SPAF 140 and SPAF 340

Frequency relays
Frequency Relays
Type SPAF 140 and SPAF 340
Features Application
• Overfrequency and underfrequency relay The frequency relay SPAF 140 is designed to
with four frequency stages be used for protecting generators and other
• Operation based on either the positive or the AC equipment against overfrequency and
negative rate of change of frequency (df/dt). underfrequency. The operation of the relay can
Can be used independently or in combina- be based on set frequency values, on the rate of
tion with a set frequency value. change of frequency, or on a combination of
these two. In generator protection applications
• Each frequency stage can be given two
the relay protects the generator and the prime
separate time delays; outputs for connection
mover against hazardous overspeeding and/or
to various output relays.
underspeeding. The relay can also be used for
• Selectable undervoltage blocking level the protection of large synchronous motors in
• Selectable rated frequency of the relay networks where automatic network restoration
• The protection stages can be blocked sepa- is used. The relay isolates the motor from the
rately via external blocking inputs network in the event of an outage, averting
• SPAF 140 includes four binary blocking dangerous unsynchronized connection.
inputs plus three relay outputs, two of which The frequency relay SPAF 340 is specially
heavy-duty type, to be configured by the adapted for load shedding in situations where
customer power consumption exceeds power capacity in
the network. In such a situation of unbalance,
• SPAF 340 includes five binary blocking the network frequency starts declining. The
inputs and eight output relays for customer SPAF 340 relay can control four circuit
needs. Four output relays can be used for breakers, allowing four feeders to be discon-
circuit breaker control. nected from the network, one by one. Should
• Flexible configuration of blocking inputs, the power deficiency still persist, the relay
protection stages and output relays through disconnects the plant for island operation.
programmable switch matrices The operation of the relay can be based on set
• Recovery function with adjustable time delay frequency values (f<), on the rate of decrease of
for the start of network restoration frequency (negative df/dt), or on both criteria
• Serial communication enabling connection (f< and df/dt ). In addition, output of each
to remote control systems, parametrization stage can be obtained via two separate time
via a PC, and reading of registers and meas- circuits and so eight different frequency/time
ured values combinations are available. Should the net-
work frequency drop rapidly, this feature
• High system reliability due to continuous
allows fast disconnection of different loads.
self-supervision
The frequency relays type SPAF 140 and
• High immunity to electrical and SPAF 340 are members of the SPACOM
electromagnetical interference; robust product family and part of the PYRAMID®
aluminium case for IP 54 installation. concept.
• CE marking according to the EC directive
for EMC.
Q1

N Q2 Q3 Q4 Q5 Q6

n
Connection Diagram

d
a d

Essential load
Rx Tx
SPA-ZC_

+ (~)
Uaux
- (~) Alarm Open Q2 Open Q3 Open Q4 Open Q5
SERIAL
BS3 BS4 BS5 BS2 BS1 IRF SS1 TS1 SS2 TS2 SS3 TS3 SS4 TS4 PORT
(SPA)

X0 63 13 14 16 17 19 20 1 2 3 4 5 6 7 8 9 28 29 25 26 27 X1 10 9 8 7 6 5 4 3 2 1 X0 62 61 X2 14 15 16 X2 12 13 X2 3 4 X2 9 10 11 X2 1 2 X2 7 8 X1 15 16 X2 5 6 X1 11 12 13 14

+ + + + + + + + +

5A
5A
5A
5A

1A
1A
1A
1A

100V
100V
100V
100V
~
_

U5 + -

U1 IRF
SS1
TS1
4 SS2
TS2
f SS3
TS3
SS4
TS4
4 I/O
BS1
BS2 df/dt
BS5
BS4
BS3

connection diagram for the

in load shedding application


Simplified block diagram and

frequency relay SPAF 340 C3


Connection Diagram

0
A
+
N
1

+
n
-
d
a d
1 0

- Rx Tx

SPA-ZC_
+ (~)
Uaux
- (~)

