You are on page 1of 15

SYSTEM SUB-CONTRACTOR)

(BY SYSTEM SUB-CONTRACTOR)

LOCATED AT DB ROOM
(ISOLATOR SWITCH BY
FOR SCADA POWER SUPPLY

CONTINUATION TO SHEET 2 OF 2 AT DRAWING NO.


ISOLATOR SWITCH

KVLRT3-APEX-GS05-STN14-ELEC-MSB-SLD-850101
MATCHLINE
KERAJAAN MALAYSIA
PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


CABLING BY SYSTEM SUB-CONTRACTOR TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

UPS ROOM
EASTERN CORRIDOR
UPS
(BY SYSTEM)

200A TPN SUPERVISING AGENCY :


ISOLATOR SWITCH

4 X 1C 6mm² PVC/PVC CU. CABLE + EARTH IN TRUNKING


CABLING BY SYSTEM

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,

4 X 1C 70mm² LSOH FLAME RETARDANT

4 X 1C 10mm² LSOH FLAME RETARDANT


4 X 1C 6mm² LSOH FLAME RETARDANT
No. 25 Jalan Raja Laut,

T.C.L = 11.15kW

T.C.L = 10.25kW

T.C.L = 15.15kW
T.C.L = 2.21kW

T.C.L = 4.02kW

T.C.L = 1.00kW

T.C.L = 1.36kW

T.C.L = 2.22kW

T.C.L = 3.45kW

T.C.L = 8.79kW

T.C.L = 3.60kW

T.C.L = 1.50kW

T.C.L = 2.75kW

T.C.L = 7.30kW
T.C.L = 1.80kW
CU. CABLE + EARTH IN G.I CONDUIT
50350 Kuala Lumpur Tel : 03 - 2603 6600

M.D = 1.99kW

M.D = 3.61kW

M.D = 0.90kW

M.D = 1.22kW

M.D = 2.00kW

M.D = 3.10kW

M.D = 7.91kW

M.D = 3.24kW

M.D = 8.36kW

M.D = 1.10kW

M.D = 5.98kW

M.D = 8.20kW

M.D = 4.60kW
M.D = 1.62kW
CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING


M.D = 0.6kW
Laman Web : www.apad.gov.my

LOCATED AT GROUND LEVEL LIFT (ACCESS 1 & ACCESS 2)

LOCATED AT GROUND LEVEL LIFT (ACCESS 1 & ACCESS 2)

LOCATED AT GROUND LEVEL LIFT (ACCESS 1 & ACCESS 2)


2 x 1C 2.5mm² FIRE RATED LSOH

DB-CL-BOH/L

DB-CL-BOH/P

DB-CL-FOH/P
DB-CL-FOH/L

DB-GL1/R1

DB-GL2/R1
DB-GL1/P

DB-GL2/P
DB-GL1/L

DB-GL2/L

DB-EL1/P

DB-EL2/P
DB-EL1/L

DB-EL2/2

SPARE
DB-PL/L

DB-PL/P
DB-SG

DB-FL
(BESIDE REPEATER FIRE ALARM PANEL)

(BESIDE REPEATER FIRE ALARM PANEL)

(BESIDE REPEATER FIRE ALARM PANEL)


PROJECT OWNER :
FIREMAN SWITCH 1 (2 NOs)

FIREMAN SWITCH 2 (2 NOs)

FIREMAN SWITCH 3 (2 NOs) PRASARANA MALAYSIA BERHAD (467220-U)


B-20-1, LEVEL 20, MENARA UOA BANGSAR,
NO. 5 JALAN BANGSAR UTAMA 1,
FS FS FS FS FS FS 59000 KUALA LUMPUR.

Tel: 603-22991999 Fax: 603-22991919

CONTRACTOR :
ELR

30A 30A 30A 30A 30A 30A 30A 200A 30A 30A 30A 30A 30A 30A 30A 30A 30A 40A 40A 30A
TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN SPN SPN SPN
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCB MCB MCB MRCB GEORGE KENT SDN BHD
800A 4 POLE
BUSBAR COUPLER LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
400V, 800A, 3 PHASE,
4 WIRE, 50kA, 1 SEC. RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB7 RYB8 RYB9 RYB10 RYB11 RYB12 RYB13 RYB14 RYB15 RYB16 RYB17 R18 Y18 B18
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
AUTO SELANGOR DARUL EHSAN.
EF/OC 400/5A POWER FACTOR
CL 5P10 REGULATOR 4 NOS
400A PFR 800/5A, 15VA 1000/5A, 15VA Tel: 603-50336888 Fax: 603-50336999
ST
TPN CL 1.0
4 x 240mm²/1C MCCB 4 NOS
XLPE/PVC COPPER CABLE TO SCADA DPM 800/5A, 15VA 1000/5A, 15VA
2 x 20A CL 1.0 LEAD CONSULTANT :
4 x 400A TINNED 1 x 40A
COPPER BUSBAR 1 x 80A 3x5A CTs
2 x 150A
AUTOMATIC POWER 2 x 22A
FACTOR CORRECTION 1 x 40A
CAPACITOR BANK 1 x 80A 6 STEPS
AUTO P.F R Y B
3x5A MINCONSULT SDN. BHD.
c/w 6 STEPS AUTOMATIC 2 x 150A REGULATOR (Company No. : 58835-P)
P.F REGULATOR
2 x 15 KVAR Minconsult
1 x 30 KVAR 4 NOS
3XOC EF 800/5A, 15VA 1000/5A, 15VA
1 x 60 KVAR
2 x 120 KVAR 5P20 LOT 6, JALAN 51A/223,
46100 PETALING JAYA, SELANGOR, MALAYSIA.
INTERTRIP 800A Tel : 603-79545757, 79525757
RELAY 4P Fax : 603-79547373, 79547575
ST ATS
(LV BOARD) ACB
SURGE ARRESTOR CLASS 1 CB1 MECHANICAL INTERLOCK by ACB SUPPLIER
c/w 315A AUTO/OFF/MANUAL,
HEALTHY/FAIL COORDINATED ATS MICROPROCESSOR CONTROLLER C/W
limp (N-PE) = 100kA STATUS MCCB ELECTRICALLY INTERLOCKED.
(10/350us) SPD SUBCONTRACTOR :
limp (L-N) = 25kA
(10/350us)
IP31 Isccr = 50kA rms
U 1.5kV @ l
p imp
UV

MSB-UiTM SHAH ALAM 3x5A


T.C.L. = 469.89kW R Y B
2 x 1Cx2.5mm² LSOH CU. CABLE+EARTH
M.D. = 296.75kW IN G.I CONDUIT COMMUNICATIONS SDN BHD
187475-V
(LOCATED AT MSB ROOM)
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
EMERGENCY PUSH BUTTON
ACB STATUS FOR AUTOMATIC CHANGEOVER OPERATION Tel : 03-2148 8810 Fax : 03-2142 4211
SUPPLY MODE
ACB ACB BUSBAR EXIT DOOR
CB1 CB2 COUPLER
1 & 2 SUPPLY HEALTHY Rev Date Description Desg Check Appr
CLOSED CLOSED OPEN
(NORMAL CONDITION)
(INSIDE MSB ROOM) H00 20/09/21 FIRST SUBMISSION M N CM
ONLY 1 SUPPLY HEALTHY CLOSED OPEN CLOSED

ONLY 2 SUPPLY HEALTHY OPEN CLOSED CLOSED

1 & 2 SUPPLY UNHEALTHY ACB STATUS SHALL BE AS PER LAST POSITION


INCOMING NO. 1
3 SETS 4x1C 240mm2 XLPE/SWA/PVC
OPERATION REQUIREMENT : CU. CABLE + 120mm2 LSOH EARTH ON CABLE TRAY
(BY SUB - CONTRACTOR)
1. ELECTRICAL INTERLOCK FOR CIRCUIT BREAKERS, CB1, CB2 & BUSBAR COUPLER
IS ACHIEVED WHEN ONLY TWO OR LESS CIRCUIT BREAKER CAN BE CLOSED AT
ONE TIME. Designed By : MALCOLM
2. AUTO / OFF / MANUAL KEY SWITCH SHALL BE PROVIDED. Drawn By : MARIAM
3. WHEN EMERGENCY PUSH BUTTON IS ACTIVATED. THE RESPECTIVE CONNECTED Checked By : NADZIRAH
ACB SHALL BE TRIPPED.
Approved By : CHANDRAN MOORTHY
ACB STATUS FOR AUTOMATIC CHANGEOVER OPERATION CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-MSB-SLD-300101_H00
Scale : N.T.S
NOTE :
Date : SEPT 2021
Drawing Title :
1. CAPACITOR BANK SHALL BE PROVIDED TO CORRECT OVERALL STATION
POWER FACTOR TO AT LEAST 0.85 LAGGING. CAPACITOR BANK SIZING
LV BOARD KVLRT3 BUJS PKG GS05
SUBJECT TO MANUFACTURER'S RECOMMENDATION. (BY PS & DS SUB-CONTRACTOR) STATION 14 UiTM SHAH ALAM
2. RATING SUBJECT TO MANUFACTURER'S RECOMMENDATION. SINGLE LINE DIAGRAM
MAIN SWITCHBOARD
(SHEET 1 OF 2)
Drawing No : Rev
*PLEASE REFER IFC DRAWING NO: KVLRT3-MRCBGK-GS05-STN14-ELEC-MSB-SLD-250101
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-MSB-SLD-300101 H00
KVLRT3-MRCBGK-GS05-STN14-ELEC-MSB-SLD-850101
CONTINUATION FROM SHEET 1 OF 2 AT DRAWING NO.
KERAJAAN MALAYSIA

SYSTEM SUB-CONTRACTOR)
(BY SYSTEM SUB-CONTRACTOR)
MATCHLINE

LOCATED AT DB ROOM
(ISOLATOR SWITCH BY
FOR SCADA POWER SUPPLY
PROJECT TITLE:

ISOLATOR SWITCH
CONSTRUCTION AND COMPLETION OF LIGHT RAIL
TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EASTERN CORRIDOR

SUPERVISING AGENCY :
CABLING BY SYSTEM SUB-CONTRACTOR
1-4C x 10mm² FIRE RATED LSOH Cu. CABLE
C/W EARTHING CABLE IN CABLE TRAY/TRUNKING

UPS ROOM AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
UPS 50350 Kuala Lumpur Tel : 03 - 2603 6600
(BY SYSTEM) Laman Web : www.apad.gov.my

200A TPN 200A TPN


ISOLATOR SWITCH ISOLATOR SWITCH
CABLING BY SYSTEM

4 x 1C 35mm² LSOH FLAME RETARDANT

4 x 1C 16mm² LSOH FLAME RETARDANT

4 x 1C 70mm² LSOH FLAME RETARDANT


4 x 1C 10mm² LSOH FLAME RETARDANT
4 x 1C 6mm² LSOH FLAME RETARDANT

2 x 1C 6mm² LSOH FLAME RETARDANT

CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING


CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING

CU. CABLE + EARTH IN TRUNKING


PROJECT OWNER :

T.C.L = 37.00kW

T.C.L = 73.00kW

T.C.L = 53.76kW
T.C.L = 47.00kW
SSB-ESCALATOR (U)
M.D = 27.75kW

T.C.L = 6.20kW
SSB-ESCALATOR (P)

T.C.L = 3.50kW

T.C.L = 5.00kW

T.C.L = 3.36kW

T.C.L = 6.68kW

T.C.L = 2.88kW

T.C.L = 3.06kW

T.C.L = 3.06kW

T.C.L = 1.00kW
M.D = 54.75kW

M.D = 26.88kW
M.D = 35.25kW

SSB-FIRE FIGHTING
M.D = 6.20kW

M.D = 2.63kW

M.D = 3.75kW

M.D = 2.26kW

M.D = 3.96kW

M.D = 2.08kW

M.D = 1.94kW

M.D = 1.94kW

M.D = 1.00kW
DB-CL-ADV

DB-PL-ADV

DB-CL/R1

DB-CL/R2
DB-CTER
SSB-LIFT
SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
DB-ATM
DB-MDF
SSB-ME
PRASARANA MALAYSIA BERHAD (467220-U)

DB-BR
B-20-1, LEVEL 20, MENARA UOA BANGSAR,
NO. 5 JALAN BANGSAR UTAMA 1,
59000 KUALA LUMPUR.

Tel: 603-22991999 Fax: 603-22991919

CONTRACTOR :

MRCB GEORGE KENT SDN BHD


LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
ELR 40000, SHAH ALAM,
SELANGOR DARUL EHSAN.

30A 100A 150A 100A 60A 100A 30A 30A 200A 30A 30A 30A 40A 40A 150A 60A 60A 30A 30A 30A 30A 30A 30A 30A Tel: 603-50336888 Fax: 603-50336999
SPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN SPN SPN SPN SPN SPN SPN
MCB 800A 4 POLE MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
BUSBAR COUPLER
LEAD CONSULTANT :
B18 RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB7 RYB8 RYB9 RYB10 RYB11 RYB12 RYB13 RYB14 RYB15 RYB16 RYB17 R18 Y18 B18 R19 Y19 B19

AUTO AUTO
MINCONSULT SDN. BHD.

