You are on page 1of 8

Beck.

The differential pressure


­transmitter for air
Differential pressure
transmitter 984

General description Volume flow measurement


The differential pressure transmitters of the 984 series are (optional)
used to measure differential pressure, overpressure and The shape of the output signal can be switched from linear to
vacuum. square root using a jumper in order to measure the volume flow
They provide up to 8 pressure ranges and 2 output signals, via a differential pressure.
which are easily selectable by jumper or rotary selector switch.
Switching output
Applications (optional, not available with 2-wire version)
Monitoring of gaseous, non-aggressive media. Possible usage To give a switch signal at an user defined pressure level the
areas are: transmitter has an adjustable transistor switching output with
l  uilding automation and air conditioning systems
B a maximum switching capacity of 30 Vdc/100 mA.
l Overpressure measurement in clean rooms and laboratories
l Measurement of constant pressure in VAV applications Display
l Dynamic filter and ventilator monitoring (optional, not available with 2-wire version)
In addition to the analogue output signal the pressure value
Configurable pressure range can be read out on a red LED-display in Pascal or other
For an optimum adaptation to the application, the transmitter
pressure units.
can be switched between various pressure ranges. The factory
Measuring method
setting is the most sensitive range. For the series 984M and
984A the less sensitive second range will be selected by simply Piezoresistive pressure transducer
removing a jumper. For the series 984Q the available eight
ranges can be selected by a rotary selector switch. Mounting position
Can be mounted in any position. The zero offset calibration
Output signal selection eliminates any possible position error.
The output signal of the 3-wire version is configurable.
The factory setting is for a 0 ...10 Volt output signal which can
be changed to a 4 ... 20 mA signal by removing a jumper.
The series 984M is even available in a 2-wire version with
4 ... 20 mA output signal.

Configurable response time


The response time of the output signal can be configured using
a jumper. If the jumper is in place the response time is slow
(factory setting), which is useful for suppressing brief pressure
peaks. If the application requires a fast response time the
jumper must be removed.

Easy offset calibration


The output signal of the 984M series can be calibrated to zero
by pressing the M push-bottun in a pressureless state of the
transmitter.
The series 984A and 984Q perform an automated zero offset
compensation. Here any drift of the zero-point is automatically
corrected in regular intervals. No re-calibration is needed
which reduces monitoring and maintenance efforts.

2
Overview on technical data

Series 984M 984M 984A 984Q


Electrical connection 3-wire 2-wire 3-wire 3-wire
Measuring method Piezoresistive pressure transducer
Supply voltage 18 ... 30 18 ... 30 22 ... 30 22 ... 30
Vac/Vdc Vdc Vac/Vdc Vac/Vdc
Output signal selectable with jumper – with jumper with jumper
Output signal 0 ... 10 Volt ■ – ■ ■
Output signal 4 ... 20 mA ■ ■ ■ ■
Output signal 0 ... 5 Volt  –  
Output signal 0 ... 20 mA  –  
LED display, red, 4 digits, units in Pascal  –  
LED display, red, 4 digits, units in mbar  –  
LED display, red, 4 digits, units in inWC  –  
Switching output (npn) for max 30 Vdc/100 mA  –  
Output signal selection from linear to square root    
max. current draw without display 60 mA 21 mA 160 mA 160 mA
max. current draw with display 110 mA – 210 mA 210 mA
Load for 0 ... 10 V output ≥ 1kΩ (≤ 10 mA)
Load for 0 ... 20 mA output 20 ... 500 Ω
Pressure medium Air and non-aggressive gases
with Rotary Selector
Configuration of pressure range with jumper with jumper with jumper
Switch
max. number of pressure range 2 2 2 8
only one customized pressure range    –
Manuel offset compensation ■ ■ – –
Automated offset compensation – – ■ ■
Working temperature 0 ... +50°C
Storage temperature –10 ... +70°C
Linearity error ± 1% of full scale
Typical long-term stability ≤ 2.5% of fs/year ≤ 2.5% of fs/year 0.0% 0.0%
Repetition accuracy ≤ ± 0.2% of full scale
Position dependence ≤ 0.2% of full scale/g
Humidity 0 ... 95% rel, non-condensing
Response time, selectable with jumper with jumper with jumper with jumper
Response time (0,1 s and 1 s) ■ ■ ■ ■
Response time free selectable between 0.1 s and 20 s    
Process connection P1 and P2 Hose connection with 6 mm outer diameter
Electrical connection Screw terminal block for wires and strands up to 1.5 mm²
Mounting Screw mounting with serrated screws
Housing material housing with process connection P2 (–) made from ABS
base part with process connection P1 (+) made from POM
Housing dimensions approx. Ø 85 x 58 mm
Weight approx. 135 gr approx. 120 gr approx. 150 gr approx. 150 gr
Protection class acc. to EN 60529 IP54 with protection cap or IP00 without protection cap
Cable conduit on protection cap M16x1.5 ■ ■ ■ ■
Cable conduit on protection cap M20x1.5    
CE Conformance EN 60770, EN 61326 ■ ■ ■ ■
RoHS Conformance according to 2011/65/EEC ■ ■ ■ ■

