You are on page 1of 8

1

A Strategy for Protection Coordination in Radial


Distribution Networks with Distributed Generators
Amin Zamani, Student Member, IEEE, Tarlochan Sidhu, Fellow, IEEE, and Amir Yazdani, Senior Member, IEEE

Abstract—In this paper, a simple and effective strategy is the other aforementioned issues have not been considered,
proposed for the coordination of protective devices in typical and also recloser settings must be changed after the first
radial distribution networks embedding distributed generation reclosure. In reference [7], the idea is to employ fault current
units. The proposed strategy benefits from microprocessor-based
reclosers and directional elements for feeder relays, and addresses limiters (FCL)s for limiting fault currents to such low levels
the issues of blinding of protection, false tripping, recloser- that the coordination issue does not manifest itself. Although
fuse and fuse-fuse miscoordination, and failed auto-reclosing. consistent with the general sense that devices with limited
Another salient feature of the proposed strategy is that it does fault currents, e.g. electronically-interfaced DGs, do not com-
not require adaptive protective devices. The effectiveness of the promise the protection coordination, at least as drastically as
proposed algorithm is demonstrated by simulation case studies
conducted on a model of an example distribution network, their rotating machine-based counterparts, the study has not
in the PSCAD/EMTDC software environment. The paper also formulated or characterized the problem, nor has it considered
presents the steps taken to characterize the impact of DGs on the effectiveness of the scheme for transient regimes.
the protection coordination, for host and neighboring feeders. In this paper, a simple and effective strategy is proposed
for the coordination of protective devices in radial distribution
Index Terms—Distributed generation, distribution system,
fault analysis, protection coordination, recloser, relay. networks embedding distributed generation units. The pro-
posed strategy benefits from microprocessor-based reclosers
and directional elements for feeder relays. The algorithm
I. I NTRODUCTION also addresses the issues mentioned above associated with
RADITIONALLY, distribution systems have been de- the introduction of DGs to distribution networks. Another
T signed to operate radially, that is, the power flows from
the upper voltage levels down to customers connected to radial
salient feature of the proposed strategy is that it does not
require adaptive protective devices. The effectiveness of the
feeders. This simple configuration has enabled straightfor- proposed algorithm is demonstrated by simulation case studies,
ward protection strategies. Thus, the conventional distribution conducted on a model of an example distribution network in
networks are protected by such simple protective devices as the PSCAD/EMTDC software environment. The paper also
overcurrent relays, reclosers, and fuses [1], [2]. With the intro- presents the steps taken to characterize the impact of DGs on
duction of distributed generation, however, the radial structure the protection coordination, for host and neighboring feeders.
of the networks is compromised, and protection coordination The rest of this paper has been organized in five sections.
may be affected, or entirely lost in some cases. The issues Section II briefly reviews the traditional method of protection
include blinding of protection, false tripping, recloser-fuse and coordination, for a typical distribution network. In Section
fuse-fuse miscoordination, and failed auto-reclosing [3]-[5]. III, the impacts of addition of distributed generators on the
The aforementioned issues have prompted research activities traditional coordination are investigated, and a methodology is
to find effective solutions. proposed for coordination of protection that aims at resolving
The impact of distributed generators (DG)s on the sys- the issues listed above. In Section IV, the application of
tem short-circuit current has been investigated in [4]. The the proposed coordination methodology is illustrated for an
authors recommend that the margin required for preserving example system. Sections V and VI provide the simulation
the protection coordination be checked whenever a new DG results and conclusions, respectively.
is added to the network. The possibility of maintaining the
coordination in radial distribution systems with DGs, if there II. T RADITIONAL P ROTECTION C OORDINATION
is enough margin between relay characteristic curves, has been
demonstrated in [5]; however, the authors have not formulated In a feeder, fuses must be coordinated with the recloser
the problem. According to [5], the relay parameters have to installed at the beginning or middle of the feeder. The coor-
be reset to revised relay curves in case the coordination is dination means that a fuse must operate only if a permanent
lost although no method has been presented for the revision. fault impacts the feeder (fuse saving scheme). For a temporary
Reference [6] proposes the use of adaptive microprocessor- fault, however, the recloser must rapidly open to isolate the
based reclosers to solve the fuse-recloser coordination problem feeder and to give the fault a chance to self-clear. If the fuse
in a typical one-feeder test system embedding a DG; however, fails to operate for a permanent fault, the recloser will back it
up by operating in its slow mode. The feeder relay will operate
The authors are with the University of Western Ontario, Lon- lastly only if both the recloser and the fuse fail [8], [9].
don, ON, Canada (e-mails: mzamani2@uwo.ca, tsidhu@eng.uwo.ca, ayaz-
dan2@uwo.ca). Fig. 1 illustrates the basics of the conventional coordina-
tion practice for the relay, recloser, and fuses in a typical

