHOD\PRGXOH63&8&
Undervoltage stage Start voltage U< 0.4…1.2 × Un
U< Start time, preset values 0.1 s, 1 s, 5 s or 30
s
Operate time at definite time operation characteristic 0.1…10.0 s
Time multiplier k< at inverse time operation characteristic 0.1…1.00
Reset time, typically 80 ms
Drop-off/pick-up ratio, typically 1.03
Operation time accuracy at definite time ±2% of set value
characteristic and or ±25 ms
start time accuracy
at inverse time ±25 ms or the
characteristic inaccuracy
appearing when the
measured voltage
varies ±3%
Operation accuracy ±3% of set value
Undervoltage stage Start voltage 3U<< 0.1…1.2 × Un
3U<< Start time, preset values 0.1 s or 1.0 s
Operate time at definite time operation characteristic 0.1…10.0 s
Reset time, typically 80 ms
Drop-off/pick-up ratio, typically when the start ≤1.03
value of the 3U<<
stage ≥0.4
when the start approx. 1.1
value of the 3U<<
stage <0.4
Operation time accuracy and start time accuracy ±2% of set value
or ±25 ms
Operation accuracy ±3% of set value
4
Voltage relay SPAU 331 C
1MRS 750404-MBG
7DEOH'DWDFRPPXQLFDWLRQ
Transmission mode Fibre-optic serial bus
Data code ASCII
Data transfer rate, selectable 4800 or 9600 Bd
Electrical/optical bus connection module powered for plastic core cables SPA-ZC 21BB
from the host relay for glass fibre cables SPA-ZC 21MM
Electrical/optical bus connection module powered for plastic core cables SPA-ZC 17BB
from the host relay or from an external power source for glass fibre cables SPA-ZC 17MM
7DEOH7HVWVDQGVWDQGDUGV
Test voltages Dielectric test voltage (IEC 255-5) 2.0 kV, 50 Hz, 1 min
Impulse test voltage (IEC 255-5) 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance (IEC 255-5) >100 MΩ, 500 V dc
Interference tests High-frequency (1 MHz) 2.5 kV
disturbance test (IEC 255-22-1),
common mode
High-frequency (1 MHz) 1.0 kV
disturbance test (IEC 255-22-1),
differential mode
Fast transients (IEC 255-22-4, 4 kV, 5/50 ns
class III and IEC 801-4, level 4),
power supply inputs
Fast transients (IEC 255-22-4, 2 kV, 5/50 ns
class III and IEC 801-4, level 4),
other inputs
Electrostatic discharge 8 kV
(IEC 255-22-2 and IEC 801-2,
class III), air discharge
Electrostatic discharge 6 kV
(IEC 255-22-2 and IEC 801-2,
class III), contact discharge
RF electromagnetic field test (IEC 10 V/m, f = 80…1000 MHz
1000-4-3 and ENV 50140)
Conducted RF disturbance test 10 V, f = 150 kHz…80 MHz
(IEC 1000-4-6 and ENV 50141)
Environmental conditions Service temperature range -10…+55°C
Transport and storage -40…+70°C
temperature range (IEC 68-2-8)
Damp heat test (IEC 68-2-30) <95%, +55°C, 6 cycles
Degree of protection by enclosure IP 54
when panel mounted
Weight ~5.5 kg
5
Voltage relay SPAU 331 C
1MRS 750404-MBG
Block diagram L1
L2
L3
A
dn
da
R Tx
SPA-
+(~)
U
- - (~) aux
63
13
14
15
16
17
18
19
20
21
28
29
30
10
11
61
62
70
71
72
79
80
81
76
77
78
73
74
75
67
68
69
65
66
100 V
100 V
100 V
100 V
110 V
110 V
110 V
110 V
~
F E D C B A
+ -
1 1 1 1
U5
U6
U1 IRF SGR 8 7 5 6 1 2 3 4
U >
BS1 0 TS1
U >>
BS1 0 TS2
I/O
U2 IRF SS1
U<
TS1
SS2
BS1 3U<< TS2
I/O
U3
SPAU 331 C1 U4
spau331blc
6
Voltage relay SPAU 331 C
1MRS 750404-MBG
139 ±1
Panel
162
136
cut-out
dim300
Semi-flush mounting
a b
Raising frame a b
SPA-ZX 301 219 74
SPA-ZX 302 179 114
SPA-ZX 303 139 154
SFM300_1
SPA-ZX304 SPA-ZX306
SPA-ZX305 SPA-ZX307
SPA-ZX201 SPA-ZX317
SPA-ZX318
+0,4 242 306
482,6 –0 (19")
197
ø6
177 –0 (4U)
101,6
7
+0,4
312
292
6
197 98
21,5
304_5_6
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
7
Voltage relay SPAU 331 C
1MRS 750404-MBG
Ordering :KHQRUGHULQJSOHDVHVSHFLI\
Ordering information Ordering example
1. Type designation and quantity SPAU 331 C, 5 pieces
2. Order number RS 613 031-AA
3. Rated values Un=110 V, fn =50 Hz
4. Auxiliary voltage Uaux=110 V dc
5. Accessories -
6. Special requirements -
2UGHUQXPEHUV
Voltage relays SPAU 331 C_
SPAU 331 C1, incl. modules SPCU 1C6 and RS 613 031-AA, CA, DA, FA
SPCU 3C15
SPAU 331 C5, incl. module SPCU 3C15 RS 613 035-AA, CA, DA, FA
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/d
rated frequency fn and the auxiliary voltage Uaux of CA equals fn = 50 Hz and Uaux = 18…80 V dc
the relay as follows:
DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc
References $GGLWLRQDOLQIRUPDWLRQ
Colour brochure “Voltage relays SPAU 300 Series” 1MRS 750326-MDS EN
User’s manual and technical description “Voltage 1MRS 750123-MUM EN
relay SPAU 331 C”
ABB Oy
P.O. Box 699
FIN-65101 Vaasa, Finland
Tel +358 10 224 000
Fax +358 10 224 1094
www.abb.com/substationautomation