Professional Documents
Culture Documents
●● Modular Horizontal
ducted unit
●● Improved comfort
42NH
Original instructions
Contents
1 - FUNCTIONS................................................................................................................................................................................ 4
2 - FEATURES.................................................................................................................................................................................. 4
2.1 - Configuration............................................................................................................................................................................. 4
2.2 - Low noise levels........................................................................................................................................................................ 4
2.3 - Compact design ........................................................................................................................................................................ 4
2.4 - Physical and electrical data at Eurovent conditions............................................................................................................. 5
2.5 - Dimensional drawings.............................................................................................................................................................. 6
3 - MAIN MODULES AND COMPONENTS............................................................................................................................ 8
3.1 - M
ulti-speed fan motor assembly compliant with ErP 2015 regulation............................................................................... 8
3.2 - Water coil.................................................................................................................................................................................... 8
3.3 - One-piece condensate drain pan............................................................................................................................................. 8
3.4 - Filter............................................................................................................................................................................................ 8
3.5 - Fan wiring solutions.................................................................................................................................................................. 8
3.6 - Electric heater (option)............................................................................................................................................................ 8
4 - TECHNICAL SPECIFICATIONS & OPTIONS................................................................................................................... 9
4.1 - Valves (option)........................................................................................................................................................................... 9
4.2 - Filters ......................................................................................................................................................................................... 9
5 - Control (OPTION)............................................................................................................................................................ 10
6 - 42NH PERFORMANCE DATA............................................................................................................................................ 11
6.1 - Cooling capacity - water coil.................................................................................................................................................. 11
6.2 - Heating capacity - water coil.................................................................................................................................................. 14
6.3 - Sound power levels................................................................................................................................................................. 16
6.4 - Electrical data.......................................................................................................................................................................... 17
6.5 - Water coil pressure drop......................................................................................................................................................... 18
6.6 - Air flow data............................................................................................................................................................................ 18
7 - SPECIFICATION GUIDE...................................................................................................................................................... 19
The photograph on the front cover is for illustrative purposes only and is not part of any offer for sale or contract.
The manufacturer reserves the right to change the design at any moment without prior warning.
3
1 - FUNCTIONS Without the rectangular flange inlet (plain inlet), the filter
removal is from the rear.
• The Carrier 42NH is available in different sizes with
2-pipe, 2-pipe plus electric heater or 4-pipe coils, with an
air flow range from 530 to 2800 m3/h, a total nominal
cooling capacity range from 3.7 kW to 12.6 kW and a
nominal heating capacity range from 5.1 kW to 17.5 kW.
• Compact ducted unit, designed for false ceiling
installation.
• Reliable and economical for light commercial and office
applications.
• Low height of 285 mm.
• Compatible with the Carrier 35BD diffuser range.
• Extremely low sound levels for ducted applications.
• Five-speed fan motor offers a wide choice of medium
speeds.
• High-pressure centrifugal fan. Filter
• G1 filters as standard.
• Safe factory-installed electric heater with multiple 2.2 - Low noise levels
capacity stages choices.
• Low water pressure drop with factory-installed valves. In order to further enhance occupant comfort this product
• Factory-installed options (valves and controllers) for fast range offers especially low noise levels. The casing of the
and easy installation in false ceilings. 42NH is made of galvanised sheet steel with full high-
efficiency internal lining for optimised thermal and sound
2 - FEATURES insulation of the unit.
2.1 - Configuration In order to comply with the various local regulations (fire
class) the 42NH is available with both class M1 type
Each of the available sizes can be provided with an insulation (according to NF P 92-507) and Euroclass level
rectangular flange air inlet and outlet (practical to connect B-s3-d0 (according to EN 13501) compliant with British
the fan-coil unit to the air duct network). Class O requirements. It is also equipped with anti-
vibration mounts as standard.
In this configuration filter removal is from below
(trapdoor). 2.3 - Compact design
Filter
4
2.4 - Physical and electrical data at Eurovent conditions
* Eurovent conditions: Entering air temperature = 27°C db/47% rh – entering water temperature = 7°C, water temperature difference = 5 K.
** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling.
*** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 70°C, water temperature difference = 10 K.
5
2.5 - Dimensional drawings
NOTE: All drawings shown have the coil connections on the right-hand side. Units with left-hand connections are
symmetrical.
Size 635 & 645 (with rectangular flange inlet and outlet)
Size 635 & 645 (without rectangular flange inlet and outlet)
6
Size 735 & 745 (with rectangular flange inlet and outlet)
Size 735 & 745 (without rectangular flange inlet and outlet)
7
3 - MAIN MODULES AND COMPONENTS 3.5 - Fan wiring solutions
3.1 - M
ulti-speed fan motor assembly compliant with The fan motor has five speeds, offering the unit greater
ErP 2015 regulation flow control flexibility.
Motor description When ordering, three of the five speeds must be selected to
• Asynchronous motors, 230 V - 1 ph - 50 Hz, 4 poles allow connection of the fan motor in accordance wih the
with internal overload protection. applicable controls (NTC, HDB, Electrical Box).
• Permanent capacitor.
• Class B winding insulation, varnish class F. With the electrical box option, the installer can connect the
unit to a terminal board. The electrical box can be opened
The 42NH have a multi-speed fan motor assembly with with a screw driver.
forward curved, double inlet, double wheel fans.
The electrical box option permits changing the speed
Five speeds are available as standard. Three speeds must be wiring without access to the motor. Three of the available five
selected to allow connection of the fan motor in accordance speeds are connected (minimum speed = 5, maximum speed
with applicable electromechanical or electronic control. = 1).
• Minimum speed : terminal 5
• Maximum speed : terminal 1
• 42NH units can be supplied with Carrier numerical Wiring example: 5-3-1
controls and prewired to a selection of three speeds. Two other speeds available, easy access
• For other fan motor Speed wiring combinaisons refer
to the unit codification.
8
4 - TECHNICAL SPECIFICATIONS & OPTIONS 4.2 - Filters
NOTE: The motor valve assembly is normally closed. • G1 filter : supplied as standard
• G3 filter : metal wire frame.
4.1.1 - Valve actuators
The actuator is available with two or four-way valve bodies
(three-way with integral bypass). It provides an on/off 100.00
1
control and is 230 V a.c. supplied. 2
• Straight valve body with arrow indicating direction of Air Flow m3/h, (l/h)
Air Flow m3/h, (l/h)
flow embossed on valve body Legend
• Nominal size DN 20 for 3/4’’ valve 1. Additional pressure drop - Filter G3 for size 6-5
• Fluid: water and glycol solution (max. 40% glycol) 2. Additional pressure drop - Filter G3 for size 7-5
1
100
2
Pressure drop (kPa)
Pressure drop (kPa)
10
1
100 1000 10000
(0.027) (0.27) (2.7)
Legend
1. 3/4’’ valve for size 6-5 (Kvs = 2.5)
2. 3/4’’ valve for size 7-5 (Kvs = 4.0)
9
5 - Control (OPTION)
Legend
HDB Hydronic Dual Board
NTC New Terminal Controller
X Standard function
O Available as an option
10
6 - 42NH PERFORMANCE DATA
Legend
TC Total cooling capacity (kW)
NOTE: Operating limits: air discharge temperature 11 °C
SHC Sensible cooling capacity (kW) when the unit is installed in an ambient temperature of
SAT Supply air temperature (°C) 27°C dry bulb and 65% relative humidity.
WF Water flow rate (l/h)
NOTE: To convert l/h to l/s, divide by 3600.
11
6.1.1 - Two-pipe water coil (cont.)