MARSHALLING CABINET
POWER FACTOR POWER FACTOR 400/5A
REGULATOR EF/OC
REGULATOR 4 NOS 4 NOS CL 5P10 (Company No. : 58835-P)
PFR 800/5A, 15VA 800/5A, 15VA PFR 400A
CL 1.0 ST
CL 1.0 TPN Minconsult
4 NOS 4 NOS MCCB 4 x 240mm²/1C
TO SCADA DPM 800/5A, 15VA 800/5A, 15VA DPM TO SCADA XLPE/PVC COPPER CABLE LOT 6, JALAN 51A/223,
CL 1.0 CL 1.0 2 x 20A
1 x 40A 4 x 400A TINNED 46100 PETALING JAYA, SELANGOR, MALAYSIA.
CTs CTs 3x5A COPPER BUSBAR
3x5A 1 x 80A Tel : 603-79545757, 79525757
2 x 150A
Fax : 603-79547373, 79547575
2 x 22A AUTOMATIC POWER
3x5A 3x5A 1 x 40A FACTOR CORRECTION
6 STEPS 1 x 80A CAPACITOR BANK
R Y B R Y B AUTO P.F 2 x 150A c/w 6 STEPS AUTOMATIC
REGULATOR P.F REGULATOR
4 NOS 2 x 15 KVAR
4 NOS 1 x 30 KVAR
3XOC EF 800/5A, 15VA 800/5A, 15VA EF 3XOC
5P20 1 x 60 KVAR
5P20 2 x 120 KVAR SUBCONTRACTOR :

800A 800A INTERTRIP


4P 4P RELAY
ST ATS ST (LV BOARD)
ACB ACB
SURGE ARRESTOR CLASS 1 CB1 MECHANICAL INTERLOCK by ACB SUPPLIER CB2 SURGE ARRESTOR CLASS 1
c/w 315A AUTO/OFF/MANUAL, 315A c/w
HEALTHY/FAIL COORDINATED ATS MICROPROCESSOR CONTROLLER C/W COORDINATED HEALTHY/FAIL
STATUS MCCB ELECTRICALLY INTERLOCKED. MCCB STATUS limp (N-PE) = 100kA
SPD SPD
(10/350us) COMMUNICATIONS SDN BHD
limp (L-N) = 25kA 187475-V
(10/350us)
Isccr = 50kA rms 12th Floor, Menara Hap Seng
UV UV
U 1.5kV @ l
p imp Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211
3x5A 3x5A
R Y B R Y B 50x6mm EARTH COPPER BAR
2 x 1Cx2.5mm² LSOH CU. CABLE+EARTH
IN G.I CONDUIT
Rev Date Description Desg Check Appr
1x1C 300mm2 LSOH FLAME RETARDANT
CU. GREEN CABLE
(BY SUB-CONTRACTOR)
H00 20/09/21 FIRST SUBMISSION M N CM
EMERGENCY PUSH BUTTON

EXIT DOOR

(INSIDE MSB ROOM)

INCOMING NO. 2
3 SETS 4x1C 630mm2 FLAME RETARDANT 3 SETS 4x1C 240mm2 XLPE/SWA/PVC
CU. CABLE + 300mm2 LSOH EARTH ON CABLE TRAY CU. CABLE + 120mm2 LSOH EARTH ON CABLE TRAY Designed By : MALCOLM
(BY SUB - CONTRACTOR) (BY SUB - CONTRACTOR)
Drawn By : MARIAM
Checked By : NADZIRAH
Approved By : CHANDRAN MOORTHY
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-MSB-SLD-300102_H00
Scale : N.T.S
Date : SEPT 2021
Drawing Title :

KVLRT3 BUJS PKG GS05


STATION 14 UiTM SHAH ALAM
LV BOARD SINGLE LINE DIAGRAM
(BY PS & DS SUB-CONTRACTOR) MAIN SWITCHBOARD
(SHEET 2 OF 2)
Drawing No :
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-MSB-SLD-250102_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-MSB-SLD-300102
Rev
H00
T.C.L = 2.20kW

T.C.L = 1kW

T.C.L = 1kW
T.C.L = 0.5kW

T.C.L = 0.5kW

T.C.L = 0.5kW

T.C.L = 0.5kW
M.D = 2.20kW

2 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE


M.D = 1kW

M.D = 1kW
M.D = 0.5kW

M.D = 0.5kW

M.D = 0.5kW

M.D = 0.5kW

T.C.L = 1kW
M.D = 1kW

C/W EARTHING CABLE IN TRUNKING/CONDUIT


4 x 1C 16mm² FIRE RATED LSOH CU. CABLE
3 x 1C 6mm² FIRE RATED LSOH CU. CABLE
M.D = 13.5 kW

M.D = 13.5 kW

M.D = 13.5 kW
C.L = 18 kW

C.L = 18 kW

C.L = 18 kW
KERAJAAN MALAYSIA

REPEATER FIRE ALARM PANEL

REPEATER FIRE ALARM PANEL


4 x 1C 10mm² FIRE RATED CU. CABLE

AT FHR TANK & PUMP ROOM


PROJECT TITLE:

+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT

AT LIFT LOBBY (ACCESS 1)

AT LIFT LOBBY (ACCESS 2)


HOSE REEL PUMP PANEL

MAIN FIRE ALARM PANEL


CONSTRUCTION AND COMPLETION OF LIGHT RAIL

T.C.L = 2.89kW
+ E IN TRUNKING/CONDUIT
TRANSIT LINE 3 (LRT3) FROM

T.C.L = 2.10kW
M.D = 2.75kW

M.D = 1.89kW
BANDAR UTAMA TO JOHAN SETIA

FM200 PANEL 1

FM200 PANEL 2

FM200 PANEL 3

FM200 PANEL 4
ISOLATOR (L14 - 01)

ISOLATOR (L14 - 02)

ISOLATOR (L14 - 03)

AT MSB ROOM

AT SCR ROOM
AT UPS ROOM

AT EER ROOM

AT SER ROOM
PROJECT PACKAGE:

PL - UPS/L
CL - UPS/L
(RFAP -1)

(RFAP -2)

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
EASTERN CORRIDOR

SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
Tel : 03 - 2603 6600
40A 40A 40A 40A 30A 30A 30A 30A 30A 30A 30A 30A 30A 40A 30A 30A 30A 30A 30A 50350 Kuala Lumpur
Laman Web : www.apad.gov.my
TPN TPN TPN TPN SPN SPN SPN SPN SPN SPN SPN SPN SPN TPN SPN SPN SPN SPN SPN
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
415V, 60A, 3 PHASE, 415V, 40A, 3 PHASE,
415V, 100A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. RYB1 RYB2 RYB3 4 WIRE, 30kA, 3 SEC. RYB1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 RYB5 4 WIRE, 30kA, 3 SEC. R1 R2 Y2 B2 R3

100/5A 60/5A 40/5A


CLASS 1.0 CLASS 1.0 PF
CLASS 1.0 PF
CT CT 5A CT 5A PROJECT OWNER :
PF
5A
3x5A SPD CLASS II (7-MODE) 3x5A SPD CLASS II (7-MODE)
SPD CLASS II (7-MODE) R Y B R Y B
3x5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
ZCT Isccr = 25kA rms ZCT Isccr = 25kA rms ZCT Isccr = 25kA rms
UP @ Imax ≤ 1.5kV ELR
UP @ Imax ≤ 1.5kV
ELR
UP @ Imax ≤ 1.5kV PRASARANA MALAYSIA BERHAD (467220-U)
ELR FUSE UP @ Uoc/Isc ≤ 1.5kV
FUSE
SPD
UP @ Uoc/Isc ≤ 1.5kV FUSE
SPD
UP @ Uoc/Isc ≤ 1.5kV
SPD UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) (FUSE RATING (FUSE RATING B-20-1, LEVEL 20, MENARA UOA BANGSAR,
100A
(FUSE RATING
AS RECOMMENDED
60A AS RECOMMENDED 40A AS RECOMMENDED
S/T TPN BY MANUFACTURER) S/T TPN BY MANUFACTURER) S/T TPN BY MANUFACTURER) NO. 5 JALAN BANGSAR UTAMA 1,
MCCB MCCB MCCB 59000 KUALA LUMPUR.
IP31 IP31 3x5A SWITCHBOARD EARTHING BAR 25mm x IP31 3x5A SWITCHBOARD EARTHING BAR 25mm x
SWITCHBOARD EARTHING BAR 25mm x R Y B R Y B
SSB-LIFT 3x5A SSB-FF(FIRE FIGHTING) 3mm TINNED COPPER BAR WITH MS BOLTS SSB-UPS 3mm TINNED COPPER BAR WITH MS BOLTS
R Y B 3mm TINNED COPPER BAR WITH MS BOLTS T.C.L = 7.20kW T.C.L = 6.20kW
T.C.L = 54.0 kW & NUTS
& NUTS & NUTS Tel: 603-22991999 Fax: 603-22991919
M.D = 40.50 kW M.D = 7.20kW M.D = 6.20kW
(LOCATED AT MSB ROOM) (LOCATED AT MSB ROOM) (LOCATED AT DB ROOM)
CONTRACTOR :

4 x 1C 16mm² LSOH FLAME RETARDANT CU. CABLE 4 x 1C 10mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN TRUNKING + E IN TRUNKING
4 x 1C 35mm² LSOH FLAME RETARDANT CU. CABLE (CABLING BY SUB-CONTRACTOR)
+ E IN TRUNKING
FROM MSB-UiTM SHAH ALAM FROM UPS ISOLATOR SWITCH (ISOLATOR SWITCH BY SYSTEM SUB-CONTRACTOR)
(LOCATED AT DB ROOM)
MRCB GEORGE KENT SDN BHD
FROM MSB-UiTM SHAH ALAM
LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999


M.D = 11.25kW

M.D = 11.25kW
C.L = 15kW

C.L = 15kW

M.D = 16.5 kW

M.D = 16.5 kW

M.D = 16.5 kW

M.D = 16.5 kW
LEAD CONSULTANT :

C.L = 22 kW

C.L = 22 kW

C.L = 22 kW

C.L = 22 kW
MINCONSULT SDN. BHD.
4 x 1C 10mm² FIRE RATED CU. CABLE

Minconsult
ISOLATOR (FOR ESCALATOR 5)

ISOLATOR (FOR ESCALATOR 6)

4 x 1C 10mm² FIRE RATED CU. CABLE


+ E IN TRUNKING/CONDUIT

ISOLATOR (FOR ESCALATOR 1)

ISOLATOR (FOR ESCALATOR 2)

ISOLATOR (FOR ESCALATOR 3)

ISOLATOR (FOR ESCALATOR 4)


+ E IN TRUNKING/CONDUIT

SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211
40A 40A 40A 40A 40A 40A
TPN TPN TPN TPN TPN TPN
MCCB MCCB MCCB MCCB MCCB MCCB
Rev Date Description Desg Check Appr
415V, 100A, 3 PHASE, 415V, 150A, 3 PHASE,
H00 20/09/21 FIRST SUBMISSION M N CM
4 WIRE, 30kA, 3 SEC. RYB1 RYB2 4 WIRE, 30kA, 3 SEC. RYB1 RYB2 RYB3 RYB4

100/5A 150/5A
CLASS 1.0 CLASS 1.0
CT PF CT
5A PF
5A
3x5A SPD CLASS II (7-MODE) SPD CLASS II (7-MODE)
R Y B
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) 3x5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
ZCT Isccr = 25kA rms ZCT Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
ELR FUSE UP @ Uoc/Isc ≤ 1.5kV ELR FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) Designed By : MALCOLM
100A AS RECOMMENDED 150A
(FUSE RATING
AS RECOMMENDED Drawn By :
S/T TPN BY MANUFACTURER) S/T TPN BY MANUFACTURER)
MARIAM
MCCB MCCB
Checked By : NADZIRAH
IP31 IP31
SSB-ESCALATOR (P)
SWITCHBOARD EARTHING BAR 25mm x SWITCHBOARD EARTHING BAR 25mm x Approved By : CHANDRAN MOORTHY
3x5A 3mm TINNED COPPER BAR WITH MS BOLTS SSB-ESCALATOR (U) 3x5A 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L = 30.0kW R Y B & NUTS T.C.L = 88.0 kW R Y B
M.D = 22.5kW
& NUTS CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-SSB-SLD-300103
M.D = 66.0 kW
(LOCATED AT MSB ROOM) (LOCATED AT MSB ROOM) Scale : N.T.S
Date : SEPT 2021
4 x 1C 35mm² LSOH FLAME RETARDANT CU. CABLE Drawing Title :
+ E IN TRUNKING 4 x 1C 70mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN TRUNKING
KVLRT3 BUJS PKG GS05
FROM MSB-UiTM SHAH ALAM FROM MSB-UiTM SHAH ALAM STATION 14 UiTM SHAH ALAM
SINGLE LINE DIAGRAM
SUB-SWITCHBOARD

Drawing No :
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-SSB-SLD-250103_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-SSB-SLD-300103
Rev
H00
ENTRANCE LINK POB

