1 Model TRANE Series R 2 Type of Chiller Water cooled Serew Chiller with VFD Starter 3 Cooling Capacity (Nominal) Tr 450 4 Cooling Capacity (Actual) Tr 420 5 Refrigerant R 134a 6 No of Compressors Nos 1 7 No of Refrigerant circuits Nos 1 8 Type of Motor TEFC SQ. CAGE INDUCTION MOTOR 9 Unit Input Power Supply V , Ph , HZ 415+- 10%/3 Ph/50 Hz 10 Type of Motor Starter VFD 11 COP at AHRI Conditions COP 6.25 12 100% Load IKW/TR on design Conditions IKW/TR 0.64 Cooler Operating Parameters 13 Water Temp. Out/In Deg.F 42/52 14 Flow Rate USGPM 967 15 Fouling Fcator FPS 0.0005 16 Evap Pressure Drop M 8.54 Condenser Operating Parameteres 17 Water Temp. Out/In Deg.F 96.6/88 18 Flow Rate USGPM 1350 19 Fouling Fcator FPS 0.001 20 Cond. Pressure Drop M 4.4 h VFD Starter