Entering/ Size 745
leaving water Relative humidity 50%
temperature, Air flow, m3/h (l/s)
°C 750 (208) 1250 (347) 1600 (444) 1900 (527) 2300 (639) 2600 (722)
Entering air dry-bulb temperature, °C
27 25 23 27 25 23 27 25 23 27 25 23 27 25 23 27 25 23
6-12 TC 6.13 4.90 3.81 9.40 7.49 5.84 11.41 9.14 7.15 12.99 10.47 8.21 15.00 12.10 9.59 16.48 13.30 10.57
SHC 4.12 3.64 3.18 6.47 5.73 5.02 7.98 7.09 6.23 9.20 8.21 7.23 10.77 9.64 8.52 11.94 10.69 9.46
SAT 10.3 10.3 10.2 11.1 10.9 10.6 11.5 11.2 10.8 11.8 11.4 10.9 12.2 11.7 11.0 12.4 11.8 11.1
WF 958 765 595 1469 1171 912 1783 1428 1117 2030 1636 1283 2344 1891 1497 2575 2078 1651
7-12 TC 5.82 4.60 3.54 8.92 7.04 5.46 10.81 8.60 6.69 12.31 9.81 7.69 14.22 11.34 8.96 15.63 12.46 9.89
SHC 3.98 3.50 3.06 6.26 5.53 4.84 7.72 6.85 6.01 8.90 7.93 6.97 10.44 9.30 8.22 11.58 10.32 9.13
SAT 10.8 10.8 10.6 11.6 11.4 10.9 12.0 11.6 11.1 12.3 11.8 11.2 12.6 12.1 11.3 12.8 12.2 11.4
WF 1001 790 609 1534 1211 938 1858 1478 1149 2117 1687 1322 2445 1950 1541 2687 2142 1701
8-13 TC 5.23 4.07 3.10 8.01 6.23 4.81 9.72 7.61 5.92 11.05 8.72 6.83 12.76 10.10 8.00 14.02 11.12 8.85
SHC 3.73 3.27 2.85 5.88 5.18 4.51 7.27 6.42 5.60 8.39 7.45 6.50 9.84 8.75 7.67 10.92 9.72 8.52
SAT 11.8 11.7 11.3 12.5 12.2 11.5 12.8 12.4 11.6 13.1 12.5 11.7 13.3 12.7 11.7 13.5 12.8 11.7
WF 900 700 534 1378 1072 827 1671 1310 1019 1902 1501 1175 2195 1738 1375 2412 1913 1523
10-15 TC 4.10 3.11 2.44 6.27 4.82 3.82 7.66 5.93 4.72 8.75 6.84 5.46 10.13 8.02 6.43 11.14 8.86 7.13
SHC 3.26 2.85 2.43 5.17 4.52 3.81 6.42 5.62 4.71 7.44 6.52 5.46 8.75 7.69 6.43 9.71 8.54 7.13
SAT 13.7 13.2 12.0 14.1 13.4 12.0 14.3 13.5 12.0 14.4 13.5 12.0 14.6 13.6 12.0 14.7 13.6 12.0
WF 705 535 421 1080 830 658 1318 1021 813 1507 1178 941 1745 1380 1107 1918 1524 1227
12
6.1.2 - Four-pipe water coil (cont.)
