Test certificate of seismic withstand capability

Seismic qualified

Eaton Corporation’s equipment identified below was As required by the codes, the equipment demonstrated
tested for seismic withstand capability and tested in its ability to function after the seismic tests. The seismic
accordance with the combined requirements specified capability of the equipment exceeds the worst-case
in the International Building Code, the California Building required levels, as illustrated in the figure below.
Code, and the Uniform Building Code.

Pow-R-LineT 5P Switchboards

Period (seconds)
.31 .25 .20 .16 .13 .10 .08 .06 .05 .04 .03 0
3.5
The frequency sweep
3.0
tests revealed that the
Damping = 5% lowest equipment natural
frequency is:
2.5

Response
2.0 4.5 Hz
Acceleration
(g)
Zero Period Acceleration

1.5

1.0
Eaton’s Equipment Capability
IBC 2009, CBC 2010
.5 UBC Zone 4 Requirement

0
3.2 4 5 6.4 8 10 13 17 20 26 32 Drawing Number
Frequency (Hz) 69A1006H01

Mostafa A. Ahmed For interpretation of testing data,


Westinghouse Electric Company, LLC 3RD PARTY TEST ENGINEER IN CHARGE refer to Eaton
Publication SA12501SE
TESTED BY
Wyle Laboratories
January 1998 – 46688-1

Eaton Corporation
Electrical Sector
1111 Superior Ave. Eaton is a registered trademark
Cleveland, OH 44114 © 2011 Eaton Corporation of Eaton Corporation.
United States All Rights Reserved
877-ETN-CARE (877-386-2273) Printed in USA All other trademarks are property
Eaton.com August 2011 of their respective owners.