978-1-4244-6551-4/10/$26.00 ©2010 IEEE


2

calculated with no DGs considered, whereas the latter


3
10
Fuse TCT
one is calculated for the configuration where the DGs
Ifmin Ifmax are in place. Such a choice of I f min and If max ensures
2 IR IF
10 preservation of the coordination, even, if the DGs are
Fuse MMT
disconnected from the network, for example due to an
1
10
anti-islanding exercise.
time(s)

Relay
0
3) The characteristic curves of the devices are coordinated
10
Reclose based on the conventional method explained in Section
Slow
1
II, which requires the values I f min and If max .
10
Reclose
Fast
4) Since in the presence of DGs the recloser fault current
2
10
IR is less than the fuse fault current I F , the recloser fast
margin characteristic curve, obtained in Step 3, is revised. This
3
10
2 3 4
requires that the lowest value of I R /IF (less than unity)
10 10 10
current(A)
be calculated, e.g. using an appropriate phase-sequence
equivalent circuit, for the worst-case scenario.
Fig. 1. Typical characteristic curves, their coordination, and the mar-
gin remaining after the addition of a DG
5) The recloser fast characteristic curve is shifted down
through its multiplication by the minimum value of
IR /IF . The revised fast characteristic curve is pro-
distribution network. The figure illustrates that the devices are grammed in the recloser. Thus, the proposed methodol-
coordinated in such a way that, for all fault currents between ogy assumes that the recloser is of the microprocessor-
If min (minimum fault current of the feeder) and I f max (max- based type and therefore programmable.
imum fault current of the feeder), the fast characteristic curve 6) The impact of the DG on the fuse-fuse coordination
of the recloser lies below the fuse Minimum Melting Time of the neighboring feeders is studied to confirm that
(MMT) curve, whereas the slow characteristic curve of the the coordination is preserved. The study methodology,
recloser lies above the fuse Total Clearing Time (TCT) curve and a simple solution for the case where coordination
(descriptions of these curves are provided in the Appendix). is lost will be introduced in Section IV-D. It should
Hence, the recloser opens before the fuse starts to melt and be emphasized that the fuse-fuse coordination loss is
gives temporary faults a chance to self-clear. However, for unlikely to happen in the host feeder. This is due to
a permanent fault the fuse will operate before the recloser our assumption that the DGs get disconnected after the
opens in the slow mode. Fig. 1 also indicates that the relay first operation of the recloser and, thus, the coordination
provides an overall back-up protection since its characteristic fulfilled as explained above retains its validity.
curve lies above all the other curves. Hence, to maintain the The algorithm proposed above assumes that a directional
coordination, one has to ensure that the fault current passing relay is employed at the beginning of the feeders that embed
through the devices remains between I f min and If max . DGs, in order to guarantee that false tripping is avoided.
Moreover, it is assumed that the DGs will be dropped out once
III. I MPACT OF DG ON T RADITIONAL C OORDINATION the feeder recloser opens the circuit [4]-[6]; this is ensured by
AND THE P ROPOSED S OLUTION a transfer-trip mechanism and/or the anti-islanding schemes
incorporated in the individual DGs, as also identified by the
Addition of a DG to a feeder, anywhere downstream of
IEEE Std. 1547 [10]. Fig. 2 provides a graphical illustration
the relay and the recloser, changes I f max and If min and also
of the proposed algorithm.
increases the fuse current as compared to the recloser [5].
The immediate consequence is that the coordination will be
lost if the fault current exceeds I f max , due to the DG. The IV. D ESIGN E XAMPLE
other consequence is that, since as shown in Fig. 1 the recloser To illustrate its effectiveness, the proposed methodology
current IR becomes less than the fuse current I F , the fuse may is applied to, and discussed in the context of, an example
melt before the recloser opens in its fast mode of operation. distribution network which, hereinafter, is referred to as the
To accommodate the impact of distributed generation in the “test system”.
protection coordination, and to overcome the issues mentioned
in Section I, the following algorithm is proposed in this paper.
1) The impact of the DG to be added on the recloser-fuse A. Distribution Network Structure
coordination of the host feeder or a neighboring feeder Fig. 3 illustrates a single-line schematic diagram of the test
is investigated. This is possible based on the approach system, which consists of a 13.8-kV two-feeder distribution
introduced in Section IV-D. If the coordination remains subsystem that supplies the loads L1 through L4 via two
intact in spite of the addition of a DG, the algorithm is feeders, i.e. Feeder 1 and Feeder 2. The subsystem is radially
to be followed from Step 6. Otherwise, the algorithm is connected to the main grid through a transformer and a 69-
exercised from Step 2. kV line. The grid is represented by a 69-kV bus of 1000-MVA
2) The fault current extremes I f min and If max are calcu- short-circuit capacity. The loads consist of linear RL branches
lated for the feeder under study; the former extreme is of different power factors. The basic system configuration and
3