Entering/ Size 745
leaving water Relative humidity 50%
temperature, Air flow, m3/h (l/s)
°C 750 (208) 1250 (347) 1600 (444) 1900 (527) 2300 (639) 2600 (722)
Entering air dry-bulb temperature, °C
27 25 23 27 25 23 27 25 23 27 25 23 27 25 23 27 25 23
6-12 TC 6.23 5.01 3.91 9.22 7.42 5.79 10.88 8.76 6.88 12.10 9.72 7.69 13.50 10.82 8.65 14.43 11.55 9.25
SHC 4.16 3.68 3.22 6.37 5.67 4.97 7.69 6.85 6.03 8.70 7.76 6.87 9.92 8.87 7.87 10.78 9.63 8.54
SAT 10.1 10.1 10.0 11.2 10.9 10.6 11.8 11.4 10.9 12.3 11.8 11.1 12.8 12.1 11.3 13.1 12.4 11.4
WF 973 782 610 1440 1160 905 1700 1368 1074 1890 1518 1202 2109 1691 1351 2254 1805 1445
7-12 TC 5.89 4.68 3.63 8.71 6.94 5.40 10.29 8.18 6.44 11.43 9.11 7.20 12.76 10.16 8.10 13.64 10.88 8.71
SHC 4.01 3.54 3.09 6.15 5.45 4.79 7.43 6.60 5.82 8.42 7.50 6.62 9.62 8.58 7.59 10.45 9.34 8.25
SAT 10.7 10.7 10.5 11.7 11.4 10.9 12.3 11.9 11.2 12.7 12.2 11.4 13.2 12.5 11.5 13.4 12.7 11.6
WF 1013 805 623 1498 1193 929 1769 1406 1108 1966 1565 1238 2194 1746 1392 2345 1871 1497
8-13 TC 5.32 4.14 3.18 7.85 6.15 4.77 9.26 7.28 5.72 10.29 8.09 6.44 11.46 9.05 7.29 12.24 9.72 7.83
SHC 3.76 3.30 2.88 5.79 5.11 4.47 7.01 6.21 5.43 7.95 7.05 6.18 9.08 8.07 7.07 9.88 8.79 7.66
SAT 11.7 11.6 11.2 12.6 12.2 11.5 13.1 12.5 11.6 13.4 12.8 11.7 13.8 13.0 11.8 14.0 13.2 11.9
WF 915 712 547 1351 1058 821 1593 1252 984 1770 1392 1107 1973 1557 1254 2107 1672 1348
10-15 TC 4.16 3.17 2.50 6.17 4.78 3.80 7.29 5.72 4.58 8.10 6.45 5.19 9.22 7.40 6.00 9.73 7.83 6.38
SHC 3.29 2.88 2.47 5.10 4.47 3.78 6.20 5.44 4.57 7.04 6.20 5.19 8.17 7.17 6.00 8.79 7.67 6.38
SAT 13.5 13.1 11.9 14.1 13.4 12.0 14.5 13.5 12.0 14.7 13.6 12.0 14.9 13.7 12.0 15.0 13.7 12.0
WF 717 546 431 1063 822 654 1255 986 788 1395 1111 894 1588 1273 1033 1675 1348 1099
Legend
TC Total cooling capacity (kW)
NOTE: Operating limits: air discharge temperature 11 °C
SHC Sensible cooling capacity (kW) when the unit is installed in an ambient temperature of
SAT Supply air temperature (°C) 27°C dry bulb and 65% relative humidity.
WF Water flow rate (l/h)
NOTE: To convert l/h to l/s, divide by 3600.
13
6.2 - Heating capacity - water coil
14
6.2.2 - Four-pipe coil, heating circuit
Entering/ Sizes 645
leaving water Air flow, m3/h (l/s)
temperature, 850 (236) 1150 (319) 1450 (402) 1800 (500) 2000 (556) 2200 (611)
°C Entering air dry-bulb temperature, °C
21 20 19 21 20 19 21 20 19 21 20 19 21 20 19 21 20 19
70-60 HC 6.54 6.72 6.90 7.83 8.05 8.27 8.93 9.18 9.43 10.04 10.32 10.60 10.61 10.90 11.19 11.13 11.44 11.75
SAT 43.9 43.4 43.0 41.3 40.8 40.3 39.3 38.8 38.2 37.6 37.0 36.4 36.8 36.2 35.6 36.1 35.4 34.8
WF 575 591 607 689 708 727 785 807 829 883 907 932 933 959 984 979 1006 1033
60-50 HC 4.81 4.98 5.16 5.74 5.95 6.16 6.54 6.78 7.02 7.33 7.60 7.87 7.74 8.02 8.31 8.12 8.42 8.72
SAT 37.8 37.4 36.9 35.9 35.4 34.9 34.4 33.9 33.3 33.1 32.5 31.9 32.5 31.9 31.3 32.0 31.4 30.7
