You are on page 1of 34

Ver.3.

MANUAL BOOK

[ASE2000]
Direct Simulation to FRTU
DNP Protocol
29 September 2017
Content

1. System Configuration
2. Start Operation
2.1. ASE2000 (DNP)
2.2.FRTU (DNP)
2.3. ASE2000 (TCP)
2.4. FRTU (TCP)
3. Start Simulation
3.1 Communication
3.2 Read Class
3.3 Control BO
4. Troubleshoot
Setting Over Serial
System Configuration

Connect to side port RS232


FRTU RS232 Cross

PC Open ASE2000 Software

Serial
Cable

Power
Cable
Supply DC
Power
Supply

USB
To
Serial
Start Operation

ASE2000 (DNP)

1. Open Program ASE2000

2. Klik “File” -> “Select Protocol” -> “Select DNP3.0” -> OK


Start Operation

ASE2000 (DNP)

3. Select “Properties” -> “Communication”


Change Page “Channel” -> “Port Channel A” to COM already set

4. Select “Properties” -> “Communication”


Change Page “Line” -> “Baudrate”
Start Operation

ASE2000 (DNP)

3. Select “Properties” -> “Protocol-Specific”


Change Page -> “Exchange Default”, “Asynch”, “DNP3.0”

Dest = Slave address


Source = Master Address (unsolicited Address)

*Change data length,


Stop bits and Parity
Start Operation

ASE2000 (DNP)
For DNP3.0, checklist minimum “ All stations and Class”
Also in RTU Simulations checklist “Enable Unsolicited”
and “Echo Controls”
Start Operation

ASE2000 (DNP)
4. After that , Double Click “Link Status” in column “ Exchange List”

Check this and then


click Ok

This is use for “read status communication”.


Start Operation

ASE2000 (DNP)
5. Next , Double Click “Class 1/2/3/0 Data” in column “ Exchange List”

Check this and then


click Ok

This is use for “read Priorty Class and also can check data/value of Status and Analog”.
Start Operation

FRTU (DNP)

1. Setting Manual FRTU , in this manual we use FTU P200

2. Choose and Select “Communication” in Configuration Menu


Start Operation

FRTU (DNP)

3. Setting In “SCADA Port”


a. Comm.Speed
b. Slave address
c. Protocol (Select DNP)
d. Port (Select RS232C)

4. Setting In “DNP Parameters”


a. Unsol.Mode (Select ON)
b. Unsol address (as Master Address)

5. Click Save
Start Simulation

Communication

1. Choose “Link Status” in ASE2000

2. On the Toolbar choose “Send Continously”

3. Check in “Line Monitor” data row

If get answer data like picture above, it’s means success communication
*Indication success communication is , when transmitt (- - >) and get receive (< - -)
Start Simulation

Communication

4. Also Check , column bar on the right side below

Ok = this means how much data success transmitt


No Resp = this means how much data failed transmitt

5. And make sure , on display FRTU Status indicator for “SCADA” (Tx, Rx and RTS) is blinking

Rx = Communication Data Receive


Tx = Communication Data Transmitt
RTS = Data transmission request to Modem
Start Simulation

Read Class

1. Choose “Class 1/2/3/0” in ASE2000

2. On the Toolbar choose “Send Continously”

3. Check in “Line Monitor” data row

If get answer data like picture beside,


it’s means success communication.
*Indication success communication is ,
when transmitt (- - >) and get receive (<
- -)
Start Simulation

Read Class

4. Also Check , column bar on the right side below

Ok = This means how much data success transmitt


No Resp = This means how much data failed transmitt

5. And make sure , on display FRTU Status indicator for “SCADA” (Tx, Rx and RTS) is blinking

Rx = Communication Data Receive


Tx = Communication Data Transmitt
RTS = Data transmission request to Modem
Start Simulation

Additional Info

1. You can also view “Point Values” in ASE2000, by select View Bar
to view DI and AI data in table and compare it with data sheet (Refer to Appendix DNP)
in manual FRTU

Number Point at “Point Values” and


address binary input in “appendix”
can matching
Setting Over TCP/IP
System Configuration Over TCP