Fig. 3. Single-line schematic diagram of the studied test system

To consider the worst condition, we assume the capacity of


DG1 to be 200% of the maximum feeder load; any larger
capacity is considered unrealistic [6]. We further assume that
the impedance of DG1 is 0.1 pu, as the worst condition [1].
Fig. 2. Flowchart of the proposed method
Moreover, the leakage reactance of the corresponding interface
transformer is assumed to be conservatively low, i.e. 5% [6], to
further contribute to the worst-case condition. The foregoing
parameters are extracted from the benchmark system of the
scenario corresponds to the maximum contribution of DG1
IEEE Std. 399 [11].
to the fault current (for our test system) and results in the
The test system described above also includes two DGs,
largest disparity between the fault currents passing through
DG1 and DG2, of the corresponding capacities of 5.4 MVA
the fuses and the recloser. If the coordination can be fulfill for
and 3.8 MVA, interfaced with Feeder 1 and Feeder 2, respec-
this scenario, it can be achieved for any other condition.
tively. The DGs are considered to be based on the synchronous
The first step of the coordination process is a fault analysis
machine, since electronically-interfaced DGs are limited in
based on Step 2 of the proposed algorithm (see Section III),
terms of fault current and thus may not reveal the protection
in order to determine I f min and If max . For the test system
coordination issues.
of Fig. 3, it can be shown that the maximum fault current
corresponds to a fault taking place at the fuse end of Feeder
B. Coordination of Protection 1, i.e. location Flt1, when DG1 is in place, whereas the fault
Let us first assume that DG2 is not present and, as such, current is minimum when the fault takes place at the end of
the protective devices are coordinated for the configuration the load feeder, location Flt2, in the absence of DG1; such
in which only DG1 exists on Feeder 1. We also assume that a calculation is made separately for phase and earth faults,
DG1 can disrupt the initial coordination of Feeder1, achieved since different settings are usually employed for phase and
through the traditional practice (Section II). Thus, the worst- earth relays. Table I reports the fault analysis results for single-
case scenario that can affect the protection coordination is and three-phase faults impacting Feeder 1, obtained through
considered, and then the coordination strategy of Section simulation of the test system. The table also includes the value
III is employed to reclaim the coordination for Feeder 1. of IR /IF , for each fault scenario. The fault analysis can also
4

3
10
Ifmin
100E Fuse 3052A
TCT Ifmax
2 4661A
10
Relay
100E Fuse (Ext.Inverse,
MMT TD3)
1
10

time(s)
Recloser Slow
0 (Curve8*,TD16)
10

Fig. 4. Equivalent circuit for (IR /IF ) calculation 10


1

Recloser Fast
Original
TABLE I 10
2
(N104,TD2,Min. 0.018)

FAULT CALCULATION RESULTS FOR THE TEST SYSTEM Recloser Fast


Revised
(N104,TD1,Min. 0.012)
IR /IF
3
Fault Fault No DG with DG1 10
2 3 4
10 10 10
Location Type IF (A) IR (A) IF (A) IR (A) with DG1
current(A)
Flt1 ABC 3219 3219 4661 3011 0.646
A-G 1814 1814 2196 1548 0.705 Fig. 5. Coordination of protective devices of Feeder 1 for phase unit
Flt2 ABC 3052 3052 4231 2733 0.646
A-G 1737 1737 1901 1334.5 0.702
3
10
Ifmin
1737A Ifmax
100E Fuse
TCT 2196A
2
10
be conducted based on appropriate phase-sequence equivalent 100E Fuse
MMT
circuits, such as the one shown in Fig. 4 which corresponds 1
10
to the three-phase fault worst case; a similar equivalent circuit Relay
(Ext.Inverse,
time(s)
can also be constructed for a single-phase fault. It can be 0 Recloser Slow
TD1)
10
observed that the value of I R /IF based on the equivalent (Curve8*,TD10)

