Warning Daikin products are manufactured for export to numerous countries throughout the world.

Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product PLXSID1605
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Use only those parts and accessories supplied or specified by Daikin.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

HEAD OFFICE :

SERVICE AND SPARE PARTS, Telp.: 021-736 92899 • Training Center, Telp. : 021-295 61950 • Bekasi, Telp.: 021-2945 0585,
Tangerang, Telp.: 021-5314 1195 • Bandung, Telp.: 022-5225 150 • Semarang, Telp.: 024-841 2695 • Yogyakarta, Telp.: 0274-551 321
Surabaya, Telp.: 031-503 1138 • Denpasar, Telp.: 0361-900 5514 • Makassar, Telp.: 0411-446 263 • Palembang, Telp.: 0711-319 776

Specifications, designs and other content appearing in this brochure are current as of June 2016 but subject to change without notice. c All rights reserved BEBAS CFC DAN HCFC
The solution for light commercial sector
Providing the ideal solution for all kinds of small commercial space such as shops, restaurant and
small offices. The Sky Air series offers a complete comfort solution that puts you in total control.

Product Lineup
PK 2.0 2.5 3.0 3.0 4.0 5.0 6.0
Capacity Btu/h 18500 23000 28000 28000/29000* 36000 42000 55000
kW 5.4 6.7 8.2 8.2/8.5* 10.5 12.3 16.1

Ceiling Cassette
Type

Indoor unit FCRN50FXV14 FCRN60FXV14 FCRN71FXV14 FCRN71FXV14 FCRN100FXV14 FCRN125FXV14


Outdoor unit RN50CXV1A4 RN60CXV1A4 RR71CXV1A4 RR71CXY1A4 RR100DXY1A4 RR125DXY1A4

Floor Standing
Type

Indoor unit FVRN71BXV14 FVRN71BXV14 FVRN100BXV14 FVRN125BXV14 FVRN140BXV14


Outdoor unit RR71CXV1A4 RR71CXY1A4 RR100DXY1A4 RR125DXY1A4 RR140DXY1A4

Outdoor Unit

RN50CXV1A4 RN60CXV1A4 RR71CXV1A4 RR71CXY1A4 RR100DXY1A4 RR125DXY1A4 RR140DXY1A4


*Only applicable for Floor Standing Type

01 02
4-way air flow Compact body and quiet operation
Ceiling Cassette This unit promotes even air distribution covering every corner of
the room by combining 4-ways air discharge and large discharge
area.
Indoor units as an aerodynamically designed Difuser Turbo Fan.

Type
4 way air flow ceiling cassette

FCRN50/60/71/100/125FXV14
Draft resistance has been reduced by incorporating into a single
Fine square panels unit, an impeller and a diffuser to control air flow inside the unit.
Panel size is same for all models. It is easy to maintain a neat The Diffuser Turbo Fan is both quiet during operation and
appearance when multiple units are installed. compact.

Indoor Unit Low Quiet


dB(A) dB(A)
FCRN50F 33 29
FCRN60F 34 31
950mm
FCRN71F 35 32
FCRN100F 37 34
FCRN125F 41 37
950mm

Wired Controller: Wireless Controller:


BRC51A62 BRC52A62 Optimal comfort and convenience assured by air discharge modes
* Optional * Supplied with panel To increase the comfort level of the air conditioned area, the system is built-in with 3 different types of air flow pattern to suit different
requirements.

2 3
1 Air direction in draft Air direction in ceiling
Air direction in prevention setting soiling prevention setting
standard setting Select this setting to Recommended for
For gentle drafts. eliminate direct drafts location with light colour
which can lead to ceiling that must be kept
discomfort. spotless.

COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES OPTIONS


The default setting for air swing pattern is 1. The air swing pattern can be selected through the wireless remote control.
Network Interface Module (NIM)
Two selectable temperature

Pre-charged for up to 7.5m

External command control


Weekly scheduled timer

Drain pump mechanism


Washable saranet filter
Switchable fan speed

using G-way or BAG


Auto random restart

Fresh-air intake kit


Programme “Dry”

Group control by

Two selectable temperature sensors


Timer selector

Self diagnosis
Swing pattern
Auto swing

sensor

Both indoor unit and wired remote controller (option) contain temperature-sensors. Temperature sensing can be set at the unit or, to
further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by
the technicians.
* Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperature-sensor.
*1 *1

*1 Applicable when wired controller is used.

03 04
Switchable fan speed: Indoor unit ON/OFF switch Drain pump is equipped as standard accessory with 700mm lift
The unit can be conveniently started manually in the event the This unit comes with a condensate water drain pump which can pump water up to 700mm higher from drain pipe outlet. Safety float is
High ➡ Medium ➡ Low ➡ Quiet wireless remote controller is misplaced or the wireless remote incorporated to monitor water level.
controller batteries are not charged.
High setting provides maximum reach while low setting
minimises drafts.
Extra protection
This unit covered with insulation material acts as extra protection
Timer selector when installed under very high humidity environment to prevent
Operation starts when the preset time of the ON timer elapses 700mm
condensation.
and stops when the preset time of the OFF timer elapses.

Powerful operation
New powerful operation boosts airflow to maximum volume for a
20-minute period with highest fan speed. After this, the unit
automatically returns to its previous settings.

Easy Maintenance
Easy Installation
Quick and easy to install Panel-hook mechanism Easier to maintain
The condition of the drain pan and drain water can be checked by
Just 246mm high. Installable in tight ceiling spaces. This feature enables the installer to work with both hands as the
removing the drain plug and intake grille.
Just open the
panel can be hung on the unit. intake grille!

Drain plug
*246mm Simple step to change fan motor
• Without removing panel, it can be
* 246mm high with FCRN50/60/71 easily access and service to fan motor
* 288mm high with FCRN100/125 • Reduced troubleshooting and
servicing time Self-diagnosis function
• Three simple steps: This intelligent feature helps to detect faults or malfunctioning in
All models can be installed without using lifter because of the the system and give user a warning by blinking of the LED light or
light weight. display error code on wired controller.
Control box ➡ Fan cover ➡ Blower fan ➡ Fan motor

Detachable corner
For the ease and flexibility of installation, this unit is designed Position of connecting pipe and drain
with 4 detachable corners where installer is able to fit their hand
hose Options required for specific operating environments
in to adjust hanging hook and perform drain leakage check.
In order to create more space for installer to work on connection
pipe of indoor unit, the connection pipe of gas and liquid are
located further from each other and purposely not align to Fresh air intake kit
hanging hook. Using this kit*, a duct can be fitted to increase the intake of
To enhance the convenience of installation, drain hose location is outdoor air.
relocated to another side of cassette unit (not same side with
connection pipe)
Knock-out hole
The built-in knock-out hole are available for fresh air intake or
branch duct.
Easy accessible control box
Control box of this unit can be accessed directly from the intake
grille for ease of installation and servicing process. Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

05 06
Floor Standing Auto-swing mode Timer selector
Type This unit uses its automatic horizontal swing louver to spread
comfortable air flow to cool every corner of the room. Its vertical
louvers are adjusted manually to match different interior spaces
Operation starts when the preset time of the ON timer elapses
and stops when the preset time of the OFF timer elapses.

The floor standing is designed to look sleek, stylish and and partition as well as to avoid direct airflow.
modern to blend into any environment. Its slim profile Powerful operation
promotes an ideal way of space saving with style and New powerful operation boosts airflow to maximum volume for a
functionality. Its high gloss finishing makes it easy for 20-minute period with highest fan speed. After this, the unit
automatically returns to its previous settings.
cleaning. With its ease of installation, it is suited to be
installed in offices, commercial shops, restaurants,
showrooms and mosque. Indoor unit ON/OFF switch
The unit can be conveniently started manually in the event the
wireless remote controller is misplaced or the wireless remote
controller batteries are not charged.
FVRN71/100/125/140FXV14 Auto horizontal swing
Manual setting of
vertical airflow louvers

