You are on page 1of 73

 

Maple Armor 
 
 

FW106, FW106C 
Fire Alarm Control Panel 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installation and Operation Manual 
DOC‐FW106‐UM‐R1.6 

 
Installation and Operation Manual                                                                                                   

TABLE OF CONTENTS 
Control Panel Limitations ................................................................................................................................................... 1 
Agency Listings, Approvals ................................................................................................................................................. 2 
Underwriters Laboratories (UL/ULC) .......................................................................................................................... 2 
Requirements for All Installations ...................................................................................................................... 2 
Requirements for Local Protected Fire Alarm Systems ...................................................................................... 2 
Overview ............................................................................................................................................................................ 3 
FW106/FW106CFire Alarm Control Panel .................................................................................................................. 3 
Board Assembly Diagram ........................................................................................................................................... 5 
FW106/FW106C Configuration .................................................................................................................................. 6 
Specifications and Features ........................................................................................................................................ 7 
System Components ................................................................................................................................................... 8 
Components Overview ....................................................................................................................................... 8 
AMI ..................................................................................................................................................................... 9 
PTU ................................................................................................................................................................... 10 
PCU ................................................................................................................................................................... 11 
ALU ................................................................................................................................................................... 12 
NOU .................................................................................................................................................................. 13 
ROU................................................................................................................................................................... 14 
XNU ................................................................................................................................................................... 15 
Battery .............................................................................................................................................................. 15 
INSTALLATION ................................................................................................................................................................... 16 
Cautions .................................................................................................................................................................... 16 
Control Panel Location ............................................................................................................................................. 16 
Control Panel Installation Notice .............................................................................................................................. 16 
FW106/FW106C Mounting Space ............................................................................................................................ 17 
FW106/FW106C Installation Size ............................................................................................................................. 18 
Cabinet Mounting ..................................................................................................................................................... 19 
Remove Knock‐Outs ................................................................................................................................................. 19 
Battery Installation ................................................................................................................................................... 21 
Unit Address Setting ................................................................................................................................................. 22 
SYSTEM WIRING ............................................................................................................................................................... 23 
Wiring Notes ............................................................................................................................................................. 23 
Power Limiting .......................................................................................................................................................... 23 
Wiring Entering the Enclosure .......................................................................................................................... 23 
Wiring Separation ............................................................................................................................................. 24 
Power Supply Wiring ................................................................................................................................................ 24 
AC Connection .................................................................................................................................................. 24 
Battery Connection ........................................................................................................................................... 27 
Addressable Loop Circuit Wiring .............................................................................................................................. 28 
Addressable Loop Circuit Wiring – Class A ....................................................................................................... 28 
Addressable Loop Circuit Wiring – Class B ....................................................................................................... 29 


   
Installation and Operation Manual                                                                                                   
Notification Appliance Circuit Wiring ....................................................................................................................... 30 
Notification Appliance Circuit Wiring – Class A ................................................................................................ 30 
Notification Appliance Circuit Wiring – Class B ................................................................................................ 31 
Relay Output Circuit Wiring ...................................................................................................................................... 32 
External Network Circuit Wiring ............................................................................................................................... 33 
External Network Circuit Wiring ‐ Class B ......................................................................................................... 33 
Auxiliary Power Output Wiring ................................................................................................................................. 34 
Communication Port Connection ............................................................................................................................. 34 
System Checkout ...................................................................................................................................................... 36 
Before Turning the Power ON ........................................................................................................................... 36 
Power‐up Procedure ......................................................................................................................................... 36 
Troubleshooting ........................................................................................................................................................ 37 
Circuit Trouble .................................................................................................................................................. 37 
Ground Fault ..................................................................................................................................................... 37 
Battery Trouble ................................................................................................................................................. 37 
Common Trouble .............................................................................................................................................. 37 
Operation ......................................................................................................................................................................... 38 
Status handling ......................................................................................................................................................... 38 
Standby Condition ............................................................................................................................................ 38 
Alarm Conditions .............................................................................................................................................. 38 
Trouble Conditions ........................................................................................................................................... 39 
Supervisory Conditions ..................................................................................................................................... 41 
Device, Appliance Handling ...................................................................................................................................... 42 
NAC Activation and Silence .............................................................................................................................. 42 
Device Supervision ........................................................................................................................................... 42 
Detector Monitor.............................................................................................................................................. 42 
Manual Station Response ................................................................................................................................. 43 
Drift Compensation .......................................................................................................................................... 43 
Alarm Verification ............................................................................................................................................. 43 
Positive Alarm Sequence (PAS) ......................................................................................................................... 44 
Two‐Stage ......................................................................................................................................................... 45 
By‐pass .............................................................................................................................................................. 45 
Auto addressing ................................................................................................................................................ 45 
Event History ............................................................................................................................................................ 46 
LED, Buzzer, Buttons ................................................................................................................................................. 47 
LEDs Operation ................................................................................................................................................. 47 
Buzzer Operation .............................................................................................................................................. 48 
Button Operation .............................................................................................................................................. 49 
LCD Display ....................................................................................................................................................... 50 
Lamp Test .......................................................................................................................................................... 50 
Configuration and Maintenance ............................................................................................................................... 51 
PC Configuration ............................................................................................................................................... 51 
Control Panel Access Control ............................................................................................................................ 51 
Control Panel Configuration ............................................................................................................................. 52 
Appendix‐A: Compatible Devices ..................................................................................................................................... 57 
II 
   
Installation and Operation Manual                                                                                                   
Devices for Addressable Loop Circuits ...................................................................................................................... 57 
Appliances for Notification Appliance Circuits ......................................................................................................... 57 
Appendix‐B: Wire Selection Guide ................................................................................................................................... 58 
SLC Wire Selection Guide ......................................................................................................................................... 58 
NAC Wire Selection Guide ........................................................................................................................................ 59 
Annunciator Wire Selection Guide ........................................................................................................................... 59 
Appendix‐C: Quantities of Notification Appliances .......................................................................................................... 60 
Appendix‐D: Battery Calculations ..................................................................................................................................... 61 
Total System Currents Calculations .......................................................................................................................... 61 
Battery Capacity ....................................................................................................................................................... 63 
Appendix‐E: Glossary and Acronyms ................................................................................................................................ 64 
 
   

III 
   
Installation and Operation Manual                                                                                                   
List of Figures 
Figure 1 FW106/FW106C Control Panel ............................................................................................................................. 3 
Figure 2 Assembly Diagram ................................................................................................................................................ 5 
Figure 3 Assembly Diagram (Inside) ................................................................................................................................... 5 
Figure 4 AMI (Front) ........................................................................................................................................................... 9 
Figure 5 AMI (Back) .......................................................................................................................................................... 10 
Figure 6 PTU ..................................................................................................................................................................... 10 
Figure 7 PCU ..................................................................................................................................................................... 11 
Figure 8 ALU ..................................................................................................................................................................... 12 
Figure 9 NOU .................................................................................................................................................................... 13 
Figure 10 ROU ................................................................................................................................................................... 14 
Figure 11 XNU ................................................................................................................................................................... 15 
Figure 12 FW106/FW106C Enclosure Mounting Size ....................................................................................................... 17 
Figure 13 FW106/FW106C Installation Size ..................................................................................................................... 18 
Figure 14 Wiring Separation ............................................................................................................................................. 20 
Figure 15 Battery Installation ........................................................................................................................................... 21 
Figure 16 Unit Address Switch .......................................................................................................................................... 22 
Figure 17 Wiring Terminals Location ................................................................................................................................ 24 
Figure 18 AC Power Supply Wiring ................................................................................................................................... 25 
Figure 19 Ground Wiring .................................................................................................................................................. 25 
Figure 20 AC Power Supply Wiring (Terminal) .................................................................................................................. 26 
Figure 21 Battery Connection ........................................................................................................................................... 27 
Figure 22 Addressable Loop Circuit Wiring – Class A ....................................................................................................... 28 
Figure 23 Addressable Loop Circuit Wiring – Class B ....................................................................................................... 29 
Figure 24 Notification Appliance Circuit Wiring – Class A ................................................................................................ 30 
Figure 25 Notification Appliance Circuit Wiring – Class B ................................................................................................ 31 
Figure 26 Relay Output Circuit Wiring .............................................................................................................................. 32 
Figure 27 External Network Circuit Wiring ‐ Class B ......................................................................................................... 33 
Figure 28 Auxiliary Power Output Wiring ......................................................................................................................... 34 
Figure 29 AMI ................................................................................................................................................................... 35 
Figure 30 LCD (Standby) ................................................................................................................................................... 38 
Figure 31 LCD (Trouble) .................................................................................................................................................... 39 
Figure 32 Alarm Verification ............................................................................................................................................. 43 
Figure 33 Positive Alarm Sequence .................................................................................................................................. 44 
Figure 34 Two‐Stage Alarm ............................................................................................................................................... 45 

IV 
   
Installation and Operation Manual                                                                                                   
List of Tables 
Table 1 FW106/FW106C Module Units .............................................................................................................................. 6 
Table 2 FW106/FW106C Control Panel Specifications ....................................................................................................... 7 
Table 3 System Components .............................................................................................................................................. 8 
Table 4 Battery Space ....................................................................................................................................................... 21 
Table 5 Unit Address Range .............................................................................................................................................. 22 
Table 6 Circuit Trouble ...................................................................................................................................................... 37 
Table 7 Trouble Event Type ............................................................................................................................................... 40 
Table 8 LEDs Operation ..................................................................................................................................................... 47 
Table 9 Buttons Function .................................................................................................................................................. 49 
Table 10 Access Level 0 Operation ................................................................................................................................... 52 
Table 11 Access Level 1 Operation ................................................................................................................................... 52 
Table 12 Access Level 2 Operation ................................................................................................................................... 52 
Table 13 Access Level 3 Operation ................................................................................................................................... 53 
Table 14 Device for Addressable Device Circuits .............................................................................................................. 57 
Table 15 Appliance for Notification Appliance Circuits .................................................................................................... 57 
Table 16 Addressable Loop Wiring ................................................................................................................................... 58 
Table 17 NAC Wiring Table ............................................................................................................................................... 59 
Table 18 Annunciator Wiring Table .................................................................................................................................. 59 
Table 19 Maximum Numbers of NA ................................................................................................................................. 60 
Table 20 System Currents Calculation .............................................................................................................................. 61 
Table 21 Battery Calculation ............................................................................................................................................. 63 
 
 
   


   
Installation and Operation Manual                                                                                                   

Control Panel Limitations 
The FW106/FW106C control panel may not show an alarm condition without compatible initiating devices 
(smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the 
initiation and notification appliances must be compatible with the electrical ratings of the control panel 
and must be properly interconnected. The wiring used for interconnection must be large enough to carry 
the total current for all appliances without excessive voltage drop. Please refer to Appendix‐B: Wire 
Selection Guide for detail. 