circuit of Fig. 4 closely agrees with the minimum value of 1


10
IR /IF in Table I. Based on Fig. 4, the value of I R /IF is Recloser Fast
Original
(N104,TD3)
IR ZDG1 2
10
= = 0.65,
Recloser Fast
(1) Revised
IF Zth + ZDG1 (N104,TD2,Min. 0.06)
3
10
where ZDG1 is the aggregate of the impedance of DG1 and 10
2
10
3
10
4

the impedance of the transformer that connects DG1 to the current(A)

network, and Z th is the network Thevenin impedance viewed Fig. 6. Coordination of protective devices of Feeder 1 for earth unit
from the DG1 point of interconnection.
After selection of appropriate characteristic curves based on
Step 3 of the proposed methodology, Section III, the original feeder. In such a scenario, the directional element of the feeder
recloser fast characteristic curve is multiplied by the minimum under study rapidly block its own circuit breaker, for a pre-
value of IR /IF , and the new curve is stored in the program specified period of time, to allow the protective devices of the
of the recloser. The revised characteristic curve is effective faulty feeder to isolate the fault on their own. The blockage,
even after the first opening of the recloser when DG1 gets however, does not continue any longer than the duration of
disconnected. The rationale is that any fault current that might the relay reverse definite time; afterwards, the circuit breaker
develop after the first action of the recloser will certainly be is commanded to open, as a back-up protection. This concept
between If min and If max , and, therefore, the coordination is illustrated in Fig. 7 where t d and td + tgm denote the
made in Steps 2 through 5, Section III, is still applicable; relay forward and reverse definite times, respectively, with D
it is remembered that If max has been calculated with the denoting the output of the directional element. It is noted that
contribution of DG1 considered, whereas I f min is obtained the reverse definite time is larger than its forward counterpart
in the absence of DG1. by a suitable grading margin, t gm .
Figs. 5 and 6 illustrate the original and revised characteristic One potential issue that may arise due to the inclusion
curves employed for the phase and earth units. It should be of directional elements is that of protection loss in case
noted that the recloser must be coordinated with the fastest a fault directly impacts the substation. To circumvent this
fuse of the feeder (100E in this example). In this study, the issue, all circuit breakers are commanded to open once their
characteristics curves of the fuse and recloser are constructed directional elements simultaneously detect a reverse fault. For
based on the analytical equations given in the Appendix. the test system of Fig. 3, this function is realized by the logic
circuit illustrated in Fig. 8, where D 1 and D2 signify the
outputs of the directional elements for Feeder 1 and Feeder 2,
C. Design of Directional Element respectively. The directional elements and their parameters are
As pointed out in Section III, the proposed algorithm introduced in more detail in the Appendix. Fig. 9 illustrates
requires a directional element on each feeder that embeds DGs, the characteristic of the directional elements used in this paper,
to preclude false tripping when a fault impacts a neighboring for the test system.
5

0.6
Zth=0.15pu
Z =0.2pu
0.4 th
Z =0.25pu
th
Zth=0.3pu
0.2

tR2 − M M TF 2 (s)
0

0.2

0.4

0.6 Decreasing Network Z =3.71pu


Thevenin Impedance DG2

0.8
0 0.1 0.2 0.3 0.4 0.5
(ZDG2 )−1 (pu)
Fig. 10. Curves characterizing the recloser-fuse grading time as a
function of (the inverse of) ZDG2