User-friendly controls Easy Maintenance


The unit comes with a stylish black control panel with white LED
light for clear display. It comes with a keylock function to prevent Safety clip
setting change from unauthorised personnel. The safety clip feature allows the users to remove the washable
saranet filter with ease during maintenance. At the same time, it
OFF State ON State also acts as a safety feature to prevent the users from reaching
White display lights up to
indicate modes and temperature
into the electrical and mechanical components.
settings when switched on

Keylock icon displayed


when activated

Keylock Function: Safety clip


Activation and deactivation of
keylock by pressing “SWING”
and “TURBO” together for
5 seconds

Wired Controller: Wireless Controller: Additionally, this unit is incorporated with


BRC51A62 BRC52A62 Far air flow infrared sensor for usage with wireless
* Optional * Supplied with unit The Daikin floor standing is able to achieve air flow distance as far as controller (BRC52A62) which comes with Space for water drain pump
25m* which is about the size of a basketball court. the unit as the standard package. Thus, it There is a space in the unit below the fan that allows users to
can also be controlled using wireless install an external condensate water pump.
* The condensate water drain pump is separately purchased and field installed.
V_r (m/s)
controller for the flexibility in controls.
Global
2.44

1.22

0.00

25m Two selectable temperature sensors


* Note: Based on size 140
Both indoor unit and wired remote controller (option) contain
temperature-sensors. Temperature sensing can be set at the unit
or, to further improve comfort level, closer to the target area at
COMFORT CLEANLINESS WORK & SERVICING CONTROL FEATURES the wired remote control. This feature must be set during
commissioning by the technicians.
Network Interface Module (NIM)
Two selectable temperature

Pre-charged for up to 7.5m

External command control


Weekly scheduled timer

Washable saranet filter


Switchable fan speed

* Temperature-sensor on indoor unit must be used when the air conditioner is controlled
using G-way or BAG
Auto random restart
Programme “Dry”

Group control by

from another room.


Timer selector

Self diagnosis
Auto swing

** Wireless remote controller does not have a temperature-sensor


sensor

Switchable fan speed:


High ➡ Medium ➡ Low
*1 *1 Piping Condensate
High setting provides maximum reach while low setting minimizes Floor Standing Unit water
*1 Applicable when wired controller is used. drain pump
drafts.

07 08
Outdoor Unit Controllers
Wireless controller BRC52A62

1 “Glow-in-the-dark” ON/OFF switch 6 Vertical auto-swing


1 2 Fan speed selection: 7 Selectable mode: Cool, Dry, Fan
6
2 Low, Medium, High, Auto
7
8 Turbo function
8 3 Temperature setting: Up & down 9 Quiet function
3
RR100DXY1A4 9 4 Sleep mode function 10 On timer setting
RN50CXV1A4 RR71CXV1A4 RR125DXY1A4 4
10 5 5 Off timer setting 11 Real time clock
RN60CXV1A4 RR71CXY1A4 RR140DXY1A4
11

Fitted with wide inlet fan Equipped with scroll compressor for
Fully shaped aerodynamic propellers are designed to push air
quiet operation
with a large wing surface, providing both high blow volume and Wired controller BRC51A62
quiet operation with turbulence. Smooth running, minimal vibration, low operating sound.
* Only applicable to RR100/125/140DXY1A4
1

1 Real time clock and day display 7 Turbo function


2 2 Temperature operate in ˚C and ˚F 8 Cool, Dry, Fan mode
7 3 3 Swing function 9 Delay timer (1 or 2 hours)
RR71C RR71C 8
Outdoor RN50C RN60C
(1PH) (3PH) 9
4 4 Quiet function 10 7-days programmable timer
Sound Pressure Level dBA 52 52 56 56 10 5 5 Sleep function 11 Low, Medium, High, Auto fan speed
11 6 6 ON/OFF switch
Outdoor RR100D RR125D RR140D

Sound Pressure Level dBA 58 60 65

Wide inlet fan Wired controller BRC51A62 can directly be connected to the unit’s main board to start operating without extra setting or modification.
It also has a built-in temperature sensor that enables temperature sensing closer to target area for improved comfort (no settings required
to activate the handset temperature sensor).