BS4 BS3 BS2 BS1 SERIAL


IRF SS1 TS1 TS2 PORT
(SPA)
+

48 47 46 45 23 22 11 10 62 61 70 71 72 68 69 85 86 87 88
X0 63 13 14 16
100 V

Used

+ + + +
Not

~
_

U3 U2 + -

U1 IRF
SS1
TS1
4 SS2
TS2
f SS3
TS3
SS4
TS4
4 I/O
BS1
BS2 df/dt
BS3
BS4
BS5
Simplified block diagram and
connection diagram for the
frequency relay SPAF 140 C

Technical Data
Energizing inputs Output contacts
Voltage inputs Trip contacts
Rated voltage Un 100 V, 110 V,115 V Rated voltage 250 V ac/dc
or 120 V Continuous current carrying
Continuous voltage withstand 200 V capacity 5A
Rated burden of voltage Make and carry for 0.5 s 30 A
input at Un <0.5 VA Make and carry for 3 s 15 A
Rated frequency fn, Breaking capacity for dc
programmable 30 ... 65 Hz when the control circuit time
constant L/R _40 ms at the
Current inputs* control voltage levels
Rated current In 0.2 A 1A 5A - 48 V dc 5A
Thermal current - 110 V dc 3A
withstand - 220 V dc 1A
- continuously 1.5 A 4A 20 A Contact material AgCdO2
- for 10 s 5A 25 A 100 A
- for 1 s 20 A 100 A 500 A Signalling contacts
Dynamic current Rated voltage 250 V ac/dc
withstand Continuous current carrying
- half-wave value 50 A 250 A 1250 A capacity 5A
Input impedance <750 mΩ <100 mΩ <20 mΩ Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc
when the control circuit time
constant L/R _40 ms at the
control voltage levels
- 48 V dc 1A
- 110 V dc 0.25 A
- 220 V dc 0.15 A
Contact material AgCdO2
External control inputs Environmental conditions
Operative control Service temperature range -10...+55°C
voltage range 18...250 V dc or Transport and storage
80...250 V ac temperature range according
Current drain of activated to IEC 68-2-8 -40...+70°C
control input 2...20 mA Damp heat test,
cyclic (12 h + 12 h)
Auxiliary power supply *) according to IEC 68-2-30 +25°C/+55°C
Power module SPGU 240A1 RH = 93%, 6 cycles
- rated voltages Un = 110/120/230/ Degree of protection by
240 V ac enclosure of flush mounting
Un = 110/125/220 V dc relay case IP 54
- operative voltage range 80...265 V ac/dc Weight of fully equipped relay
including flush mounting
Power module SPGU 48B2 relay case *) ~6 kg
- rated voltages Un = 24/48/60 V dc Weight of fully equipped relay
- operative voltage range 18...80 V dc including flush mounting
Power consumption, quies- relay case **) ~3,5 kg
cent/operation conditions ~10 W/~15 W
*) Concerning only SPAF 340 C3
Power supply and output relay module **) **) Concerning only SPAF 140 C
Supply and output relay module SPTU 240R4
- rated voltages Un = 110/120/230/
240 V ac
Un = 110/125/220 V dc RELAY MODULE DATA
- operative voltage range 80...265 V ac/dc Combined frequency and rate of change of frequency
Supply and output relay module SPTU 48R4 module SPCF 1D15
- rated voltages Un = 24/48/60 V dc Four protection stages, which include over- and
- operative voltage range 18...80 V dc underfrequency function, rate of change of frequency
Power consumption, quies- function and two timer functions.
cent/operation conditions ~4 W/~6 W
f function
Data communication Rated frequency 30.00 ... 65.00 Hz
Transmission mode Fibre-optic serial bus Setting range 25.00 ... 70.00 Hz
Coding ASCII Measuring range 20.00 ... 75.00 Hz
Data transfer rate, selectable 4800 or 9600 Bd Frequency measuring time 3 ... 20 periods
Electrical/optical bus (programmable)
connection module powered Drop-off hysteresis 20 mHz
from the host relay Operation accuracy
- for plastic core cables SPA-ZC 21BB - for SPAF 140 C ±20 mHz
- for glass fibre cables SPA-ZC 21MM - for SPAF 340 C3 ±10 mHz
Electrical/optical bus Minimum measuring voltage 0.25 x Un
connection module powered
from the host relay or from df/dt function
an external power source Setting range 0.2 ... ±10.0 Hz/s
- for plastic core cables SPA-ZC 17BB (step 0.1 Hz/s)
- for glass fibre cables SPA-ZC 17MM Operation accuracy ±150 mHz/s
Minimum measuring voltage 0.25 x Un
Test voltages
Timer function
Dielectric test voltage Operation time delay
according to IEC 255-5 2.0 kV, 50 Hz, 1 min setting range *) 0.10 ... 120.00 s
Impulse test voltage - the minimum time is
according to IEC 255-5 5 kV, 1.2/50 µs, 0.5 J depending on the frequency
Insulation resistance measuring time
according to IEC 255-5 >100 MΩ, 500 V dc Operation time accuracy ±1% or ±30 ms
Disturbance tests Undervoltage blocking
High-frequency (1MHz) Setting range 0.30 ... 0.90 x Un
disturbance test according Measuring range 0.0 ... 1.4 x Un
to IEC 255-22-1, class III Operation accuracy ±3% of the set value
- common mode 2.5 kV (in the range 25…70 Hz)
- differential mode 1.0 kV
Fast transients according to Recovery function
IEC 255-22-4, class III and Setting range for frequency 0.1 ... 10.0 Hz
IEC 801-4, level 4 difference from the nominal
- power supply inputs 4 kV, 5/50 ns frequency
- other inputs 2 kV, 5/50 ns Time delay setting range 1 s ... 120 min 59 s
Electrostatic discharge test Operation time accuracy ±1% or ±30 ms
according to IEC 255-22-2
and IEC 801-2, class III *) The minimum operation time depends on the rated
- air discharge 8 kV frequency and the number of cycles to be used in the
- contact discharge 6 kV frequency measurement.
Mounting and Dimensions for SPAF 140 C