WF 421 436 451 503 521 540 572 593 614 642 666 689 678 702 728 711 737 763
55-40 HC 2.92 3.10 3.29 3.50 3.72 3.94 4.00 4.25 4.50 4.50 4.78 5.07 4.76 5.06 5.36 5.00 5.31 5.62
SAT 31.2 30.8 30.4 30.1 29.6 29.1 29.2 28.7 28.2 28.4 27.9 27.3 28.1 27.5 26.9 27.8 27.2 26.6
WF 170 181 191 204 217 230 233 248 262 262 279 295 277 295 312 291 309 328
50-40 HC 4.21 4.42 4.64 6.01 6.31 6.61 7.02 7.36 7.71 7.77 8.16 8.54 8.67 9.10 9.54 9.28 9.74 10.21
SAT 37.7 37.5 37.3 35.3 35.0 34.6 34.1 33.7 33.2 33.2 32.7 32.3 32.2 31.7 31.3 31.6 31.1 30.6
WF 245 258 270 350 368 385 409 429 449 453 475 498 505 530 556 541 568 595
Entering/ Sizes 735
leaving water Air flow, m3/h (l/s)
temperature, 750 (208) 1250 (347) 1600 (444) 1900 (527) 2300 (639) 2600 (722)
°C Entering air dry-bulb temperature, °C
21 20 19 21 20 19 21 20 19 21 20 19 21 20 19 21 20 19
70-60 HC 6.72 6.90 7.08 9.64 9.90 10.16 11.34 11.65 11.95 12.65 12.98 13.32 14.21 14.59 14.97 15.28 15.68 16.09
SAT 47.7 47.3 46.9 44.0 43.5 43.0 42.1 41.6 41.1 40.8 40.3 39.7 39.4 38.8 38.2 38.5 37.9 37.3
WF 591 607 623 848 871 894 997 1024 1051 1112 1142 1172 1250 1283 1316 1343 1379 1415
60-50 HC 5.11 5.29 5.47 7.20 7.46 7.71 8.35 8.64 8.94 9.19 9.51 9.83 10.13 10.48 10.84 10.73 11.10 11.48
SAT 41.3 40.9 40.6 38.2 37.7 37.2 36.5 36.0 35.5 35.4 34.8 34.3 34.1 33.5 32.9 33.3 32.7 32.1
WF 448 463 479 631 653 675 731 757 782 804 832 861 887 918 949 939 972 1005
55-40 HC 3.55 3.73 3.91 4.99 5.24 5.49 5.75 6.04 6.32 6.29 6.61 6.92 6.89 7.24 7.58 7.27 7.63 8.00
SAT 35.1 34.8 34.4 32.9 32.4 32.0 31.7 31.2 30.7 30.9 30.3 29.8 29.9 29.3 28.8 29.3 28.7 28.1
WF 207 217 228 291 305 320 335 352 368 367 385 403 402 422 442 423 445 466
50-40 HC 3.43 3.60 3.78 4.80 5.04 5.29 5.54 5.82 6.11 6.08 6.39 6.70 6.68 7.02 7.37 7.06 7.42 7.79
SAT 34.6 34.3 33.9 32.4 32.0 31.5 31.3 30.8 30.3 30.5 30.0 29.4 29.6 29.1 28.5 29.1 28.5 27.9
WF 299 314 329 418 440 461 483 508 533 530 557 585 582 612 643 615 647 679
Entering/ Sizes 745
leaving water Air flow, m3/h (l/s)
temperature, 750 (208) 1250 (347) 1600 (444) 1900 (527) 2300 (639) 2600 (722)
°C Entering air dry-bulb temperature, °C
21 20 19 21 20 19 21 20 19 21 20 19 21 20 19 21 20 19
70-60 HC 8.08 8.29 8.51 11.57 11.87 12.19 13.58 13.95 14.31 15.12 15.53 15.93 16.96 17.41 17.86 18.20 18.69 19.18
SAT 53.1 52.8 52.6 48.5 48.2 47.8 46.3 45.9 45.5 44.7 44.2 43.8 43.0 42.5 42.0 41.8 41.3 40.8
WF 710 729 748 1017 1044 1072 1195 1227 1259 1330 1365 1401 1491 1531 1571 1601 1644 1686
60-50 HC 6.07 6.29 6.50 8.67 8.97 9.27 10.17 10.52 10.88 11.30 11.70 12.09 12.66 13.10 13.55 13.58 14.06 14.53
SAT 45.1 44.9 44.6 41.6 41.3 40.9 39.9 39.5 39.1 38.7 38.3 37.8 37.4 36.9 36.4 36.6 36.0 35.5
WF 532 550 569 759 785 812 890 921 952 990 1024 1059 1109 1147 1186 1189 1231 1272
55-40 HC 4.21 4.42 4.64 6.01 6.31 6.61 7.02 7.36 7.71 7.77 8.16 8.54 8.67 9.10 9.54 9.28 9.74 10.21
SAT 37.7 37.5 37.3 35.3 35.0 34.6 34.1 33.7 33.2 33.2 32.7 32.3 32.2 31.7 31.3 31.6 31.1 30.6
