INVEN flO AC. CH-60s2 Hergiewil Etror Description P' oRn ELEVATORS “GEGRS, TOM Table of contents Description Page E00. Attempt to start not allowed 4 £01 Attempt to restart not sliowed ......4 E02 Overtemperature .. 4 £03. SW warning s s £04 DL overvol srigg 5 E05 DL overvoli Ls EOS DC link undervottage 6 £07 Control Ha:dware command wrang .6 £0 Charging OC ling failure . £09. Discharging OC link failure 7 E10. Current loop not OK 7 EM Dea a EAE Thik contactor failure a ea" Charge contactor failure 8 E14 Current difference warning 9 E15 SWencoder warning 9 E16 Over current warning 9 E17 Over speed warning 0 EIE Start aireetion wrong 10 06.94 Aco Description E4P Speed reference warning £20 —Time control motor exceeded E21 Receive UART failure E22 E23 E26 sssage source failure Message length failure Receive state wrong Transmit state wrong EPROM checksur fats RAM failure Board battery failure RAM checksum failure Watchdog |. Transmit failure ss. Open safety circuit HW encoder warning Exception vector Contactor time exceeded Driver print power faiture .. Overtemperature bral esistor Page Training Center, Ebikon 18 INVENTIO AG DAI: (CH-6652 Hergiswi Error Description PYF Copyright © 1996 [All rights reserved. No part ofthis publication may be reproduced, stored of ansmittes in any form without the written permission of the copyright owner. Application for such permission should be addresses to: INVENTIO AG (CH-6052 Hergiswil First edition, June 1994 06.94 Aco Training Center, Ebikon 185 139 € INVENTIO AG, prive Error Description PVF CH-6052 Hergiswil snoemansenantiesrenesa es ae ——— — — — si $2 f \ | 3 Bild 1: 7-segment display with buttons $1 and S2 on prot PVF Remark: The most recent error is memorized and displayed until the buttons St and S2 are sintdl- taneously pressed (reset of display) ‘ INVENTIO AG CH-6052 Hergiswal came sce ra E00 Description: This error can only be detected at the start of the 1st trip and usually occurs when 1 or more fatal errors were detected during either the stand-still or boot-phase. Re mae ttempt to start not allowed” Qslarinotalowed: ee Pos: le error causes: Actions to be taken’ a) Gne of more of the following errors were de- ~Check the corresponding error de- tected: £26, E27, £29, £30. scription. [E01 Attem Description: This error can occur of the start of any trip and includes that a fatal error has already been detected and stored. Possible error causes So peee 730 V. Checked at start and every 10 ms during the trip by software, Possible error causes: Actions to be taken: a) Variodyn 70: Malfunction of the Brake Chopper, + Check Print TBR Brake Resistor. b) Variodyn 100/140 has its own control circuits and + ignore this monitoring function is redundant, 05 DI Lovervolt™ Description: DG link voltage above upper limit. Could be preceded by E04, Can also be produced by Charge and Test DC link functions with CAD! ” Possible error causes: a) See E04, INVENTIO AG DRAINS CH-605 Hergiswil Error Description PVF fevelDGinkundenollage 0 Description: 1.) OC link voltage below lower limit 2.) VE70 may be produced by current loop test with CAI, ken: ns to be Possible error causes: Ae a) The charge- or input-coniactor bad, or wrong pa- + Check parameters rameters (‘T char on’, T char off,'T inp on’, 'T inp off’, in which case error £06 is combined with error E35, £08, E12 or E13 (Variodyn 70 only), . b) OG link or main supply malfunction. The parame- ter T DCL, time for charging DC link too short, ontrol Hat Description: Internal SW monitoring function. Has nothing to do with physical HW, states and should never occur, Possible error causes: Actions to be taken: a) Wrong program logic. + Contact VX Center. b) Run-time failures. | £08. Charging DC link failure. Description: Occurs if the DC link cannot be charged at the beginning of a trip or during a test function, o Possible error causes Actions to be taken: a) Input contactor or charge contactor malfunction, - Check