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT ENTRANCE LINK POB


1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT SERVICE CORRIDOR
HR & ELECT RISER

BICYCLE PARKING

BICYCLE PARKING

STATION ACCESS

STATION ACCESS

STATION ACCESS

ENTRANCE 1

ENTRANCE 1

ENTRANCE 1
TEL RISER &

STAIRCASE
LIFT SHAFT
LIFT LOBBY

LIFT LOBBY

LIFT LOBBY

LIFT LOBBY
LIFT SHAFT

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR
KERAJAAN MALAYSIA

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL

5 - 1 x 38W LED BATTEN FITTING W/PROOF


1 - 1 x 38W LED BATTEN FITTING W/PROOF

6 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

4 - 1 x 38W LED BATTEN FITTING W/PROOF

4 - 1 x 38W LED BATTEN FITTING W/PROOF


1 -1 x 38W LED BATTEN FITTING W/PROOF

3 -1 x 38W LED BATTEN FITTING W/PROOF

2 -1 x 38W LED BATTEN FITTING W/PROOF

5 -1 x 38W LED BATTEN FITTING W/PROOF

4 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

7 -1 x 38W LED BATTEN FITTING W/PROOF

7 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

7 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF


TRANSIT LINE 3 (LRT3) FROM

2 x 1C 1.5mm² LSOH FLAME RETARDANT

2 x 1C 1.5mm² LSOH FLAME RETARDANT


CU CABLE + E IN CONDUIT / TRUNKING
CU CABLE + E IN CONDUIT / TRUNKING
BANDAR UTAMA TO JOHAN SETIA

1 - LED ILLUMINATED 'KELUAR' SIGN


PROJECT PACKAGE:

2 - 1 x 23W LED BATTEN FITTING

2 - 1 x 23W LED BATTEN FITTING


EASTERN CORRIDOR

2 - 100W LED HIGHBAY


SUPERVISING AGENCY :

SPARE

SPARE
SPARE
SPARE
AGENSI PENGANGKUTAN AWAM DARAT ( APAD )
Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

PROJECT OWNER :
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN 10A 10A 10A 10A 10A 10A 10A 10A 10A
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB SPN SPN SPN SPN SPN SPN SPN SPN SPN
415V, 30A, 3 PHASE, MCB MCB MCB MCB MCB MCB MCB MCB MCB
415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 PRASARANA MALAYSIA BERHAD (467220-U)
RCCB 30A 4P (100 mA)
SPD CLASS II (7-MODE) RCCB 30A 4P (100 mA) SPD CLASS II (7-MODE) B-20-1, LEVEL 20, MENARA UOA BANGSAR,
3x5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
NO. 5 JALAN BANGSAR UTAMA 1,
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 3 x 5A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms
R Y B Isccr = 25kA rms 59000 KUALA LUMPUR.
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED Tel: 603-22991999 Fax: 603-22991919
BY MANUFACTURER) BY MANUFACTURER)

IP-31 30A IP-31 30A CONTRACTOR :


DB-GL1/L TPN SWITCHBOARD EARTHING BAR 25mm x DB-EL1/L TPN SWITCHBOARD EARTHING BAR 25mm x
MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 1.03 kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 3.02 kW & NUTS & NUTS
M.D. = 2.72 kW M.D. = 0.93 kW
(LOCATED IN SERVICE CORRIDOR) (LOCATED AT ENTRANCE LINK 1)
4 x 1C 6mm2 PVC/PVC CU. CABLE MRCB GEORGE KENT SDN BHD
+ E IN CABLE TRAY / TRUNKING 4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY / TRUNKING LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
FROM MSB - UiTM SHAH ALAM FROM MSB - UiTM SHAH ALAM
40000, SHAH ALAM,
SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT ENTRANCE LINK POB


ENTRANCE LINK POB

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT ENTRANCE LINK POB

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT ENTRANCE LINK POB


LEAD CONSULTANT :
STATION ACCESS 1

STATION ACCESS 1

STATION ACCESS 1

ENTRANCE 2

ENTRANCE 2
MINCONSULT SDN. BHD.

STAIRCASE
LIFT SHAFT
LIFT LOBBY

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT LIFT LOBBY

LIFT LOBBY

LIFT LOBBY

LIFT LOBBY

LIFT LOBBY

LIFT LOBBY
LIFT SHAFT

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

(Company No. : 58835-P)


Minconsult

LOT 6, JALAN 51A/223,

3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

46100 PETALING JAYA, SELANGOR, MALAYSIA.


Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575

1 - 1 x 38W LED BATTEN FITTING W/PROOF

7 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

6 - 1 x 38W LED BATTEN FITTING W/PROOF

4 - 1 x 38W LED BATTEN FITTING W/PROOF


1 -1 x 38W LED BATTEN FITTING W/PROOF

3 -1 x 38W LED BATTEN FITTING W/PROOF

3 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

6 -1 x 38W LED BATTEN FITTING W/PROOF

2 x 1C 1.5mm² LSOH FLAME RETARDANT


2 x 1C 1.5mm² LSOH FLAME RETARDANT

CU CABLE + E IN CONDUIT / TRUNKING


CU CABLE + E IN CONDUIT / TRUNKING

1 - LED ILLUMINATED 'KELUAR' SIGN


SUBCONTRACTOR :
2 - 100W LED HIGHBAY

4 - 100W LED HIGHBAY

4 - 100W LED HIGHBAY

3 - 100W LED HIGHBAY

2 - 100W LED HIGHBAY

3 - 100W LED HIGHBAY

3 - 100W LED HIGHBAY

3 - 100W LED HIGHBAY

COMMUNICATIONS SDN BHD


187475-V

SPARE

SPARE

SPARE

SPARE
SPARE

SPARE
SPARE

SPARE

12th Floor, Menara Hap Seng


Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


H00 21/09/21 FIRST SUBMISSION M N CM

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
415V, 30A, 3 PHASE, MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4
RCCB 30A 4P (100 mA) Designed By : MALCOLM
SPD CLASS II (7-MODE) RCCB 30A 4P (100 mA) SPD CLASS II (7-MODE)
Drawn By : MARIAM
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
3x5A
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 3 x 5A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Checked By : HIDAYAH
Isccr = 25kA rms R Y B Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc /Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
Approved By : CHANDRAN MOORTHY
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300104_H00
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER) Scale : N.T.S
IP-31 30A IP-31 30A Date : SEPT 2021
DB-GL2/L TPN SWITCHBOARD EARTHING BAR 25mm x DB-EL2/L TPN SWITCHBOARD EARTHING BAR 25mm x
MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 1.36 kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS Drawing Title :
T.C.L. = 4.02 kW & NUTS & NUTS
M.D. = 3.61 kW M.D. = 1.22 kW
(LOCATED IN SERVICE CORRIDOR) (LOCATED AT ENTRANCE LINK 2) KVLRT3 BUJS PKG GS05
4 x 1C 6mm2 PVC/PVC CU. CABLE
+ E IN CABLE TRAY / TRUNKING 4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE STATION 14 UiTM SHAH ALAM
+ E IN CABLE TRAY / TRUNKING
SINGLE LINE DIAGRAM
FROM MSB - UiTM SHAH ALAM FROM MSB - UiTM SHAH ALAM
LIGHTING FOR GROUND & ENTRANCE LINK

Drawing No : Rev
*PLEASE REFER IFC DRAWING NO :KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250104_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300104 H00
FROM
SCADAPH
IP-31

(N)

IP-31
TIME
24 hrs
DB-CL/BOH/L
M.D. = 1.94 kW
T.C.L. = 2.16 kW

DB-CL/FOH/L
N

SWITCH TS

M.D. = 2.96 kW
T.C.L. = 3.29kW
(LOCATED IN DB ROOM)
2 x 1C 1.5mm² LSOH FLAME RETARDANT

(LOCATED IN DB ROOM)
CU CABLE + E IN CONDUIT / TRUNKING

400V, 30A, 3 PHASE,


4 WIRE, 30kA, 3 SEC.

SWITCH
4 - 2 x 23W LED BATTEN FITTING

415V, 30A, 3 PHASE,


4 WIRE, 30kA, 3 SEC.
C

BY PASSN
R1
2 x 1C 1.5mm² LSOH FLAME RETARDANT 2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT EER ROOM

10A
SPN

10A
MCB
CU CABLE + E IN CONDUIT / TRUNKING 8 - 1 x 38W LED BATTEN FITTING (W/PROOF) DCW &

FUSE
Y1
3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT RWH TANK + PUMP

10A
SPN
MCB
2 - 1 x 23W LED BATTEN FITTING CHR ROOM 4 - 2 x 23W LED BATTEN FITTING

R1
B1
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT SER ROOM

10A
SPN
MCB
10A
SPN
2 - 1 x 23W LED BATTEN FITTING

MCB
JANITOR ROOM 5 - 2 x 23W LED BATTEN FITTING

Y1
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT BOH CORRIDOR

R2
3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB
6 - 15W LED RECESSED DOWNLIGHT TOILET (M)

B1
2 - 1 X 8W SURFACE MOUNTED EMERGENCY LIGHT 5 - 1 x 38W LED BATTEN SUSPENDED FITTING ACU 3 ROOM

Y2

10A
SPN
MCB
10A
SPN
MCB
1 - 1 x 38W LED BATTEN FITTING (W/PROOF) SERVICE CORRIDOR 4 -1 x 38W LED BATTEN FITTING W/PROOF

R2
(ANTI CORROSIVE) UPS ROOM

B2
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB
7 - 15W LED RECESSED DOWNLIGHT 2 -1 x 38W LED BATTEN FITTING W/PROOF
TOILET (F)

Y2
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT (ANTI CORROSIVE) GAS ROOM

R3
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB
3 - 15W LED RECESSED DOWNLIGHT
DISABLE TOILET 4 - 1 x 23W LED BATTEN FITTING

B2
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT ENGINEER ROOM

Y3
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
6 - 15W LED RECESSED DOWNLIGHT MCB
SURAU (M) 3 - 1 x 23W LED BATTEN FITTING

R3
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT BOH CORRIDOR 2
B3
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB

6 - 15W LED RECESSED DOWNLIGHT SURAU (F) 5 - 1 x 23W LED BATTEN FITTING

Y3
30A
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT BOH CORRIDOR 2

TPN
R4

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

MCCB

10A
SPN
3x5A

MCB
10A
SPN
MCB

4 - 35W LED RECESSED FLAT PANEL

FROM MSB - UiTM SHAH ALAM


FA ROOM 2 - 35W (600x600)mm LED FLAT PANEL

B3
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT STAFF ROOM
Y4

R
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB

2 - 35W LED RECESSED FLAT PANEL


Y

FUSE
SMO ROOM 4 - 1 x 23W LED BATTEN FITTING

R4
(FUSE RATING
RCCB 30A 4P (100 mA)

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT DB ROOM


B4

AS RECOMMENDED
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
BY MANUFACTURER)
B

SPN
MCB
10A
SPN
MCB

2 - 35W LED RECESSED FLAT PANEL SCR ROOM 6 - 2 x 23W LED BATTEN FITTING

Y4
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT MSB ROOM
R5

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
10A
SPN
MCB

2 - 35W LED RECESSED FLAT PANEL CSO ROOM

B4
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 4 - LED ILLUMINATED 'KELUAR' SIGN UPS ROOM & EER ROOM
Y5

10A
+ E IN CABLE TRAY / TRUNKING

SPN
MCB
10A
SPN
MCB

6 - 15W LED RECESSED DOWNLIGHT PAID AREA SER ROOM, DB ROOM

R5
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 4 - LED ILLUMINATED 'KELUAR' SIGN
B5

& MSB ROOM

10A
SPN
MCB
10A
SPN
MCB

5 - 15W LED RECESSED DOWNLIGHT


SPD

PAID AREA

Y5
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 2 - 1 x 38W LED BATTEN SUSPENDED FITTING ACU 2 ROOM
R6

10A
SPN
MCB
10A
SPN
MCB

6 - 1 x 23W LED BATTEN FITTING STORE

B5
4 x 1C 10mm2 LSOH FLAME RETARDANT CU. CABLE

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT SPARE


Y6

& NUTS

10A
SPN
MCB
10A
SPN
MCB

5 - 15W LED RECESSED DOWNLIGHT CSO ROOM

R6
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT SPARE
B6

Isccr = 25kA rms


UP @ Imax ≤ 1.5kV

10A
UP @ Uoc/Isc ≤ 1.5kV

SPN
MCB
10A

SPD CLASS II (7-MODE)


SPN
MCB

6 - 15W LED RECESSED DOWNLIGHT PAID AREA

Y6
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
5 - 15W LED RECESSED DOWNLIGHT
SWITCHBOARD EARTHING BAR 25mm x
3mm TINNED COPPER BAR WITH MS BOLTS

PAID AREA
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap

UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)

B6
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
6 - 15W LED RECESSED DOWNLIGHT PAID AREA

R7
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
1 - LED ILLUMINATED 'KELUAR' SIGN STAIRCASE 1