seen from the point of DG2 connection. The result will look
something similar to the equivalent circuit of Fig. 4, in which
subscript “1” is replaced by “2”. The equivalent circuit is used
Fig. 7. Diagrams showing a) forward and reverse definite times for for calculation of I F and IR which are substituted in (2) and
relays, and b)logics of implementation (3), Appendix, to determine the minimum melting time of
fuse F 2, i.e. M M TF 2 , and the operating time of recloser R2,
i.e. tR2 . The coordination is preserved if the recloser operates
faster than the fuse, that is, t R2 − M M TF 2 ≤ 0.
Fig. 10 illustrates the grading time t R2 − M M TF 2 as a
Fig. 8. Symbolic logic circuit for substation protection function of (the inverse of) Z DG2 [Fig. 3], for different network
Thevenin impedances. The figure shows that, for a given
network Thevenin impedance, the recloser-fuse coordination
D. Impact of a DG on the Protection Coordination is preserved if ZDG2 is larger than a minimum value. In
our example, this value is 3.71 pu for the network Thevenin
Thus far, we have ignored the impact of DG2 on the
impedance of 0.2 pu. Also, for a given Z DG2 , the coordination
protection coordination. It is thus imperative to revisit the
is preserved if the network Thevenin impedance is larger than
design, in order to ensure that the coordination is preserved if
a threshold.
DG2 also comes on line. We start this by investigating the
impact of DG2 on its own feeder protection, and then its As will be discussed in Section IV-D3, the fuse-fuse coor-
impact on the coordination of Feeder 1 will be studied. dination of a feeder cannot be compromised by DGs on that
feeder, and therefore is not dealt with in this paper.
1) Impact on the recloser-fuse coordination of the host
feeder (Feeder 2): To investigate the impact of DG2 on 2) Impact on the recloser-fuse coordination of a neighbor-
Feeder 2, the worst condition in which a three-phase fault ing feeder (Feeder 1): An investigation similar to the one
takes place downstream of DG2 is considered. Considering introduced in Section IV-D1 can be conducted to identify the
DG1, a Thevenin equivalent circuit is derived for the network impact of DG2 on the coordination between recloser R1 and
fuse F 1, of Feeder 1. The results indicate that the value of
ZDG2 that causes miscoordination between R1 and F 1 is
considerably smaller than that needed for miscoordination in
Feeder 2. In our test system, this value is 0.395 pu for the
network Thevenin impedance of 0.2 pu. Thus, it is expected
in general that any impedance of a DG (Z DG ) that does
not disrupt the recloser-fuse coordination of its host feeder,
will not compromise that coordination of the neighboring
feeders embedding DGs if the proposed algorithm is used
for the protection coordination of the feeders. However, the
impedance of a DG may be so low that the recloser-fuse
coordination of the host feeder is lost. This may also result in
disruption of the recloser-fuse coordination in a neighboring
feeder. If this is the case, the coordination algorithm of Section
Fig. 9. Characteristic of the directional element (phase comparison) III must be executed for the neighboring feeder, as well as the
6

0.06 3
Zth=0.1pu 10 Ifmax
2279A Ifmax
Z =0.15pu 80E Fuse 3570A
0.04 th TCT
2
Zth=0.2pu 10 Relay
80E Fuse (Ext.Inverse,
0.02 Zth=0.25pu TD2)
MMT
T CTF 12 − M M TF 1 (s)

1
10
0

time(s)
0 Recloser Slow
0.02 10 (Curve8*,TD12)

1
0.04 10
Recloser Fast
Decreasing Network Original
Thevenin Impedance (Curve8*,TD2,Min. 0.02)
0.06 2
10
Recloser Fast
Revised
0.08 (Curve8+,TD1,Min. 0.013)
Z =0.088pu 3
10
DG2
2 3 4
10 10 10
0.1
0 5 10 15 20 current(A)
(ZDG2 )−1 (pu)
Fig. 12. Coordination of protective devices of Feeder 2 for phase unit
Fig. 11. Curves characterizing the fuse-fuse grading time as a function
of (the inverse of) ZDG2
3
10 Ifmin
80E Fuse
TCT 1461A Ifmax
2004A
host feeder. 2
10
3) Impact on the fuse-fuse coordination of a neighboring 80E Fuse
MMT
feeder (Feeder 1): As pointed out in Section I, DGs may 1
10
Relay

time(s)
compromise fuse-fuse coordinations. Based on the design (Ext. Inverse,
TD1)
0 Recloser Slow
10
procedure of Section III, DGs cannot disrupt the coordinations (Curve8*,TD8)

between the fuses of their host feeder, since for any fault 1 Recloser Fast
10
Original
impacting the host feeder, the recloser is supposed to operate (B117,TD2)

and the DGs get dropped out. However, DGs may affect the 2
10
Recloser Fast
Revise
fuse-fuse coordination of neighboring feeders. For example, if (Curve8*,TD1.5,Min. 0.04)