Installation and Maintenance


Pre-charged for up to 7.5 metres
Model Pre-charged Max. Piping Max. Piping
Piping Length, m Length, m Elevation, m
RN50C 7.5 30 15
RN60C 7.5 30 15
RR71C(1PH) 7.5 45 25
RR71C(3PH) 7.5 45 25 IR receiver on wired handset
received the signal
RR100D 7.5 50 30
RR125D 7.5 50 30
RR140D 7.5 45 25
Signal sent from
wireless handset

Durability
• The unit is covered with corrosion-proof galvanized steel to enhance its durability.
• Heat exchange fins are provided with anti-corrosion treatment.

09 10
Simple system that provides flexibility of controls Sequential control by Sequential Network Interface Module (S-NIM)
Control two units of air conditioner in a master and slave system, operating at alternate sequence of preset hours (3/4/5/7/9/11/12 hours),
Control Pattern Remote Controls controlled by a single BRC51A62 controller.
The S-NIM controls consist of:

• Mainboard
• Control panel (BRC51A62)
Group control by Network For simultaneous control of • S-NIM controller
Interface module (NIM) up to 16 indoor units NIM NIM NIM NIM • Communication bus

The S-NIM is suitable in environment requiring 24-hours air conditioning, such as server room, room containing critical electronics
equipment, laboratories, telecommunication towers, railway switching centre and 24-hours shoplets. It also extends the operating lifetime
of existing air conditioning units.

For sequential control of Preset Switching After 3 hours


Sequential control by Time: 3 hours
Sequential Network Interface 2 indoor units at alternate
Module (S-NIM) sequence of pre-set hour S-NIM S-NIM
S-NIM S-NIM S-NIM S-NIM

ON OFF OFF ON

Operation and surveillance


Control by external command is carried out using the contact
using G-way or BAG signal from the operation
G-way/ G-way/ G-way/
control box in the building BAG BAG BAG
surveillance (security) room.
BMS
When the operating unit is faulty, the standby unit automatically takes over. Other features of S-NIM:

• Auto restart feature with last state settings.


Group control by Network Interface Module (NIM) • Error indication via error code display on the control panel.
• Pre-set operation hours via DIP switch.
• Maximum point to point distance of 1000m.
The NIM group controls consist of:

• Mainboard
• Control panel (BRC51A62) Control by external command using G-way
• NIM controller
• Communication bus
The G-way controls consist of:
NIM utilizes master-slave configurations. One master can control up to 15 slave units in a
group. The master unit operates in conjunction with a control panel. Any settings done via the • Mainboard
control panel connected to the master overwrite the settings of its slave units. Slave units can • Control panel (BRC51A62)
be operated with or without control panel. If a slave unit is operating with a control panel, its • G-way controller
settings can be changed without following its master’s. • Communication bus

It is a gateway between the air conditioning unit and basic Building


• DIP switch setting for group and unit address Management System (BMS). G-way controller enables:
• Automatic detection of control panel
• Error codes and error unit’s ID indication on control panel • Remote (ON/OFF) of air conditioner via BMS.
• Supported configurations of NIM: • Unit error indication via BMS and BRC51A62 controller.
• Unit operation status monitoring via BMS.
Master Slave
• DIP switch setting for control or monitoring function.
BRC51A62 • Maximum point-to-point distance of 1000m.
NIM controller BRC52A62 G-way controller

11 12
Control by external command using BMS Access Gateway (BAG) Abundance of functions that provide comfortable air-conditioning in
stores and offices
BAG interfaces the air conditioner unit to BMS system via input contacts, resistance
inputs and dry contacts outputs which allows the monitoring and controls of the air
conditioner. The BAG enables:
Comfort

