You are on page 1of 1

Sensors:

Sensors providing a pulse width modulated output shall be utilized for oil
pressure, coolant temperature sensing and shall be protected against a fault
to battery. The usable output range of the sensor shall be limited to 5% to
95% duty cycle. Output outside the usable range shall be diagnosed as a fault
condition and appropriate diagnostic shall be provided. Separate speed
sensing signals shall be provided for overspeed protection and electronic
governor.

BATTERY CHARGER
A. A dual rate 10 ampere battery charger shall be provided which shall accept
120 volt AC single phase input to provide 24 volt DC output. It
shall be fused on the AC input and DC output, incorporate current limiting
circuitry, and include a DC ammeter and voltmeter. The use of a crank
disconnect relay to protect the charger during starting is not acceptable. The
charger shall be housed in a NEMA 1 enclosure vibration suitable for wall
mounting.

B. The charger shall include LED annunciation for low battery voltage, high
battery voltage, battery charger malfunction, and AC failure; and dry contacts
for battery charger malfunction and low battery voltage.