a three-phase fault impacts branch L2, recloser R1 operates 3


10
2
10
3
10
4
10
first, and DG1 will be disconnected. Therefore, DG1 cannot current(A)
affect the coordination between F 1 and F 12; however, DG2 Fig. 13. Coordination of protective devices of Feeder 2 for earth unit
is still on line and can disrupt that coordination. This is
better shown by Fig. 11 where the coordination grading time
between F 1 and F 12, i.e. T CT F 12 − M M TF 1 , is plotted as Figs. 12 and 13 illustrate the original and the revised char-
a function of (the inverse of) Z DG2 , for a three-phase fault acteristic curves, respectively, for the phase and earth relays.
(worst condition) that has taken place at branch L2. Thus, the The curves are for the devices of Feeder 2; the characteristic
fuse-fuse coordination is maintained if the minimum melting curves for the devices of Feeder 1 are produced in a similar
time of F 1 is less than the total clearing time of F 12, that is, fashion, but are not shown here due to space limitations.
T CTF 12 − M M TF 1 ≤ 0. As Fig. 11 indicates, this happens
if and only if Z DG2 is larger than 0.088 pu. It is seen again if V. S IMULATION R ESULTS
ZDG2 can keep coordination between recloser and the fuse, it
will certainly ensure the fuse-fuse coordination for the studied To verify the effectiveness of the proposed coordination
system. algorithm, the test system of Fig. 3 has been modeled and
simulated by PSCAD/EMTDC software. To that end, the same
characteristic curves used for the analytical studies of the
E. Retrieval of protection Coordination after System Alter- proceeding sections have also been utilized for simulation of
ations the relays, the reclosers, and the fuses. This section reports the
Let us consider the worst-case scenario in which the ca- simulation corresponding to a three-phase fault. The results for
pacity of DG2 is two times the host feeder load, and its other types of fault are similar and thus not included.
impedance is 0.1 pu. For our test system, it turns out that Let us first assume that DG2 is not connected, the devices of
this condition results in disruption of the recloser-fuse coor- Feeder 2 are coordinated according to the traditional method,
dination of both feeders (see Sections IV-D1 and IV-D2), but and a permanent three-phase fault impacts the location X1 on
it does not affect the fuse-fuse coordination of Feeder 1 (see Feeder 2, at t = 0.5 s. Fig. 14 illustrates the current waveforms
Section IV-D3). Consequently, we need to repeat the algorithm of the recloser R1 and the fuse F 2. It can be observed that the
proposed in Section III for both feeders, with both DG1 and recloser operates twice in the fast mode of operation and then
DG2 considered, to retrieve the coordination. Had the fuse- the fuse interrupts the fault current. It should be noted that
fuse coordination of Feeder 1 been also lost, we would have the typical operating sequence of a recloser is fast-fast-slow-
needed to increase Z DG2 as the last step of the coordination slow, with a time delay between each two consecutive actions
practice. [2], [5], [6]. Fig. 14 shows that the fault causes the current
7

Current of Recloser R2 Current of Recloser R2


4 4

IR2 (kA)

IR2 (kA)
2 2
0 0
2 2
4 4
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4
Current of Fuse F2 Current of Fuse F2
4 5

IF 2 (kA)
IF 2 (kA)

2
0 0
2
4 5
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4
Current of Recloser R1 Current of Recloser R1
0.5 0.5

IR1 (kA)
IR1 (kA)

0 0

0.5 0.5
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4
time(s) time(s)

Fig. 14. Coordination of devices when DG2 is not in place Fig. 16. Retrieval of coordination after the addition of DG2

Current of Recloser R2 Current of Recloser R2


4 4

IR2 (kA)
IR2 (kA)

2 2
0 0
2 2
4 4
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4 1.6
Current of Fuse F2 Current of Fuse F2
5 5

IF 2 (kA)
IF 2 (kA)

0 0

5 5
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4 1.6
Current of Recloser R1 Current of Recloser R1
0.5 0.5
IR1 (kA)

IR1 (kA)

0 0

0.5 0.5
0.4 0.6 0.8 1 1.2 1.4 0.4 0.6 0.8 1 1.2 1.4 1.6
time(s) time(s)

Fig. 15. Coordination loss when DG2 is added to the test system Fig. 17. Operation of the recloser in the slow mode when the fuse
fails to operate