The control panel must be connected to a dedicated primary electrical source that has a high degree of 
reliability and adequate capacity for this control panel. The means of disconnecting this power source shall be 
available only to authorized personnel and clearly marked "Fire Alarm Circuit Control". 

A battery set (24V) that has enough capacity to properly operate the system for 24 hours standby and 
30 minutes alarm per UL864 10th Edition (section 69.2.3 and 69.2.5) / ULC‐S527 3rd Edition (section 10.5) or as 
otherwise required by local codes and the AHJ must also be connected to the control panel. These batteries do 
lose capacity with age. Batteries must be replaced when they fail to provide the control panel with the required 
standby and alarm power or after 4 years, whichever happens first. These batteries must be checked for 
performance at least twice a year or more often, if local requirements dictate. 

Even though this control panel was made to last for the expected life of the fire alarm system, parts can fail at 
any time. Therefore, a regular test program should be followed and documented to make sure each part of the 
system is tested, as indicated in Chapter 7 of NFPA 72, and CAN/ULC‐S536, or more often if dictated by local 
code requirements. Malfunctioning units must be replaced or repaired immediately by factory authorized 
service personnel. 

This control panel is designed to show an alarm condition when the initiating devices connected to it 
  detects  specific  conditions.  These  conditions  may  or  may  not  represent  a  life‐threatening  condition. 
Unneeded  evacuation  of  a  building  or  an  area  may  subject  individuals  to  an  unnecessary  hazard. 
Therefore, it is important that the building owner, manager, or representative promulgate, distribute, 
and/or  post  instructions  describing  steps  to  be  taken  when  the  fire  alarm  control  panel  signals  an 
alarm condition. These instructions should be developed in co‐operation with representatives of the 
local authority having jurisdiction and in accordance with the applicable standards. 
 
   


   
Installation and Operation Manual                                                                                                   

Agency Listings, Approvals 
Underwriters Laboratories (UL/ULC) 

Requirements for All Installations 
The general requirements are described in this section. When installing an individual device, refer to the specific 
section of the manual for additional requirements. 
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code, CSA C22.1 Canadian 

Electrical Code Part 1, CAN/ULC‐S524, NBC, NBC, NFC, AHJ, and local code requirements. 

2. Use the addressable smoke detectors listed in the compatibility chart (Appendix‐A: Compatible Devices). 

3. Use UL/ULC listed notification appliances compatible with the FW106/FW106C from those specified in 

Appendix‐A: Compatible Devices of this manual. 

4. A full system verification must be performed every time the panel is programmed or reprogrammed. 

Requirements for Local Protected Fire Alarm Systems 

At least one UL listed supervised notification appliances must be used. 
 
   


   
Installation and Operation Manual                                                                                                   

Overview 
FW106/FW106CFire Alarm Control Panel 
The FireWatcher FW106/FW106C is an intelligent Fire Alarm Control Panel designed for small to medium‐scale 
facilities. The FireWatcher FW106/FW106C is ideally suited for both new and retrofit commercial, institutional, 
and industrial fire detection and notification applications. The only difference between FW106 and FW106C is 
the language. FW106 is in English and FW106C is in French.   
 

      
(a) FW106 (English)                                  (b) FW106C (French) 
Figure 1 FW106/FW106C Control Panel 
 
The FireWatcher FW106/FW106C is an addressable fire control system that meets the requirements of UL 864 
10th Edition, and CAN/ULC‐S527 3rd edition. It can support:   
 4 Addressable Loop Circuits and 1,008 addressable devices/points   
 4 Notification Appliance Circuits 
 5 form C dry relay contacts. 
 
The FW106/FW106C has   
 A 7” color LCD and a resolution of 800×480 
 6 auxiliary function keys 
 9 LED indicators making it the most intuitive fire‐alarm user interface. 
 
   


   
Installation and Operation Manual                                                                                                   

The FW106/FW106C can also connect with up to 110 panels and/or remote annunciators via a CAN bus to form 
a fire emergency detection and notification network system. 
 
Networked panels and/or annunciators can share the following events and manual controls:   
 Event (signal) type: ALARM, SUPERVISORY, TROUBLE, MONITOR, OUTPUT 
 Manual Control type: Signal Silence, Buzzer Silence, Reset, Acknowledge 
 
Event/control sharing can be configured in three modes – Peer to Peer, Group, and Master/Slave. 
 Peer‐to‐Peer 
All panels/annunciators are intended to function as a single system and share events/controls of each 
other.   
 Group 
Panels/annunciators can be assigned into multiple groups. There are two options of event/control 
sharing: 
o “Events & Operation” – Events and controls are only shared within individual group; Events and 
Controls are NOT shared across the groups. 
o “Operation Only” – Events are shared across the network. Controls are shared within individual 
group. Each panel/annunciator can silence troubles locally outside of the group. 
 Master/Slave 
o Only one panel (address #1) can be the Master panel. The Master panel can receive events from all 
networked panels, as well as have controls over all panels. 
o All the other panels are Slave panels. A slave panel can only view events from its own inputs, and 
control its own outputs. 
o All annunciators act like the Master panel. 
 
 
 

   


   
Installation and Operation Manual                                                                                                   

Board Assembly Diagram 
The FW106/FW106C provides modular assemble style. Figure 2 and Figure 3 show the assembly diagram: 

 
Figure 2 Assembly Diagram 
8 slots optional for 
External  Internal  Grounded  ALU/NOU/ROU/XNU
AMI
Door Door Wire

Enclusure

Mounting 
Hole
×4

PCU

Battery

Grounded  PTU
Wire  
Note: Refer to Table 1 for the optional slots for ALU/NOU/ROU/XU 
Figure 3 Assembly Diagram (Inside) 

   
Installation and Operation Manual                                                                                                   

FW106/FW106C Configuration 
The FW106/FW106C function is governed by several modules. All the functional module units are shown in Table 1: 
Table 1 FW106/FW106C Module Units 
Fixed/ 
Module Units Type  Qty.  Notes 
Configurable 

Includes: CPU board, LCD, Keypad, LED, buzzer,
AMI  1  Fixed 
etc. 

 
1  Fixed   
PTU 

PCU  1  Fixed   

One ALU supports one addressable loop circuit 
ALU  1 ‐ 4  Configurable 
and 252 devices.   

NOU  1 ‐ 5  Configurable  One NOU supports two NACs.   

ROU  0‐1  Configurable   

XNU  0‐1  Configurable  For network 

 
Notes: ALU, NOU, ROU, and XNU are all of same dimension and same mechanical interface. 
   


   
Installation and Operation Manual                                                                                                   

Specifications and Features 
The specifications and features of the FW106/FW106C Control Panel are described in Table 2. 
Table 2 FW106/FW106C Control Panel Specifications 
General  Digital signal processor based design, fully configurable from front panel with 
password protection 
Environmental   Operating temperature : 32 ‐ 120F (0 ‐ 49C) 
 Relative humidity : Up to 93% @ 90F (32C) 
 To be installed in normal dry indoor environment only 
Primary Supply   110 ‐ 120 VAC 60Hz (3.86A), or 
 220 ‐ 240 VAC 50Hz (1.96A) 
Secondary Power   Two 12V in series lead‐acid batteries set 
Supply   Charging capacity: 40AH   
Power Outputs  Internal power supply for   
 AMI 
 ALUs and Addressable Loop Circuits 
 NOUs and Notification Appliance Circuits 
 XNUs, External Network Circuits 
 ROUs 
One auxiliary power supply 
 Non‐Resettable/Resettable Power Output (configurable) 
 Power limited 
 24VDC 
 Output current: 500mA in normal standby, 1200mA in alarm 
 Power Factor Rating: 0.35 
 Special application: Compatible devices are the Annunciator Model FW121 / 
FW121C /FW122W / FW122R / FW122CW / FW122CR / FW123 / FW123C and IO 
Module Model FW821. 
Relays Output   One programmable relay 
   4 non‐programmable status relays 
 Status: Alarm, Supervisory, Trouble, Monitor 
 Form C Contact 
 Contact Rating: 2A 30VDC 
 Power Factor Ration:0.35 
Notification Appliance   Total of 10 circuits supported, total power available 8A 
Circuits   2 Class A or 2 Class B circuits on each NOU 
 Maximum Current: 2A per NAC circuit 
 Alarm Voltage: 24V nominal 
 Bell code: Temporal 3 
 Panel supports one regulated 24 VDC NAC, or up to 10 special application 24VDC 
NAC. Refer to Table 20 for specific appliances/devices.   
 Max line loss: 1.8 V. 
   


