You are on page 1of 6

engineers newsletter

volume 35–3 • providing insights for today’s hvac system designer

per square foot of floor area -- a huge


maintaining a comfortable environment in amount! How did that happen?

Places of Assembly Humidity ratio tells the story. Humidity


ratio is grains of water vapor per pound
of air. The humidity ratio at 75°F dry
Designing comfort systems for places bulb and 50 percent RH, the desired
of assembly (auditoriums, Occupancy a Major Factor space condition, is 64.7 grains of water
gymnasiums, arenas, houses of vapor per pound of air. The 55°F supply
worship) presents some vexing People constitute a significant portion air has a humidity ratio of 60.4 gr/lb. At
challenges. Such facilities often have of the space sensible cooling load, over these conditions, each pound of supply
acoustical requirements that place 50 percent. However, it is the impact air we introduce into the space can
limits on equipment location and air on humidity that makes occupancy a remove 4.3 grains of water vapor. If
distribution design. Many places of difficult load to manage. The space each occupant contributes 200 Btu/hr
assembly experience extremely sensible heat ratio for this example is to the latent load, 1200 people add 230
diverse loads and occupancy only 0.69 (Figure 1). pounds of water vapor (1,610,000
schedules, complicating part-load grains) to the air in the gymnasium. If
system control. But perhaps the If the target space comfort condition is each pound of supply air can remove
biggest challenge is occupancy itself, 75°F and 50 percent relative humidity only 4.3 grains of water vapor, it will
and its impact on ventilation and (RH), and the air distribution system is take 374,000 pounds of supply air per
humidity control. Design guidelines designed for 55°F supply air, the hour. This equates to approximately
that are commonly applied in required supply airflow is over 4 cfm 83,000 cfm, or 4.6 cfm/ft2. That's a lot
commercial office space mayget us of air!
into trouble here.

A simple example can illustrate some


of these issues: a school gymnasium Figure 1. Design sensible and latent loads
during a band concert. As this is a good
high school band, both the bleachers
and the floor are full. Occupancy is at
the fire marshal’s rated seating
capacity. The 18,000 ft2 gymnasium is
designed for 1200 people, including
use of the gym floor. A load calculation
reveals the following space loads:
SHR = 0.69
Roof 69,600 Btu/hr Space
Wall 43,000 Btu/hr
Glass 10,500 Btu/hr Supply Air latent load
Lights 122,900 Btu/hr
People 300,000 Btu/hr (sensible)
240,000 Btu/hr (latent)
sensible
Totals 546,000 Btu/hr (sensible) load
240,000 Btu/hr (latent)