• Controls of the air conditioner unit’s ON/OFF status, operating mode, Auto-swing Two selectable temperature-sensors
fan speed setting, room temperature setting as well as forcing off the unit in Delivers comfortable air-conditioning to all areas, near to and far Temperature-sensors are included in the indoor unit and
the event of fire. from the air-conditioner. optional wired remote controller. temperature sensing closer
• Indication to warn the control room in the event of air conditioner failure. to target area is possible to further increase the comfort level.
• Maximum point-to-point distance of 1100m (please refer to the
installation manual) Swing pattern selection Use the temperature-sensor in the indoor unit when
You can freely set 3 air discharge setting by remote controller. controlling air conditioning from another room.
Inputs Inputs Controls Applications
BAG controller Input Force off/unchange Smoke alarm system 1) Air direction in standard setting
contacts ON/OFF Long distance unit ON/OFF control
The BAG controls consist of: Temperature setting Long distance unit temperature
Resistance
• Mainboard Inputs (16˚C-30˚C) setting control 2) Air direction in draft prevention
setting
• Control panel (BRC51A62) Outputs Output Indications Applications
• BAG controller Relay ON/OFF Status
Long distance unit operation status monitoring
• Communication bus outputs Unit faulty / normal 3) Air direction in ceiling soiling
prevention setting
Note: Wireless remote controllers have no temperature-sensor
Individual air conditioners can be turned on from the control room’s Input Contact
connection Switchable fan speed (*available on all models) Timer selector
Selectable High, Medium and Low fan speed. High setting Operation starts when the preset time of the ON timer elapse
provides maximum reach while low setting minimizes drafts. and stops when the preset time of the OFF timer elapses.

Programme “Dry” (*available on all models) Weekly schedule timer


Dehumidification is microprocessor controlled to prevent abrupt Available in Timer 1 & Timer 2 with operation ON/OFF
and uncomfortable changes in air temperature. Useful for settings programmed for 7 days of the week.
reducing uncomfortable humidity without uncomfortable cooling
of the room.

Cleanliness
BAG Washable saranet filter
BAG Removal of air-borne dust particles through saranet filter ensures cleaner air supply.

BAG
CONTROL
Work and Servicing
ROOM BAG

Comparison between G-way controls and BAG controls


Drain pump mechanism
Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.
Features G-way BAG
Force Off
ON/OFF Pre-charge for up to 7.5 metres
Input Contacts Operating Mode If refrigerant piping length does not exceed 7.5m, there is no need for on-site gas charging. However for any piping length more than
Fan Speed 7.5m, requires for additional charge.
(Applies for all models)
Set Temperature
ON/OFF Status
Dry Contact
Outputs
Operating Mode
Fault Status
Self diagnosis function (*available on all models)
The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly
Note:
monitored using a microcomputer. This intelligent feature helps to detect faults or malfunctioning in the system and give user a
Communication Bus warning by blinking of the LED light on the unit or display error code on the wired controller.
A 2-way twisted pair cable is used as the communication bus. Recommended cable for communication bus is a pair of screened & shielded, wisted single core wire with
core diameter of 0.5mm to 1.0mm.