WF 245 258 270 350 368 385 409 429 449 453 475 498 505 530 556 541 568 595
50-40 HC 4.07 4.28 4.48 5.77 6.07 6.36 6.75 7.10 7.44 7.49 7.88 8.26 8.38 8.81 9.24 8.97 9.43 9.90
SAT 37.2 36.9 36.7 34.8 34.4 34.1 33.6 33.2 32.8 32.7 32.3 31.9 31.8 31.4 30.9 31.3 30.8 30.3
WF 355 373 391 504 529 555 589 619 649 654 687 721 731 768 806 783 823 863
Legend NOTE: The supply air temperature should be kept below 35°C
HC Heating capacity (kW) in order to avoid the risk of stratification.
SAT Supply air temperature (°C)
WF Water flow rate (l/h)
NOTE: To convert l/h to l/s, divide by 3600.
15
6.3 - Sound power levels
Legend
SUP Supply (dB re = 10-12 W)
RET Return (dB re = 10-12 W)
RAD Radiated (dB re = 10-12 W)
R Fixed speed
16
6.4 - Electrical data
42NH 6-5 (multi-speed version) 42NH 7-5 (multi-speed version)
Speed I P Qv Qv PR PR Speed I P Qv Qv PR PR
G1 Filter G3 Filter G1 Filter G3 Filter
(A) (W) (l/s) (m /h)
3
(Pa) (Pa) (A) (W) (l/s) (m /h)
3
(Pa) (Pa)
R1 1.54 350 643 2315 1 - R1 1.88 408 782 2815 1 -
1.53 348 639 2300 10 - 1.80 391 750 2700 14 -
1.47 334 611 2200 32 - 1.73 377 722 2600 24 -
1.40 321 583 2100 49 - 1.67 364 694 2500 34 -
1.35 309 556 2000 63 6 1.61 351 667 2400 43 0
1.30 297 528 1900 73 22 1.55 338 639 2300 52 12
1.25 286 500 1800 82 36 1.50 326 611 2200 60 24
1.20 276 472 1700 89 49 1.45 314 583 2100 68 35
1.16 266 444 1600 96 60 1.40 303 556 2000 76 46
1.12 257 417 1500 102 70 1.35 292 528 1900 83 56
1.08 248 389 1400 108 80 1.30 282 500 1800 90 66
1.05 239 361 1300 114 90 1.26 271 472 1700 97 75
1.01 231 333 1200 121 100 1.22 262 444 1600 103 84
0.98 223 306 1100 127 110 1.18 252 417 1500 109 92
0.94 215 278 1000 134 119 1.14 243 389 1400 115 101
0.90 207 250 900 140 128 1.10 235 361 1300 121 109
1.07 226 333 1200 127 116
R2 1.40 298 556 2000 1 -
1.04 219 306 1100 133 124
1.31 280 528 1900 31 -
1.01 211 278 1000 138 131
1.23 263 500 1800 52 6
0.98 204 250 900 144 138
1.15 248 472 1700 66 26
0.95 197 222 800 149 144
1.09 234 444 1600 77 40
R2 1.76 384 628 2260 0 -
1.03 222 417 1500 85 53
1.70 371 611 2200 10 -
0.97 211 389 1400 92 64
1.60 350 583 2100 24 -
0.92 200 361 1300 99 75
1.51 331 556 2000 38 8
0.88 190 333 1200 107 87
1.42 313 528 1900 50 23
0.83 180 306 1100 116 99
1.34 296 500 1800 61 37
0.79 170 278 1000 125 111
1.27 281 472 1700 72 50
0.75 161 250 900 133 121 1.20 266 444 1600 81 62
0.70 151 222 800 139 130 1.14 252 417 1500 90 73
0.65 140 194 700 140 133 1.08 240 389 1400 98 83
R3 1.32 274 454 1635 0 - 1.03 228 361 1300 106 93
1.27 264 444 1600 13 - 0.98 217 333 1200 113 102
1.14 240 417 1500 41 10 0.94 207 306 1100 120 111
1.08 229 403 1450 51 22 0.89 197 278 1000 126 119
1.04 219 389 1400 60 32 0.86 188 250 900 132 126
0.99 211 375 1350 66 41 0.82 180 222 800 138 133
0.95 203 361 1300 73 49 0.79 172 194 700 144 140
0.92 196 347 1250 78 56 R3 1.41 300 389 1400 2 -