input or charge contractors in which case this error appears together with (SGRW, SGA). error £12 or £13. b) Wrong feedback from one of these contactors. + Check auxiliary contacts and wiring, ©) Converter power supply problems + Check converter power supply. « d) Wrong PVF parameters, concerning input- and . load-contactor timing 09.94 Ao INVENTIO AG CH-6052 Hergiswi ee ’ DRIVE : Error Description PVF SRN Description: This failure may occur during ‘Test current loop’ and "Test DC link’ functions started from CADI. The command to switch-off both charge- and:input- contactors is issued but the DC link voltage does not decrease. With Variodyn 100/140 this error will always occur, because the OC link and contac- tors are not under control of the PVF print. Possible error causes: Actions to be taken: a) Input contactor or charge contactor malfunction, +» Check input and charge contractors in which case this error appears together with SGRW, SGR. error E12 of E13. b) Wrong feedback from one of these contactors. + Check auxiliary contacts on SGRW, sca Description: 1.) Feedback from LEM's missing. 2.) VF 70 only: CADI test loop function detects difference between IST-and REF out- side tolerance. Poss! le error causes: Actions to be taken: a) The feedback cable X1 bad or not connected in its socket b) Interruption in the current toop, any of the com- ponents: power IGBT’s, motor supply in cables, motor wiring. LEM's Malfunction or wrong instal: “ lation, ¢) The shortcut circuit monitor system at the driver print has triggered. @) Wrong current measurement resistors on PVF. «Check print e) Wrong PVF parameters ‘Is ADC12 res’ orfand ‘Is ADCE res’ f) The cable X6, link from PVF to the driver prints, bad or wrong wired : INVENTIO AG ORIVE Ch-6052 Hergiswil Error Description PVF Natramenmeriemate ac Description: Current value not zero at end of trip. Possible error causes: Actions to be taken: a) + Contact VX Center EiaupuLGone a E12 Inputcontactor failure Description: 1.) Input contractor (SGR) not responding to switch on signal 2.) Input contractor (SGR} not responding to switch off signal Possible error causes: Actions to be taken: a) Input contactor failure (Variodyn 70.only). -= Check contractor coil (SGA) b) Wrong feedback. X3.4 andlor X4.10 wrong wir- + Check auxiliary contacts, and wiring ing. EAS. Charge. contactor failure Description: 1.) Charge contractor (SGRW) not responding ic switch on signal. 2.) Charge contractor (SGAW) not responding to switch off signal. Possible error causes: Actions to be taken: a) Charge contactor failure (Variodyn 70 only) + Check contractor coil : ») Wrong feedback, X3.3 andlor X4.11 wrong wir.» Check auxiliary contacts and wiring ing. INVENTIO AG ‘ DRIVE CH-s0s2 eHergont Error Description PVF Description: Current difference between actual and reference detected during.a trip. Possible error causes: Actions to betaken: — a) Interrupted-current loop: IGB1 short circuit (Va- Check IGBTS tiodyn 70) o¢ any other monitoring function (Va- riodyn 100/140: overcurrent, overvoltage, etc.) activated. b) The current controller reaches its limits, tuo much current seeded, €) Interrupted motor contactors and wrong TOPT information or SFUE™ (X4.6) See also Possible causes for error E10. : d) Wrong PVE parameters. = + Check parameters Description: Software detects no movement of motor. Possible error causes: Actions to be taken: a) The motor is blocked, mechanical brake is + Check adjustment of brake. closed or opens too slowly, b) The motion of the car is blocked. ©) The motor-tacho opto-electronic bad or tacho + Check motor tacho. disc is slipping -E16 Over current warning Description: Over current detected during a trip. Possible error causes: Actions to be taken: : a) The motor consumes to much elect. energy: the + Check machine and mechanical brake mechanical brake does not open properly; the Check car & counter weight are bal- car is overloaded; wrong counterweight