   
Installation and Operation Manual                                                                                                   

Network Circuit   Class B circuit 
   For up to 110 panels and/or remote annunciators connection 
 Communications protocol: CAN 
 Max. line capacitance = 0.05 uF 
 Max. line resistance = 25 Ohm 
Addressable Loop   Maximum Current (short ): 0.4A 
Circuits   Class A/Class B circuit 
   252 addresses: detectors and modules max 
 Output voltage range: 20.2V ~ 26.2V 
 Maximum normal standby current: 100mA 
 Maximum alarm current: 220mA 
 Max. line capacitance = 0.1 uF 
 Max. line resistance = 10 Ohm 
 

System Components 

Components Overview 
Table 3 describes the FW106/FW106Ccomponents. 

Table 3 System Components 

Model  Description  FW106/FW106C Components

FW201/FW201C  AMI(Advanced Machine Interface)  √ 

FW391  PTU(Power‐supply Transformer Unit)  √ 

FW397  PCU (Power‐supply and Charger Unit)  √ 

FW327  ALU (Addressable Loop Unit)  √ 

FW337  NOU (Notification Output Unit)  √ 

FW347  ROU (Relay Output Unit)  √ 

FW357  XNU(External Network Unit)  √ 

 
   


   
Installation and Operation Manual                                                                                                   

AMI 

The AMI is the main control unit of FW106/FW106C panel, which integrates the CPU board, 4 Signal status LEDs, 
5 system status LEDs, 4 navigation buttons and 1 enter button, 6 functionality buttons and a buzzer.   

 
(a) FW201 

 
(b) FW201C 

Figure 4 AMI (Front) 

   
Installation and Operation Manual                                                                                                   

 
Figure 5 AMI (Back) 

PTU 

The PTU contains an internal transformer, which converts 110‐120VAC, or 220‐240VAC input to 24VAC output to 
PCU. 
 
 
110-120 VAC, 60Hz, 3.86A
Or 220-240 VAC 50Hz, 1.96A  24VAC

 
Figure 6 PTU 
 
110‐120VAC or 220‐240VAC input is optional. A slide switch is used to fulfill this 
  function. Please refer to Power Supply Wiring section for switch usage information. 

 
10 
   
Installation and Operation Manual                                                                                                   

PCU 

 Provide power supply output to the system (AMI, ALU, NOU, ROU, XNU, Addressable Loop Circuits, 
Notification Appliance Circuits, Relay output, Network circuits).   
 Terminals BAT+ and BAT‐ connect two lead‐acid batteries (12VDC) in series.   
 Maximum Charge Voltage: 27.8 VDC 
 Maximum  Charge  Current:  3A.  Sufficient  battery  charging  capability  is  available  to  charge  40AH  sealed 
lead‐acid batteries within code requirements for up to 24 hours standby plus 30 minutes alarm. 
 Use a microprocessor‐controlled transfer circuit to switch power supply for the system to standby batteries 
when AC power is off or low.   
 Communicate to the AMI to report fault conditions.   
 PCU address is set by the rotary switch on the board. The default is "1". 
 

 
Figure 7 PCU 
 
The PCU must be set to a correct address before use. Please refer to Unit Address 
  Setting section for detail. 

 
 
 
   

11 
   
Installation and Operation Manual                                                                                                   

ALU 

 One ALU can support one addressable loop circuit, which supports up to 252 points of addressable devices.   
 Initializes and operates all devices residing on the loop and communicates all relevant devices and event 
information, such as alarms and troubles, to the System CPU.   
 Circuit topology support: Class A or Class B.   
 ALU address is set by the rotary switch on the board. The valid address range is 1~4.   
 
Addressable Loop
 
Circuit

 
Figure 8 ALU 
 
The ALU must be set to a correct address before use. Please refer to Unit Address 
  Setting section for detail. 

 
   

12 
   
Installation and Operation Manual                                                                                                   

NOU 

 One NOU can support two independent notification appliance circuits. 
 Circuit topology support: Class A or Class B.   
 Maximum Current: 2A per NAC circuit, 4A total per NOU 
 NOU address is set by the rotary switch on the board. The valid address range is 1~5.   

 
Figure 9 NOU 
 
The NOU must be set to a correct address before use. Please refer to Unit Address 
  Setting section for detail. 

   

13 
   
Installation and Operation Manual                                                                                                   

ROU 

 One ROU card supports five dry contact relays. 
o Alarm Relay 
o Supervisory Relay 
o Trouble Relay 
o Monitor Relay 
o Programmable Relay 
 The relay contacts are Form C style. 
 ROU address is set by the rotary switch on the board. The valid address range is 1.   
 

 
Figure 10 ROU 
 
The ROU must be set to a correct address before use. Please refer to Unit Address 
  Setting section for detail. 

 
   

14 
   
Installation and Operation Manual                                                                                                   

XNU 

 TheFW106/FW106C control panel communicates to panels/annunciators, up to 110 nodes on a network. 
 Circuit topology support: Class B.   
 XNU  address  is  set  by  configuration  from  the  panel  or  configurator.  The  valid  address  range  of  the 
FW106/FW106C or a compatible annunciator is 1 to 110. 

Figure 11 XNU 

The XNU must be set to a correct address before use. Please refer to Unit Address 
  Setting section for detail. 

Battery 

FW106/FW106C can support 40 AH sealed lead‐acid batteries within code requirements for up to 24 hours 
normal standby plus 30 minutes alarm. 

Batteries must be replaced when they fail to provide the control panel with the required standby and alarm 
power or after 4 years, whichever happens first. 

Please refer to Battery Calculations to select an appropriate Battery Capacity. 
15 
   
Installation and Operation Manual                                                                                                   

INSTALLATION 
Cautions 
1. Remove the PCB for any procedure that may cause dust, metal shavings, grease, or such matter to affect the 
operation of the boards or get in contact with the units.   

2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring 
and programming jumpers. 

3. Group the incoming wires through the top of the enclosure. For easy identification and neatness use a wire 
tie. 

4. DO NOT insert cables through bottom of the box. This space is reserved for Batteries. 

Control Panel Location   
The control panel should be located near an exit at ground level where the normal ambient temperature is 
maintained within the control panel specification (see the Specifications and Features section). The unit should 
be in an area free of dust, vibration, moisture, and condensation. Any auxiliary battery box or other accessory 
not connected through a protective device or a circuit designed for remote connection must be within 20 ft. and 
in the same room, connected through the electrical conduit. 

Control Panel Installation Notice 
The cabinet must be fastened securely to a clean, dry, shock‐free, and vibration‐free surface in a protected 
environment. Consider the following when mounting the cabinet: 

 Mounting height for visual and manual access to the Display Board 
 Weight and size of cabinet 
 Local mounting codes 
 

When mounting the cabinet, position the cabinet clear of obstructions so that the door can open freely and 
indicators and controls are easily accessible. 

The fire alarm control panel must be mounted in a properly accessible location, as required by the applicable 
codes and the AHJ.   

Installation must be done by qualified personnel who have thoroughly read and who understands these 
instructions.   

   

16 
   
Installation and Operation Manual                                                                                                   

FW106/FW106C Mounting Space 
The FW106/FW106C cabinet can be surface‐mounted or flush‐mounted. 

Do NOT flush mount in a wall designated as a fire separation. 
 

 
Figure 12 FW106/FW106C Enclosure Mounting Size 
17 
   
Installation and Operation Manual                                                                                                   

FW106/FW106C Installation Size 

 
Figure 13 FW106/FW106C Installation Size 
   

18 
   
Installation and Operation Manual                                                                                                   

Cabinet Mounting 
To install the cabinet: 

 Select a clean, dry, shock, and vibration‐free surface in a protected environment. 
 Position the cabinet clear of obstructions so that the front door opens freely and the controls and 
indicators are easily accessible. 
 Mark the locations of the two upper mounting bolts of the cabinet on the wall. 
There are two key‐shaped cutouts on the top of the back box. Make sure the end with 
  the two key‐shaped cutouts is on top when installing the back box. 
 
 Drill the two holes marked in the previous step and screw in the top bolts, leaving a small gap between 
the wall and each top bolt. 
 
Choose a screw type and length able to support the control panel, options, and battery 
  set. You may need a different screw type depending on the wall material. 
 
 Place the cabinet over the two top bolts and allow it to slide down over the bolts. 
 Mark, drill, and install the two bottom bolts in the cabinet. 
 Tighten all four bolts securely against the back wall of the cabinet. 

Remove Knock‐Outs 
Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entry points. The optional 
knockout locations and quantities are shown in Figure 14. The power limited and non‐power limited conductors 
must be separated. In order to maintain the minimum separation, follow the wire routing shown in Figure 14. At 
least 1/4 in.is required between the non‐power limited and power limited conductors. Power limited and 
non‐power limited wiring must be run in a separate conduit.   

Attach conduit (if required) and run wires as required. Label each field cable for future reference. 

Basic system wiring and detector positioning must be done in accordance with NFPA 72 or other applicable 
codes and instructions from the appropriate local authority having jurisdiction. Unit connections and limitations 
are as indicated on the wiring diagrams included in the SYSTEM WIRING section of this manual. 

