CAC ACCESSORIES
0CAA9-01A
LG Airconditioners Product Data
TABLE OF CONTENTS
Table of contents Page
CAC Accessories 1
2 CAC Accessories
Wireless Remote Control
Picture
AHWRHS AHWRCD
AUWRHS AHWRHD
• Applicable to Ceiling Cassette, Ceiling Concealed Duct, Ducted Split & Single
Applicable Models Package (6.25~25RT).
Installation Procedure :-
Mounting on the wall
1. Mount the remote control stand on the wall with the help of screw dri-
ver and screw purchased locally.
CAC Accessories 3
Wireless Remote Control
1. Remove the battery cover from the remote control. Slide the cover
in the direction of arrow.
2. Insert two batteries. Take care about the polarity(+/-) and batteries
should be new.
How to Use :
For Ceiling Cassette :
Point the signal transmitter towards the front panel of the cassette indoor unit (for C, D, E, F Chassis
models) and press any function key. For B chassis point the signal transmitter towards the wired remote
control and press any function key.
4 CAC Accessories
General Central Control
Picture
Power display LED
• Indicate the state of DC
Power supply in central
controller unit. Total Off button
-On : red • Stop all linked units sequentially.
-Off : no signal
- Error mode : blinking Total On button
• Operate all linked units sequentially.
Applicable Models • Applicable to Ceiling Cassette, Ceiling Concealed Duct, Floor Standing, Ducted
Split & Single Package.
CAC Accessories 5
General Central Control
Installation Procedure :
1. Hold the control as shown in the picture than push
the front case slightly and pull front & rear cases in
front & rear direction to separate the case.
2. Set screws to the holes of case.
3. Set the dip switch according to Range of Control as Range of Control 1~16 Set 17~32 Set 33~48 Set 49~64 Set
trolling 17th ~128th indoor unit. Don't remove resis- Range of Control 60~80 Set 81~96 Set 97~112Set 113~128 Set
OFF 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
R66
CH1
S1 S2
6 CAC Accessories
General Central Control
Wiring Schematic :
- Ceiling Cassette
- Ceiling Concealed Duct
- Floor Standing
M M M M M M M M M
1 2 16 17 18 32 113 114 128
CH1
CH2
TB
TA
CH1
CH2
TB
TA
CENTRAL CENTRAL CENTRAL
CONTROLLER CONTROLLER CONTROLLER
#1 #2 #8
- Ducted Split
- Single Package
M M M M M M M M M
1 2 16 17 18 32 113 114 128
CH1
CH2
TB
TA
CH1
CH2
TB
TA
CAC Accessories 7
Zone Control
Case
Main lead wires
Zone Control PCB
Picture
Trans
8 CAC Accessories
Zone Control
Installation Procedure :-
• The control should be mounted to control panel using 4 screws sup-
plied.
• Fasten it to any holes on control panel as long as there is enough
space to install. If necessary drill holes to install on proper position.
• When drilling, ensure that metal swarf does not foul any electronic
components.
Wiring Diagram :
• Connect main lead wires between main PCB and Zone Control.
• Connect thermostat to Zone Control according to thermostat maker's manuals.
• Connect Damper Motor to Zone Control according to Damper Motor maker's manuals.
CAC Accessories 9
Zone Control
L L L L
Indoor Unit
Damper Damper Damper Damper
Trans : 12VA
Zone CH1 Thermostat #1 Motor Motor Motor Motor
(24V/130mA*4) CH2 Thermostat #2
Controller CH3 Thermostat #3 #1 #2 #3 #4
Trans PCB CH4 Thermostat #4
N
COM N N N
COM
COM
COM
AC 24V
Main 24V
PCB 24V
Power Input
24V
AC(L) AC(N)
AC220~240V 50/60Hz
S S S S
Indoor Unit
Damper Damper Damper Damper
Trans : 12VA
(24V/130mA*4) Zone CH1 Thermostat #1 Motor Motor Motor Motor
CH2 Thermostat #2
Controller CH3 Thermostat #3 #1 #2 #3 #4
Trans PCB CH4 Thermostat #4
N
COM N N N
COM
COM
COM
AC 24V
Main 24V
PCB 24V
Power Input
24V
AC(L) AC(N)
L : Live
N : Neutral
AC220~240V 50/60Hz S : Signal
To maintain an adequate flow of air and static pressure through the HVAC system, a by-pass system
can be used that is equipped with a motorized damper and a static pressure control.