or bal- anced. ance. b) Wrong PVF parameters + Readjust PVF parameters. INVENTIO AG cone 7, CH-6082 Hergiswil Error Description PVF [Eig Over speed warning 5 7 Description: Overspeed detected during PVF test trip. Note: This monitoring function is inactive during normal operation, i.e. if PVF is running together with an interface print. Poss! le error causes: ions to be taken: a) Must not occur in normal installations. + Contact VX Center foo le ee Description: Car moves in wrong direction. Possible error causes: Aci ns to be taken: a) The motor leads-in or motor-tacho wrongly wired, - Check motor direction. b) Wrong LMS data. a ©) The caris overloaded. : Check LMS system. Check car load, ) Wrong counterweight or balance. + Check car is balanced. E19: Speed reference warning Description: 1.) Speed reference telegram not received at start 2.) Speed reference telegram not received during trip. Possible error causes: Actions to be take! a) Loss of communication + Check connection to IVXVF print... b) Problem with the interface print. + Check IVXVE print. 09.94 Aan INVENTIO AG ’ ORIVE (CH-6052 Hergiswil . Error Description PVF soemennssementeoeerzeementnte etn: Description: Software programme loop time exceeded. , Possible error causes: a) Run-time problems. Rec Description: Error detected in UART. Possible error causes: Actions to be taken: in disturbance or interference. . a) Communic Check communication between PVF & ae IVXVF. Check for interference. + Change print PVF if persists. b) Bad UART, | "E22, Message source failure. Ese cS a Ie. Description: Comes in combination with £21, Communication lost Possible error cause Actions to be taken: ( a) See error €21 Description: Comes in combination with £21. Possible error causes: Actions to be taken: a) See error E21 INVENTIO AG os CH-6052 Hersiswal Error Description F _ RRs Description: SW monitoring detects communication failure. Pos: le error causes: Actions to be taken: a) Wrong program logic, run-time failures. + Contact VX Center. Description: Software monitoring detects communication failure. on Possible error cause: Actions to be taken: a) Wrong program logic, run-time failures. + Contact VX Center. Description: Missmatch between EPROM and RAM. Possible error cause: Actions to be taken: a) EPROM or RAM failure, + Change Software. + Change Print. 'b) The previous content of RAM is not deleted be- + Empty RAM (Check instruction) fore exchanging EPROMs. A failure E27 Description: Fault in RAM detected. Possible error cause: a) RAM failure. Actions to be taken: + Change Print na a4 Aen INVENTIO AG ’ ORIVE (CH6052 Hergiswal 5 Error Description PVF hoarseness Ne senescence eee Description: System battery check detects failure. Possible error causes Actions to be taken: - a) Old or too long operated batiery. + Replace battery. Check date on bat. tery. b) Wrong mounting or handling. + Check connections. : ©) Discharged through bad packaging material Tsao E29 RAM chec! Description: RAM check detects failure. Possible error causes: Actions to be taken: 1 a) The previous content of RAM is not deleted be- + Empty RAM (as before) fore exchanging EPROMs. b) RAM failure. + Change Print. Description: At the beginning of the first system boot, the functionality of the HW Watchdog is proved ‘The watchdog should react if the 1ms task is not active. By setting a static flag before the test and checking its value after boot, itis possible to find out that the reset was initiated by the watchdog. « If no reset occurs, watchdog test is unsuccessful. The check function can be started from CADI, too, Watchdog failed during boot phase. Possible error causes: Actions to be taken: a) Watchdog IC failure or wrong mounting + Change print o INVENTIO AG ORIVE C6052 Hergiswil Error Description PVF tera a ences Description: Atleast one byte to send is waiting to be sent. The interrupt is activated but RTS (Ready-to-send) status of the communication UART is not set. Communication failure Possible error caus Actions to be taken: a) The communication line PVF-IVXVF is blocked. + b) Bad UART. ©) IVXVF not responding. Teaalopen saree Description: 1.) After receiving a start command from the interface print or using inputs ORE_U and DRE_D, the state of motor contactors SH1 is proved. If they are open, this error is generated 2.) During test function ‘check current loop’, started from CADI motor éontactors must be closed If they are not, the current loop is open and the test is finished by issuing this error. 