Y7
10A
SPN
MCB
6 - 15W LED RECESSED DOWNLIGHT CORRIDOR

B7
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

10A
SPN
MCB
1 - 1 x 23W LED BATTEN FITTING ELV RISER

R8
10A
SPN
MCB
1 - 1 x 38W LED BATTEN FITTING (W/PROOF) LIFT 1

Y8
10A
SPN
MCB
1 - 1 x 23W LED BATTEN FITTING LV RISER

B8
10A
SPN
MCB
IP-31

5 - 15W LED RECESSED DOWNLIGHT PAID AREA

R9
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 2 x 1C 1.5mm² LSOH FLAME RETARDANT

10A
SPN
MCB
DB-CL-UPS/L

CU CABLE + E IN CONDUIT / TRUNKING


M.D. = 2.73 kW

7 - 15W LED RECESSED DOWNLIGHT


T.C.L. = 2.87 kW

PAID AREA

Y9
240V, 30A, 1 PHASE,

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


2 WIRE, 30kA, 3 SEC.

10A
SPN
MCB
2 - 2 x 23W LED BATTEN FITTING EER ROOM
R1

7 - 15W LED RECESSED DOWNLIGHT PAID AREA

B9
(LOCATED IN DB ROOM)

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


2 - 2 x 23W LED BATTEN FITTING SER ROOM

10A
Y1

SPN
MCB
6 - 15W LED RECESSED DOWNLIGHT

30A
TPN
PAID AREA 3 -1 x 38W LED BATTEN FITTING W/PROOF
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

R10

MCCB
UPS ROOM
B1

3x5A
(ANTI CORROSIVE)

10A
SPN
MCB
5 - 15W LED RECESSED DOWNLIGHT PAID AREA 3 - 15W LED RECESSED DOWNLIGHT

R
CORRIDOR
R2

FROM MSB - UiTM SHAH ALAM


2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

Y10
10A
SPN
MCB

FUSE
RCCB 30A 4P (100 mA)
PAID AREA

(FUSE RATING
Y2

6 - 15W LED RECESSED DOWNLIGHT PAID AREA 6 - 15W LED RECESSED DOWNLIGHT

B10
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

AS RECOMMENDED
BY MANUFACTURER)
B
10A
6 - 15W LED RECESSED DOWNLIGHT PAID AREA
SPN
B2

MCB
5 - 15W LED RECESSED DOWNLIGHT PAID AREA
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

R11
6 - 15W LED RECESSED DOWNLIGHT PAID AREA
R3

10A
SPN
MCB
5 - 15W LED RECESSED DOWNLIGHT
ACCESS 1 STATION 2 - 15W LED RECESSED DOWNLIGHT PAID AREA
Y3

Y11 2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

+ E IN CABLE TRAY / TRUNKING


10A
SPN
MCB

5 - 15W LED RECESSED DOWNLIGHT 5 - 15W LED RECESSED DOWNLIGHT PAID AREA
B3

ACCESS 1 STATION
3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT
B11
10A
SPN
MCB

SPD
8 - 15W LED RECESSED DOWNLIGHT PAID AREA
R4

7 - 15W LED RECESSED DOWNLIGHT UNPAID AREA


3 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT
R12
10A

6 - 15W LED RECESSED DOWNLIGHT PAID AREA


Y4

SPN
MCB

4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE


ACU 4

& NUTS
1 - 1 x 38W LED BATTEN FITTING (W/PROOF)
Y12

6 - 15W LED RECESSED DOWNLIGHT PAID AREA


30A
B4

SPN

FROM UPS

10A
SPN
MCB
MCCB

4 - 1 x 23W LED BATTEN FITTING


3 x 5A

CORRIDOR
Isccr = 25kA rms
B12

UP @ Imax ≤ 1.5kV

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT 1 - 35W (600x600)mm LED FLAT PANEL CSO
R5

UP @ Uoc/Isc ≤ 1.5kV
10A

SPD CLASS II (7-MODE)


R

SPN
MCB

2 - LED ILLUMINATED 'KELUAR' SIGN UNPAID AREA 1 - 35W (600x600)mm LED FLAT PANEL SCR
Y5

R13
Y

FUSE

(FUSE RATING
RCCB 30A 4P (100 mA)

10A
SPN
MCB

SWITCHBOARD EARTHING BAR 25mm x


3mm TINNED COPPER BAR WITH MS BOLTS
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
AS RECOMMENDED

UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)


BY MANUFACTURER)
B

In/Imax (L-N & N-PE) = 40/80kA (8/20µs)

1 - 1 x 38W LED BATTEN FITTING (W/PROOF) ACU 5 1 - 35W (600x600)mm LED FLAT PANEL SMO
B5

Y13
10A
SPN
MCB

5 - 15W LED FLAT PANEL PAID AREA


R6

1 - LED ILLUMINATED 'KELUAR' SIGN STAIRCASE 2


B13
10A
SPN
MCB

4 - 15W LED FLAT PANEL


Y6

3 - 15W LED RECESSED DOWNLIGHT PAID AREA


+ E IN CABLE TRAY / TRUNKING

STAIRCASE 2
R14

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


10A

5 - 15W LED FLAT PANEL


SPN
B6

PAID AREA
MCB

3 - LED ILLUMINATED 'KELUAR' SIGN CORRIDOR


Y14
SPD

SPARE
R7

10A
SPN
MCB

SPARE
B14

SPARE
2 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE
Y7

10A
& NUTS

SPN
MCB

SPARE SPARE
B7

R15
10A
SPN
Isccr = 25kA rms

MCB
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A

UP @ Imax ≤ 1.5kV
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB

UP @ Uoc/Isc ≤ 1.5kV

SPARE
SPD CLASS II (7-MODE)

Y15
R8

1 - VENTILATION FAN PANEL (VFP-6021) UPS ROOM


10A
SPN
MCB

SPARE 1 - VENTILATION FAN PANEL (VFP-6031) SER ROOM


Y8

B15
SWITCHBOARD EARTHING BAR 25mm x
3mm TINNED COPPER BAR WITH MS BOLTS
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap

UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)


In/Imax (L-N & N-PE) = 40/80kA (8/20µs)

*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250105_WW01


10A
SPN
MCB

1 - VENTILATION FAN PANEL (VFP-6041) EER ROOM


B8
10A 10A 10A
SPN SPN SPN
MCB MCB MCB

R9

SPARE

SPARE
Y9
10A 10A
SPN SPN
MCB MCB

SPARE
B9

2 x 1C 4mm² LSOH FLAME RETARDANT


CU CABLE + E IN CONDUIT / TRUNKING
SHOP DRAWING
H00
Rev

Date :
Scale :
Minconsult

Drawn By :

Drawing No :
PROJECT TITLE:

CONTRACTOR :

Drawing Title :
Date
21/09/21
SUBCONTRACTOR :

N.T.S
PROJECT OWNER :
PROJECT PACKAGE:

LEAD CONSULTANT :

SEPT 2021
MARIAM
Checked By : HIDAYAH
SUPERVISING AGENCY :

Designed By : MALCOLM
Tel: 603-22991999

LOT 6, JALAN 51A/223,


50350 Kuala Lumpur

Tel: 603-50336888
No. 25 Jalan Raja Laut,

Approved By : CHANDRAN MOORTHY


Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575

FIRST SUBMISSION
Description

LIGHTING FOR
EASTERN CORRIDOR

46100 PETALING JAYA, SELANGOR, MALAYSIA.


40000, SHAH ALAM,
59000 KUALA LUMPUR.

CONCOURSE LEVEL
12th Floor, Menara Hap Seng

SINGLE LINE DIAGRAM


M
SELANGOR DARUL EHSAN.

187475-V
TRANSIT LINE 3 (LRT3) FROM

Desg
Jalan P Ramlee 50250 Kuala Lumpur
NO. 5 JALAN BANGSAR UTAMA 1,

KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300105
Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,

STATION 14 UiTM SHAH ALAM


COMMUNICATIONS SDN BHD
BANDAR UTAMA TO JOHAN SETIA

MRCB GEORGE KENT SDN BHD

Tel : 03-2148 8810 Fax : 03-2142 4211


(Company No. : 58835-P)

KVLRT3 BUJS PKG GS05


NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
B-20-1, LEVEL 20, MENARA UOA BANGSAR,

N
Fax: 603-22991919

LEVEL 3, MENARA BANK RAKYAT SHAH ALAM

Check
Fax: 603-50336999
CONSTRUCTION AND COMPLETION OF LIGHT RAIL
KERAJAAN MALAYSIA

CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300105_H00

H00
Rev
MINCONSULT SDN. BHD.
Laman Web : www.apad.gov.my

CM
AGENSI PENGANGKUTAN AWAM DARAT ( APAD )

Tel : 03 - 2603 6600

PRASARANA MALAYSIA BERHAD (467220-U)

Appr
KERAJAAN MALAYSIA
PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EER ROOM

SER ROOM

UPS ROOM

CORRIDOR

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA
EASTERN CORRIDOR

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


SUPERVISING AGENCY :

6 - 1 x 38W LED BATTEN FITTING W/PROOF


6 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

6 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF

6 - 1 x 38W LED BATTEN FITTING W/PROOF

5 - 1 x 38W LED BATTEN FITTING W/PROOF


2 x 1C 1.5mm² LSOH FLAME RETARDANT
CU CABLE + E IN CONDUIT / TRUNKING
AGENSI PENGANGKUTAN AWAM DARAT ( APAD )
Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

SPARE

SPARE

SPARE

SPARE

SPARE
PROJECT OWNER :

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
240V, 30A, 1 PHASE,
2 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 PRASARANA MALAYSIA BERHAD (467220-U)
RCCB 30A 2P (100 mA) B-20-1, LEVEL 20, MENARA UOA BANGSAR,
3 x 5A NO. 5 JALAN BANGSAR UTAMA 1,
R Y B SPD CLASS II (7-MODE)
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) 59000 KUALA LUMPUR.
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms
UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) Tel: 603-22991999 Fax: 603-22991919
(FUSE RATING
AS RECOMMENDED
BY MANUFACTURER)
CONTRACTOR :
IP-31 30A
DB-PL-UPS/L SPN SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 2.10 kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS
M.D. = 1.89 kW
(LOCATED IN DB ROOM)
MRCB GEORGE KENT SDN BHD
4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY / TRUNKING LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
FROM UPS NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

5 - 1 X 38W LED BATTEN FITTING (W/PROOF)


6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

5 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

5 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

5 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)

6 - 1 X 38W LED BATTEN FITTING (W/PROOF)


LEAD CONSULTANT :
2 x 1C 1.5mm² LSOH FLAME RETARDANT
CU CABLE + E IN CONDUIT / TRUNKING

MINCONSULT SDN. BHD.


2 - 1 X 23W LED BATTEN FITTING

2 - 1 X 23W LED BATTEN FITTING

2 - 1 X 23W LED BATTEN FITTING


(Company No. : 58835-P)
Minconsult

LOT 6, JALAN 51A/223,


46100 PETALING JAYA, SELANGOR, MALAYSIA.
Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575

SPARE

SPARE

SPARE
SUBCONTRACTOR :

(N)
N
C
FROM PH
SCADA TIME COMMUNICATIONS SDN BHD
SWITCH TS BY PASS N
24 hrs SWITCH 187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A Tel : 03-2148 8810 Fax : 03-2142 4211
FUSE SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9 R10 Y10 B10 R11 Y11 B11 R12 Y12 B12 R13 Y13 B13 R14 Y14 B14 Rev Date Description Desg Check Appr
30A 4P (100 mA) H00 21/09/21 FIRST SUBMISSION M N CM
RCCB
SPD CLASS II (7-MODE)
3 x 5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms
UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
AS RECOMMENDED
BY MANUFACTURER)

IP-31 30A SWITCHBOARD EARTHING BAR 25mm x


DB-PL/L TPN 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 8.20 kW MCCB & NUTS
M.D. = 7.38 kW
(LOCATED IN LV RISER AT PLATFORM LEVEL)
(LIMIT DB WIDTH TO 450mm) 4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE Designed By : MALCOLM
+ E IN CABLE TRAY / TRUNKING Drawn By : MARIAM
Checked By : NADZIRAH
FROM MSB-UiTM SHAH ALAM
Approved By : CHANDRAN MOORTHY
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300106_H00
Scale : N.T.S
Date : SEPT 2021
Drawing Title :

KVLRT3 BUJS PKG GS05


STATION 14 UiTM SHAH ALAM
SINGLE LINE DIAGRAM
LIGHTING FOR
PLATFORM LEVEL
Drawing No :
*PLEASE REFER IFC DRAWING NO :KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250106_WW01 SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300106
Rev
H00
COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY
3 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