10 CAC Accessories
Zone Control
When the area dampers open or close, the static pressure control will open or close the by-pass damper so
as to maintain the adequate static pressure. Dimensions of the by-pass damper depends on the cooling
capacity of the unit.
CAC Accessories 11
Tele Control
Picture
Applicable Models • Applicable to Ceiling Concealed Duct & Floor Standing type of air conditioner.
Installation Procedure :
1. Connect the tele control PCB with main Socket
PCB of Indoor unit through the connecting
wire provided. Tele-Control
PCB ASM
3 Wire
Main PCB
12 CAC Accessories
Tele Control
Socket
Tele-Control
PCB ASM
Telephone Line Plug
System Schematic :-
Multi Plug Telephone Line
Socket
Tele-Control
PCB ASM Normal & ARS Telephone
Telephone Line Plug
Telephone Line
Indoor unit
CAC Accessories 13
Low Ambient Kit
• Even when the outdoor temperature reaches low ambient with low ambient kit
you can get cooling operation.
Functions • As the ambient air temperature rises and falls, the outdoor fan speed increases
and slows down, to produce the variable cooling effect needed to give constant
pressure.
Picture
Applicable Models • Applicable to Convertible, Ceiling Cassette & Ceiling Concealed Duct.
14 CAC Accessories
Low Ambient Kit
Installation Procedure :-
Fixing : - The control should be mounted to control panel within the condensing unit using two screws sup-
plied. Fasten it to any holes on control panel as long as there is enough space to install.
If necessary, drill holes to install on proper position.
Electrical Connections :-
(MOTOR)
MAIN L 1
INPUT N 2 P.C.B.
ROOM
SUPPLY N 3
TO FAN(S) L 4 SW01F
5
PIPE
6
7
8
9 P1 P2
1 = Live input
2 = Neutral input
Sensor 3 = Neutral output (to motor)
4 = Live output (to motor)
5 = Do not use
FROM 4 WAY VALVE 6 = Live from 4 way valve
7 = Neutral from 4 way valve
8 = sensor
9 = sensor
Some condensing units are equipped with two fans. In that case, connect the lead wire of each motor to ter-
minal numbers 3 and 4. But some condensing units also require a separate control for each fan.
Heat Pump Models : - When the Low Ambient Control is to be used with a Heat Pump, the condenser fan
needs to run at full speed during the heating mode, and is only modulated during
the cooling mode.
When fitted to a Heat Pump, terminal numbers 6 and 7 should be wired directly to
the reversing solenoid valve ; in all cases both live and neutral side of solenoid
valve should be connected to the control.
CAC Accessories 15
Low Ambient Kit
Cooling Only Models : - On cooling only units, where a reversing valve is not fitted, terminal numbers 6 and
7 Should be left unconnected.
Fitting the Sensor : - Locate a return bend, two or three bends above a convenient liquid line exit from the
Condenser. This should ideally be chosen with its temperature closest to that of dis-
charge saturation temperature.
Setting the Control : - First check whether switch SW01F is towards pipe or not. If not than slide it towards
pipe.