3.) During a trip, if the motor contactors open for the period of time shorter than 10 ms, and close again, a warning is issued to suggest that the PVF controller may get problems to follow reference current values. Subsequent warning or error may be error E14 Ifthe motor contactors become open during a trip, and stay open for longer then 10 ms, no warning is generated. The PVF assumes that such a tip is finished and stops immediately. This is usual situation for the installation or inspection trip Possible error causes: Actions to be taken: a) At the beginning of a trip, motor contactors are. : switched-off before PVF gets'stop command, ‘ after the start command is already received: the car or shaft door contacts, or any other compo- ‘nent in the safety chain not stable. b) Bad TOPT. ©) Wrong wiring of the motor contactors. 90 a4 Aan INVENTIO AG o DRIVE CH-6052 Hergisw e Error Description PVF causes: Actions to be taken: = a) Bad tacho electronic or tacho cable. Disturbance + Check the motor tacho. , z or interference. b) Mechanical vibrations of the tacho plate at the beginning and the end of a trip Cee a Description: M680x0 CPU exceptions are caught by the PVF SW Exception handler module. The processing is passed t6 the ISR which saves the content of all CPU registers and calls funclion to save a ‘high level’ information, too; e.g, trip number, time, etc. Afterwards, this error is generated, and the CPU peripheral is reset. This causes a reset of the CPU ise. For the diagnostic purposes the PVF ‘exception log’ & ‘exception counters’ should be used as well as ‘Warning & Error Logs’ and ‘Warning & Error Counters’ Software monitoring function. Possible error causes: Actions to be taken: a) CPU or peripherals failure. Disturbance or inter- + Change prints. ference. b) Bad power supply. + Otherwise, contact VX Center. Check Uwe. " : INVENTIO AG ORIVE CH-6052 Hergiswil Error Description PVE ‘Seamemmane: Description: During each switching-on or -off of the charge- and/or load-contactor, their logical states are controlled by the monitoring function. Ifany of these states is not defined for longer than ‘max. delay time’ this warning will bbe generated. Same as before Possible error causes: Actions to be taken: a) Bad X4.10 {SGR) of X4.11 (SLKZ) inputs. : b) Bad set of PVF parameters: 't_char on, ‘t char off’, ‘tinp on’, ‘tinp off and "t del’ Pag arm Eprintpowe: Description: During boot cycle of the SWa signal is set to the Power-supply print (UWF) to switch ‘on the relay for the power supply of the inverted driver prints. If the power-supply print cannot supply driver prints, a PWOK signal, which is lead back to the PVF omits. PVF is reset and boot-cycie is started again. If driver prints are not supplied after max. number of retries (currently'3), the SW sets no signal for swithing-on, continues with the boot-process and generates this error. This logic is currently implementable only for Variodyn 100/140. If this failure is gen- erated with the Variodyn 70, it may be a by-product of other power-supply problems. Possible error causes: Actions to be taken: a) Bad power-supply print or wiring, b) Bad driver print(s) or wiring + Check UVVF or change. ©) Power supply problems, grounding (may occur with the Variodyn 70, too) INVENTIO AG CH-6052 Hergisl eee DRIVE 7 Error Description PVE era sist EST Ove Description: Overtemperature check has detected