30GXN,R

Sizes 080-350
Air-Cooled Chillers with ComfortLink™ Controls
50/60 Hz

Wiring Diagrams
DIAGRAM INDEX
POWER SCHEMATICS
Unit 30GXN,R Voltage Figure Number Label Diagram
No. 30GX
080-175 ALL 1 503505
204-350 XL START ALL 2 503504
204-350 YD START ALL 3 503503
LEGEND
XL — Across-the-Line Start
YD — Wye-Delta

CONTROL SCHEMATICS
Unit 30GXN,R Voltage Figure Number Label Diagram
No. 30GX
503770
080-350 24 4
504008
503823
080-175 STD FAN 115, 230 5
504017
504009
080-175 STATIC FAN 115, 230 6
504047
504237
204-350 STD FAN 115, 230 7
504239
504238
204-350 STATIC FAN 115, 230 8
504240

COMPONENT ARRANGEMENTS
Unit 30GXN,R Voltage Figure Number Label Diagram
No. 30GX
080-175 ALL 9 502931
204-350 ALL 10 504423

FAN POWER
Label Diagram
Unit 30GXN,R Voltage Figure Number
No. 30GX
080-175 ALL 11 503295
204-350 STD FAN ALL 12 503502
204-350 STATIC FAN ALL 13 503501

NOTE: For operating sequence, refer to Controls, Start-Up, Operation, Service, andTroubleshooting literature.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 903 Catalog No. 533-00013 Printed in U.S.A. Form 30GXN-1W Pg 1 6-00 Replaces: New
Tab 5c
LEGEND
ALM — Alarm MM — Motormaster® Controller
C — Contactor, Compressor NEC — National Electrical Code
CB — Circuit Breaker OAT — Outdoor-Air Thermistor
CCP — ComfortLink™ Compressor Protection OPC — Oil Pump Contactor
CH — Cooler Heater OPT — Oil Pressure Transducer
CHC — Cooler Heater Control PL — Plug Assembly
CLHR — Cooler Heater Relay PRI — Primary
COMP — Compressor PWR — Power
CPM — Compressor Protection Module S — Wye Start Connection
CR — Control Relay SCB — Screw Compressor Board
CWFS — Chilled Water Flow Switch SN — Sensor (Toroid)
CWP — Chilled Water Pump SPT — Suction Pressure Transducer
CWPI — Chilled Water Pump Interlock SW — Switch
DGT — Discharge Gas Thermistor T — Thermistor
DPT — Discharge Pressure Transducer TB — Terminal Block
EMM — Energy Management Module TEMP — Temperature
EPT — Economizer Pressure Transducer TRAN — Transformer
EQUIP — Equipment XL — Across-the-Line
EXD — Electronic Expansion Device 1M — Compressor Contactor (Wye Delta)
EXV — Electronic Expansion Valve 2M — Compressor Contactor (Delta)
FC — Fan Contactor Terminal Block Connection
FCB — Fan Circuit Breaker
FIOP — Factory-Installed Option Marked Terminal
FM — Fan Motor
FR — Fan Relay Unmarked Terminal
FU — Fuse
GFI-CO — Ground Fault Interrupter Convenience Outlet Unmarked Splice
GND — Ground Marked Wire
HTR — Heater
HPS — High-Pressure Switch Marked Splice
LD — Loader
LDR — Loader Factory Wiring
LL — Liquid Level Field Control Wiring
LLSV — Liquid Line Solenoid Valve
LR — Loader Relay Field Power Wiring
LS — Level Switch Indicates common potential. (Does not
LWT — Leaving Water Temperature represent wiring.)
MBB — Main Base Board
MLC — Minimum Load Control Accessories or Options
MLV — Minimum Load Valve

NOTES
1. Replacement of original wires must be with type 105° C wire or its equivalent.
2. Numbers on the right side of label diagrams indicate the line location of applicable contacts. An under-
lined number signifies normally closed contacts. A plain number denotes normally open contacts. Line
numbers are shown on the left side of the diagrams.
3. Factory wiring is in accordance with National Electrical Code (NEC) U.S.A. Field modifications or addi-
tions must be in compliance with all applicable codes.
4. Wiring for main field power supply must be rated 75° C minimum. Use copper for all units. Maximum
incoming wire size for each terminal block is 500 kcmil.
5. Power for control circuit should be supplied from a separate source through a field-supplied disconnect
with 30-amp maximum protection (50-amp maximum with cooler heaters) for 115-volt control circuits
and 15-amp maximum protection (25-amp maximum with cooler heaters) for 230-volt control circuit.
Connect control circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2
of TB4. Control circuit conductors for all units must be copper only.

2
3
Fig. 1 — Power Schematic, 30GXN,R080-175
4
Fig. 2 — Power Schematic, 30GXN,R204-350, XL Start
5
Fig. 3 — Power Schematic, 30GXN,R204-350, Y-Delta Start
6
Fig. 4 — Control Schematic, 30GXN,R080-350 (24 V)
Fig. 4 — Control Schematic, 30GXN,R080-350 (24 V) (cont)

7
8
Fig. 5 — Control Schematic, 30GXN,R080-175, Standard Fan (115, 230 V)
Fig. 5 — Control Schematic, 30GXN,R080-175,
Standard Fan (115, 230 V) (cont)

9
10
Fig. 6 — Control Schematic, 30GXN,R080-175, Static Fan (115, 230 V)
Fig. 6 — Control Schematic, 30GXN,R080-175,
Static Fan (115, 230 V) (cont)

11
12
Fig. 7 — Control Schematic, 30GXN,R204-350, Standard Fan (115, 230 V)
13
Fig. 7 — Control Schematic, 30GXN,R204-350, Standard Fan (115, 230 V) (cont)
14
Fig. 8 — Control Schematic, 30GXN,R204-350, Static Fan (115, 230 V)
15
Fig. 8 — Control Schematic, 30GXN,R204-350, Static Fan (115, 230 V) (cont)
16
Fig. 9 — Component Arrangement, 30GXN,R080-175
17
Fig. 10 — Component Arrangement, 30GXN,R204-350
18
Fig. 11 — Fan Power, 30GXN,R080-175
Fig. 12 — Fan Power, 30GXN,R204-350, Standard Fan

19
Fig. 13 — Fan Power, 30GXN,R204-350, Static Fan

Copyright 2000 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 903 Catalog No. 533-00013 Printed in U.S.A. Form 30GXN-1W Pg 20 6-00 Replaces: New