■  standard equipment     optional equipment

3
Differential pressure transmitter 984M
with manual offset compensation

Pressure ranges
Model Range 1 Range 2 Overload capacity Bursting pressure Temperature error
984M.5X3 -50 ... 0 ... +50 Pa – 20 kPa 40 kPa ≤ ± 5 % of full scale
984M.5W3 -100 ... 0 ... +100 Pa – 20 kPa 40 kPa ≤ ± 5 % of full scale
984M.523 0 ... 100 Pa 0 ... 250 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
984M.533 0 ... 250 Pa 0 ... 500 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
984M.543 0 ... 500 Pa 0 ... 1.000 Pa 20 kPa 40 kPa ≤ ± 3.5 % of full scale
984M.553 0 ... 1 kPa 0 ... 2.5 kPa 40 kPa 70 kPa ≤ ± 1 % of full scale
984M.573 0 ... 5 kPa 0 ... 10 kPa 60 kPa 120 kPa ≤ ± 1 % of full scale
984M.593 0 ... 25 kPa 0 ... 50 kPa 300 kPa 500 kPa ≤ ± 1 % of full scale
984M.5B3 0 ... 100 kPa 0 ... 250 kPa 1.2 MPa 2 MPa ≤ ± 1 % of full scale

Order matrix
IP protection class IP 54 with cable conduit M16x1.5 984M. 5
IP 54 with cable conduit M20x1.5 3
Configurable -50 ... 0 ... +50 Pa (-0,5 ... 0 ... +0,5 mbar) X
pressure range -100 ... 0 ... +100 Pa (-1.0 ... 0 ... +1,0 mbar) W
0 ... 100 Pa (1.0 mbar) 0 ... 250 Pa (2.5 mbar) 2
0 ... 250 Pa (2.5 mbar) 0 ... 500 Pa (5.0 mbar) 3
0 ... 500 Pa (5.0 mbar) 0 ... 1.000 Pa (10 mbar) 4
0 ... 1 kPa (10 mbar) 0 ... 2.5 kPa (25 mbar) 5
0 ... 5 kPa (50 mbar) 0 ... 10 kPa (100 mbar) 7
0 ... 25 kPa (250 mbar) 0 ... 50 kPa (500 mbar) 9
0 ... 100 kPa (1.000 mbar) 0 ... 250 kPa (2.500 mbar) B

Pressure unit Pascal 3


mbar 1

Output signal and 0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, with switching output 1
supply voltage 0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, without switching output 7
4 ... 20 mA, 2-wire, 24 Vdc 2
4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, with switching output 3
4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, without switching output D

Display no display 0
with LED-display, 4 digits (not for 2-wire) 1

Electrical connection via screw terminal block 4


Factory settings printed in bold type.