Connect to side LAN Port


FRTU LAN Cable

PC Open ASE2000 Software

LAN Ex:
IP : 192.168.1.20
Cable
Port : 20001
Master ID : 1
Power
Slave ID : 10
Cable
Supply DC
Power Ex:
Supply IP : 192.168.1.10
Port : 20001
Start Operation

ASE2000 (TCP)

1. Open “Network Setting” in PC Configuration/Control Panel

2. Set the IP address


with following picture

3. Click OK
Start Operation

ASE2000 (TCP)

1. Open Program ASE2000

2. Klik “File” -> “Select Protocol” -> “Select DNP3.0 LAN/WAN” -> OK
Start Operation

ASE2000 (TCP)

3. Select “Properties” -> “Protocol-Specific”


Change Page “Exchange Defaults” -> Change Dest(Slave) and Source (Master)
Start Operation

ASE2000 (TCP)

3. Select “Properties” -> “Protocol-Specific”


Change Page “Host” -> Change Host IP and Port (Port make sama as FRTU)

IP FRTU
Start Operation

ASE2000 (TCP)

4. Change in “Exchange List”  “Link Status” and checklist “Transmit”


Start Operation

FRTU (TCP)

1. Setting In “TCP/IP”
a. IP Address (set ex :192.168.1.20)
b. DNP Port (set ex :20001)
2. Setting In “Master IP Address”
a. Master IP #1 (set ex : 192.168.1.10)

3. DNP Parameter
Slave : ex 10
Unsolicited (Master) : ex 1

4. Save OK
Start Simulation

Communication

1. Choose “Link Status” in ASE2000

2. On the Toolbar choose “Send Continously/Send Once”

3. Check in “Line Monitor” data row

If get answer data like picture above, it’s means success communication
*Indication success communication is , when transmitt (- - >) and get receive (< - -)
Start Simulation

Communication

4. Also Check , column bar on the right side below

Ok = this means how much data success transmitt


No Resp = this means how much data failed transmitt

5. And make sure , on display FRTU Status indicator for “Ethernet” (Link and Act) is blinking

Link = Ethernet Linking


Act = Ethernet Active
Start Simulation

Read Class

1. Choose “Class 1/2/3/0” in ASE2000

2. On the Toolbar choose “Send Continously”

3. Check in “Line Monitor” data row

If get answer data like picture beside,


it’s means success communication.
*Indication success communication is ,
when transmitt (- - >) and get receive (<
- -)
Start Simulation

Communication

4. Also Check , column bar on the right side below

Ok = this means how much data success transmitt


No Resp = this means how much data failed transmitt

5. And make sure , on display FRTU Status indicator for “Ethernet” (Link and Act) is blinking

Link = Ethernet Linking


Act = Ethernet Active
Start Simulation

Control BO
BO means Binary Output, this function to operate digital control on FRTU

1. Open View  Digital Control

Row 1 for select/choose what to operate


Row 2 “RTU” it’s slave ID and Frequency in time
Row 3 “Point” for Index Binary Output “Start, Next, Stop” for operating function
Row 4 to operate function
Start Simulation

Control BO
How to operation :

1. Choose in row 1 what to operate (you can check by open DNP.config FTU)
2. RTU is automatic set, if not, manually set by check slave ID.
Set the frequency as you want
3. Value point at upper column for index, middle column no need set (for counter)
lower column for step to stop the counter
4. After all setting , click send once or send continous
Troubleshoot

1. Q : Connection done, but can not connect or communication ?


A : Check cable Serial, it is must cross connection and check PIN DB9 must solder pin (2,3,5,7 and
8)

2. Q : Line Monitor Not showing anything ?


A : Check slave and master address is already correct and check baudrate and parity

3. Q : Always show “Respond time out”?


A : Please check , setting in FRTU and connection cable also check COM setting

4. Q : Reading data not same with Appendix/Mapping Address?


A : Please check, mapping address use DNP Config (FRTU application)

5. Q : Application after setting can not connect?


A : Restart the FRTU
Troubleshoot
How to check ?
1. Open DNP Config in FTU-Man folder

2. Read data from FRTU , until table


(Binary Input, Binary Output, Analog
Input and Counter) Open

3. We can compare “Index” with mapping


address in ASE2000 point value. We also
can add and edit name data with this
application by only double click.
Thank you