brake resistors overheated. When lift is at standstilit will be blacked if in motion trip will be completes. over 30 sec. emergency stop follows. remains in motion for Possible error causes: Actions to be taken: a) Variodyn 70: Overtemperature on the Invetrer's + Check brake resistor. Malfunction of the Brake Chopper, Brake Resistor. b) Variodyn 70/100/140 wrong wiring of the input + Check connection of thermai KTHBR. signai X4.9. INVENTIO AG o CONTROL, ‘CH-6052 Hergiswit a Error Description RS, PIOG, RC Te .Config ‘Schindler 0 Description: RC CONFIGURATION DATA ERROR. “The cabine print did not receive all the configuration data, or the data contained invalid values. nse to PCT version number request Extra Info: rameter list received from controller (06 = The local PCT checksum is not consistent with data checksum. No error, internal message: the cabin print requested a new configuration. No error, internal message: the cabin print received a new configuration. Possible error causes: ‘Actions to be taken: 1a) Cabine print ID switch not + Check eabine print ID switch correctly set. b) Configuration data not re- + Check it bus connection to contreis. ceived Check if configuration data is loaded on the controller. x 4 . 07.94 AeO Training Center, Ebikon . " 155 186 E INVENTIO AG CONTROL (CH-6052 Hergiswil - Control overview censors mR AaRTOR MORES ¢ 2.5 RC 1.Q (car pcb) Hs 1 fa] ———— — B} 1 1 : 1 nadress decode | LEDs : 1 - LEI) nizal | (xo L050) BY PY Xt t0 EN ao HEPSO [Ret avec xutat H'O [Reamc JL. Fig. ACTO . 07.94 Aeo ‘Training Genter, Ebikon 12 4185 164 . INVENTIO AG (CH-6052 Hergiswil ‘Description: Extra Info: Possible error causes: ‘Source ID: Possible error causes: a) Damaged reversing devi DOOR REVERSING DEVICE ERROR. Error Des CONTROL, scription RS, PIOG, RC ‘The same reversing device was during 5 complete openning and closing cycles at least twice permanently active. 01 = DT-O is permanently active. 02 = RPHT is permanently active. 03 = Radar is permanently active. 04 = (not used) force limiter KSKB is permanently ac pomanenty ave es Actions to be taken: + Check the reversing devices: DOOR CONTR PROBLEM. = Check t jon,of the cabig ive. ‘The status of one of the 24 Volt cabine print outpuls is not as expected or the cabine print power level has dropped below a certain point 01 = Power supply level of the cabin print too low. (02 = Output VAVAT (2nd door speed) jutput VRET (door inspection) Output AVEC (cabine ventilator) Output ALG (cabine light) ‘Output VAMGH (holding-brake) Output VKETSO (light-ray) Output VENABLE (door bridging device) 09 = Output VKSPEPO (lobby radar) None 0: 0: 0: of 7 of Actions to be taken: '2) Defective output or short cir.» Check the wiring of the output. cuit 07.94 Aed Training Center, Ebikon J155 186 Exchange cabine print 13 Schindler 0 aoa . INVENTIO AG 7 (cH-6052 Hergisw . 2.6 PIOC 124.0 (Parallel Inpu/Output Car PCB) : 4 =| fa = x34 BOGGOG) |e. - g & 8 = x42 xitt wort ee Fig. 7: PIOLG 124M ; 07.94 AeO = ‘Training Center, Ebikon a J155 164 E 4 . t= INVENTIO AG CONTROL, (cH-6082 Hergiswi : Error Description RS, PIOG, RC =) Description: DOOR CONTROLLER DEVICE ERROR. ‘One of the devices connected to the cabine print has an error. Extra Info: Identifies which component. Schindler ight ray (PROGARD L) VO-Bus error 03 = JHCT pressed. 04 = JRET pressed. Possible error causes: a) Faulty device + Examine the device and if necessary exchange it. b) Extra info = 2 ‘= Check VO-bus cable, Check /O-bus drivers ¢) Extra Info e) Extra Info = 209 DoorContact Description: _Hand-operated and semi-automatic doors: Shaft-door doesn't close after a close or lack command from the controller. “Extra info: None. Source ID: None. Possible error causes: Actions to be taken: i a) Faulty RTS device * Examine the device and if necessary exchange it, b) Shaft door has been let ‘+ None (close the door) ‘opened 07.94 AeO Training Center, Ebikon A 45 J155 188

You might also like