Core Effects Tony McGrail Doble Engineering Company Core effect
Nameplate Configuration Y-D
Coolant Mineral Oil
KV 114 - 16
VA 166 MVA
Tank Type Sealed Conservator
Test Procedure
Core is Magnetized
Broad Spectrum increase in
frequency
HV Open Circuit Test Results
Green: A Blue: B Red: C
Image from Doble SFRA for M5200/M5300 V1.3
HV Windings with LV Shorted
• HV with LV windings short
circuited indicate sever problem with winding • M5200/M5300 Analysis tool clearly indicates a warning throughout the Low Frequency range: 20Hz- 2kHz • We expect Short Circuit test results to have a 0.1 dB spread at low frequency Results of Internal Inspection • Main winding and connections were good • Core condition was not so good.......