You are on page 1of 5

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery

Core Effects
Tony McGrail
Doble Engineering Company
Core effect

Nameplate
Configuration Y-D

Coolant Mineral Oil

KV 114 - 16

VA 166 MVA

Tank Type Sealed Conservator


Test Procedure

Core is Magnetized

Broad Spectrum increase in


frequency

HV Open Circuit Test Results


Green: A
Blue: B
Red: C

Image from Doble SFRA for M5200/M5300 V1.3


HV Windings with LV Shorted

• HV with LV windings short


circuited indicate sever
problem with winding
• M5200/M5300 Analysis tool
clearly indicates a warning
throughout the Low
Frequency range: 20Hz-
2kHz
• We expect Short Circuit test
results to have a 0.1 dB
spread at low frequency
Results of Internal Inspection
• Main winding and connections were good
• Core condition was not so good.......

• Core laminations had burn marks along steps due


to overheating. Found nearly all over the core

You might also like