3 - 1 X 38W WEATHERPROOF LED BATTEN FITTING


2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


KERAJAAN MALAYSIA

7 - 1 X 38W WIREGUARD LED BATTEN FITTING

6 - 1 X 38W WIREGUARD LED BATTEN FITTING

6 - 1 X 38W WIREGUARD LED BATTEN FITTING


2 - 1C X 1.5mm² LSOH FLAME RETARDANT

2 - 1C x 1.5mm² LSOH FLAME RETARDANT


CU CABLE + E IN CONDUIT / TRUNKING

CU CABLE + E IN CONDUIT / TRUNKING


PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EASTERN CORRIDOR

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

N N
C C

TIME TIME
SWITCH TS BY PASS SWITCH TS BY PASS PROJECT OWNER :
24 hrs SWITCH 24 hrs SWITCH

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
FUSE SPN SPN SPN SPN SPN SPN FUSE SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
415V, 30A, 3 PHASE, 415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 PRASARANA MALAYSIA BERHAD (467220-U)
RCCB 30A 4P SPD CLASS II (7-MODE) RCCB 30A 4P SPD CLASS II (7-MODE) B-20-1, LEVEL 20, MENARA UOA BANGSAR,
(100 mA) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
(100 mA) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
6A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 6A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
NO. 5 JALAN BANGSAR UTAMA 1,
R Y B Isccr = 25kA rms R Y B Isccr = 25kA rms 59000 KUALA LUMPUR.
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER)
Tel: 603-22991999 Fax: 603-22991919

IP-31 IP-31 CONTRACTOR :


DB-CW1/L 30A SWITCHBOARD EARTHING BAR 25mm x DB-CW2/L 30A SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 0.75kW TPN 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 0.24kW TPN 3mm TINNED COPPER BAR WITH MS BOLTS

M.D. = 0.68kW MCCB & NUTS


M.D. = 0.22kW MCCB & NUTS

(LOCATED AT (LOCATED AT
COVERED WALKWAY) 4 - 1C x 6mm² LSOH FLAME RETARDANT CU. CABLE SERVICE CORRIDOR) 4 - 1C x 6mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY / TRUNKING + E IN CABLE TRAY / TRUNKING
MRCB GEORGE KENT SDN BHD
FROM FEEDER PILLAR 1 ( FP1 ) FROM FEEDER PILLAR 1 ( FP1 ) LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY

COVERED WALKWAY
SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999

LEAD CONSULTANT :
7 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

7 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

6 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

5 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

6 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

2 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

5 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

5 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

5 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

4 - 1 X 38W WEATHERPROOF LED BATTEN FITTING


MINCONSULT SDN. BHD.
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


6 - 1 X 38W WEATHERPROOF LED BATTEN FITTING

Minconsult
2 - 1C x 1.5mm² LSOH FLAME RETARDANT

2 - 1C x 1.5mm² LSOH FLAME RETARDANT


CU CABLE + E IN CONDUIT / TRUNKING

CU CABLE + E IN CONDUIT / TRUNKING


SUBCONTRACTOR :
SPARE

SPARE

SPARE

SPARE
COMMUNICATIONS SDN BHD
187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


N N H00 20/09/21 FIRST SUBMISSION M N CM
C C

TIME TIME
SWITCH TS BY PASS SWITCH TS BY PASS
24 hrs SWITCH 24 hrs SWITCH

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
FUSE SPN SPN SPN SPN SPN SPN SPN SPN SPN FUSE SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
415V, 30A, 3 PHASE, 415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2

RCCB 30A 4P RCCB 30A 4P


(100 mA) (100 mA) Designed By : MALCOLM
6A 6A
R Y B R Y B Drawn By : MARIAM
SPD CLASS II (7-MODE) SPD CLASS II (7-MODE) Checked By : NADZIRAH
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Approved By : CHANDRAN MOORTHY
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300107_H00
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc /Isc ≤ 1.5kV
SPD SPD
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) Scale : AS SHOWN
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER) Date : SEPT 2021
30A
IP-31 TPN IP-31 Drawing Title :
DB-CW3/L MCCB SWITCHBOARD EARTHING BAR 25mm x DB-CW4/L 30A SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 1.59kW 3mm TINNED COPPER BAR WITH MS BOLTS T.C.L. = 0.77kW TPN 3mm TINNED COPPER BAR WITH MS BOLTS
M.D. = 1.43kW & NUTS
M.D. = 0.69kW MCCB & NUTS
KVLRT3 BUJS PKG GS05
(LOCATED AT (LOCATED AT
SERVICE CORRIDOR) 4 - 1C x 6mm² LSOH FLAME RETARDANT CU. CABLE SERVICE CORRIDOR) 4 - 1C x 6mm² LSOH FLAME RETARDANT CU. CABLE STATION 14 UiTM SHAH ALAM
+ E IN CABLE TRAY / TRUNKING + E IN CABLE TRAY / TRUNKING
SINGLE LINE DIAGRAM
FROM FEEDER PILLAR 2 ( FP2 ) FROM FEEDER PILLAR 2 ( FP2 ) LIGHTING FOR
COVERED WALKWAY
Drawing No : Rev
NOTE: THIS DRAWING SHALL BE SUBJECT TO CHANGES AS PER TERMS, CONDITIONS AND / OR APPROVAL OF THE RELEVANT AUTHORITY *PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250107-W01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300107 H00
SUCTION TANK ROOM
SERVICE CORRIDOR

FHR TANK & PUMP

FHR TANK & PUMP

ESCSLSTOR 1 PIT

ESCSLSTOR 2 PIT
TEL & ELEC RISER
ESCSLSTOR 1 PIT

ESCSLSTOR 2 PIT

RWH TANK ROOM


FHR TANK & PUMP

LIFT 2 PIT (L14-2)


ENTRANCE LINK
ENTRANCE LINK
SUCTION TANK

SUCTION TANK
SUCTION TANK

ENTRANCE 2
LIFT LOBBY
LIFT 1 PIT

RETAIL 1

RETAIL 2
ROOM

ROOM
RISER

ROOM

2 x 1C 2.5mm² LSOH FLAME RETARDANT


2 x 1C 2.5mm² LSOH FLAME RETARDANT

CU CABLE + E IN CONDUIT / TRUNKING


CU CABLE + E IN CONDUIT / TRUNKING

CU CABLE + E IN CONDUIT / TRUNKING


KERAJAAN MALAYSIA

2 x 1C 4mm² LSOH FLAME RETARDANT

MOUNTED S/S/O (WEATHER PROOF)


2 - VARIABLE SPEED PUMP PANEL
PROJECT TITLE:

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE


1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE


1- 13A METALCLAD SURFACE

2- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- VENTILATION FAN PANEL

2 - TRANSFER PUMP PANEL


MOUNTED S/S/O (C/W RCD)

MOUNTED S/S/O (C/W RCD)

MOUNTED S/S/O (C/W RCD)

1 - 20A SPN ISOLATOR FOR


1 - 20A SPN ISOLATOR FOR

1 - 20A SPN ISOLATOR FOR


1- VENTILATION FAN PANEL

1 - 60A TPN ISOLATOR FOR

1 - 60A TPN ISOLATOR FOR


MOUNTED S/S/O (C/W RCD)
CONSTRUCTION AND COMPLETION OF LIGHT RAIL

1- 13A FLUSH MOUNTED


TRANSIT LINE 3 (LRT3) FROM

SECURITY SHUTTER 2
SECURITY SHUTTER 1

SECURITY SHUTTER 2
BANDAR UTAMA TO JOHAN SETIA

MOUNTED S/S/O

MOUNTED S/S/O

MOUNTED S/S/O
MOUNTED S/S/O

MOUNTED S/S/O

MOUNTED S/S/O

MOUNTED S/S/O

MOUNTED S/S/O

(CP-RWHP-601)
PROJECT PACKAGE:

S/S/O (TWIN)

(CP-TP-901)
(VFP-9301)

(VFP-9311)

RETAIL 1

RETAIL 2

SPARE

SPARE

SPARE

SPARE
EASTERN CORRIDOR

SPARE

SPARE

SPARE
SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB PROJECT OWNER :
400V, 30A, 3 PHASE, 400V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 RYB6 RYB7 RYB8 RYB9 RYB10 RYB11 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3

RCCB 30A 4P (30 mA) RCCB 30A 4P (30 mA)


SPD CLASS II (7-MODE) SPD CLASS II (7-MODE)
3 x 5A
R Y B In/Imax (L-N & N-PE) = 40/80kA (8/20µs) 3 x 5A
R Y B In/Imax (L-N & N-PE) = 40/80kA (8/20µs) PRASARANA MALAYSIA BERHAD (467220-U)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
B-20-1, LEVEL 20, MENARA UOA BANGSAR,
FUSE
SPD
UP @ Uoc/Isc ≤ 1.5kV FUSE
SPD
UP @ Uoc /Isc ≤ 1.5kV NO. 5 JALAN BANGSAR UTAMA 1,
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING 59000 KUALA LUMPUR.
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER)

IP31 30A IP31 30A Tel: 603-22991999 Fax: 603-22991919


DB-GL1/P TPN SWITCHBOARD EARTHING BAR 25mm x DB-GL2/P TPN SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 20.25kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS T.C.L. = 1.50kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS & NUTS CONTRACTOR :
M.D. = 12.91 kW M.D. = 0.60kW
(LOCATED IN BUS REGULATOR ROOM) (LOCATED IN BUS REGULATOR ROOM)

4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE 4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY / TRUNKING + E IN CABLE TRAY / TRUNKING MRCB GEORGE KENT SDN BHD
LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
FROM MSB - UiTM SHAH ALAM FROM MSB - UiTM SHAH ALAM
40000, SHAH ALAM,
ENTRANCE LINK 1 POB

ENTRANCE LINK 1 POB

ENTRANCE LINK 2 POB

ENTRANCE LINK 2 POB


SELANGOR DARUL EHSAN.
ENTRANCE LOBBY

ENTRANCE LINK 2
ESCALATOR 1 PIT

ESCALATOR 2 PIT

ESCALATOR 3 PIT

ESCALATOR 4 PIT
Tel: 603-50336888 Fax: 603-50336999
LIFT 1 SHAFT

LIFT 2 SHAFT
LEAD CONSULTANT :
2 x 1C 2.5mm² LSOH FLAME RETARDANT

2 x 1C 2.5mm² LSOH FLAME RETARDANT


CU CABLE + E IN CONDUIT / TRUNKING

MINCONSULT SDN. BHD.


CU CABLE IN CONDUIT / TRUNKING

(Company No. : 58835-P)


MOUNTED S/S/O (ESCALATOR 1)

Minconsult
1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE

1- 13A METALCLAD SURFACE


MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF

MOUNTED S/S/O W/PROOF


LOT 6, JALAN 51A/223,
46100 PETALING JAYA, SELANGOR, MALAYSIA.
Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575
SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


H00 20/09/21 FIRST SUBMISSION M N CM
20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
400V, 30A, 3 PHASE, 400V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3

RCCB 30A 4P (30 mA) RCCB 30A 4P (30 mA)


3 x 5A 3 x 5A
R Y B R Y B

SPD CLASS II (7-MODE) SPD CLASS II (7-MODE) Designed By : MALCOLM


In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Drawn By : MARIAM
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV Checked By : NADZIRAH
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD SPD
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) Approved By : CHANDRAN MOORTHY
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER) CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300108_H00
IP31 30A IP31 30A Scale : N.T.S
DB-EL1/P TPN SWITCHBOARD EARTHING BAR 25mm x DB-EL2/P TPN SWITCHBOARD EARTHING BAR 25mm x
MCCB MCCB Date : SEPT 2021
T.C.L. = 1.25kW 3mm TINNED COPPER BAR WITH MS BOLTS T.C.L. = 1.50kW 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS & NUTS
M.D. = 0.50 kW M.D. = 0.60 kW Drawing Title :
(LOCATED AT SERVICE CORRIDOR AT (LOCATED AT SERVICE CORRIDOR AT
ENTRANCE LINK 1) ENTRANCE LINK 2) KVLRT3 BUJS PKG GS05
4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE 4 x 1C 6mm2 LSOH FLAME RETARDANT CU. CABLE STATION 14 UiTM SHAH ALAM
+ E IN CABLE TRAY / TRUNKING + E IN CABLE TRAY / TRUNKING
SINGLE LINE DIAGRAM
SMALL POWER FOR
FROM MSB-UiTM SHAH ALAM FROM MSB-UiTM SHAH ALAM
GROUND & ENTRANCE LINK
Drawing No : Rev
*PLEASE REFER IFC DRAWING NO :KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250108_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300108 H00
DISABLE TOILET & BABY
SERVICE CORRIDOR

ESCALATOR 3 PIT

ESCALATOR 4 PIT

ENTRANCE LINK

ENTRANCE LINK
TOILET FEMALE
TOILET MALE

CORRIDOR 2

CORRIDOR 2

CORRIDOR 2
SMO ROOM

SMO ROOM
LIFT SHAFT

CSO ROOM

CSO ROOM

CSO ROOM

CSO ROOM
PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA

PAID AREA
CHR & JAN

SURAU (M)

ELV RISER
SURAU (F)

SURAU (F)
FA ROOM

FA ROOM

LV RISER

ACU 3
KERAJAAN MALAYSIA

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

2 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O


PROJECT TITLE:

1 - ISOLATOR FOR SECURITY SHUTTER 1

1 - ISOLATOR FOR SECURITY SHUTTER 2


2 x 1C 2.5mm² LSOH FLAME RETARDANT

2 - 13A FLUSH MOUNTED S/S/O c/w RCD

2 - 13A FLUSH MOUNTED S/S/O c/w RCD

2 - 13A FLUSH MOUNTED S/S/O c/w RCD


CONSTRUCTION AND COMPLETION OF LIGHT RAIL

2 x 1C 4mm² LSOH FLAME RETARDANT


CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT

1 - WALL MOUNTED INDUSTRIAL FAN

1 - WALL MOUNTED INDUSTRIAL FAN

1 - WALL MOUNTED INDUSTRIAL FAN

1 - WALL MOUNTED INDUSTRIAL FAN

2 - WALL MOUNTED INDUSTRIAL FAN


1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

2 - 13A FLUSH MOUNTED TWIN S/S/O

2 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O


TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

2 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

2 - 13A FLUSH MOUNTED S/S/O

2 - 13A FLUSH MOUNTED S/S/O


PROJECT PACKAGE:

2 - WALL MOUNTED FAN

2 - WALL MOUNTED FAN

1 - WALL MOUNTED FAN

2 - WALL MOUNTED FAN

2 - WALL MOUNTED FAN


- DISABLE HELP POINT
EASTERN CORRIDOR

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)
SUPERVISING AGENCY :

SPARE

SPARE

SPARE
AGENSI PENGANGKUTAN AWAM DARAT ( APAD )
Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

PROJECT OWNER :

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
400V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9 R10 Y10 B10 R11 Y11 B11 R12 Y12 B12 R13 Y13 B13 R14 Y14 B14 R15 Y15 B15 PRASARANA MALAYSIA BERHAD (467220-U)
RCCB 30A 4P (30mA) SPD CLASS II (7-MODE) B-20-1, LEVEL 20, MENARA UOA BANGSAR,
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
NO. 5 JALAN BANGSAR UTAMA 1,
3 x 5A R Y B
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms 59000 KUALA LUMPUR.
UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
AS RECOMMENDED Tel: 603-22991999 Fax: 603-22991919
BY MANUFACTURER)

IP31 CONTRACTOR :
DB-CL-FOH/P(CONCOURSE LEVEL) 30A SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 13.75 kW TPN 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS
M.D. = 7.38 kW MCCB
(LOCATED AT DB ROOM)

4 x 1C 6mm2 LSOH FLAME RETARDANT MRCB GEORGE KENT SDN BHD


CU. CABLE + E IN TRUNKING LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
FROM MSB - UiTM SHAH ALAM SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999

RWH TANK + PUMP

RWH TANK + PUMP

RWH TANK + PUMP


ENGINEER ROOM

ENGINEER ROOM
BOH CORRIDOR

STAFF ROOM

STAFF ROOM
LEAD CONSULTANT :

MSB ROOM

MSB ROOM
GAS ROOM
EER ROOM

EER ROOM

EER ROOM

UPS ROOM

UPS ROOM

UPS ROOM

SER ROOM

SER ROOM

SER ROOM
CORRIDOR

CORRIDOR

DB ROOM

DB ROOM
DCW &

DCW &

DCW &
ACU 1

ACU 2
MINCONSULT SDN. BHD.
(Company No. : 58835-P)
Minconsult
1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O


LOT 6, JALAN 51A/223,
46100 PETALING JAYA, SELANGOR, MALAYSIA.
2 x 1C 2.5mm² LSOH FLAME RETARDANT

Tel : 603-79545757, 79525757


CU. CABLE + E IN TRUNKING/CONDUIT

Fax : 603-79547373, 79547575


1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O


1 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

2 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

1 - 13A FLUSH MOUNTED S/S/O

2 - 13A FLUSH MOUNTED S/S/O

2 - 13A FLUSH MOUNTED S/S/O


(WEATHERPROOF) C/W RCD SUBCONTRACTOR :
(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

SPARE

SPARE
COMMUNICATIONS SDN BHD
187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


H00 20/09/21 FIRST SUBMISSION M N CM

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
400V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9
Designed By : MALCOLM
RCCB 30A 4P (30mA) SPD CLASS II (7-MODE) Drawn By : MARIAM
3 x 5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Checked By : NADZIRAH
Isccr = 25kA rms
UP @ Imax ≤ 1.5kV Approved By : CHANDRAN MOORTHY
FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300109_H00
AS RECOMMENDED
BY MANUFACTURER) Scale : N.T.S
IP31 Date : SEPT 2021
DB-CL-BOH/P(CONCOURSE LEVEL) 30A SWITCHBOARD EARTHING BAR 25mm x

T.C.L. = 10.25 kW TPN 3mm TINNED COPPER BAR WITH MS BOLTS Drawing Title :
& NUTS
M.D. = 5.98 kW MCCB
(LOCATED AT DB ROOM) KVLRT3 BUJS PKG GS05
4 x 1C 6mm2 LSOH FLAME RETARDANT STATION 14 UiTM SHAH ALAM
CU. CABLE + E IN TRUNKING
SINGLE LINE DIAGRAM
SMALL POWER FOR CONCOURSE LEVEL

Drawing No : Rev
FROM MSB - UiTM SHAH ALAM *PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250109_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300109 H00
KERAJAAN MALAYSIA
PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


TRANSIT LINE 3 (LRT3) FROM

ESCALATOR 3 PIT

ESCALATOR 4 PIT
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

STAIRCASE
PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM

PLATFORM
ELV RISER

LV RISER
JC RISER

JC RISER
EASTERN CORRIDOR

RISER
SUPERVISING AGENCY :

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O

1 - 13A METALCLAD SURFACE MOUNTED S/S/O


AGENSI PENGANGKUTAN AWAM DARAT ( APAD )
Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
2 x 1C 2.5mm² LSOH FLAME RETARDANT

No. 25 Jalan Raja Laut,


50350 Kuala Lumpur Tel : 03 - 2603 6600
CU. CABLE + E IN TRUNKING/CONDUIT

Laman Web : www.apad.gov.my

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN

2 - INDUSTRIAL WALL FAN


PROJECT OWNER :
(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)

(WEATHERPROOF)
PRASARANA MALAYSIA BERHAD (467220-U)
B-20-1, LEVEL 20, MENARA UOA BANGSAR,
NO. 5 JALAN BANGSAR UTAMA 1,

SPARE

SPARE

SPARE
59000 KUALA LUMPUR.

Tel: 603-22991999 Fax: 603-22991919

CONTRACTOR :

MRCB GEORGE KENT SDN BHD


LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999

LEAD CONSULTANT :

MINCONSULT SDN. BHD.


(Company No. : 58835-P)
Minconsult

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A LOT 6, JALAN 51A/223,
46100 PETALING JAYA, SELANGOR, MALAYSIA.
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN Tel : 603-79545757, 79525757
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB Fax : 603-79547373, 79547575

415V, 30A, 3 PHASE,


4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9
SUBCONTRACTOR :

RCCB 30A 4P (30mA)


SPD CLASS II (7-MODE)
3 x 5A R Y B
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms
UP @ Imax ≤ 1.5kV COMMUNICATIONS SDN BHD
FUSE 187475-V
UP @ Uoc/Isc ≤ 1.5kV
SPD 12th Floor, Menara Hap Seng
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING Jalan P Ramlee 50250 Kuala Lumpur
AS RECOMMENDED Tel : 03-2148 8810 Fax : 03-2142 4211
BY MANUFACTURER)

IP31 30A Rev Date Description Desg Check Appr


DB-PL/P SWITCHBOARD EARTHING BAR 25mm x
H00 20/09/21 FIRST SUBMISSION M N CM
T.C.L. = 6.75 kW
TPN 3mm TINNED COPPER BAR WITH MS BOLTS

M.D. = 4.28 kW
MCCB & NUTS

(LOCATED IN LV RISER AT PLATFORM LEVEL)


(LIMIT DB WIDTH TO 450mm)

4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE


+ E IN TRUNKING Designed By : MALCOLM
Drawn By : MARIAM
Checked By : NADZIRAH
Approved By : CHANDRAN MOORTHY
FROM MSB - UiTM SHAH ALAM
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300110
Scale : N.T.S
Date : SEPT 2021
Drawing Title :

KVLRT3 BUJS PKG GS05


STATION 14 UiTM SHAH ALAM
SINGLE LINE DIAGRAM
SMALL POWER FOR
PLATFORM LEVEL
Drawing No :
*PLEASE REFER IFC DRAWING NO :KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250110_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300110
Rev
H00
2 - VARIABLE SPEED PUMP PANEL AT DCW TANK

2 x 1C 2.5mm² LSOH FLAME RETARDANT CU. CABLE


4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE

2 - A/C PANEL (ACP-6161) AT CSO ROOM


2 - A/C PANEL (ACP-6141) AT SCR ROOM
4 - A/C PANEL (ACP-6021) AT UPS ROOM

4 - A/C PANEL (ACP-6031) AT SER ROOM

4 - A/C PANEL (ACP-6041) AT EER ROOM


4 x 1C 6mm² FIRE RATED LSOH CU. CABLE
KERAJAAN MALAYSIA

1 - A/C POINT AT ENGINEERING ROOM


(CP-CWP-601) (1 DUTY & 1 STANDBY)
4 x 1C 6mm² LSOH FLAME RETARDANT

1 - A/C POINT AT SURAU (FEMALE)

1 - A/C POINT AT FIRST AID ROOM


(VFP-6191) (1 DUTY & 1 STANDBY)
(VFP-6181) (1 DUTY & 1 STANDBY)

1 - A/C POINT AT SURAU (MALE)


1 - A/C POINT AT STAFF ROOM
PROJECT TITLE:

2 - VF PANEL AT MSB ROOM


2 - VF PANEL AT DB ROOM
+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT
CONSTRUCTION AND COMPLETION OF LIGHT RAIL

(2 DUTY & 2 STANDBY)

(2 DUTY & 2 STANDBY)

(2 DUTY & 2 STANDBY)

(1 DUTY & 1 STANDBY)

(1 DUTY & 1 STANDBY)

1 - A/C POINT AT SMO


TRANSIT LINE 3 (LRT3) FROM

T.C.L = 6.90kW

T.C.L = 0.79kW

T.C.L = 2.34kW

T.C.L = 2.34kW
M.D = 5.18kW

M.D = 0.73kW

M.D = 0.94kW

M.D = 0.94kW
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

DB-CL/VF
DB-CL/AC

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
DB-SP1

DB-SP2
EASTERN CORRIDOR

SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 30A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN TPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCCB MCCB MCCB PROJECT OWNER :
415V, 150A, 3 PHASE, 415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB7 RYB8 RYB9 RYB10 RYB11 RYB12 RYB13 RYB14 RYB15 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4
150/5A
CLASS 1.0
CT DPM RCCB 30A 4P (100mA)
5A
SPD CLASS II (7-MODE) SPD CLASS II (7-MODE) PRASARANA MALAYSIA BERHAD (467220-U)
3x5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 3 x 5A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap B-20-1, LEVEL 20, MENARA UOA BANGSAR,
ZCT Isccr = 25kA rms R Y B Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV NO. 5 JALAN BANGSAR UTAMA 1,
ELR FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV 59000 KUALA LUMPUR.
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED
150A BY MANUFACTURER) BY MANUFACTURER)
30A Tel: 603-22991999 Fax: 603-22991919
TPN
MCCB TPN
S/T SWITCHBOARD EARTHING BAR 25mm x MCCB SWITCHBOARD EARTHING BAR 25mm x CONTRACTOR :
SSB-ME (CONCOURSE LEVEL) 3mm TINNED COPPER BAR WITH MS BOLTS DB-AC (CONCOURSE LEVEL) 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 62.75kW 3x5A & NUTS T.C.L. = 6.90 kW & NUTS
R Y B
M.D. = 25.88 kW M.D. = 5.18 kW
(LOCATED AT MSB ROOM) (LOCATED AT DB ROOM)
4 x 1C 35mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN TRUNKING MRCB GEORGE KENT SDN BHD
FROM MSB-UiTM SHAH ALAM
4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY/ TRUNKING LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
1 - VENTILATION FAN PANEL (EAF-6271) AT DCW & RWH ROOM
1 - EXHAUST AIR FAN (EAF-6231) AT CLEAN CHEMICAL ROOM

FROM SSB-ME 40000, SHAH ALAM,


SELANGOR DARUL EHSAN.
1 - TOILET EXHAUST FAN (TEF-6221) AT DISABLE TOILET
1 - TOILET EXHAUST FAN (TEF-6211) AT FEMALE TOILET

1 - TOILET EXHAUST FAN (TEF-6201) AT MALE TOILET

1 - SUBMERSIBLE PUMP 5 (SP-5) AT ESCALATOR PIT


1 - SUBMERSIBLE PUMP 2 (SP-2) AT ESCALATOR PIT

1 - SUBMERSIBLE PUMP 3 (SP-3) AT ESCALATOR PIT

1 - SUBMERSIBLE PUMP 6 (SP-6) AT ESCALATOR PIT


1 - EXHAUST AIR FAN (EAF-6211) AT JANITOR ROOM

Tel: 603-50336888 Fax: 603-50336999


2 x 1C 2.5mm² LSOH FLAME RETARDANT CU. CABLE

2 x 1C 4mm² LSOH FLAME RETARDANT CU. CABLE

2 x 1C 4mm² LSOH FLAME RETARDANT CU. CABLE

1 - SUBMERSIBLE PUMP 4 (SP-4) AT LIFT PIT


1 - SUBMERSIBLE PUMP 1 (SP-1) AT LIFT PIT

LEAD CONSULTANT :

MINCONSULT SDN. BHD.