19 
   
Installation and Operation Manual                                                                                                   

Figure 14 Wiring Separation 
   

20 
   
Installation and Operation Manual                                                                                                   

Battery Installation 
 Use the battery calculation chart to determine the battery capacity and size. Place the batteries in the 
space provided in the bottom of the enclosure. 
 Refer to Table 4 to determine the maximum available battery space. 
   
Table 4 Battery Space 
  mm  inch 
Length (for 2 batteries)   410  16.14 
Width   168  6.61 
Height   200  7.87 
 
 

Battery 
position 

 
Figure 15 Battery Installation 
 
   

21 
   
Installation and Operation Manual                                                                                                   

Unit Address Setting 
Units (ALU, NOU, ROU, PCU) have an internal rotary switch to set an address. The rotary switch is located at the 
bottom of each unit’s cover.   

 
Figure 16 Unit Address Switch 
 
XNU’s address should be programmed on the panel’s attribute screen (Refer to Programming Manual 
DOC‐FW106‐PM for details) 
 
The unit must be set to an appropriate address before use. The valid address range is listed in Table 5. 
 
Table 5 Unit Address Range 
Unit Type Address Range 

ALU  1~4 
NOU  1~5 
ROU  1 
PCU  1 
XNU  1~110 
 
 
 
 
 
 
 
22 
   
Installation and Operation Manual                                                                                                   

SYSTEM WIRING 
Before connecting the field wiring, check the wiring for opens, shorts, grounds, and stray voltages. 

WARNING 
Damage may result if a high‐voltage insulation tester is used on wiring while connected to the control panel 
and field devices. 
 
Terminate the field wiring to the main board in accordance with the diagrams in the SYSTEM WIRING section 
and in the system design documents. 

All wiring must be in accordance with local codes, National Electrical Code, and Canadian Electrical Code. 
 

Wiring Notes 
Basic system wiring and detector locations must be in accordance with NFPA 72 and CAN/ULC‐S524 or other 
applicable codes and instructions from the appropriate local authority having jurisdiction. 

Devices that may be satisfactorily used with the control panel are shown in the Appendix‐A: Compatible Devices. 
Wire reference data are listed in Appendix‐B: Wire Selection Guide. 

Power Limiting 
In accordance with NEC Article 760 and UL 864, all power limited fire protective signaling conductors must be 
located at least 1/4 inch away from all of the following wiring located within a control panel: 

 Electric light 
 Power 
 Class 1 or non‐power limited fire protective signaling conductors 
To meet these requirements, the following guidelines must be observed when installing modules and wiring to 
this control panel. 

When installing power limited field wiring, the installer must comply with NEC article 760, which states: 

The fire alarm power‐limited circuits are installed using Types FPL, FPLR, FPLP or permitted substitute cable, 
provided these power‐limited cable conductors extending beyond the jacket are separated by a minimum of 
0.25 in. (6.35 mm) or by a nonconductive sleeve or nonconductive barrier from all other conductors. 
If  energy  limited  cable  or  equivalent  is  not  used  within  the  FW106/FW106C  enclosure,  then  the  following 
guidelines do not apply. In that case, be sure to follow standard wiring practices. 
Wiring Entering the Enclosure 
 Non‐Power Limited Wiring ‐ Wiring entering the enclosure from the bottom left side and right side of the 
enclosure is considered non‐power limited wiring. Wiring must be in the shortest route and must not overlap 
any other wiring.   
     
 Power Limited Wiring ‐ Wiring entering the enclosure from the upper left side of the enclosure or the right 
side is considered power limited. Wiring must be in the shortest route and must not overlap any other wiring. 
23 
   
Installation and Operation Manual                                                                                                   

Wiring Separation 
All high voltage and non‐power limited wiring must be separated from power limited wiring. A separation of at 
least 1/4 inch must be maintained with high voltage and non‐power limited wiring running in separate conduit 
openings from power limited wiring.   

Figure 17 Wiring Terminals Location 
 

Power Supply Wiring 

AC Connection 

Wire the AC supply to the power supply on the back of the enclosure. The supply should originate from a 
dedicated 15A branch circuit. It should be provided with a breaker or other means of isolation that must be 
colored red.   

24 
   
Installation and Operation Manual                                                                                                   

  Dangerous voltages will be present on the terminal block and on other components surrounding it 
CAUTION when the AC supply is turned on. Do not touch. 
 
 AC Input terminals must be located on the left side of the enclosure and in the knockouts position shown in 
Figure 18. 
Route  all  high  voltage  and  non‐power  limited  wiring  together  and  away  from  power  limited 
  wiring. Refer to the Power Limiting section for more details. 
 

Figure 18 AC Power Supply Wiring 
 
Connect the ground cable to the earth stud on the enclosure back box. 

 
Figure 19 Ground Wiring 

25 
   
Installation and Operation Manual                                                                                                   

… Switch Matches Rated Voltage! 

Figure 20 AC Power Supply Wiring (Terminal) 
 
  Make sure the slide switch matches the rated voltage. Otherwise the PTU will be permanently 
CAUTION damaged! 
 

   

26 
   
Installation and Operation Manual                                                                                                   

Battery Connection 

WARNING 
Improper battery connections or shorting battery terminals may damage the system and/or the batteries and 
may cause personal injuries. 
 
 

The control panel battery charge capacity is up to 40AH. Use 12V batteries of the same AH rating. Determine the 
correct AH rating as per your current load calculation (see Appendix‐D: Battery Calculations).Wire batteries in 
series to produce a 24‐volt equivalent. Do not parallel batteries to increase the AH rating. 

Figure 21 Battery Connection 
 

   

27 
   
Installation and Operation Manual                                                                                                   

Addressable Loop Circuit Wiring 
One ALU card supports one addressable loop circuit. 

Addressable Loop Circuit supports Class A and Class B style. A maximum of 252 devices can be connected to the 
circuit. 

All the compatible detectors and manual stations are polarity insensitive, while the compatible modules are 
polarity sensitive. 

Refer to the instruction sheets packed with each device. 

The detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring 
style that is appropriate for your installation should be determined from the relevant building codes and the 
local Authority Having Jurisdiction. 

  Addressable Loop Circuit Wiring – Class A 

Class A provides redundant communication paths. 

 
Figure 22 Addressable Loop Circuit Wiring – Class A 
   

28 
   
Installation and Operation Manual                                                                                                   

Addressable Loop Circuit Wiring – Class B 

Class B wiring allows branching of circuit connections. 
LA+
LB+
LA‐
LB‐

Figure 23 Addressable Loop Circuit Wiring – Class B 
   

29 
   
Installation and Operation Manual                                                                                                   

Notification Appliance Circuit Wiring 
One NOU card supports two notification appliance circuits. 

Refer to the instruction sheets packed with each NAC device. 

Notification Appliance Circuit Wiring – Class A 

 
Figure 24 Notification Appliance Circuit Wiring – Class A 
   

30 
   
Installation and Operation Manual                                                                                                   

Notification Appliance Circuit Wiring – Class B 

One EOL (R=10kOhms) is needed at the end of the line to monitor the circuit integrity. 

 
Figure 25 Notification Appliance Circuit Wiring – Class B 
   

31 
   
Installation and Operation Manual                                                                                                   

Relay Output Circuit Wiring 
One ROU card supports five dry contact relays. 
 
Relay contact 
(Shown  in  normal  standby  condition,  see 
left drawing) 
 
 
NO – Normal Open 
COM – Common 
NC – Normal Close 

 
Figure 26 Relay Output Circuit Wiring 
   

32 
   
Installation and Operation Manual                                                                                                   

External Network Circuit Wiring 
External network circuit can address up to 110 panels and/or remote annunciators.   

FW106/FW106C control panel can connect to panels/annunciators by using External Network Unit. 
 
Remote Device Power – The control panel auxiliary power can provide power for 4 annunciators. Each address 
on the circuit must be fully powered from either auxiliary power of control panel UL/ULC Listed power supply 
for use in fire alarm systems. 
When connecting panels/annunciators on the external network circuit, the data wires must be daisy chained 
and with no T‐taps to preserve the integrity of the data. The following diagrams show the proper wiring. 

External Network Circuit Wiring ‐ Class B 

 
Figure 27 External Network Circuit Wiring ‐ Class B 
About the XNU Jumper 
Each XNU has an internal jumper on its upper right side which must first be correctly configured. 
     
If  this  XNU  is  located  at  the  end  of  the  external  network  circuit,  the  jumper 
must be switched to “ON”. 
 
 
 
 
 
 
   
 

33 
   
Installation and Operation Manual                                                                                                   

If this XNU is located in the middle of the external network circuit, the jumper 
must be switched to “OFF”. 
Jumper

OFF
AL
AH
BL
BH

XNU
 
 

Please refer to the Unit Address Setting section to set the XNU’s address 
 
 

Auxiliary Power Output Wiring 
The  Power‐supply  and  Charging  Unit  provide  auxiliary  power  output  connection.  This  power  output  can  be 
configured as resettable or non‐resettable. The resettable terminal interrupts the power for 6 seconds after a 
reset condition. 
 

 
Figure 28 Auxiliary Power Output Wiring 
 

Communication Port Connection 
An Ethernet standard plug is provided for temporary connection to a computer for panel programming. 

The Ethernet standard plug is connected to the Ethernet port of the computer that has the FW401 configurator 
tool. This is used to upload and/or download panel configuration for programming. 