© 2006 American Standard All rights reserved ● 1


Humidity is the Driver. So how do we create this 48°F dew that is able to regenerate at low
In this example, 83,000 cfm is required point supply air? One common method temperatures, often without the need
to handle humidity, but only 18,000 is to cool all the supply air to a dry-bulb to add heat. This allows the wheel to
cfm of this must be outdoor air for temperature of about 49°F to 50°F. This be configured in series with a cooling
ventilation (assuming 15 cfm of OA per should dehumidify the supply air to the coil. This activated alumina desiccant
person*). With a space sensible 48°F dew point required to offset the wheel is available in a Trane system
cooling load of 546,000 Btu/hr and a latent load due to people. called CDQ™ (Cool, Dry, Quiet).2 The
supply-air temperature of 55°F; addition of the CDQ wheel allows the
approximately 25,000 cfm is required Supplying 50°F air to the gymnasium system to deliver supply air at 48°F
to maintain the space temperature at provides additional benefits. It reduces dew point, while the cooling coil only
75°F. In this case, 72% of the supply air the required airflow needed to offset needs to cool the air to 54°F. With CDQ
must be outdoor air. While this is a the space sensible cooling load from there is no need to design a cold air
high fraction of outdoor air, it is 25,000 cfm to only 20,000 cfm (1.1 distribution system. Since there is no
manageable. Ventilation air is not the cfm/ft2). This concept is called cold air need to produce 50°F supply air, the
culprit. distribution, and is a common design required capacity of the cooling load is
approach when aggressive humidity substantially reduced.
This 25,000 cfm of supply air equates control is required or the design team
to 1.4 cfm/ft2. This is a large, but is seeking ways to reduce fan power or With the cold air system, the required
manageable supply air quantity. But we air handler footprint.1 All of these cooling coil capacity is about 150 tons
still need 83,000 cfm of supply air to benefits may be attractive when (based on 1200 people and 18,000 cfm
control humidity. How do we better designing for places of assembly. Cold of outdoor air) and supply fan power is
equip the supply air to handle the high air also requires careful diffuser only 10 kW. The CDQ system reduces
latent load associated with this many selection, careful temperature control, cooling coil capacity to about 140 tons,
people? Obviously the supply air needs and reliable control of building but increases fan power to 16 kW
to be drier. The drier the supply air (the pressure. In addition, supply-air because of the higher airflow and
lower the dew point), the more water temperatures below 50°F may additional static pressure from the
vapor it will remove from the space. preclude the use of conventional, desiccant wheel. Both are viable
What supply air dew point is required direct expansion (DX) equipment. options. It is noteworthy that CDQ may
to handle the space latent load? be an excellent means to achieve low
The Desiccant Approach. But do we supply air dew points with
*While many local codes may still require 15 cfm/ conventional DX equipment.
person for ventilation, the most recent version of need colder air, or do we need drier air?
ASHRAE Standard 62.1-2004 has revised the The truth is, we don't need air that is
minimum required ventilation rates for places of colder; we only need air that is drier. Don't Forget Part Load Situations.
assembly. Places of assembly often experience
Recent research in desiccants has
resulted in a Type III desiccant wheel very diverse loads. It would be wise to
Calculating Specific Humidity. The evaluate the performance of these
key is another humidity measurement
called specific humidity. Specific Figure 2. Air handling unit with a Type III series desiccant wheel (Trane CDQ)
humidity is expressed as pounds of
water vapor per pound of air. Suppose OA
we choose to design the air distribution
system for our example gymnasium for
25,000 cfm (114,000 pounds per hour). 89° F DB
83° F DB 68° F DP RA
The 1200 people generate 227 pounds 71° F DP
of water vapor each hour. Removing
WATER VAPOR

227 pounds of water vapor with


114,000 pounds of air requires that the
specific humidity of the supply air be
0.0020 lbw/lba drier than the space. Coil 60° F DB
59° F DP
65° F DB
55° F DP
The specific humidity at 75°F and 50 SA
percent RH is 0.0092 lbw/lba. So the
specific humidity of the supply air must
be 0.0072 lbw/lba to offset the latent
load of the people. This corresponds to Cooling coil Trane CDQ desiccant wheel
a supply air dew point of about 48°F.