Terminal assignments 2-wire version


3-wire version

4
npn 4 Load
3
3
0…10 V 4…20 mA 2 Load
4...20 mA
2 Load

18…30 Vac/Vdc 18...30 Vdc 1


1

4 SA Switching output, npn 4


3 GO Ground GND 3
2 Y Output signal 0 … 10 V/4 ... 20 mA 2 Y Output signal 4 ... 20 mA
1 G Supply voltage 24 VAC/ VDC 1 G Supply voltage 24 VDC

4
Differential pressure transmitter 984A
with automated offset compensation

Pressure ranges
Model Range 1 Range 2 Overload capacity Bursting pressure Temperature error
984A.5E3 -25 ... 0 ... +25 Pa – 20 kPa 40 kPa ≤ ± 5 % of full scale
984A.5X3 -50 ... 0 ... +50 Pa – 20 kPa 40 kPa ≤ ± 5 % of full scale
984A.5W3 -100 ... 0 ... +100 Pa – 20 kPa 40 kPa ≤ ± 5 % of full scale
984A.503 0 ... 25 Pa 0 ... 50 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
984A.513 0 ... 50 Pa 0 ... 100 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
984A.523 0 ... 100 Pa 0 ... 250 Pa 20 kPa 40 kPa ≤ ± 2.5 % of full scale
984A.533 0 ... 250 Pa 0 ... 500 Pa 20 kPa 40 kPa ≤ ± 2.5 % of full scale
984A.543 0 ... 500 Pa 0 ... 1.000 Pa 20 kPa 40 kPa ≤ ± 1.5 % of full scale
984A.553 0 ... 1 kPa 0 ... 2.5 kPa 40 kPa 70 kPa ≤ ± 1 % of full scale
984A.573 0 ... 5 kPa 0 ... 10 kPa 60 kPa 120 kPa ≤ ± 1 % of full scale
984A.593 0 ... 25 kPa 0 ... 50 kPa 300 kPa 500 kPa ≤ ± 1 % of full scale
984A.5B3 0 ... 100 kPa 0 ... 250 kPa 1.2 MPa 2 MPa ≤ ± 1 % of full scale

Order matrix
IP protection class IP 54 with cable conduit M16x1.5 984A. 5
IP 54 with cable conduit M20x1.5 3
Configurable -25 ... 0 ... +25 Pa (-0.25 ... 0 ... +0.25 mbar) E
pressure range -50 ... 0 ... +50 Pa (-0.5 ... 0 ... +0.5 mbar) X
-100 ... 0 ... +100 Pa (-1.0 ... 0 ... +1.0 mbar) W
0 ... 25 Pa (0.25 mbar) 0 ... 50 Pa (0.5 mbar) 0
0 ... 50 Pa (0.5 mbar) 0 ... 100 Pa (1.0 mbar) 1
0 ... 100 Pa (1.0 mbar) 0 ... 250 Pa (2.5 mbar) 2
0 ... 250 Pa (2.5 mbar) 0 ... 500 Pa (5.0 mbar) 3
0 ... 500 Pa (5.0 mbar) 0 ... 1.000 Pa (10 mbar) 4
0 ... 1 kPa (10 mbar) 0 ... 2.5 kPa (25 mbar) 5
0 ... 5 kPa (50 mbar) 0 ... 10 kPa (100 mbar) 7
0 ... 25 kPa (250 mbar) 0 ... 50 kPa (500 mbar) 9
0 ... 100 kPa (1.000 mbar) 0 ... 250 kPa (2.500 mbar) B

Pressure unit Pascal 3


mbar 1

Output signal and 0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, without switching output 7
supply voltage 4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, without switching output D
0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, with switching output 1
4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, with switching output 3
Display no display 0
with LED-display, 4 digits 1

Electrical connection via screw terminal block 4


Factory settings printed in bold type.