13 14
Auto random restart (*available on all models)
Control features
Specifications
If there is a power outage while the equipment is operating, operations will restart randomly (within 180 to 244 seconds) in the same
mode as before the power cut when electricity is restored.
Ceiling cassette
Group control by Network Interface Module (NIM) Capacity PK 2.0 2.5 3.0 3.0 4.0 5.0
You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all Indoor unit FCRN50FXV14 FCRN60FXV14 FCRN71FXV14 FCRN71FXV14 FCRN100FXV14 FCRN125FXV14
be the same and on/off will be simultaneous.) Model Outdoor unit RN50CXV1A4 RN60CXV1A4 RR71CXV1A4 RR71CXY1A4 RR100DXY1A4 RR125DXYA14
Decoration panel BC50F2XW4
External command control using G-way or BAG Nominal cooling capacity
Btu/hr 18,500 23,000 28,000 28,000 36,000 42,000
Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) kW 5.4 6.8 8.2 8.2 10.6 12.3
room. Nominal total input power W 1,760 2,050 2,930 2,900 3,660 4,110
Nominal COP W/W 3.08 3.29 2.80 2.83 2.88 3.00
Power supply V/Ph/Hz 220-240/1/50 (power from outdoor) 380-415/3/50 (power from outdoor)
Airflow (H/M/L/Q) cfm 730/620/510/360 840/700/560/440 890/760/620/490 890/760/620/491 1030/870/730/580 1120/1030/890/760
Options Sound pressure level (H/M/L/Q) dB(A) 38/35/33/29 39/37/34/31 41/38/35/32 41/38/35/33 46/41/37/34 48/45/41/37

Indoor unit
Unit mm 246x840x840 246x840x840 246x840x840 246x840x841 288x840x840 288x840x840
Dimensions
Fresh-air intake kit (HxWxD) with decoration panel mm 301x950x950 301x950x950 301x950x950 301x950x951 343x950x950 343x950x950
You can provide air-conditioning with fresh air from outside. Unit kg 22 22 22 22 25 25
Machine weight
It is convenient for places where a ventilation fan cannot be installed. decoration panel kg 5 5 5 5 5 5

Note: * Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally. Sound pressure level dB(A) 52 52 56 56 58 60
Dimensions (HxWxD) mm 651x855x328 651x855x328 753x855x328 753x855x329 852x1030x400 852x1030x400

Outdoor unit
Machine weight kg 43 47 57 56 71 95
Liquid (Flare) mm 6.35 6.35 9.52 9.52 9.52 9.52
Piping connections
Gas (Flare) mm 12.70 15.88 15.88 15.88 15.88 15.88
Max. interunit piping length m 30 30 45 45 50 50
Max. installation level difference m 15 15 25 25 30 30
1. Rated cooling capacities are based on the following conditions: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; piping length: 7.5m

Floor standing
Capacity PK 3.0 3.0 4.0 5.0 6.0
Indoor unit FVRN71BXV14 FVRN71BXV14 FVRN100BXV14 FVRN125BXV14 FVRN140BXV14
Model
Outdoor unit RR71CXV1A4 RR71CXY1A4 RR100DXV1A4 RR125DXY1A4 RR140DXY1A4
Btu/hr 29,000 28,000 36,000 42,000 55,000
Nominal cooling capacity
kW 8.5 8.2 10.6 12.3 16.1
Nominal total input power W 2,900 2,850 3,550 4,100 5,490
Nominal COP W/W 2.93 2.88 2.97 3.00 2.94

Power supply 220-240/1/50 380-415/3/50


V/Ph/Hz
(power from outdoor) (power from outdoor)
Airflow (H/M/L) cfm 675/625/530 675/625/530 1035/945/845 1035/945/845 1170/1085/985

Indoor unit
Sound pressure level (H/M/L) dB(A) 44/42/39 44/42/39 49/47/44 49/47/44 54/53/51
Dimensions (HxWxD) mm 1850x600x270 1850x600x270 1850x600x350 1850x600x350 1850x600x350
Machine weight kg 42 42 45 45 51
Sound pressure level dB(A) 56 56 58 60 65
Outdoor unit Dimensions (HxWxD) mm 753x855x328 753x855x328 852x1030x400 852x1030x400 852x1030x400
Machine weight kg 57 56 71 95 105
Liquid (Flare) mm 9.52 9.52 9.52 9.52 9.52
Piping connections
Gas (Flare) mm 15.88 15.88 15.88 15.88 19.05
Max. interunit piping length m 45 45 50 50 45
Max. installation level difference m 25 25 30 30 25

1. Rated cooling capacities are based on the following conditions: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; piping length: 7.5m

15 16
Note: Note:

17 18