Rotating part (use a proper tool to rotate) ROOM
F 0 1 F 0 1
E 2 E 2
D 3 D 3
C 4 C 4
B 5 B 5
A 6 A 6
9 8 7 9 8 7 PIPE Opt A
Preset temperature at the condenser outlet can be set by switch S/W P1 and accordingly the fan on /
off temperature will be as follows :
Opt 0 Opt 1 Opt 2 Opt 3 Opt 4 Opt 5 Opt 6 Opt 7 Opt 8 Opt 9 Opt 10 Opt 11 Opt 12 Opt 13 Opt 14 Opt 15
PRESET TEMP 19°C 20.5°C 22°C 23.5°C 25°C 26.5°C 28°C 29.5°C 31°C 32.5°C 34°C 35.5°C 37°C 38.5°C 40°C 41.5°C
FAN OFF TEMP 2°C 3.5°C 5°C 6.5°C 8°C 9.5°C 11°C 12.5°C 14°C 15.5°C 17°C 18.5°C 20°C 21.5°C 23°C 24.5°C
FAN ON TEMP 4°C 5.5°C 7°C 8.5°C 10°C 11.5°C 13°C 14.5°C 16°C 17.5°C 19°C 20.5°C 22°C 23.5°C 25°C 26.5°C
Table : Setting Temperatures ; Controlled by rotating P1
100 Opt F
90 Opt E
Opt F Opt D
80
According to preset temp. - 0 or 1 or 2, Opt C
70 Opt B
.........17, you can read the % speed ratio
Speedratio(%)
Opt A
60 Opt 9
from graph. The variation in % speed ratio is Opt 8
50
changed by position of switch S/W P2. Opt 0 Opt 7
40 Opt 6
30 Opt 5
Opt 4
20 Opt 3
Opt 2
10
Opt 1
0 Opt 0
0˚C
1˚C
2˚C
3˚C
4˚C
5˚C
6˚C
7˚C
Tem C
˚C
Tem C
˚C
Tem C
˚C
Tem C
˚C
Tem C
Tem ˚C
˚
˚
p.-0
p.-1
p.-2
p.-3
p.-4
p.-5
p.-6
p.-7
p.-8
p.-9
p.-1
p.-1
p.-1
p.-1
p.-1
p.-1
p.-1
p.-1
Tem
Tem
Tem
Tem
Tem
Tem
Tem
Tem
Tem
Tem
Tem
Tem
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
Pre
16 CAC Accessories
Low Static Motor
Picture
Installation Procedure :-
Replace the already installed motor with low static motor.
CAC Accessories 17
Drain Pump
Picture
ABDPD/ABDPE ABDPG
18 CAC Accessories
Drain Pump
Step 3. Assemble the drain pump assembly. Step 4. Attach the elbow to the side panel.
Step 5. Connect the hose and tie wrap. Step 6. Connect two lead wires to control box.
CAC Accessories 19
Drain Pump
Step 3. Remove the knock-out from the side panel. Step 4. Assemble the drain pump assembly.
Step 5. Connect two lead wires to control box. Step 6. Close the drainage hole with the provided
cap.
20 CAC Accessories
Drain Pump
Wiring Diagram :
THERMISTOR
BR
TEMP.
INDOOR DRAIN
GN/YL
MOTOR PUMP
YL
BL
BL
OR
RD
BK
BL
FUSE
1(L)
BR 250V10A
BL
2(N)
TO OUTDOOR UNIT
COMP
4 WAY
PIPE
RD Drain Pump Assy THERMISTOR
3
BK
4
FLOAT S/W
5
GN/YL REMOTE
CONTROL
TERMINAL
BLOCK
ZONE
CONTROL
YL
TEMP.
INDOOR DRAIN
GN/YL
MOTOR PUMP
OR
BR
BL
BL
BK
FUSE
250V 8A
1(L) 2(N)
BR
TRIAC
BL
TO OUTDOOR UNIT
COMP
4 WAY
PIPE
VENT
BK
4
FLOAT S/W
BL BR
5
GN/YL REMOTE
CONTROL
TERMINAL
BLOCK T/B
A/CL TELECONTROL/ ZONE OPTION
UNIT CENTRAL CONTROL CONTROL
VENTILATOR
CAC Accessories 21
Drain Pump
Functions
For D,E,F,G&H Chassis Models :
Drain Pump
Thermal insulator
(Local supply)
- To prevent condensate forming over the drain
pipe minimum 5mm thick insulation should be Drainage pipe
applied. (Local supply)
Unit
Correct Incorrect
Drainage Hole
22 CAC Accessories
Electric Heater-Ducted Split
Picture
CAC Accessories 23
Electric Heater-Ducted Split
Installation Procedure :
Duct Flange
3. Assemble the duct flange to the electric heater (In the filter assy kit)
as shown in the figure.