0.89 189 333 1200 84 64 1.33 283 375 1350 22 8
0.86 183 319 1150 90 71 1.25 267 361 1300 39 26
0.83 177 306 1100 95 78 1.17 253 347 1250 54 42
0.80 172 292 1050 101 86 1.11 239 333 1200 67 56
0.78 167 278 1000 107 93 1.05 227 319 1150 78 68
0.75 161 264 950 113 100 0.99 216 306 1100 87 78
0.73 156 250 900 118 107 0.94 206 292 1050 95 87
0.70 150 236 850 123 113 0.90 197 278 1000 102 95
0.67 144 222 800 126 117 0.86 189 264 950 108 102
R4 1.09 226 304 1096 1 - 0.83 182 250 900 114 108
1.04 218 299 1075 31 15 0.80 175 236 850 118 113
0.99 209 292 1050 53 37 0.77 169 222 800 123 118
0.95 201 285 1025 65 50 0.75 164 208 750 127 122
0.91 194 278 1000 72 58 0.72 160 194 700 131 127
0.88 188 271 975 76 63 0.71 155 181 650 134 131
0.86 183 264 950 80 68 0.69 152 167 600 138 135
0.83 179 257 925 85 73 R4 1.11 229 219 790 0 -
0.82 175 250 900 89 78 1.01 210 208 750 55 51
0.80 172 243 875 94 83 0.90 190 194 700 91 88
0.79 169 236 850 99 89 0.82 175 181 650 107 104
0.76 163 222 800 108 99 0.75 163 167 600 115 112
0.71 153 153 550 119 117
0.70 152 199 715 119 112
0.67 147 139 500 124 122
R5 0.94 188 201 722 2 -
0.65 142 125 450 130 129
0.85 175 194 700 50 43
0.63 139 111 400 137 135
0.78 165 188 675 67 61
R5 0.87 174 149 536 1 -
0.74 157 181 650 77 71
0.80 162 139 500 42 41
0.71 152 174 625 89 83
0.71 148 125 450 81 80
0.68 147 167 600 100 95
0.65 137 111 400 105 103
0.64 140 160 575 111 106
0.60 129 97 350 118 117
0.63 138 158 570 113 109 0.57 123 83 300 126 126
Legend 0.55 118 69 250 132 131
I Current drawn by the fan motor 0.54 115 56 200 137 137
P Power input to the fan motor
Qv Air flow rate
PR Available static pressure
R Fixed speed
17
6.5 - Water coil pressure drop
Water flow rate, l/s 0.14 0.17 0.19 0.22 0.25 0.28 0.33 0.39 0.44 0.50 0.56 0.61
Water flow rate, l/h 500 600 700 800 900 1000 1200 1400 1600 1800 2000 2200
Water coil type Pressure drop (kPa)
Size Two-pipe cooling 5 8 10 13 17 21 30 41 53 68 84 101
635 Two-pipe heating (change-over) 5 7 9 12 15 19 27 37 49 61 76 92
Four-pipe cooling - - - - - - - - - - - -
Four-pipe heating - - - - - - - - - - - -
Size Two-pipe cooling 4 6 8 11 13 16 24 32 42 53 66 80
645 Two-pipe heating (change-over) 4 6 8 10 12 15 22 30 39 50 61 74
Four-pipe cooling 5 8 10 13 17 21 30 41 54 68 84 102
Four-pipe heating 6 8 11 15 19 23 34 46 60 76 94 113
Size Two-pipe cooling 6 8 11 15 19 23 33 45 59 74 92 111
735 Two-pipe heating (change-over) 5 7 10 13 17 21 30 40 53 67 82 100
Four-pipe cooling 7 10 13 17 22 27 39 53 69 88 108 131
Four-pipe heating 7 11 14 19 24 29 42 57 75 95 117 142
Size Two-pipe cooling 4 6 9 12 15 18 26 35 46 58 72 87
745 Two-pipe heating (change-over) 4 6 8 10 13 16 23 32 41 52 64 78
Four-pipe cooling 6 8 11 14 18 22 32 44 57 72 89 107
Four-pipe heating 6 9 12 16 20 25 36 49 64 81 100 120
Static pressure available (Pa) as a function of the air flow, m3/h (l/s)
90
80
70
60
Available
50
40
30
20