of Feeder 1 to increase, but does not result in the operation


of Recloser 1; this is due to the blockage exercised by the First, a simple and effective protection strategy was proposed
directional element of the relay of Feeder 1. that provides coordination between protective devices of a
Fig. 15 shows the simulation results for the case where radial distribution system embedding distributed generators.
DG2 is also present, while the devices are coordinated in the The proposed strategy benefits from microprocessor-based
same way as that for the previous case. It is observed that, reclosers and directional elements for feeder relays, and ad-
in this case the same three-phase fault results in the loss of dresses the issues of blinding of protection, false tripping,
coordination, that is, F2 operates before Recloser 2. fuse-recloser and fuse-fuse miscoordination, and failed auto-
Fig. 16 demonstrates the protection response for the case reclosing. Moreover, the proposed strategy does not require
where DG2 is in place and the coordination has been revised adaptive protective devices. Then, the impact of future addi-
as explained in Section IV-E. Thus, the proper sequence of tions of distributed generators on the coordination was investi-
operation has been restored for the protective devices, and re- gated and the requirements for preservation of the coordination
closer R2 operates before F2 is damaged. In this scenario, once were identified. It was further discussed that the proposed
the recloser opens for the first time, DG2 will be disconnected algorithm could be applied for the worst-case scenario, to
subject to a brief delay and, consequently, the fault current reclaim the coordination in case the requirements are not to
stops flowing in both the recloser and the fuse. Therefore, the be met. The simulation results for a test system indicated the
recloser and the fuse will be subjected to the same current effectiveness of the method.
as in the scenario without DG2, once the recloser makes the
circuit. Nonetheless, the coordination remains effective. If the A PPENDIX
fuse fails to operate, the recloser takes action in the slow mode A. Analytical Equations of Protective Devices
and break the fault current, as shown in Fig. 17.
1) Fuse: A Fuse is typically characterized by two character-
istic curves: Minimum Melting Time (MMT) curve and Total
VI. C ONCLUSION Clearing Time (TCT) curve. The MMT curve indicates the
This paper investigated the impact of distributed generation time period between an overcurrent inception and the instant
on the protection coordination of radial distribution networks. when the fuse starts to melt, whereas the TCT curve specifies
8

