5.2.5.2 For any pipe larger than 12-inch (304-mm) nominal diameter,
a concentrated load, including the weight of piping, product,
valves, fittings, and insulation shall be used in lieu of the
40 psf (1.9 kPa). This load shall be uniformly distributed
over the pipe's associated area.
Dead loads for cable trays on pipe racks shall be estimated as follows,
unless actual load information is available and requires otherwise:
a. Operating dead load (Do): A uniformly distributed dead load of
20 psf (1.0 kPa) for a single level of cable trays and 40 psf
(1.9 kPa) for a double level of cable trays.
Comment:
These values estimate the full (maximum) level of cables in the trays.