Terminal assignments
3-wire version

npn 4 Load 4 SA Switching output, npn


3 3 GO Ground GND
0…10 V
2 Load 2 Y Output signal 0 … 10 V/4 ... 20 mA
4...20 mA
1 G Supply voltage 24 VAC/ VDC
22…30 Vac/Vdc 1

5
Differential pressure transmitter 984Q
with 8 pressure ranges

Pressure ranges
Model Position Pressure range Overload capacity Bursting pressure Temperature error
984Q.543 1 0 ... 100 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
2 0 ... 250 Pa 20 kPa 40 kPa ≤ ± 2.5 % of full scale
3 0 ... 500 Pa 20 kPa 40 kPa ≤ ± 2.5 % of full scale
4 0 ... 1000 Pa 20 kPa 40 kPa ≤ ± 1.5 % of full scale
5 -50 ... 0 ... +50 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
6 -100 ... 0 ... +100 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
7 -250 ... 0 ... +250 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
8 -500 ... 0 ... +500 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale

984Q.553 1 -100 ... 0 ... +100 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale


2 0 ... 100 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
3 0 ... 200 Pa 20 kPa 40 kPa ≤ ± 5 % of full scale
4 0 ... 500 Pa 20 kPa 40 kPa ≤ ± 2.5 % of full scale
NEW 5 0 ... 1000 Pa 20 kPa 40 kPa ≤ ± 1.5 % of full scale
6 0 ... 1500 Pa 20 kPa 40 kPa ≤ ± 1.5 % of full scale
7 0 ... 2000 Pa 20 kPa 40 kPa ≤ ± 1 % of full scale
8 0 ... 2500 Pa 20 kPa 40 kPa ≤ ± 1 % of full scale

Order matrix
IP protection class IP 54 with cable conduit M16x1.5 984Q. 5
IP 54 with cable conduit M20x1.5 3

Pressure ranges from -50 ... 0 ... +50 Pa to 0 ... 1000 Pa 4


from -100 ... 0 ... +100 Pa to 0 ... 2500 Pa 5

Pressure unit Pascal 3


mbar 1

Output signal and 0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, without switching output 7
supply voltage 4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, without switching output D
0 ... 10 V or 4 ... 20 mA, 3-wire, 24 Vac/Vdc, with switching output 1
4 ... 20 mA or 0 ... 10 V, 3-wire, 24 Vac/Vdc, with switching output 3

Display no display 0
with LED-display, 4 digits 1
Electrical connection via screw terminal block 4
Factory settings printed in bold type.

Terminal assignments
3-wire version

npn 4 Load 4 SA Switching output, npn


3 3 GO Ground GND
0…10 V
2 Load 2 Y Output signal 0 … 10 V/4 ... 20 mA
4...20 mA
1 G Supply voltage 24 VAC/ VDC
22…30 Vac/Vdc 1