Electrical Wiring :
Control Wiring :
1. Connect control wires(brown) on terminal block
(on PCB) as shown on wiring diagram attached on
control box cover.
Power Supply
Power Wiring : (High Voltage)
2. Connect the wires to high voltage terminal block.
Refer wiring diagram supplied with heater.
24 CAC Accessories
Electric Heater-Ducted Split
Dimensional Drawing:
e
Removable Panel
c
b
Electrical Data :
Applicable Heater Heater Heater Control Power Supply
Model(Ton) Model No. Kw Rating Kw Stages (Phase, Voltage)
3~5RT ANEH0521A 3.6/5.0 5 1 1ø, 208~240V
3~5RT ANEH1021A 7.2/10.0 10 1 1ø, 208~240V
6.25~12.5RT ANEH09B1B 7.8/9.0 9 1 3ø, 208~240V
6.25~17.5RT ANEH18B1B 15.6/18.0 18 1 3ø, 208~240V
15~20RT ANEH18B1C 31.2/36.0 18 1 3ø, 208~240V
15~20RT ANEH36B2C 31.2/36.0 18+18 2 3ø, 208~240V
Note : Heater kW ratings are at 240V.
CAC Accessories 25
Electric Heater-Single Package
Picture
Support
Bracket
Heater Access Panel
Compressor Access Panel
26 CAC Accessories
Electric Heater-Single Package
L2
CAC Accessories 27
Electric Heater-Single Package
Ground
10. Connect power supply wires to high voltage ter-
minal block. Power Supply
Refer to wiring diagram supplied with heater.
Electrical Data :
28 CAC Accessories
Plasma Air Purifier
• To provide odor free, dust free, allergy free, clean & healthy air.
Functions • It not only removes microscopic contaminants & dust but it also removes house
mites, pollen, and pet fur to help prevent allergic diseases like asthma.
ABPAEH(C)
Picture
ABPAGH(C)
ABPAHH(C)
CAC Accessories 29
Plasma Air Purifier
Installation Procedure :
1. Disassemble the angle attached at the return of the indoor unit.
2. Fasten the Plasma Air purifier kit using supplied Screws (M4).
3. Do the wiring as per the wiring diagram provided with Plasma Air Purifier kit.
4. Confirm there is no gap between the indoor unit and Plasma Air Purifier Kit.
5. Reassemble detached angle to the back side of the plasma Air Purifier Kit box.
Dimensional Drawing :
Dimension (mm)
Model
H D W
ABPAHH
230 180 785
ABPAHC
ABPAGH
260 180 1,092
ABPAGC
ABPAEH
ABPAEC 350 180 1,235
ABPAEZ
30 CAC Accessories
Electronic Thermostat
Accessory Model AQETC (Applicable only to Cooling Only model or Cooling Only model with
Name Electric Heater)
Note : Both the thermostat are same. Function of the keys are also same only dif-
ference between the two is marking in words and with symbol.
CAC Accessories 31
Electronic Thermostat
Wiring Diagram :-
Main UNIT
AC230V(L)
1 1
AC230V(N)
2 2
THERMOSTAT
24V TRANS
AC24V(L) R R AC24V(L)
1 1 1
AC24V(N) C C AC24V(N)
2 2 2
FAN G G FAN
3 3 3 INDOOR FAN RELAY
COOL Y1 Y1 COOL
4 4 4 COMP1 RELAY
Installation Procedure :-
Front case
Th
el
ow
er
pa
rt
Lower carefully the
under plate and open Remote
it using a screw controller
Installation (When Cord Buried) driver, etc. body
Step 2. Fix the under plate on the switch box by locally sup-
plied screw.
Take care of deformation of under plate during fixing.
Face of wall
Upper notch
Step 3. Take out the electronic thermostat cord through the
Under plate
fittings & switch box. Remote
control unit
Screw
(Local supply)
Remote
control cord
Step 4. Connect the wiring to the terminal block of the ther- Lower notch
mostat. Switch box
(Local supply)
32 CAC Accessories
Electronic Thermostat
CAC Accessories 33
Manual Hood
Accessory Model
AKHDA
Name
Picture
The manual fresh air adjustment panel with the hood is designed to provide up to 25% percent outside air.