(Company No. : 58835-P)
+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT
Minconsult

LOT 6, JALAN 51A/223,


46100 PETALING JAYA, SELANGOR, MALAYSIA.
Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575
SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A Rev Date Description Desg Check Appr
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCCB MCCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB H00 20/09/21 FIRST SUBMISSION M N CM
415V, 30A, 3 PHASE, 415V, 30A, 3 PHASE, 415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2
30/5A 30/5A
RCCB 30A 4P (100mA) CLASS 1.0 CLASS 1.0
CT 5A
PF CT 5A
PF

3 x 5A SPD CLASS II (7-MODE) RCCB 30A 4P (100mA) SPD CLASS II (7-MODE) RCCB 30A 4P (100mA) SPD CLASS II (7-MODE)
R Y B In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 3 x 5A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 3 x 5A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms R Y B Isccr = 25kA rms R Y B Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV Designed By : MALCOLM
FUSE FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
UP @ Uoc/Isc ≤ 1.5kV SPD SPD
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) (FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) Drawn By : MARIAM
(FUSE RATING
AS RECOMMENDED AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER) Checked By : NADZIRAH
BY MANUFACTURER)
30A Approved By : CHANDRAN MOORTHY
TPN 30A 30A
MCCB SWITCHBOARD EARTHING BAR 25mm x TPN SWITCHBOARD EARTHING BAR 25mm x TPN SWITCHBOARD EARTHING BAR 25mm x CAD file no : KVLRT3-MRCBGK-GS05-STN14-ELEC-MV-SLD-300111
DB-VF(CONCOURSE LEVEL) 3mm TINNED COPPER BAR WITH MS BOLTS DB-SP1(GROUND LEVEL) MCCB 3mm TINNED COPPER BAR WITH MS BOLTS DB-SP2(GROUND LEVEL) MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 0.97 kW T.C.L. = 2.34 kW & NUTS T.C.L. = 2.34 kW & NUTS Scale :
& NUTS N.T.S
M.D. = 0.73 kW M.D. = 0.94 kW M.D. = 0.94 kW
Date : SEPT 2021
(LOCATED AT DB ROOM) (LOCATED AT SERVICE CORRIDOR) (LOCATED AT SERVICE CORRIDOR)
Drawing Title :

4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE


KVLRT3 BUJS PKG GS05
4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE 4 x 1C 6mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN CABLE TRAY/ TRUNKING
+ E IN CABLE TRAY/ TRUNKING
+ E IN CABLE TRAY/ TRUNKING
STATION 14 UiTM SHAH ALAM
SINGLE LINE DIAGRAM
FROM SSB-ME FROM SSB-ME FROM SSB-ME MECHANICAL SERVICES

Drawing No : Rev
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-MV-SLD-250111_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-MV-SLD-300111 H00
2 x 1C 1.5mm² LSOH FLAME RETARDANT PVC CU. CABLE
+ E IN TRUNKING/CONDUIT C/W TERMINATION BOX

1 - 13A FLUSH WALL-MOUNTED TWIN S/S/O

1 - 13A FLUSH WALL-MOUNTED TWIN S/S/O


2 x 1C 2.5mm² LSOH FLAME RETARDANT
CU. CABLE + E IN TRUNKING/CONDUIT
ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD

ILLUMINATED SIGNBOARD
(CONCOURSE LEVEL)

(CONCOURSE LEVEL)

(CONCOURSE LEVEL)

(CONCOURSE LEVEL)

(CONCOURSE LEVEL)

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING

FACADE LIGHTING
(GROUND LEVEL)

(GROUND LEVEL)

(GROUND LEVEL)

(GROUND LEVEL)

(GROUND LEVEL)
KERAJAAN MALAYSIA

SPARE

SPARE

SPARE

SPARE
SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

10A TP N C4 C7
C1 C2 C3 C5 C6
CONT.
C EASTERN CORRIDOR
10A
TS BY PASS
SWITCH
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A
10A SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SUPERVISING AGENCY :
FUSE MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB

R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9 R1 Y1 B1 R2 Y2 B2

RCCB 30A 4P (100 mA) AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


SPD CLASS II (7-MODE) SPD CLASS II (7-MODE) Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
3 x 5A
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) RCCB 30A 2P (30mA) In/Imax (L-N & N-PE) = 40/80kA (8/20µs) No. 25 Jalan Raja Laut,
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap 50350 Kuala Lumpur Tel : 03 - 2603 6600
Isccr = 25kA rms Isccr = 25kA rms Laman Web : www.apad.gov.my
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc /Isc ≤ 1.5kV FUSE UP @ Uoc /Isc ≤ 1.5kV
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED
BY MANUFACTURER) BY MANUFACTURER)

30A SWITCHBOARD EARTHING BAR 25mm x 30A SPN SWITCHBOARD EARTHING BAR 25mm x
DB-FC/SG TPN 3mm TINNED COPPER BAR WITH MS BOLTS DB-ATM MCB 3mm TINNED COPPER BAR WITH MS BOLTS
MCCB
T.C.L. = 12.15 kW & NUTS T.C.L.= 1.00 kW & NUTS PROJECT OWNER :
M.D. = 10.94 kW M.D. = 1.00 kW
(LOCATED AT DB ROOM) (LOCATED AT DB ROOM)

4 x 1C 6mm² FIRE RATED CU. CABLE


C/W 6mm² LSOH EARTHING CABLE IN TRUNKING CHECK M
METER

FROM MSB - UiTM SHAH ALAM


2 x 1C - 6mm² LSOH FLAME RETARDANT PRASARANA MALAYSIA BERHAD (467220-U)

LSOH FLAME RETARDANT CU. CABLE

LSOH FLAME RETARDANT CU. CABLE


+ E IN TRUNKING

FROM MSB - UiTM SHAH ALAM


B-20-1, LEVEL 20, MENARA UOA BANGSAR,
2 x 1C 1.5mm² LSOH FLAME RETARDANT

NO. 5 JALAN BANGSAR UTAMA 1,


CU. CABLE + E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT

+ E IN TRUNKING/CONDUIT
59000 KUALA LUMPUR.
(DIGITAL SCREEN (TRIPS))

(DIGITAL SCREEN (TRIPS))


ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL
(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)

Tel: 603-22991999 Fax: 603-22991919


(DIGITAL SCREEN)

(DIGITAL SCREEN)

(DIGITAL SCREEN)

(DIGITAL SCREEN)

(DIGITAL SCREEN)

(DIGITAL SCREEN)

SPARE

SPARE
CONTRACTOR :
SPARE

SPARE

SPARE

DB

DB

DB

DB
MRCB GEORGE KENT SDN BHD
LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
MCCB MCCB MCCB MCCB MCCB MCCB
SELANGOR DARUL EHSAN.
10A TP N
C1 C2 C3 C4 C5
CONT. RYB1 RYB2 RYB3 RYB4 RYB5 RYB6
C Tel: 603-50336888 Fax: 603-50336999
10A
TS BY PASS
SWITCH

ITB
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A LEAD CONSULTANT :
10A SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN R Y B
FUSE MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB

415V, 30A, 3 PHASE,


4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5
SPD CLASS II (7-MODE)
MINCONSULT SDN. BHD.
(Company No. : 58835-P)
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
RCCB 30A 4P (100mA) Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Minconsult
ZCT Isccr = 25kA rms
ELR UP @ Imax ≤ 1.5kV LOT 6, JALAN 51A/223,
3 x 5A FUSE UP @ Uoc/Isc ≤ 1.5kV
R Y B SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
46100 PETALING JAYA, SELANGOR, MALAYSIA.
(FUSE RATING Tel : 603-79545757, 79525757
IP31 30A AS RECOMMENDED
Fax : 603-79547373, 79547575
DB-PL/ADV TPN BY MANUFACTURER)
T.C.L. = 3.75 kW MCCB S/T
EARTH BAR
M.D. = 2.81 kW
SWITCHBOARD EARTHING BAR 25mm x
(LOCATED IN LV RISER AT PLATFORM 1) R Y B 3mm TINNED COPPER BAR WITH MS BOLTS
SSB/DB & NUTS
(LIMIT DB WIDTH TO 450mm)
SUBCONTRACTOR :
CHECK M
METER

LSOH FLAME RETARDANT CU. CABLE


+ E IN TRUNKING
4 x 1C - 6mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN TRUNKING
FROM MSB - UiTM SHAH ALAM

COMMUNICATIONS SDN BHD


FROM MSB - DATO' MENTERI 187475-V
TYPICAL SSB/DB INTERFACE TERMINAL BLOCK (ITB) ARRANGEMENT FOR SCADA
2 x 1C 1.5mm² LSOH FLAME RETARDANT

12th Floor, Menara Hap Seng


CU. CABLE + E IN TRUNKING/CONDUIT

Jalan P Ramlee 50250 Kuala Lumpur


Tel : 03-2148 8810 Fax : 03-2142 4211
(DIGITAL SCREEN (TRIPS))
ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL

ADVERTISEMENT PANEL
(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)

(VERTICAL LIGHTBOX)
(DIGITAL SCREEN)
(WALL PANEL)

(WALL PANEL)

Rev Date Description Desg Check Appr


SPARE

SPARE

SPARE

SPARE

H00 20/09/21 FIRST SUBMISSION M N CM

10A TP N
C1 C2 C3 C4
CONT.
C
Designed By : MALCOLM
10A Drawn By :
TS BY PASS MARIAM
SWITCH
10A
10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A Checked By : NADZIRAH
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
FUSE MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
Approved By : CHANDRAN MOORTHY
415V, 30A, 3 PHASE,
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300112
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4

Scale : N.T.S
RCCB 30A 4P (100mA)
Date : SEPT 2021
3 x 5A Drawing Title :
R Y B
IP31
DB-CL/ADV
30A
TPN
KVLRT3 BUJS PKG GS05
T.C.L. = 3.00 kW MCCB
EARTH BAR
M.D. = 2.25 kW STATION 14 UiTM SHAH ALAM
(LOCATED IN DB ROOM)
M
SINGLE LINE DIAGRAM
CHECK
METER ADVERTISING, SIGNAGE, FACADE AND ATM

Drawing No : Rev
FROM MSB - DATO' MENTERI
4 x 1C - 6mm² LSOH FLAME RETARDANT CU. CABLE
+ E IN TRUNKING
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250112_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300112 H00
2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


4 - A/C PANEL (ACP-6051) AT CTER ROOM
6 - 1 x 35W (600x600)mm LED FLAT PANEL

6 - 1 x 35W (600x600)mm LED FLAT PANEL

2 - A/C PANEL (ACP-6061) AT MDF ROOM


2 x 1C 1.5mm² LSOH FLAME RETARDANT

2 x 1C 2.5mm² LSOH FLAME RETARDANT

2 x 1C 1.5mm² LSOH FLAME RETARDANT

2 x 1C 2.5mm² LSOH FLAME RETARDANT


CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT


1 - LED ILLUMINATED 'KELUAR' SIGN

1 - LED ILLUMINATED 'KELUAR' SIGN


1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

(1 DUTY & 1 STANDBY)


KERAJAAN MALAYSIA

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
PROJECT TITLE:

CONSTRUCTION AND COMPLETION OF LIGHT RAIL


TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EASTERN CORRIDOR

SUPERVISING AGENCY :

20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN AGENSI PENGANGKUTAN AWAM DARAT ( APAD )
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
R1 Y1 B1 R3 Y3 B3 R4 Y4 B4 RYB5 RYB6 R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 RYB4 RYB5 Laman Web : www.apad.gov.my

RCCB 30A 4P (100mA) RCCB 30A 4P (30mA) RCCB 30A 4P (100mA) RCCB 30A 4P (30mA)

PROJECT OWNER :
3 x 5A
SPD CLASS II (7-MODE) R Y B SPD CLASS II (7-MODE)
3 x 5A In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV
FUSE
SPD
UP @ Uoc/Isc ≤ 1.5kV FUSE
SPD
UP @ Uoc/Isc ≤ 1.5kV PRASARANA MALAYSIA BERHAD (467220-U)
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED B-20-1, LEVEL 20, MENARA UOA BANGSAR,
BY MANUFACTURER) BY MANUFACTURER) NO. 5 JALAN BANGSAR UTAMA 1,
59000 KUALA LUMPUR.
30A SWITCHBOARD EARTHING BAR 25mm x 30A SWITCHBOARD EARTHING BAR 25mm x
DB-CTER TPN 3mm TINNED COPPER BAR WITH MS BOLTS DB-MDF TPN 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L.= 6.68 kW & NUTS T.C.L.= 3.36 kW & NUTS Tel: 603-22991999 Fax: 603-22991919
M.D. = 3.96 kW
MCCB M.D. = 2.26 kW
MCCB
(LOCATED AT CTER ROOM) (LOCATED AT MDF ROOM) CONTRACTOR :