34 
   
Installation and Operation Manual                                                                                                   

The computer must be disconnected from the panel if not in use. 
 
 

 
Figure 29 AMI 
   

35 
   
Installation and Operation Manual                                                                                                   

System Checkout 
The following are the recommended steps that should be followed before and during the powering up of the 
FW106/FW106C. 

Before Turning the Power ON 

1. To prevent sparking, DO NOT connect the battery first. Connecting the batteries should only be done once the 

system has been powered from the main AC Supply. 

2. Check all field (external) wiring for opens, shorts, and ground. 

3. Check that all interconnection cables are secure and that all connectors are plugged in properly. 

4. Check all switches for proper setting. 

5. Check the AC power wiring for proper connection. Observe/check slide switch position. 

6. Close the front cover plate before powering the system from main AC supply. 

Power‐up Procedure 

1. After completing Before Turning the Power ON procedures, power‐up the panel. 

The green AC ON LED should illuminate. 

2. Since the batteries are not connected, the Battery Trouble LED should illuminate, the 

Trouble LED should flash and the Trouble Relay (on the main board) will be active. 

3. Connect the batteries while observing correct polarity; the red wire is positive (+) and black wire is negative 

(‐). 

4. All indicators should extinguish except for normal power AC ON green LED. 
   

36 
   
Installation and Operation Manual                                                                                                   

Troubleshooting 
The following are common methods to solving Circuit Troubles, Ground Fault, Battery and Common troubles. 

Circuit Trouble 

Normally when a circuit trouble occurs, the Trouble LED will be illuminated and the common trouble relay will 
be active. Usually a relative event can be shown on the LCD event list view. Use these indications to correct the 
fault, check for open wiring on that particular circuit loop. 

Table 6 Circuit Trouble 
  The minimum resistance to    The maximum resistance to 
test open fault (Ohms)  test short fault(Ohms) 
In Addressable Loop Circuit  500K  10 
In Notification Appliance Circuit  500K  10 
In Auxiliary Power Circuit  NA  5 
 

Ground Fault 

This panel has ground fault detection. To correct the fault, check for any external wiring touching the chassis or 
other Earth Ground connection. 
The maximum resistance for testing ground fault detection for extended wirings other than the network is 6.6 
kohm. 
The maximum resistance for testing ground fault detection for network wiring is 60 ohm. 
 

Battery Trouble 

Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will cause a battery trouble. 
If battery trouble condition persists, replace batteries as soon as possible. 

Common Trouble 

If only a common trouble is indicated on the main panel and none of those above confirming trouble indicators 
are on, then check the following for possible fault 
 Any missing interconnection wiring 
 Improperly secured cabling 
   

37 
   
Installation and Operation Manual                                                                                                   

Operation 
Status handling 
This section describes the control panel responses and operation in standby condition, alarm condition, trouble 
condition, and supervisory condition. 

Standby Condition 

In normal standby operation, the green AC ON LED should be the only illuminated LED. The LCD will show the 
system label and the current time. 

 
Time & Date 
2017-05-18 18:47:23

Normal
Product Name 

Project Name 

FireWatcher
Project:xxx

Functionality
Buttons 
Buzzer  Manual
Acknowledge reset Menu
Silence Alarm
 

Figure 30 LCD (Standby) 

Alarm Conditions 

When the system detects an alarm condition, the system alarm LED activates (ON – flashing) and the buzzer 
activates (ON – alarm pattern). Local audible and visual signals along with remote alarm signals operate, and the 
LCD panel indicates the zone or point initiating the alarm. The LCD is similar to the Trouble conditions shown in 
Figure 31. 

When an alarm is received, proceed in accordance with the established emergency plan. Make sure all 
personnel is accounted for and notify the Fire Department. 

38 
   
Installation and Operation Manual                                                                                                   

To silence the visible and audible devices after the evacuation (where permitted by the codes and control panel 
programming), press the SIGNAL SILENCE button, then the SILENCE HORN&STROBE button. The alarm visible 
and audible signaling devices will be silenced and the alarm silence LED will change from off to on. 

Pressing the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm indicator from 
flashing to steady. 

Do not attempt to reset the system until the alarm condition has been cleared. The LCD will indicate 
  the zone in which the alarm was detected. The LEDs on activated detectors or modules (if applicable) 
will illuminate. 
 

When the alarm condition has been corrected, return the system to normal standby operation by pressing the 
RESET button. 

Trouble Conditions 

In case of a trouble condition, the system trouble LED and any programmed trouble LEDs activate (ON – 
flashing), the LCD identifies the problem, and the buzzer sounds in trouble pattern. 

Event Type 

Event List 

Functionality
Buttons 

Figure 31 LCD (Trouble) 
   

39 
   
Installation and Operation Manual                                                                                                   

Refer to Table 7 for trouble event types and explanation of the events. 

Table 7 Trouble Event Type 
Category  Trouble Event Type  Explanation 

System  PrimaryPower_Loss  Primary power is lost 

Battery_Loss  Battery is lost 

ControlPanel_Grounding  Control panel detects ground condition 

PrimaryPower_OverVoltage  Primary power voltage is too high 

Charger_OverVoltage  Charger voltage is too high 

ArchiveFile_Missing  History record file is missing 

ConfigFile_Missing  Configuration file is missing 

ConfigFile_Damaged  Configuration file is damaged 

Unit  ALU_Conf.Mismatch  ALU’s configuration file is mismatched with 


AMI’s 

AMI_Jumper  AMI has a jumper shorted 

Unit_Missing  PCU/ALU/NOU/ROU/XNU is missing 

Ext._Missing  The network annunciator is missing 

Unit_Addr.Conflict  1. Two or more ALUs have the same 
addresses, or 

2. Two NOUs have the same addresses 

Unit_ Illegal  The unit is working, but it is not configured 

Unit_SwitchError  The unit address changed during running 

Circuit  Ext._Illegal  The network annunciator is working, but it is 


not configured 

Ext._Grounding  The network circuit is grounded 

Ext.__Addr.Conflict  Two or more annunciators on the network 
circuit have the same address 

Bus_Short  The addressable loop circuit is shorted 

40 
   
Installation and Operation Manual                                                                                                   

Bus_Open  The addressable loop circuit is open 

Bus_CrossPower  The addressable loop circuit wire is cross 
power 

NOU_CircuitTrbl  The notification appliance circuit is 
malfunctioning (open, short, grounding, etc.) 

Field Device  Heat_SensingError  The heat detector sensing has an error 

Smoke_Contamination  The chamber of the smoke detector is 
contaminated 

Smoke_SensingError  The chamber of the smoke detector is 
severely dirty and can’t be used 

Init.Device_Duplicate  Two or more devices have the same address 

Init.Device_Illegal  The device is working online, but it is not 
configured 

Init.Device_Missing  The device is configured, but it is missing 

Init.Device_WrongType  The device type is incorrectly configured   

Init.Device_Vol.Abnormal  The device detects abnormal line voltage   

Init.Device_GeneralTrbl  The device has internal hardware trouble 

When the trouble condition has been noted, pressing ACKNOWLEDGE button will silence the buzzer and change 
the trouble LED to steady ON.   

The panel has a 24‐hour Supv/Trouble Resound function. If the trouble condition is not corrected and the 
Supv/Trouble Resound Reminder timer has elapsed, the panel will re‐annunciate the trouble condition.   

When the indicated trouble condition has been cleared, the system reverts to normal standby condition 
automatically. 

Supervisory Conditions 

In case of a supervisory condition, the system supervisory LED activates (ON – flashing) and the buzzer activates 
in supervisory pattern. The LCD notes the supervisory event and the buzzer sounds in supervisory pattern. 

Supervisory event can be configured as latched or non‐latched by setting from the system attribute interface.   
Returning to normal condition will not cause the supervisory event to disappear until manually reset if it is 

41 
   
Installation and Operation Manual                                                                                                   

programmed as latched. Returning to normal condition will cause the supervisory event to disappear when it is 
programmed as non‐latched. 

When the supervisory condition has occurred, pressing ACKNOWLEDGE button will silence the buzzer and 
change the supervisory LED to steady ON.   
If the panel is configured for Supv/Trouble Resound Reminder, when the supervisory condition is not corrected 
and the Supv/Trouble Resound Reminder timer has elapsed, the panel will re‐annunciate the supervisory 
condition.   

Device, Appliance Handling 

NAC Activation and Silence 
The notification appliance circuits are controlled by a microprocessor to provide more versatility than in a total 
hardware system. 

 Output Sounding Patterns ‐ Notification appliance circuits are operable in Temporal‐3 pattern. 
 Alarm Silence Inhibit ‐ Control panel may be programmed to inhibit Alarm Silence from 0 to 20minutes from 
the last alarm. 
 All of the NACs are power limited and support synchronization of the listed devices. 
 The open, short, and grounding troubles of notification appliance circuit are monitored. 

Device Supervision 

Device type supervision: If the type reported by an addressable detector or module does not agree with the 
configuration, the system reports a trouble condition.   

Device address supervision: The system checks that the configured devices on the Addressable Device Circuit 
and the Serial Interface Circuit respond to an address poll. The system reports a trouble condition if one of the 
following conditions is detected: 
•  Configured device is missing. 
•  Unconfigured device is installed. 
•  Two or more devices are programmed with the same address location (this trouble is only detected by 
manually checking). 

Detector Monitor 

The control panel processor polls the detectors for their status. The detector determines normal, trouble, and 
alarm conditions and communicates the status to the control panel. 