Once the adjustable panel is set and the hood is installed, they will allow a fix quantity of outside air to be
introduced into the conditioned space.
34 CAC Accessories
Manual Hood
Note: Before utilizing CFM mentioned in the shaded area, refer to Table 1 for maximum allowable
fresh air for the unit.
3. Secure the fresh air adjustment panel to the unit end Unit end panel
panel with 2 screws.
Figure 1
4. Using the provided screws, assemble the fresh air
hood, as illustrated in Figure 1.
6. Install the fresh air hood onto end panel of the unit
using the 12 screws. (Installer can secure the hood
by punching on the unit end panel )
CAC Accessories 35
Manual Hood
8. Measure the full load amps of the supply fan motor. If the
amperage exceeds the full load amps, system CFM may
be too high.
Make the necessary adjustments to lower the motor
amperage by ; readjusting the fresh air damper or adjust-
ing the fan RPM.
Dimensional Drawing:
Figure 3
A 24.98 (634.5)
B 28.11 (714)
C 25.91 (658)
D 19.35 (491.5)
36 CAC Accessories
RF Remote Control
Accessory Model
PQRFA0
Name
RF Receiver
Functions
• Anyway Control
- RF remmote controller can be possible to control the air-conditioner with
Boundless & through a wall. (It help you to control the unit anywhere you are!)
- Max reciving length is 20m
Picture
PQRFA0
- Remote Control.............................1EA
- RF Control.....................................1EA
Parts Supplied - Installation Manual .......................1EA
- Battery...........................................2EA
CAC Accessories 37
RF Remote Control
Installation
1. How to Install Password
1. Insert batteries
2. Set Password
NOTE:
If you change the battery then you have to set the password again, in
condition of test operation mode (Push simultaneously hour +
room-temperature key over 3 seconds in wired remote controller.)
38 CAC Accessories
RF Remote Control
Remote
1 control cord
Cord clamper
CAC Accessories 39
Air Guide
Accessory Model
PQAGA
Name
Picture
40 CAC Accessories
Elevation Grille Kit
• When the grill comes down, it does not affect the fan.
Picture
CAC Accessories 41
Branch Distributor
Picture
(Shown PMBD3640)
42 CAC Accessories
Branch Distributor
Specifications :
R410A
Model PMBD3640 PMBD3630 PMBD3620 PMBD7230
Connectable Indoor Units Number of Indoor Units 1~4 1~3 1~2 1~3
Capacity Btu/h 7k/9k/12k/18k/24k 7k/9k/12k/18k/24k 7k/9k/12k/18k/24k 18k/24k/30k/36k
Casing color Paintingless Paintingless Paintingless Paintingless
Powre Source Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V
Power Consumption W 10 10 10 10
Runing Current A 0.05 0.05 0.05 0.05
Dimensions W*H*D inch(mm) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)
Packing Dimension W*H*D inch(mm) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)
Net Weight kg 5.0 4.9 4.8 5.0
Connecting Cable Direction Indoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Direction Outdoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Piping Connection Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
(To Outdoor Unit) Gas inch(mm) 3/4(19.05) 3/4(19.05) 3/4(19.05) 3/4(19.05)
Piping Connection Liquid inch(mm) 1/4 (6.35)*4EA 1/4 (6.35)*3EA 1/4 (6.35)*2EA 1/4 (6.35)*3EA
(To Indoor Unit) Gas inch(mm) 3/8 (9.52)*4EA 3/8 (9.52)*3EA 3/8 (9.52)*2EA 1/2 (12.7), 3/8 (15.88)*2EA
Piping length m - - - -
Piping Elevation m - - - -
Drain hose Unusable
Heat Insulation Both Liquid and Gas pipes
Accessories Hanger EA 4 4 4 4
Screw EA 8 8 8 8
Manual EA 1 1 1 1
R22
Model PMBD5440L PMBD5430L PMBD5420L
Connectable Indoor Units 1~4 1~3 1~2
Combination(Min~Max.) Btu/h 12000~54000 12000~54000 12000~54000
Casing color Paintingless Paintingless Paintingless
Powre Source Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V
Power Consumption W 10 10 10
Runing Current A 0.05 0.05 0.05
Dimensions W*H*D inch(mm) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)
Packing Dimension W*H*D inch(mm) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)
Net Weight kg 5.0 4.9 4.8
Connecting Cable Direction Indoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Direction Outdoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Piping Conntcion Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
(To Outdoor Unit) Gas inch(mm) 3/4(19.05) 3/4(19.05) 3/4(19.05)
Piping Conntcion Liquid inch(mm) 1/4 (6.35)*4 1/4 (6.35)*3 1/4 (6.35)*2
(To Indoor Unit) Gas inch(mm) 1/2 (12.7)*4 1/2 (12.7)*3 1/2 (12.7)*2
Piping Length m - - -
Piping Elevation m - - -
Drain hose Unusable
Heat Insulation Both Liquid and Gas pipes
Accessories Hanger EA 4 4 4
Screw EA 8 8 8
Connector EA - - -
Manual EA 1 1 1
Note :
1. BD unit ↔ BD unit, Indoor Unit ↔ Indoor Unit : Max. Height - 10m
Set up the BD unit and Indoor Unit in 15m.
