EVO192-Zone Control Panel V2.

9
Addendum
The following information has not been included in the EVO192 Programming Guide. The information detailed in this addendum
applies to EVO192 V2.9.

Selectable Input Resistor Values for EOL and Tamper


EVO192 provides the ability to select different resistor values for the EOL and tamper. To configure the selectable input resistor for
EOL, a new module (ZX8 v6.0 or higher) and panel section ([402] and [0402], respectively) has been added.

To access module section [402]:


1. Enter panel section [4003].
2. Enter the module’s serial number.
3. Enter module section [402] (see table 1). Each of the 8 digits represent one of the 8 inputs.
Table 1: Zone Input Options

Section Input 1 / Input 2 Input 3 / Input 4 Input 5 / Input 6 Input 7 / Input 8


[0402] _/_ _/_ _/_ _/_
Zone Input Options (0/0) (0/0) (0/0) (0/0)

The following table details the zone input options.


Table 2: Zone Input Option Individual Settings

Option EOL Value Zone A Value Zone B Value (ATZ)


0 1K 1K 2K2
1 2K2 1K5 N/A
2 3K3 3K3 N/A
3 4K7 4K7 N/A
4 4K7 6K8 N/A
5 2K2 4K7 N/A
6 8K2 8K2 N/A

Figure 1: Selectable input Resistor for EOL and Tamper


Zone
input COM

EOL Zone A Zone B (ATZ)


value

TAMPER N.C. TAMPER N.C.

EVO-EA02 05/2014 PARADOX.COM