6
71 55
50 18
71 46 71 ø5 55 57.5 57.5
57.5 65 6565
50 18 8 8 8

ø 4.5
46 46 ø5 ø5 ø4 .5ø4 ø.45 .5 21.8 21.8
21.8 50 5050
.5 .5 .5

ø 4.5

40

60
ø10
Mounting 40

60

50
ø10

60 60
40 40

60
40
ø5
0

ø4
7.7
11

Mountingø bracket
ø4
7.7
7
11
7 7

59

59
59

bracket 6401

6481

19 19

19
2

2
7.5 7.57.5
ø6 ø6ø6
18 1818
984 with cable conduit M16x1.5

70.5
90.5 65.5
70.5
Dimensional Drawings

65.5 90.5 10
19.5 65.5
65.5
10
19.5 10
10

ø5
0

Befestigungswinkel
40
60
ø5

Befestigungswinkel
0
57.5
57.557.5 65 6565

40
60

"S-Form"
8 8 8
ø4 .5ø ø.45 .5 21.8
21.821.8 50 5050

"S-Form"
.5 4.5 .5

40 40
60 60

64826482
ø5 ø4
21.5 ø4
ø5
ø5 21.5

Mounting bracket 6482


Mounting bracket 6402
ø5

1010

10 10
59
59
59

2
7.5 7.57.5

knkknmknm
18 1818 ø6 ø6ø6
984 with cable conduit M20 x1.5

ø 3.4 18.5
ø6
80

ø6

ø 6.5
57.5 57.5 57.5 65 65 65
8.5 8.5 8.5
21.8 50 50 50

Ø
21.8

Ø
40

Ø
4.5 4.5 21.8 4.5

ø 25
ø 16
ø 16

1 1

60∞
ø 3.4 59

59
59

65 18.5
7.5 7.5 7.5
Ø6 Ø6 Ø6
18 18 18

ø6

ø 6.5
Beck GmbH Allgemeintol. Werkstück
Beck GmbH Maßstab 1:1 Allgemeintol. Maßstab 1:1
Gew.:0.284kg
WerkstückAllgemeintol. Werkstück Maßstab 1:1Gew.:0.284kg Gew.:0.284kg
-kanten
Beck GmbH
DIN ISO -kanten -kanten
Druckkontolltechnik DIN ISODruckkontolltechnik Werkstoff: Werkstoff:
DIN ISO Werkstoff:
DIN 13715 Druckkontolltechnik
2768-m DIN 13715
Halbzeug: DIN 13715
2768-m Halbzeug: 2768-m Halbzeug:
Datum Name Datum Name
Benennung: Datum Name Benennung: Benennung:
Bear. 27-Nov-07 A.Kummer Bear. 27-Nov-07 A.Kummer 27-Nov-07 A.Kummer
Bear.
Gepr. Gepr. Gepr.
Norm Norm Norm DMU984M
DMU984M DMU984M
Dateiname der Zeichnung der Zeichnung
DateinZeiamechnungsnummer: Zeichnungsnummer:

ø 25
Dateiname der Zeichnung

ø 16
100 Blatt1
Zeichnungsnummer: Blatt1
2 Tol. eingefuegt 30.06.09 Ku 2 Tol. eingefuegt Ku
2 30.06.09Tol. eingefuegt 30.06.09 Ku Blatt1
1
984M
Verschraubung neu
984M 984M
1 Verschraubung neu 10.02.09 Ku 1 10.02.09Verschraubung
Ku neu 10.02.09Ku
DMU984M 2 Bl. DMU984M DMU984M2 Bl. 2 Bl.
Zust. Änderung Datum Zust.
Nam. (Urspr.) Änderung Datum(Ers.f.:) Nam. (Urspr.) (Ers.f.:) (Ers.d.:)

60
Zust. Änderung Datum Nam. (Ers.d.:)
(Urspr.) (Ers.f.:) (Ers.d.:)

Duct connection for


Duct connection for

°
Climaset® 6550/6556

Climaset® 6555/6557

7
Accessories
Metal mounting bracket S-shaped Article No. 6402
Metal mounting bracket L-shaped Article No. 6401
Snap-on plastic bracket S-shaped Article No. 6482
Snap-on plastic bracket L-spaped Article No. 6481
Climaset® consisting of 2m PVC hose and 2 plastic pipes with 80 mm length Article No. 6555
Climaset® consisting of 2 m Silicone hose and 2 plastic pipes Article No. 6557
Climaset consisting of 2 m PVC hose and 2 angled metal pipes
®
Article No. 6550
Climaset® consisting of 2 m Silicone hose and 2 angled metal pipes Article No. 6556
Duct connecting pipe for Climaset® 6555, with 80 mm length Article No. 6551
Angled metal pipe for Climaset® 6550 Article No. 6552
Rubber grommet for Climaset® 6550 Article No. 6553
Roll with 100 m PVC hose Article No. 6424
Roll with 100 m Silicone hose Article No. 6425
M16x1.5 cable conduit including seal and gland nut Article No. 6562
M20x1.5 cable conduit including seal and counter screw Article No. 6568
1/2“ NPT cable conduit without insert Article No. 6561
Folding box for individual packing (with accessories) Article No. 6428
Folding box for individual packing (with accessories) Article No. 6429

We exhibit
Copyright © 2016 Beck GmbH

15.-18. March 2016 11.-13. October 2016


Milan, Italy Nuremberg, Germany
Technical data subject to change without prior notice.

25.-29. April 2016 14.-18. March 2017


Hannover, Germany Frankfurt, Germany
984Q_data_english 03/2016

Beck GmbH
Druckkontrolltechnik
P.O. Box 11 31
D-71140 Steinenbronn
Telephone +49 (71 57) 52 87-0
Telefax +49 (71 57) 52 87-83
e-mail sales@beck-sensors.com
http://www.beck-sensors.com

You might also like