2. The piping connection must be suit the piping sizes of the indoor unit which will be connected.
(If need, use the connector which is included in the indoor unit)
3. The BD unit should be installed inside the building.
CAC Accessories 43
Branch Distributor
Installation Procedure :
• This unit may be installed suspended from the ceiling or mounted on the wall.
• This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up)
However, it may be freely installed in any direction forward or back, and to the sides.
• Be sure to leave a 600mm square opening for service and inspection as shown in the diagram below, for
both ceiling - suspended installation and wall-mounted installation.
• This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure piping
insulation.
• Service direction is the side B and C
• The piping for the indoor unit may be led around in direction A
• The inclination of side B must be within ±5°C degrees forward or back or to the sides.
Refer to model
specifications
Refer to model
specifications
(298)
(337)
A Ø9.52
250
Ø19.05
245
Suspension bolt pitch.
Main Pipe
B
(36) 50 50 50 30 50
(150)
(38) 50
(111)
(56) 50 50 50 72 300 60
Branch Pipe Cover Control
C
Min 300
Inspection opening
44 CAC Accessories
Branch Distributor
NOTICE :
• This unit has two different installation types:
(1) Ceiling-suspended type and (2) wall-mounted type.
• Choose the proper installation pattern according to the
location of installation.
• The installation location for printed wiring board can be
changed.
Follow the procedure specified in the "CONNECTING
THE WIRING" section to change the location.
(1) Ceiling-suspended type (2) Wall-mounted type
BD unit
Six-sided Nut 15.00
(M10 or M8)
Hanger metal
Flat washer
Hanging bolt
(M10 or M8)
CAUTIONS
• Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again
or cover it with alumium tape.(This is to prevent condensation)
• Be sure to install the unit with the ceiling-sie up.
• Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be
audible.
CAC Accessories 45
Branch Distributor
Connection of Wiring :
• Connect refrigerant pipes and connection wires to the appropriate ports maked with matching
alphabets (A, B and C) on this unit.
• Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor
units to terminal board numbers.(1, 2 and 3) Always fix each ground wire separately with a ground
screw.(See the figure below.)
• After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clamp
on indoor unit side is furnished. Follow the procedure below to install.
• Refer to the circuit diagram on the control cover inside outdoor unit.
NOTICE :
The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.
In Case of 3 rooms
Warning
Do not use tapped
wires, stand wires,
C room A extensioncords, or
starbust connections,
B room B as they may cause
overtheating, electrical
A room C shock, or fire.