Flush mounting relay case (dimensions in millimetres)


250 142
216 34 129 ±1
30 186

162

139 ±1
136

Panel cut-out

Semi-flush mounting
a b

Raising frame a b
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154

Mounting in 19 inch cabinets and frames Projecting mounting


An ancillary mounting plate, height 4U (~177 mm), is When projecting mounting is preferred a relay case
recommended to be used when the protection relays type SPA-ZX 110 is used. The relay case for projecting
are to be mounted in 19 inch frames or cabinets. The mounting is provided with front connectors.
ancillary mounting plate type SPA-ZX 104 accommo-
dates three relays, type SPA-ZX 105 two relays and
type SPA-ZX 106 one relay.

+0,4
482,6 –0 (19") 263
158
115
10

ø6
177 –0 (4U)
101,6

+0,4
7
21,5

312
292

SPA-ZX 104
+0,4
482,6 –0 (19")

6
177 –0 (4U)

115 98
101,6

+0,4
7
21,5

SPA-ZX 106
Mounting and Dimensions for SPAF 340 C3

Flush mounting relay case (dimensions in millimetres)


293
226
259 34 214 ±1
30 229

139 ±1
162
Panel cut-out
136

Semi-flush mounting
a b

Raising frame a b
SPA-ZX 301 219 74
SPA-ZX 302 179 114
SPA-ZX 303 139 154

Mounting in 19 inch cabinets and frames Projecting mounting


An ancillary mounting plate, height 4U (~177 mm), is When projecting mounting is preferred a relay case
recommended to be used when the protection relays type SPA-ZX 317 is used. The relay case for projecting
are to be mounted in 19 inch frames or cabinets. The mounting is provided with front connectors.
ancillary mounting plate type SPA-ZX 304 accommo-
dates two size 300 relays and type SPA-ZX 305 one size
300 relay.

+0,4
482,6 –0 (19") 242 306
197
ø6
177 –0 (4U)
+0,4
101,6

7
21,5

312
292

SPA-ZX 304
+0,4
482,6 –0 (19")
6

197 98
177 –0 (4U)
101,6

+0,4
7
21,5

SPA-ZX 305
1MRS750183-MDS EN 10.2000

ABB Substation Automation Oy


P.O.Box 699
FIN-65101 VAASAFinland
Tel. +358 10 224 000
Fax. +358 10 224 1094
http://www.abb.fi