Professional Documents
Culture Documents
Carga Latente - Trane - Ingles
Carga Latente - Trane - Ingles
2 ● Trane Engineers Newsletter volume 35–3 providing insights for today’s HVAC system designer
systems at part load. There are two conditions, while simultaneously without reheat, when all envelope
part-load conditions we should saving fan energy. conduction and solar loads are absent.
evaluate. One is quite obvious, which is
what happens when most of the How does CDQ fare with reduced Both cold air and CDQ systems
people leave. Perhaps the remaining occupancy? If the supply fan delivers a perform well at this part-load condition.
occupancy is only 40 people instead of constant volume of air, the reduced Single zone VAV results in a slightly
1200. This is an easy part-load sensible load requires the supply-air elevated space relative humidity, but
condition to accommodate. The temperature to increase to over 65°F. still well within the comfort zone. This
sensible loads drop to 256,000 Btu/hr However, the CDQ desiccant wheel comfortable condition is achieved
and the latent load due to people drops can still deliver the supply air at 55°F without reheat and uses less fan
to only 8000 Btu/hr. The resulting dew point (Figure 2). The resulting energy. Some reheat and additional fan
space sensible heat ratio increases to space humidity rises to only 52 percent energy may be needed if more precise
0.97. RH. Constant volume CDQ is certainly humidity control is desired.
adept at controlling space RH at lower
If we supply air at 50°F with the cold air occupancy, but the benefits of VAV can Each Situation Unique. Well, it was a
system, the required supply airflow is be applied to CDQ systems too. great concert, but this was a high
only 9400 cfm. This system is called school concert band, not a rock band.
"single zone VAV." Supply airflow is When Sensible Loads are Lighter. Add smoke from a pyrotechnic display,
reduced to match the reduced sensible There is another part-load condition or moisture from an Olympic size
cooling load in the space. Single zone that can be even more sinister; swimming pool, and designing a
VAV is easy to control. The supply fan reduced building-related sensible loads comfort system for "places of
airflow is modulated based on space while the space is fully occupied. What assembly" can be even more
temperature. The 9400 cfm of 50°F air happens with full occupancy (1200 challenging. In addition to reheat, cold
will remove the 256,000 Btu/hr of people) when there is envelope or air distribution and the CDQ desiccant
sensible heat and has the potential to glass loads? If the only loads in the wheel, give us additional tools to deal
remove 116 pounds of water vapor. space are due to lighting and people, with high space latent loads. Simple
However, at this reduced occupancy, the sensible heat ratio drops to 0.63. If airside control schemes like single
the people add only 7.6 pounds of we dim the lights, the situation gets zone VAV provide an easy means of
water vapor. The result is that space even worse. adapting to diverse part-load conditions
humidity is lowered to 40 percent RH. while providing some energy savings.
At this condition, the supply-air
temperature could be reset upward to Table 1. System comparison at part load (no envelope conduction or solar loads)
save some compressor energy.
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 35–3 ● 3
4 ● Trane Engineers Newsletter volume 35–3 providing insights for today’s HVAC system designer
Trane
A business of American Standard Companies
www.trane.com
Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.