CN-PWR
Connection wire for indoor units Connection wire for outdoor units
(H05VV, 4wires, 0.75mm) (H05RV, 4wires, 1.2mm)
46 CAC Accessories
Y Branch
Picture
Y Branch
Pipe fitting :
Y branch
A To Outdoor Unit
A B B To Branch Piping or Indoor Unit
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
Horizontal Facing Facing
plane downwards upwards
Within +/- 10
A
Viewed from point A
in direction of arrow
Within 3 Within 3
CAC Accessories 47
Y Branch
Speciications :
Y branch pipe [unit:mm]
ARBL052S
ø12.7 ø9.52 ø6.35
ø15.88
ARBL052L
ø15.88 ø12.7 ø6.35
ø9.52
ARBL102S
ø12.7
ø15.88 ø12.7 ø9.52 ø6.35
ARBL102L ø19.05
ø19.05 ø9.52
ø12.7
ø15.88 ø12.7 ø9.52 ø6.35
ARBL102G ø19.05
ø19.05
48 CAC Accessories
Header
Picture
Header Branch
Pipe fitting :
A
Header A To outdoor unit
B To indoor unit
C Pipe cutter
CAC Accessories 49
Header
• When the number of Indoor Units to be connected to the branch pipes is less than the number of branch
pipes available for connection then cap pipes should be fitted to the surplus branches.
B
Piched pipe
Horizontal plane
• Joints between branch and pipe should be sealed with the tape included in each kit.
Tape
Insulator
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described
above.
Insulator for cap pipe
Cap pipe
Tape
50 CAC Accessories
Header
Specifications :
Header [unit:mm]
Ø12.7 Ø12.7
Ø19.05 Ø12.7
Ø12.7 Ø15.88
Ø12.7
Ø6.35 Ø9.52 Ø9.52
7 branch Ø6.35
Ø15.88
ARBL057
Ø12.7
Ø19.05
Ø12.7 Ø15.88
Ø9.52
Ø6.35 Ø6.35
Ø15.88 Ø19.05
4 branch
Ø9.52
ARBL104 Ø12.7
Ø28.58
Ø12.7 Ø15.88
Ø6.35 Ø9.52
Ø15.88 Ø6.35
Ø19.05
7 branch
Ø9.52
ARBL107 Ø28.58 Ø12.7
Ø12.7
Ø15.88 Ø6.35 Ø9.52 Ø6.35
Ø15.88 Ø19.05
10 branch
ARBL1010 Ø28.58 Ø9.52 Ø12.7
Ø12.7
Ø15.88 Ø9.52 Ø6.35
Ø15.88 Ø19.05 Ø6.35
CAC Accessories 51
Dry Contact module
It toggles into On/OFF of Automatic Operation when pressing the Reservation Cancel button of the
Wireless Remote Controller in a series of 3 times within 3 minutes, with it facing to the main body.
At first, the Automatic Operation is not set.
1
1 CN-POWER : AC 220V Connector
2 CN-CC : MAIN PCB Connector
3 CN_DRY (L) : DRY CONTROLLER Connector
Picture 2 4 CN_DRY ( SIG ) : DRY CONTROLLER Connector
5 CN_DRY (ERROR CHECK) : ERROR Check
Display Connector
6 CN_DRY( OPER STATE): Operation Display
Connector
3 4 5 6
52 CAC Accessories
Dry Contact module
Installation Procedure :
MAIN
PCB 4 4
3 3
CN-CC CN-CC 2 2
1 1
2 1
2 1 AC 220V
MAIN
PCB 4 4
3 3
CN-CC CN-CC 2 2
1 1
2 1
2 1 AC 220V
BR1
C01A
OSC01B
IC01A
S1
SWITCH
Central Control
(Ex : PHNFP14A0 or PSNFP14A0...)
L1 2 3 4
LED01G
LED02G
LED03G
LED1
ON
U03Y U04Y U02Y
TANS01Y
CN_COMM
C04Y
ZNR01Y
C03Y
- To apply power source through PCB - To apply power source from the outside
DRY CONTACT DRY CONTACT
SUB PCB SUB PCB
CAC Accessories 53
20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355
Seoul 150-721, Korea
Phone: 3777-7969 Fax: 3777-5137/8
http://www.lge.com
Approvals:
EN ISO 9001
BS EN ISO 9001
ANSI/ASQC Q9001
KS A 9001
P/No.: 3828A20346H For continual product development, LG reserves the right to change specifications without notice.
©LG Electronics INC. Printed in Korea. December/2004