1 Poles

1.1 Type UB-200 Steel Structure


1.2 Height of pole (Mtrs) 13

2 Insulators
2.1 Type Disc/Pin
2.2 Insulator material Porcelain
2.3 Diameter (mm) *
2.4 Min Creepage distance of each disc (mm) *
2.5 Minimum failing load (KN) *
2.6 Method or attachment between units Ball and Socket
2.7 Ball diameter (mm) *
2.8 Nominal Voltage (kV) 11
2.9 Highest Voltage (kV) 12
2.10 Wet power frequency withstand voltage (KVrms) *
2.11 Power frequency puncture withstand voltage (KV rms) *
2.12 Impulse withstand voltage (KVp) *
2.13 Colour *
2.14 Minimum visible discharge voltage (kV rms) *
2.15 Power frequency puncture withstand voltage (KV rms) *

3 Clamp & Connectors


3.1 Rated Short time current (kA) 13.2 kA for 1 Sec
Depending upon point of application &
3.2 Rated Current (Amp) as per system requirement
Made from cold forged Al. Alloy plate i.e
3.3 Type of Clamps & connectors Extruded Al. compression / Bolted or both as per requirement.

4 ACSR Conductor
4.1 Voltage 11kV
4.2 Code Name *
4.3 Calculated Aluminium area (sqmm) 50
4.4 Wire Strand (Al/Steel) 6/1
4.5 Nominal diameter of strand (Al./Steel) (mm) 3.35/3.35
4.6 Weight (Kg/Km) *
4.7 Calculated Co-eff. of linear expansion per °C *
4.8 Approx. Ultimate Tensile Strength (kgf) *
4.9 Max. DC resistance at 20 °C (Ω/Km) *
4.10 Diameter of conductor (mm) *
4.11 Calculated Modules of Elasticity (kg/sq.cm.) *
4.12 Direction of lay of the outer layer Right hand
Standard according to which the conductor
4.13 will be manufactured and tested *

5 Disconnecting Switch
5.1 Type Mechanically gang operated
5.2 Service Outdoor
5.3 Pole 3
5.4 Rated voltage (Nominal/Maximum) kVrms 11/12
5.5 Rated Frequency 50 Hz+/- 5%
5.6 System Neutral Earthing Effectively Earthed
5.7 Reference Standard IEC
5.8 Rated Insulation Level
5.8.1 Rated lightning impulse withstand voltage kVpeak
a. Across isolating distance *
b. To earth & between poles *
5.8.2 One Minutes Power Frequency Withstand Voltage kVrms
a. Across isolating distance *
b. To earth & between poles *
5.9 Rated Current
5.9.1 Continuous at 40 °C ambient 100Amp
5.9.2 Rated short time current for 1 sec. kArms 13.2
5.9.3 Peak withstand current kApeak *
5.9.4 Rated short circuit making current for Earth Switch kApeak *
5.10 Temperature rise
5.10.1 Design ambient temp. oC 40
5.10.2 Maximum temp. rise over design ambient temp. As per IEC
5.11 Minimum creepage distance mm *
5.12 Operating Mechanism
5.12.1 Main blade Manual
5.12.2 Earth Switch Manual
5.13 Mounting Galvanized Steel structure
5.14 Phase to Phase Spacing mm *
5.15 Minimum clearances mm
a. phase to phase *
b. phase to earth *
5.16 Terminal Connector Bimetallic, clamp type
5.17 Mechanical Terminal Load *

6 LIGHTNING ARRESTER *
6.1 Type Station class, Metal oxide gapless, Heavy duty
6.2 Service Outdoor
6.3 Reference Standard IEC
6.4 System Details
6.4.1 Voltage (Nominal/Maximum) kVrms 11/12
6.4.2 Nos. of Phases 3
6.4.3 Frequency 50Hz ±5%
6.4.4 System Neutral Effectively Earthed
6.4.5 Design ambient temperature ...oC 40
6.4.6 Short circuit current of the system kArms 13.2
6.5 L.A. Rating *
6.5.1 Rated Voltage kV rms *
6.5.2 Permissible continuous operating voltage (COV) kV rms *
6.5.3 Nominal discharge current, 8/20µ-Sec kApeak *
6.5.4 Long duration Discharge class *
Maximum residual voltage at Lightning discharge
6.5.5 current of 8/20 µs wave kV peak *
6.5.6 Maximum switching impulse Residual voltage kV peak *
6.5.7 Maximum steep current impulse Residual voltage kV peak *
6.5.8 Energy absorption capability kJ/kV *
6.6 Insulation Level of arrester housing
6.6.1 1-minute 50 Hz withstand voltage (wet) kV rms *
6.6.2 Lightning Impulse withstand Voltage kV peak *
6.7 Maximum radio interference voltage at 1.1Urated /√3 *
6.8 Partial discharge level at 1.05 COV pc *
6.9 Creepage distance mm/kV *
6.10 Pressure relief current kA *
6.11 Pressure relief class *
6.12 Mounting Galvanized steel structure
6.13 Terminal Connector Bimetallic, clamp type
6.14 Ground terminal *

NOTE: * marks are to be filled-in by the vendor