CHECK M CHECK M
METER METER

4 x 1C-10mm² LSOH FLAME RETARDANT CU. CABLE 4 x 1C-10mm² LSOH FLAME RETARDANT CU. CABLE MRCB GEORGE KENT SDN BHD
+ E IN CABLE TRUNKING + E IN CABLE TRUNKING
LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
NO. 1, JALAN INDAH 14/8, SEKSYEN 14,

1 - A/C PANEL (PCU-9291) AT BUS REGULATOR ROOM


FROM MSB -UiTM SHAH ALAM FROM MSB - UiTM SHAH ALAM 40000, SHAH ALAM,

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999


1 - 1 x 35W (600x600)mm LED FLAT PANEL

1 - 1 x 35W (600x600)mm LED FLAT PANEL


2 x 1C 1.5mm² LSOH FLAME RETARDANT

2 x 1C 2.5mm² LSOH FLAME RETARDANT


CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT


1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 20A SPN ISOLATOR FOR PIDS


LEAD CONSULTANT :

1 - 100W CEILING FAN


MINCONSULT SDN. BHD.
(Company No. : 58835-P)
Minconsult

SPARE
SPARE

SPARE

SPARE

SPARE

SPARE
LOT 6, JALAN 51A/223,
46100 PETALING JAYA, SELANGOR, MALAYSIA.
Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575

SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 187475-V
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB 12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211
R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 RYB5

RCCB 30A 4P (100mA) RCCB 30A 4P (30mA)


Rev Date Description Desg Check Appr
H00 20/09/21 FIRST SUBMISSION M N CM

3 x 5A
R Y B SPD CLASS II (7-MODE)
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms
UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
AS RECOMMENDED
BY MANUFACTURER) Designed By : MALCOLM
Drawn By : MARIAM

30A SWITCHBOARD EARTHING BAR 25mm x Checked By : NADZIRAH


DB-BUS REGULATOR (DB-BR) TPN 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L.= 2.78 kW Approved By : CHANDRAN MOORTHY
M.D. = 1.92 kW
MCCB & NUTS
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300113
(LOCATED AT BUS REGULATOR ROOM)
Scale : N.T.S
Date : SEPT 2021
CHECK M
METER Drawing Title :

4 x 1C-6mm² LSOH FLAME RETARDANT CU. CABLE


+ E IN CABLE TRUNKING
KVLRT3 BUJS PKG GS05
STATION 14 UiTM SHAH ALAM
FROM MSB -UiTM SHAH ALAM
SINGLE LINE DIAGRAM
DB-CTER, DB-MDF AND DB-BR

Drawing No :
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250113_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300113
Rev
H00
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


2 - 1 x 35W (600x600)mm LED FLAT PANEL

2 - 1 x 35W (600x600)mm LED FLAT PANEL

2 - 1 x 35W (600x600)mm LED FLAT PANEL

2 - 1 x 35W (600x600)mm LED FLAT PANEL


2 x 1C 2.5mm² LSOH FLAME RETARDANT

2 x 1C 1.5mm² LSOH FLAME RETARDANT

2 x 1C 2.5mm² LSOH FLAME RETARDANT

2 x 1C 1.5mm² LSOH FLAME RETARDANT


CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT

CU. CABLE + E IN TRUNKING/CONDUIT


1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O

1 - 13A FLUSH MOUNTED TWIN S/S/O


KERAJAAN MALAYSIA
PROJECT TITLE:

1 - A/C POINT

1 - A/C POINT
CONSTRUCTION AND COMPLETION OF LIGHT RAIL

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
TRANSIT LINE 3 (LRT3) FROM
BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EASTERN CORRIDOR

SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A 20A No. 25 Jalan Raja Laut,
SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN SPN Tel : 03 - 2603 6600
50350 Kuala Lumpur
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB Laman Web : www.apad.gov.my

R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4

RCCB 40A 4P (100mA) RCCB 40A 4P (30mA) RCCB 40A 4P (100mA) RCCB 40A 4P (30mA)

PROJECT OWNER :

3 x 5A 3 x 5A
R Y B SPD CLASS II (7-MODE) R Y B SPD CLASS II (7-MODE)
In/Imax (L-N & N-PE) = 40/80kA (8/20µs) In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
Iimp (N-PE) = 12kA (10/350µs) Spark-Gap Iimp (N-PE) = 12kA (10/350µs) Spark-Gap PRASARANA MALAYSIA BERHAD (467220-U)
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV B-20-1, LEVEL 20, MENARA UOA BANGSAR,
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD SPD NO. 5 JALAN BANGSAR UTAMA 1,
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED 59000 KUALA LUMPUR.
BY MANUFACTURER) BY MANUFACTURER)

Tel: 603-22991999 Fax: 603-22991919


40A SWITCHBOARD EARTHING BAR 25mm x 40A SWITCHBOARD EARTHING BAR 25mm x
DB-CL/R1 TPN 3mm TINNED COPPER BAR WITH MS BOLTS DB-CL/R2 TPN 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 3.26 kW & NUTS T.C.L. = 3.26 kW & NUTS
CONTRACTOR :
M.D. = 2.30 kW
MCCB M.D. = 2.30 kW
MCCB
(LOCATED AT KIOSK) (LOCATED AT KIOSK)

CHECK M CHECK M
METER METER
MRCB GEORGE KENT SDN BHD
LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
4 x 1C-10mm² LSOH FLAME RETARDANT 4 x 1C-10mm² LSOH FLAME RETARDANT NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
+ E IN TRUNKING + E IN TRUNKING
40000, SHAH ALAM,
SELANGOR DARUL EHSAN.
FROM MSB -UiTM SHAH ALAM FROM MSB -UiTM SHAH ALAM
Tel: 603-50336888 Fax: 603-50336999

TYPICAL RETAIL/ KIOSK DISTRIBUTION BOARD ( PROVISIONAL ) TYPICAL RETAIL/ KIOSK DISTRIBUTION BOARD ( PROVISIONAL )
LEAD CONSULTANT :

MINCONSULT SDN. BHD.


(Company No. : 58835-P)
Minconsult

LOT 6, JALAN 51A/223,


46100 PETALING JAYA, SELANGOR, MALAYSIA.
Tel : 603-79545757, 79525757
Fax : 603-79547373, 79547575

SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


H00 20/09/21 FIRST SUBMISSION M N CM

Designed By : MALCOLM
Drawn By : MARIAM
Checked By : NADZIRAH
Approved By : CHANDRAN MOORTHY
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300114_H00
Scale : N.T.S
Date : SEPT 2021
Drawing Title :

KVLRT3 BUJS PKG GS05


STATION 14 UiTM SHAH ALAM
SINGLE LINE DIAGRAM
RETAILS

Drawing No :
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250114_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300114
Rev
H00
UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY


KERAJAAN MALAYSIA

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

3 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

5 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING


PROJECT TITLE:

2 - 1C X 1.5mm² LSOH FLAME RETARDANT

2 - 1C X 1.5mm² LSOH FLAME RETARDANT


CONSTRUCTION AND COMPLETION OF LIGHT RAIL

CU CABLE + E IN CONDUIT / TRUNKING


TRANSIT LINE 3 (LRT3) FROM

CU CABLE IN CONDUIT / TRUNKING


BANDAR UTAMA TO JOHAN SETIA

PROJECT PACKAGE:

EASTERN CORRIDOR

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
SUPERVISING AGENCY :

AGENSI PENGANGKUTAN AWAM DARAT ( APAD )


Aras G, M dan 20 Menara Tun Ismail Mohamed Ali,
No. 25 Jalan Raja Laut,
50350 Kuala Lumpur Tel : 03 - 2603 6600
Laman Web : www.apad.gov.my

N N
C C PROJECT OWNER :

TIME TIME
SWITCH TS BY PASS SWITCH TS BY PASS
24 hrs SWITCH 24 hrs SWITCH

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A
FUSE SPN SPN SPN SPN SPN SPN SPN SPN SPN FUSE SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB PRASARANA MALAYSIA BERHAD (467220-U)
415V, 30A, 3 PHASE, 415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 B-20-1, LEVEL 20, MENARA UOA BANGSAR,
NO. 5 JALAN BANGSAR UTAMA 1,
RCCB 30A 4P RCCB 30A 4P 59000 KUALA LUMPUR.
(100 mA) SPD CLASS II (7-MODE) (100 mA) SPD CLASS II (7-MODE)
6A In/Imax (L-N & N-PE) = 40/80kA (8/20µs) 6A In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap R Y B Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
Isccr = 25kA rms Isccr = 25kA rms
UP @ Imax ≤ 1.5kV UP @ Imax ≤ 1.5kV Tel: 603-22991999 Fax: 603-22991919
FUSE UP @ Uoc/Isc ≤ 1.5kV FUSE UP @ Uoc/Isc ≤ 1.5kV
SPD SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs) UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING (FUSE RATING
AS RECOMMENDED AS RECOMMENDED
CONTRACTOR :
BY MANUFACTURER) BY MANUFACTURER)

IP-31 30A IP-31 30A


DB-UiTM/L1 TPN SWITCHBOARD EARTHING BAR 25mm x DB-UiTM/L2 TPN SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 0.85kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
T.C.L. = 0.92kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS & NUTS
M.D. = 0.77kW M.D. = 0.83kW
MRCB GEORGE KENT SDN BHD
(LOCATED AT (LOCATED AT
COVERED WALKWAY) 4 - 1C X 6mm² LSOH FLAME RETARDANT CU. CABLE COVERED WALKWAY) 4 - 1C X 6mm² LSOH FLAME RETARDANT CU. CABLE LEVEL 3, MENARA BANK RAKYAT SHAH ALAM
+ E IN CABLE TRAY / TRUNKING + E IN CABLE TRAY / TRUNKING NO. 1, JALAN INDAH 14/8, SEKSYEN 14,
40000, SHAH ALAM,
FROM DTAC FROM DTAC SELANGOR DARUL EHSAN.

Tel: 603-50336888 Fax: 603-50336999


UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

UiTM COVERED WALKWAY

LEAD CONSULTANT :

MINCONSULT SDN. BHD.


Minconsult
1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

2 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT

1 - 1 x 8W SURFACE MOUNTED EMERGENCY LIGHT


5 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

5 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING

4 - 1 X 35W WIREGUARD LED BATTEN FITTING


2 - 1C X 1.5mm² LSOH FLAME RETARDANT
CU CABLE + E IN CONDUIT / TRUNKING

SUBCONTRACTOR :

COMMUNICATIONS SDN BHD


SPARE

SPARE

SPARE

187475-V
12th Floor, Menara Hap Seng
Jalan P Ramlee 50250 Kuala Lumpur
Tel : 03-2148 8810 Fax : 03-2142 4211

Rev Date Description Desg Check Appr


H00 20/09/21 FIRST SUBMISSION M N CM

N
C

TIME
SWITCH TS BY PASS
24 hrs SWITCH

10A 10A 10A 10A 10A 10A 10A 10A 10A 10A Designed By : MALCOLM
FUSE SPN SPN SPN SPN SPN SPN SPN SPN SPN
MCB MCB MCB MCB MCB MCB MCB MCB MCB Drawn By : MARIAM
415V, 30A, 3 PHASE,
4 WIRE, 30kA, 3 SEC. R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 Checked By : NADZIRAH
Approved By : CHANDRAN MOORTHY
RCCB 30A 4P
(100 mA) SPD CLASS II (7-MODE)
CAD file no : KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300115_H00
In/Imax (L-N & N-PE) = 40/80kA (8/20µs)
6A Iimp (N-PE) = 12kA (10/350µs) Spark-Gap
R Y B Isccr = 25kA rms Scale : N.T.S
UP @ Imax ≤ 1.5kV
FUSE UP @ Uoc/Isc ≤ 1.5kV Date : SEPT 2021
SPD
UOC/ISC ≥ 10kV (1.2/50µs) / 5kA (8/20µs)
(FUSE RATING
AS RECOMMENDED Drawing Title :
BY MANUFACTURER)

IP-31 30A
TPN
KVLRT3 BUJS PKG GS05
DB-UiTM/L3 SWITCHBOARD EARTHING BAR 25mm x
T.C.L. = 0.97kW MCCB 3mm TINNED COPPER BAR WITH MS BOLTS
& NUTS
STATION 14 UiTM SHAH ALAM
M.D. = 0.87kW
SINGLE LINE DIAGRAM
(LOCATED AT
COVERED WALKWAY) 4 - 1C X 6mm² LSOH FLAME RETARDANT CU. CABLE LIGHTING FOR
+ E IN CABLE TRAY / TRUNKING UiTM COVERED WALKWAY
Drawing No :
FROM DTAC
*PLEASE REFER IFC DRAWING NO : KVLRT3-MRCBGK-GS05-STN14-ELEC-LPS-SLD-250115_WW01
SHOP DRAWING KVLRT3-APEX-GS05-STN14-ELEC-LPS-SLD-300115
Rev
H00