The control panel can automatically trigger an alarm or a trouble for various conditions, including: 
 Active 
 Illegal 
 Wrong Type 
 Missing 
 Address Conflict 
42 
   
Installation and Operation Manual                                                                                                   

 General Trouble 
 Sensing Error 
 Contamination 
Please refer to the Trouble Conditions section for more detail on each event type. 

Manual Station Response 

Addressable manual stations may be intermixed on the circuit with proper response programmed into the 
control panel. 

Drift Compensation 

The Drift Compensation is built into a compatible detector and is not performed by the panel. Drift 
compensation automatically adjusts for gradually increasing effects of dust and other accumulations of dirt in 
the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual 
change in the normal clean air value received. When it can no longer compensate for an increasingly dirty 
detector, a dirty detector trouble (Contamination trouble) is indicated for that device. 

Alarm Verification 

The Alarm Verification function is supported by this panel. One typical alarm verification phase can be divided 
into 2 periods. The first period is a retard period in which no alarm reports on the Fire Alarm Control Panel 
(FACP). The second period is a confirmation period in which alarm reports on the Fire Alarm Control Panel if a 
device is in alarm status. The detail alarm verification phase is illustrated in Figure 32.   
 

 
Figure 32 Alarm Verification 
 
A ‐ Smoke detector goes into alarm. (LED on device turns to steady on) 
AB ‐ Retard Period: Fire Alarm Control Panel senses detector in alarm and delays alarm signal for 50s. During 
this period, no alarm event reports on the Fire Alarm Control Panel. 
BC ‐ Confirmation Period: Detector is operational for alarm at point B. If the detector is still in alarm at point B, 
the Fire Alarm Control Panel will report an alarm. If the detector is not in alarm, the system returns to standby. 
If the detector re‐alarms at any time during the confirmation period the Fire Alarm Control Panel will alarm. 
The period length is 60s. 
CD – Restart next alarm verification period if new alarm occurs. 
43 
   
Installation and Operation Manual                                                                                                   

Positive Alarm Sequence (PAS) 

When an alarm causing device associated with a zone with PAS feature is initiated, the alert condition is reported 
on the panel. The activation of all system evacuation signals are delayed for 15 seconds (PAS delay time) waiting 
for a manual acknowledgement response.   
If  no  response  is  received  within  15  seconds,  the  panel  proceeds  to  activate  system  evacuation  signals.  See 
Figure A. 
If  the  alarm  event  is  acknowledged  during  the  PAS  delay  time,  the  programmable  PAS  investigation  time  (180 
seconds) is added to the PAS delay time before system evacuation signals are activated. See Figure B. 
However,  if  a  2nd  alarm  is  initiated  anytime  during  the  PAS  delay  time  or  PAS  investigation  time,  the  system 
evacuation signals are immediately activated. See Figure C. 
Pressing the Reset button at anytime during the PAS sequence will initiate a reset condition and try to restore 
the panel to stand‐by state. 

Figure 33 Positive Alarm Sequence 

   

44 
   
Installation and Operation Manual                                                                                                   

Two‐Stage 

When an alarm causing device associated with a zone with two‐stage feature is initiated, it will enter first stage 
alarm and the alert condition is reported on the panel. A countdown timer will start at the moment and buzzer 
will sound in alert tone. Notification appliance will sound in alert tone. 
If the timer counts down to 0 or pressing “To Second Stage” button, system will enter second stage alarm status. 
Alarm  event  will  display  on  LCD,  along  with  buzzer  with  alarm  tone  and  notification  appliance  in  alarm  tone 
(Temporal 3). 
If “Auto Alarm Signal Cancel” button or “Signal Silence” button is pressed during first stage alarm, the system will 
enter  the  automatic  alarm  signal  cancel  status.  Automatic  alarm  signal  cancel  event  will  display  on  LCD.  The 
countdown timer is cancelled, buzzer keeping in alert tone, and notification appliance sounding in alert tone (if 
it’s not silenced).   
 

Figure 34 Two‐Stage Alarm 

By‐pass 

The by‐pass function is provided for user if they don’t want to receive message from specified devices. 
 

Auto addressing 

Auto addressing mode which is applied to assign addresses for field devices by panel. When panel goes 
into Auto Addressing mode, devices installed on this loop will be automatically assigned addresses in 
sequence  which  is  convenient  for  filed  commissioning.  Please  refer  to  the  programming  manual  for 
details.  
 
45 
   
Installation and Operation Manual                                                                                                   

Event History 
The control panel includes a non‐volatile memory recording 5000events, plus a separate 1000 alarm‐only events. 
Identified alarm, trouble, supervisory, status, and other significant events will be recorded along with the date 
and time of occurrence. These can be viewed by operating the front panel push buttons. 

To recall past events, proceed as follows: 

 Press the “MENU” button. 

 On the “MENU” display, select “Archive”. 

 Press the “Enter” button. 

 Use the up button next to the LCD to see the previous event display. 

 Use the down button next to the LCD to see the next event display. 

The history record rule is: 

 New events overwrite old events when filled. 
 The events are sorted by time occurrence sequence. 
 

Events recorded in the history are: 

 Alarm, Trouble, Supervisory, and Monitor conditions 

 Alarm silence/Resound 

 System reset 

 System startup 

 Enable/disable function 

 Start and stop of Walk Test 

 Trouble/supervisory reminder 

 Trouble/supervisory restored to normal 

   

46 
   
Installation and Operation Manual                                                                                                   

LED, Buzzer, Buttons 
The FW106/FW106C has a buzzer, 9 LEDs, 5 navigational buttons and enter button, 6functionality buttons. 

LEDs Operation 

Refer to Table 8 for the LEDs operation. 

Table 8 LEDs Operation 
Indicates  that  there  are  alarm  events  and  all 
Steady ON 
alarm events have been acknowledged. 

Indicates  that  there  is  no  alarm  event  in  the 


ALARM  Red  OFF 
system. 
Indicates  that  there  are  alarm  events  in  the 
Flashing  system,  but  some  of  them  have  not  been 
acknowledged. 
Indicates  that  there  are  supervisory  events 
Steady ON 
and all of them have been acknowledged. 

Indicates that there is no supervisory event in 
SUPERVISORY  Yellow  OFF 
the system. 
Indicates  that  there  are  supervisory  events  in 
Flashing  the system, but some of them have not been 
acknowledged. 
Indicates that there are trouble events and all 
Steady ON 
of them have been acknowledged. 
Indicates that there is no trouble event in the 
OFF 
TROUBLE  Yellow  system. 
Indicates  that  there  are  trouble  events  in  the 
Flashing  system,  but  some  of  them  have  not  been 
acknowledged. 
Indicates  that  there  are  other  signal  events 
Steady ON 
and all of them have been acknowledged. 
Indicates that there is no other signal event in 
OTHER SIGNALS  Yellow  OFF 
the system. 
Indicates that there are other signal events in 
Flashing  the system, but some of them have not been 
acknowledged. 
On control Panel: 
POWER ON  Green  Steady ON  Indicates that the system's main power works 
normally. 

47 
   
Installation and Operation Manual                                                                                                   

On Annunciator: 
 
Indicates that the power works normally. 
On control Panel: 
Indicates  that  the  system  is  not  powered  on 
yet or the system is powered by battery. 
OFF 
On Annunciator: 
Indicates  that  the  system  is  not  powered  on 
yet. 
Indicates that there are activated NAC devices 
Steady ON 
and at least one of them has been silenced. 
SIGNAL SILENCE  Yellow 
Indicates  that  there  is  no  NAC  activated  or  a 
OFF 
NAC is activated and not silenced. 
Indicates that there are Ground Fault events in 
Steady ON 
the system. 
GROUND FAULT  Yellow 
Indicates  that  there  is  no  Ground  Fault  event 
OFF 
in the system. 
Steady ON  Indicates that there are disabled events. 
BY PASS  Yellow 
OFF  Indicates that there are no disabled events. 

Steady ON  Indicates that the CPU is in fault. 
CPU FAULT  Yellow 
OFF  Indicates that there is no CPU fault. 

Buzzer Operation 

The buzzer operates as follows: 

Normally  OFF  –  indicates  that  the  system  is  in  normal  condition  or  all  events  in  the  system  have  been 

acknowledged. 

ON (continuous) – indicates that at least ONE unacknowledged alarm is present in the system. 

ON (1 pulse per 0.25 second) – indicates that at least ONE unacknowledged Alert event is present in the system 

ON (1 pulse per 0.5 second) – indicates that at least ONE unacknowledged supervisory event is present in the 

system. 

ON (1 pulse per 1 second) – indicates that at least ONE unacknowledged trouble event is present in the system. 

ON  (1  pulse  per  2  second)  –  indicates  that  at  least  ONE  unacknowledged  other  signal  event  is  present  in  the 

system. 

   

48 
   
Installation and Operation Manual                                                                                                   

Button Operation 

The control panel has 5 navigational and enter buttons, 6functionality buttons. The button function sare listed in 
Table 9.   

Table 9 Buttons Function 

↑↓←→  To select the items in the menu, or to select letters or digits for input. 
Navigation Buttons 
  Cursor movement will be speedy if the button keeps being pressed. 

 
Enter Button  To select or confirm information 
 
Notes: The functionality buttons below have different roles depending on the view. The roles in main view are 
listed below. 

F1  Acknowledge  Acknowledges once a single unacknowledged event in the system. 

