You are on page 1of 1

RTHD B1B1B1 Tag: CRTHD-1

Part Load Performance

Load % Cap. LWT EWT Flow WPD EWT LWT Flow WPD Kw Eff
Evap Evap Evap Evap Cond Cond Cond Cond
100 180.3 7.00 12.00 30.24 2090 84.20 98.60 22.58 2040 126.4 0.7008
90 162.3 7.00 12.00 27.22 1640 80.36 93.06 22.58 2060 99.76 0.6148
80 144.2 7.00 12.00 24.19 1310 76.52 87.62 22.58 2080 78.37 0.5433
70 126.2 7.00 12.00 21.17 1020 72.68 82.26 22.58 2110 60.99 0.4832
60 108.2 7.00 12.00 18.14 755 68.84 76.98 22.58 2130 47.42 0.4383
50 90.15 7.00 11.74 15.96 619 65.00 71.74 22.58 2150 35.92 0.3984
40 72.12 7.00 10.79 15.96 618 65.00 70.40 22.58 2160 26.63 0.3692
30 54.09 7.00 9.84 15.96 618 65.00 69.12 22.58 2160 21.33 0.3944
20 36.06 7.00 8.89 15.96 618 65.00 67.86 22.58 2160 16.68 0.4625

Data Generation Date: 10/29/2020


Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Version: 239.0 October 29, 2020