2 ● Trane Engineers Newsletter volume 35–3 providing insights for today’s HVAC system designer
systems at part load. There are two conditions, while simultaneously without reheat, when all envelope
part-load conditions we should saving fan energy. conduction and solar loads are absent.
evaluate. One is quite obvious, which is
what happens when most of the How does CDQ fare with reduced Both cold air and CDQ systems
people leave. Perhaps the remaining occupancy? If the supply fan delivers a perform well at this part-load condition.
occupancy is only 40 people instead of constant volume of air, the reduced Single zone VAV results in a slightly
1200. This is an easy part-load sensible load requires the supply-air elevated space relative humidity, but
condition to accommodate. The temperature to increase to over 65°F. still well within the comfort zone. This
sensible loads drop to 256,000 Btu/hr However, the CDQ desiccant wheel comfortable condition is achieved
and the latent load due to people drops can still deliver the supply air at 55°F without reheat and uses less fan
to only 8000 Btu/hr. The resulting dew point (Figure 2). The resulting energy. Some reheat and additional fan
space sensible heat ratio increases to space humidity rises to only 52 percent energy may be needed if more precise
0.97. RH. Constant volume CDQ is certainly humidity control is desired.
adept at controlling space RH at lower
If we supply air at 50°F with the cold air occupancy, but the benefits of VAV can Each Situation Unique. Well, it was a
system, the required supply airflow is be applied to CDQ systems too. great concert, but this was a high
only 9400 cfm. This system is called school concert band, not a rock band.
"single zone VAV." Supply airflow is When Sensible Loads are Lighter. Add smoke from a pyrotechnic display,
reduced to match the reduced sensible There is another part-load condition or moisture from an Olympic size
cooling load in the space. Single zone that can be even more sinister; swimming pool, and designing a
VAV is easy to control. The supply fan reduced building-related sensible loads comfort system for "places of
airflow is modulated based on space while the space is fully occupied. What assembly" can be even more
temperature. The 9400 cfm of 50°F air happens with full occupancy (1200 challenging. In addition to reheat, cold
will remove the 256,000 Btu/hr of people) when there is envelope or air distribution and the CDQ desiccant
sensible heat and has the potential to glass loads? If the only loads in the wheel, give us additional tools to deal
remove 116 pounds of water vapor. space are due to lighting and people, with high space latent loads. Simple
However, at this reduced occupancy, the sensible heat ratio drops to 0.63. If airside control schemes like single
the people add only 7.6 pounds of we dim the lights, the situation gets zone VAV provide an easy means of
water vapor. The result is that space even worse. adapting to diverse part-load conditions
humidity is lowered to 40 percent RH. while providing some energy savings.
At this condition, the supply-air
temperature could be reset upward to Table 1. System comparison at part load (no envelope conduction or solar loads)
save some compressor energy.

Problem with Constant Volume


Systems. What happens if the cold air
system is a constant volume design
rather than VAV? The reduced sensible
cooling load requires a warmer supply-
air temperature, about 63°F for this
example. At this supply-air This reduction in the space sensible Article by Don Eppelheimer, applications
engineer,Trane. You can find this and previous
temperature, the 20,000 cfm of supply cooling load creates a sensible heat issues of the Engineers Newsletter at
air will remove 256,000 Btu/hr of ratio more severe than what the www.trane.com/engineersnewsletter. To
system was originally designed to comment, e-mail comfort@trane.com.
sensible heat, but less than 7.6 pounds
of water vapor. Space humidity rises to accommodate. Increasing the supply- 1.A2000 Engineers Newsletter (volume 29-2,
65 percent RH, well above our target of air temperature or reducing supply "Cold Air makes Good $ense") provides more
detail on the benefits and design issues related
50 percent. Not only does a constant airflow in response to the reduced cold air distribution systems.
volume system use more fan energy at sensible load will hinder the ability to
2A
part load, but it is less adept at remove moisture. Reheat can help 2005 Engineers Newsletter (volume 34-4,
when the sensible heat ratio is lower "Advances in Desiccant-Based Dehumidification")
removing moisture. By comparison, a provides more detail on the series configuration of
single zone VAV system reduces fan than design. Both cold air and CDQ a Type III desiccant wheel (Trane CDQ).
energy while adequately removing have the ability to reduce sensible
moisture. Single zone VAV with cold air cooling capacity while maintaining a
provides humidity control at most load lower supply air dew point. Table 1
compares these systems, with and

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 35–3 ● 3
4 ● Trane Engineers Newsletter volume 35–3 providing insights for today’s HVAC system designer
Trane
A business of American Standard Companies
www.trane.com

For more information, contact your local Trane


office or e-mail us at comfort@trane.com

Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.

5 ● Trane Engineers Newsletter volume 35–3 ADM-APN021-EN (September 2006)


6 ● Trane Engineers Newsletter volume 35–3 providing insights for today’s HVAC system designer

You might also like