R5 R4 R3 R2 R1
10
0
500 1000 1500 2000 2500
(138) (278) (417) (556) (694)
100
90
80
70
60
50
40
30
20
R5 R4 R3 R2 R1
10
0
0 400 800 1200 1600 2000 2400 2800
(0) (111) (222) (333) (444) (556) (667) (778)
AirAir Flow,
m3m/h/h (l/s)
3
18 Flow, (l/s)
7 - SPECIFICATION GUIDE
• Supply 42NH fan coil units in accordance with the • Fans shall be a double-inlet centrifugal forward-curved
certified drawings. type.
• The performance of each 42NH unit shall conform to • 42NH units shall be suitable for connection to electro-
the published technical and performance data. nic controllers (wall-mounted thermostats) that allow
• The casings of 42NH units shall be made from galva- fan speed changes to adjust the unit’s heating and
nised sheet steel, thermally and acoustically insulated, cooling capacity.
and shall be provided with adequate access for service • Electrical connections carried out on 42NH units shall
and maintenance. 42NH units shall be provided with be the quick-connection type in order to simplify
suspension lugs with rubber anti-vibration mounts. maintenance. A plastic cover shall protect the terminals.
• 42NH units shall be equipped with either a cooling/
heating changeover coil, a monobloc heating and Numerical control
cooling coil or a cooling coil and an electric heater. • The numerical controls shall use the CCN (Carrier
The water coils shall be provided with manual air Comfort Network) communication protocol.
purge valves. • These controls shall have the following functions:
• The cooling and heating coils shall be made from - Control of the 42NH fan speed.
copper tubes and aluminium fins. The maximum water - Control of the water flow through the on/off type
side working pressure shall not exceed 10 bar two or three-way valves with reference to internal
(1000 kPa). and external loads, in order to maintain a constant
• The aluminium drain pan beneath the coil and valves ambient temperature in the conditioned space.
shall be monobloc to avoid the possibility of leaks. - Provide on/off control of the resistance wire type
• The two-way or three-way on/off water flow control electric heater.
valves shall be provided with flexible water pipes with - Be controlled by a Zone User Interface.
3/4’’ BSP union nuts to simplify connections on site • The power supply to the controller shall be 230 V a.c.
and maintenance and servicing work. (+6%; –10%) single-phase, 50 Hz, to avoid the need
• 42NH units supplied shall at least be provided with G1 for a transformer. The electric heater shall be
class filters controlled directly from the numerical controller to
• Filter access shall be: avoid the need for a power Triac.
- From below the unit for ducted models,
- From the rear of the unit for non-ducted models.
19
Order No.: 10008-20, 12.2014.
Manufacturer reserves the right to change any product specification without notice. Printed in the European Union.