Signal Silence ‐ Silences specific NAC devices in the system. This will cause 
specific activated NAC devices to become silenced. 
Signal Silence/ 
F2  Signal  Resound  ‐  Resound  specific  NAC  devices  in  the  system.  This  will 
Resound 
cause specific activated, but silenced NAC devices, to resound. 
 
Buzzer  Buzzer Silence – Silence the buzzer 
F3 
Silence/Resound  Buzzer Resound – Resound the buzzer 

Clears all obsolete events and resets all devices, except those disabled in 
F4  Reset 
the system.   

F5  Manual Alarm  Activates NAC devices 

F6  Menu  Button for user operations. 


 

   

49 
   
Installation and Operation Manual                                                                                                   

LCD Display 

The LCD can display 8 events at a time. Users can browse more events by pressing the up/down button until the 
first event or last event message is reached. 
 
Events are displayed according to the following rules: 
1: Events priority: 
Alarm > Supervisory > Trouble > Other Signal>Output 
2: Within events of the same priority, all events are displayed in order of occurrence, the latest being displayed 
first. 
However, the sequence of alarm event is configurable. 

Lamp Test 

When selected, the lamp test activates the LCD, the buzzer, and turns on all the LEDs on the user interface. It 
then reverts to its previous state. 

To initiate a lamp test, proceed as follows: 

1: Press the "MENU" button. 

2: Select “Lamp Test “to run. 

The lamp test operates the indicators only on the units being operated. No record is reported to the system 
history. 

   

50 
   
Installation and Operation Manual                                                                                                   

Configuration and Maintenance 

PC Configuration 

Programming the panel may be done by temporarily connecting the programming port to a computer. This is 
the recommended method to configure the panel. 

The Maple Armor FW401 Configurator software is available to configure of the control panel using a Personal 
Computer (PC) with an Ethernet port. This allows ease of operation by preparing the program in advance and 
downloading it to the control panel by a simple and fast operation. 

Control Panel Access Control 

The FW106/FW106C provides configuration and maintenance functions to set and control various features in 
the system.   

The configuration and maintenance functions are protected by access control. The following levels of security 
protect the system from unauthorized use: 

 Level 1 – Locked Door 
 Level 2 – Locked Door and 4‐digit Password, Level 2 provides control functions. 
 Level 3 – Locked Door and 4‐digit Password, Level 3 provides control functions and parameter change 
functions. 
To access the maintenance features, press the “MENU” button and select “Access To System”, enter the four 
digit code when prompted, then press “OK”.   

The User Level is also accessible from the Remote LCD Annunciators. 
 
 
   

51 
   
Installation and Operation Manual                                                                                                   

Control Panel Configuration 

The configuration and the maintenance of the control panel may be accomplished through the keypad included 
in the control panel. 

Different access levels have different operation rights. Refer to Table 10 to 
 
Table 13 for more details. 
Table 10 Access Level 0 Operation 
Access Control  No 

Accessible Functions  View real‐time event(s) displayed on LCD 

 
Table 11 Access Level 1 Operation 
Access Control  Locked door 

Browse all real‐time events(s)   

Browse all system nodes’ properties 

Acknowledge all real‐time events(s) 

Silence/Resound buzzer 
Accessible Functions 
Silence/Resound notification appliances 

Reset System 

Activate Manual Alarm 

Query History Record 

 
Table 12 Access Level 2 Operation 
Access Control  Locked Door and 4‐digit Password 

All Access Level 1 functions 

Set System Time 

Accessible Functions  Set System Date 

Bypass Field Devices 

Bypass NACs 

52 
   
Installation and Operation Manual                                                                                                   

Bypass Status Relays 

 
 
Table 13 Access Level 3 Operation 
Access Control  Locked Door and 4‐digit Password 

Accessible Functions  All Access Level 2 functions 

  Browse/Edit/Add/Delete control logic 

Update Firmware 

Browse/Edit/Add/Delete User (Name and Passcode) 

System  Change Customer Text 

Set Network mode 

Set system time 

Set system date 

Set Alarm Sequence 

Set Supervisory Latched 

Set Monitor Latched 

Set Daylight Saving Time 

Set Login Time 

Set Silence Inhibit Time 

Set LCD Shutdown Time 

Set Two‐stage Time 

Set PAS Bypass 

Set Debug Mode 

Control Panel  Change Customer Text 

Annunciator  Change Customer Text 

ALU  Change Topology 

53 
   
Installation and Operation Manual                                                                                                   

Device Duplicate Check 

Device Register 

Device Auto Register 

NOU  Change Topology 

FW511 Smoke Detector  Change device address 

Change device type 

Bypass device 

Change Customer Text 

Change Assigned Zone 

Change Alarm Delay Property 

Change UID 

FW521 Heat Detector  Change device address 

Change device type 

Bypass device 

Change Customer Text 

Change Assigned Zone 

Change Alarm Delay Property 

Change UID 

FW721 Manual Station  Change device address 

Change device type 

Bypass device 

Change Customer Text 

Change UID 

Change Assigned Zone 

Change Alarm Delay Property 

54 
   
Installation and Operation Manual                                                                                                   

FW811 Input Module  Change device address 

Set Input Function 

Bypass device 

Change Customer Text 

Change UID 

Change Assigned Zone 

Change Alarm Delay Property 

FW821 Input‐Output Module  Change device address 

Bypass device 

Change Customer Text 

Change UID 

Change Type 

FW831 Relay Module  Change Device Address 

Bypass Device 

Change Customer Text 

Change UID 

Change Type 

Notification Appliance Circuit  Change Customer Text 

Change UID 

Programmable Relay  Bypass device 

Change UID 

Change Type 

PCU  Change Aux. Power Resettable/Non‐resettable 

Manual Zone  Change Customer Text 

Auto Zone  Change Customer Text 

55 
   
Installation and Operation Manual                                                                                                   

   

  When disabling an input oran output device, the application will indicate a trouble 
condition. 
 

56 
   
Installation and Operation Manual                                                                                                   

Appendix‐A: Compatible Devices 
Devices for Addressable Loop Circuits 
Table 14 Device for Addressable Device Circuits 
Model No.  Description 
FW511  Optical Smoke Detector 
FW521  Heat Detector 
FW721  Manual Station 
FW721C  Manual Station (Canada) 
FW811  Input module 
FW821  Input‐Output Module 
FW831  Relay Module 
FW851  Isolator Module 
 

Appliances for Notification Appliance Circuits 
Table 15 Appliance for Notification Appliance Circuits 
Model No.  Description 
FW961R/FW961W  Horn/Strobe Light 
FW971R/FW971W  Horn 
FW981R/FW981W  Strobe Light 
FW962R/FW962FW  Multi‐candela Horn Strobe 
FW982R/FW982W  Multi‐candela Strobe 
 
   

57 
   
Installation and Operation Manual                                                                                                   

Appendix‐B: Wire Selection Guide 
SLC Wire Selection Guide 
Maximum Loop Current = 100mA@NSB, 220mA@Alarm 

Maximum Loop Capacitance = 0.1uF 

Table 16 Addressable Loop Wiring 
Wire Gauge  Maximum Wiring Run to Last Device 
Wire  Maximum current  Maximum current  Maximum current 
(AWG)  Resistance  90mA  150mA  220mA 
(ohms/km) ft  m  ft  m  ft  m 
12  5.31  15099    4603    9060    2762    6177    1883   
13  6.69  11985    3654    7191    2192    4903    1495   
14  8.45  9488    2893    5693    1736    3882    1183   
15  10.6  7564    2306    4538    1384    3094    943   
16  13.5  5939    1811    3563    1086    2430    741   
17  16.3  4919    1500    2951    900    2012    613   
18  21.4  3747    1142    2248    685    1533    467   
 

   

58 
   
Installation and Operation Manual                                                                                                   

NAC Wire Selection Guide 
Table 17 NAC Wiring Table 
Maximum Wiring Run to Last Device  Maximum 
Total Signal 
Line 
Load  AWG12  AWG14  AWG16  AWG18 
Resistance 
Amperes  ft  m  ft  m  ft  m  ft  m  Ohms  
0.3  4530    1381    2847  868  1782  543  1124    343    7.33   
0.6  2265    691    1423  434  891    272  562    171    3.67   
0.9  1510    460    949    289  594    181  375    114    2.44   
1.2  1132    345    712    217  445    136  281    86    1.83   
1.5  906    276    569    174  356    109  225    69    1.47   
2  679    207    427    130  267    81    169    51    1.10   

NAC circuits are rated for of 2 Amperes each. 
 
Maximum voltage drop can’t exceed 1.8V (for regulated circuit). 

Annunciator Wire Selection Guide 
Table 18 Annunciator Wiring Table 
Wire 
(AWG)  Resistance  ft  m 
(ohms/km)
12  5.31  15443  4708 
13  6.69  12257  3737 
14  8.45  9704  2959 
15  10.6  7736  2358 
16  13.5  6074  1852 
17  16.3  5031  1534 
18  21.4  3832  1168 
   

59 
   
Installation and Operation Manual                                                                                                   

Appendix‐C: Quantities of Notification Appliances 
 
Table 19 lists the maximum number of notification appliances (FW961R / FW961W, FW971R / FW971W, 
FW981R / FW981W, FW962R / FW962W, and FW982R / FW982W) per NAC in the worst case scenario for 
Synchronization system. 
Table 19 Maximum Numbers of NA 
Model No.  Description  Maximum number per NAC 
FW961R/FW961W  Horn/Strobe Light  15 
FW971R/FW971W  Horn  110 
FW981R/FW981W  Strobe Light  16 
FW962R / FW962W  Multi‐candela Horn Strobe  33 
FW982R / FW982W  Multi‐candela Strobe  33 
 
If these 3 types of notification appliances are mixed in the same circuit, the total 
  current of the circuit must be <= 2 Amperes. 