the total time elapsing from the beginning of an overcurrent R EFERENCES


to the circuit interruption. The fuse characteristic curves can [1] P. P. Barker, R. W. de Mello, ”Determining the impact of distributed
be approximated by an exponential function whose argument generation on power systems: part I-radial distribution systems”, IEEE
is a polynomial of the natural logarithm of the fuse current Trans. on Power Delivery, vol. 15, pp. 486-493, Apr. 2000.
[2] A. Fazanehrafat, S. A. M. Javadian, S. M. T. Batbaee, M. R. Haghifam
[9], [12]: ”Maintaining the recloser-fuse coordination in distribution systems in
 k  presence of DG by determining DG’s size”, in Proc. IET 9th International
 Conference on Developments in Power System Protection (DPSP), pp.
n
tf = exp an ln (If ) , (2) 132-137, Mar. 2008.
n=0 [3] K. Maki, S. Repo, P. Jarventausta, ”Methods for assessing the protection
impacts of distributed generation in network planning activities”, in Proc.
in which k is the polynomial order, I f is the current mag- IET 9th International Conference on Developments in Power System
nitude, and t f is MMT or TCT; the coefficients a n are Protection (DPSP), pp. 484-489, March 2008.
determined through a curve-fitting exercise. In this study, [4] N. Hadjsaid, J. F. Canard, F. Dumas ”Disperse generation impact on
distribution network”, IEEE Computer Application In Power, Vol. 12,
a fifth-order polynomial function of the natural logarithm Issue 2, pp. 22-28, Apr. 1999.
of the fuse current has been used to approximate the fuse [5] A. Girgis and S. M. Brahma, ”Effect of distributed generation on
characteristic curve, i.e. k = 5, the coefficients of which are protective device coordination in distribution system,” in Proc. Large
Engineering Systems Conference on Power Engineering, pp. 115-119,
given in Table II. Jul. 2001.
2) Recloser and Relay: Similarly, relays and reclosers can [6] S. M. Brahma and A. Girgis, ”Microprocessor-based reclosing to coor-
be characterized by inverse-time characteristic curves. Such dinate fuse and recloser in a system with high penetration of distributed
generation,” in Proc. IEEE Power Eng. Soc. Winter Meeting, vol. 1, pp.
curves are generally represented by the following equation 453-458, 2002.
[13]: [7] G. Tang and M. R. Iravani, ”Application of a fault current limiter to
⎡ ⎤ minimize distributed generation impact on coordinated relay protection,”
A presented at the Int. Conf. Power Systems Transients, Montreal, QC,
top (I) = T D ⎣  p + B⎦ , (3) Canada, Jun. 2005.
I
Ipick−up − 1 [8] ”Power System Protection”, Vol. 1-4, Published by Institution of Electri-
cal Engineers, London, UK, Second Edition, 1995
[9] S. Chaitusaney and A. Yokoyama, ”Impact of Protection Coordination on
where top is the device operating time, I is the device current, Sizes of Several Distributed Generation Sources”, in Proc. 7th Interna-
T D is the time dial setting, Ipick−up is the device current set- tional Power Engineering Conference (IPEC), Vol. 2. pp 669-674, Dec.
point, and A, B and p are constant parameters [13], [14]. 2005
[10] IEEE Standard for Interconnecting Distributed Resources with Electric
TABLE II Power Systems, IEEE Std. 1547-2003
C OEFFICIENTS OF FUSE CHARACTERISTIC CURVES [11] IEEE Recommended Practice for Industrial and Commercial Power
System Analysis, IEEE Std. 399-1997.
Fuse a0 a1 a2 a3 a4 a5 [12] S. Santoso and T. A. Short, ”Identification of fuse and recloser operations
Type in a radial distribution systems”, IEEE Trans. on Power Delivery, Vol.
80E,MMT 2976.4 -5341.2 3836.2 -1376 246.4 -17.6 22, No. 4, pp. 2370-2377, Oct. 2007
80E,TCT -77.68 192.64 -156.9 58.6 -10.46 0.73 [13] IEEE Standard Inverse-Time Characteristic Equations for Over-current
100E,MMT -138.13 354.83 -306.54 122.4 -23.38 1.74 Relays, IEEE Standard C37.112-1996, September 1996.
100E,TCT 568.41 -859.72 528.3 -164 25.58 -1.6 [14] ”ABB PCD Control Protection Curves”, online available at:
125E,MMT -1849.8 3143.8 -2104.6 696.1 -114 7.4 http://library.abb.com/GLOBAL/SCOT/scot235.nsf/VerityDisplay
125E,TCT 498.37 -659.1 348.22 -91.14 11.69 -0.58 [15] T. S. M. Rao, ”Power system protection: static relays with microproces-
150E,MMT -214.59 203.02 -57.515 7.07 -2.69 0.31 sor applications”, 2nd Edition, New Delhi, Tata Mc. Graw-Hill, c1989
150E,TCT 1453.8 -2110.3 1231.1 -359.9 52.61 -3.07
M. Amin Zamani (S’09) received the B.Sc. degree from Iran University
of Science and Technology (IUST), Tehran, Iran, and the M.Sc. degree
form Shahid Chamran University (SCU), Ahvaz, Iran, in 2003 and 2005,
respectively. Presently, he is a Research Assistant with the University of
B. Directional Characteristic Western Ontario, London, Ontario, Canada, working towards the Ph.D. degree.
His research area includes power system protection, control, and monitoring;
The directional characteristic function has been realized in distributed generation, power electronic converters, and microgrids.
this paper through a comparator whose inputs S 1 and S2 are
Tarlochan S. Sidhu (M’90-SM’94-F’04) is a Professor and Chair of the
derived from the feeder voltage and current, as follows [8], Electrical and Computer Engineering Department at the University of Western
[15]: Ontario, London, ON, Canada. He is also the Hydro one Chair in Power
Systems Engineering. From 1990 to 2002, he was with the Department
S1 = |S1 |∠α1 = σV , S2 = |S2 |∠α2 = χI, (4) of Electrical Engineering, University of Saskatchewan, as a Professor and
Graduate Chairman of the department. His research interests include power
where σ is a real number, and χ = |χ|∠θ is a complex number system protection, monitoring, control, and automation.
(of impedance dimension) which, conceptually, emulates the Dr. Sidhu is a Fellow of the IEEE, a Fellow of the Institution of Engineers
(India), and a Fellow of the Institution of Electrical Engineer (U.K.). He is a
feeder impedance and thus converts the feeder current into a Registered Professional Engineer in the Province of Ontario and a Chartered
suitable voltage. The comparator identifies a fault as a forward Engineer in the U.K.
fault, i.e. D = 1, if Amirnaser (Amir) Yazdani (M’05-SM’09) received the Ph.D. degree from
π π the University of Toronto, Toronto, ON, Canada, in 2005. He was with Digital
− ≤ α1 − α2 ≤ or Predictive Systems (DPS) Inc., Mississauga, ON, Canada. Currently, he is an
2 2
π π Assistant Professor with the University of Western Ontario, London, ON,
− + θ ≤ ϕl ≤ + θ, (5) Canada. His research interests include dynamic modeling and control of
2 2 electronic power converters, distributed power generation and energy storage,
where ϕl = ϕv −ϕi is the phase difference between the voltage renewable energy, and microgrids. Dr. Yazdani is a Professional Engineer in
the Province of Ontario.
and the current.

You might also like