 
   

60 
   
Installation and Operation Manual                                                                                                   

Appendix‐D: Battery Calculations 
Total System Currents Calculations 
Table 20 System Currents Calculation 
IMPORTANT NOTICE 

The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous 
power without provision of any disconnect devices. Use #12 AWG wire with 600 volt insulation and proper 
over‐current circuit protection that complies with the local codes. For specifications, refer to the 
Specifications and Features section. 
Functional Unit's Currents (All currents are in ampere) 
Model Number  Description  Qty  Standby  Total  Alarm  Total 
Standby  Alarm 

FW201/FW201C  AMI  1  × 0.143    0.146   

FW391  PTU  1  × NA    NA   

FW397  PCU  1  × 0.065    0.065   

FW327  ALU    × 0.027    0.027   

FW337  NOU    × 0.036    0.054   

FW347  ROU  1  × 0.035    0.035   

FW357  XNU    × 0.027    0.027   

Field Devices Currents (All currents are in ampere) 

The total quantities of each loop must <= 252. The total current of field devices per loop is 100 mA @standby, 
and 220 mA @alarm. 

FW511  Optical Smoke Detector    × 0.00014    0.001   

FW521  Heat Detector    × 0.0001    0.001   

FFW721  Manual Station    × 0.0001    0.001   

FW721C  Manual Station (Canada)    × 0.0001    0.001   

FW811  Input Module    × 0.00017    0.00079  

FW821  Input‐Output Module    × 0.00015    0.00026  

FW831  Relay Module    × 0.00015    0.00026  

61 
   
Installation and Operation Manual                                                                                                   

FW851  Isolator Module    × 0.0016    0.0108   

NAC Devices Currents (All currents are in ampere) 

The total currents of each loop must <= 2A 
FW961R/FW961W  LED Horn/Strobe    × 0.0000045    0.117   

FW971R/FW971W  Horn    ×     0.017   

FW981R/FW981W  LED Strobe Light    × 0.0000045    0.075   

FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.164   


(@130 cd setting)  (@130 cd setting) 
FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.126   
(@105 cd setting)  (@105 cd setting) 
FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.085   
(@85 cd setting)  (@85 cd setting) 
FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.055   
(@50 cd setting)  (@50 cd setting) 
FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.047   
(@35 cd setting)  (@35 cd setting) 
FW962R/FW962W  Multi‐candela Horn Strobe    × 0.0000045    0.030   
(@20 cd setting)  (@20 cd setting) 
FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.156   
(@130 cd setting)  (@130 cd setting)   

FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.119   


(@105 cd setting)  (@105 cd setting)   

FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.080   


(@85 cd setting)  (@85 cd setting)   

FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.049   


(@50 cd setting)  (@50 cd setting)   

FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.043   


(@35 cd setting)  (@35 cd setting)   

FW982R/FW982W  Multi‐candela Strobe  × 0.0000045    0.028   


(@20 cd setting)  (@20 cd setting)   

Miscellaneous (All currents are in ampere) 

62 
   
Installation and Operation Manual                                                                                                   

  EOL    × 0.00082    0.00082  

Auxiliary Power Supply  Standby    Alarm   

Total Currents  Standby    Alarm   

Battery Capacity 
Table 21 Battery Calculation 
Total Standby Current  Hours of Standby Required per UL864 Standard    AH for Standby 
(from above)   
  A  x 24 Hours  = 

 
Total Alarm Current  5 Minutes of Alarm Operation  AH for Alarm 
(from above)  per  UL864  Standard,  30  Minutes  of  Alarm   
Operation per ULC‐S527 and 5 Minutes of Alert 
for Two‐stage. 
A  x 0.09 Hours(For UL compliance)  = 

A  x 0.6 Hours(For ULC compliance)  = 

 
A.H. for Standby    A.H. for Alarm  Calculated A.H.  De‐rating  A.H. Required Battery 
Factor  Capacity 
  +  =  X 1.25  = 

 
Maximum available battery space: 
 
Length: 8.07 in., width: 6.61in., height: 7.87 in. 

Maximum battery capacity: 40AH 

 
 
Notes:   
Use of alternative batteries may result in failure of the panel to meet agency and regulatory requirements and 
may result in shortened battery life. Batteries should be tested regularly and replaced at least every four years. 
If the Battery Trouble indicator activates, the required service should be performed by an authorized agent. 
   

63 
   
Installation and Operation Manual                                                                                                   

Appendix‐E: Glossary and Acronyms 
Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a 
manual station or an automatic smoke detector. 

Alarm Silence Inhibit. An option that prevents a human operator from silencing the notification appliances for a 
preset period of time. 

Alarm System. A combination of compatible initiating devices, control panels, and notification appliances 
designed and installed to produce an alarm signal in the event of a fire. 

Alarm Verification. A preset option that causes the control panel to verify alarms originated by smoke detectors 
before indicating an alarm. 

ALU. Addressable Loop Unit. 

AMI. Advanced Machine Interface. 

Annunciator. A remotely located, electrically powered display separate from the control panelwith LEDs or 
lamps to indicate the states of the fire alarm system. 

Audible Signal.A sound produced by one or more audible notification appliances, such as bells or horns, in 
response to the operation of an initiating device. 

Class A Circuit. An initiating device or notification appliance circuit within which all components remain fully 
functional, even though a single open or a ground is present in the circuit. 

Class B Circuit. An initiating device or notification appliance circuit within which some or all components may be 
disabled with a single open or a ground exists in the circuit. 

CPU. Central Processing Unit. 

Detector ‐ FirePrint™. An intelligent fire detector that blends photoelectric, thermal, and neural network 
technologies for superior protection without false alarms. 

Detector ‐ Smoke, Photoelectric Type. A detector using the photoelectric principle of reflection or obstruction 
of light by smoke. 

Detector ‐ Thermal Type. An addressable thermal sensor programmable as either a fixed temperature (135° F) 
or as a rate of rise detector. 

Enable / Disable. Refers to the state of individual circuits (inputs and outputs) or logic functions, regardless of 
the presence of its corresponding modules. 

End Of Line (EOL). A device used to terminate a supervised circuit. 

FACP. Fire Alarm Control Panel. 

64 
   
Installation and Operation Manual                                                                                                   

Ground Fault. A trouble condition in which a low resistance has been detected between the system wiring and 
the conduit ground. 

Initiating Device.A manually or automatically operated device, such as a manual station, a smoke detector, a 
heat detector, a waterflow switch, a or tamper switch. 

Initiating Device Circuit (IDC). A circuit to which initiating devices are connected. 

Labeled. Equipment or materials to which is attached a label, a symbol, or another identifying mark of an 
organization acceptable to the authority having jurisdiction and concerned with product evaluation, which 
maintains the periodic inspection of the production of such labelled equipment or materials. And by whose 
labelling the manufacturer indicates compliance with appropriate standards or performance in a specified 
manner. 

LED. Light Emitting Diode. 

LCD. Liquid Cristal Display. 

Listed. Equipment or materials included in a list published by an organization acceptable to the authority having 
jurisdiction and concerned with product evaluation that maintains the periodic inspection of the production of 
the listed equipment or materials, and whose listing states either that the equipment or material meets the 
appropriate standards or has been tested and found suitable for use in a specified manner. 

NEC. National Electrical Code, also published as NFPA standard 70. 

Notification Appliance. An electrically operated appliance used to indicate the system status, such as a bell, 
horn, strobe light, or speaker. 

NAC (Notification Appliance Circuit).A circuit to which notification appliances are connected. 

NOU. Notification Output Unit. 

PCU. Power Supply and Charger Unit. 

Power Supply. The part of the Fire Alarm Control Panel which provides the power needed to operate all control 
panel modules, as well as needed to operate all electrically powered initiating devices and all notification 
appliances. 

Programming  Tool.  Refers  to  an  external  proprietary  software  package  that  allows  the  user  to  program  the 
panel. 
 
PTU. Power Supply Transformer Unit. 

Quick Test.Term pertaining to the test mode of the system that automatically resets after a service technician 
tests the initiating devices. 

ROU. Relay Output Unit. 

65 
   
Installation and Operation Manual                                                                                                   

Reset Condition. Condition in which the panel is forced to return to its normal state, usually performed by 
pressing the “SYTEM RESET” button after all known events / conditions are cleared.   

Supervisory. A signal indicating the operation of a supervisory device. 

Supervisory Device. A device that monitors the condition of a sprinkler system, such as a gate‐valve switch, a 
water‐level switch, a low‐pressure switch, a low temperature switch, or a fire‐pump monitor. 

Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or a ground, occurring 
in the device or in the wiring associated with a fire alarm signal. 

Waterflow Switch. An assembly approved for service and built accordingly. The assembly is installed in a way 
that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler 
head will activate the switch and subsequent indication of an alarm condition. 

XNU (External Network Unit).A unit that provides interface circuit to communicate with other networked panel 
and/or annunciator. 

Zone.A designated area of a building, commonly identified as a zone, is interchanged with an initiating device 
circuit. 

   

66 
   
 

Maple Armor 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
© 2019 MAPLE ARMOR FIRE ALARM DEVICE CO., LTD. 
8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2 
Data and design subject to change without notice. 
All rights reserved.   
www.maplearmor.com 
 

You might also like