Structural Design of Octagonal Steel Lighting Columns

Design Standards
· BS EN 40-3-1:2000 Lighting Columns, Design and Verification, Specification for Characteristic Loads
· BS EN 40-3-3:2003 Lighting Columns, Design and Verification, Verification by Calculation
· PD 6547:2004 Guidance on the use of BS EN 40-3-1 and BS EN 40-3-3
· BD 26/99 (*) Design Manual for Roads and Bridges, Design of Lighting Columns
(*) where applicable

· Reference should be made to the above standards and other parts of BS EN 40 to ensure full compliance.

Restrictions of the Program


· Main tapered steel octagonal section column, with short CHS top section.
· Max column height 14m using base and 6no. shaft sections not > 2.0m in height.
· The program is intended to be used on typical UK lighting columns, with typical features and attachments.
· Columns mounted in an elevated location (e.g. on a bridge or building) are not covered - seek specialist advice.
· Columns mounted in exposed locations (e.g. coastal areas, sites subject to local wind funnelling or > 250m
above sea level) are not covered - seek specialist advice.

Program Users
· Familiarity of the user with the above design standards is assumed.
· The program will perform calculations using the data input by the user - it is the responsibility of the user
to ensure that this data is correct and complies with any restrictions laid down in the standards.

General Use of the Program


· A master read-only copy of the program file should be kept, with individual jobs saved under a new filename
if required. Failure to do this may result in the formulas in any overwritten cells being permanently deleted.
· Cell colours indicate the following: yellow - user input data
shaded - auto-calculated by the program, but can be overwritten by user
- care should be taken, as the automatic formulas in these
cells are permanently lost once overwritten.
green - calculated by the program
red - error, often caused by missing data (i.e. required data not
entered in yellow cells)
· Attachment offsets from the column C/L should be entered as positive if on the same side as the bracket
arm (single-arm columns), and negative if on the opposite side. For other columns, either side may be
considered positive and the opposite negative, provided signs are consistent.
· The orientation of the door to the wind ('A' or 'B') can be specified. Default option 'A' is normally the worst
case, and should be left unchanged unless there are specific requirements to the contrary.
· Worksheet tabs can be summarised as follows :
RWF's - Rationalised Wind Factors from PD 6547 (for reference only)
Wind Map - Mean hourly wind speeds (for reference only)
Design Summary - General wind loading data and EN40 / BD26 parameters
Column Data - Details of the lighting column and any attachments, with a summary of EN40 checks
and BD26 fatigue checks (except baseplate)
EN 40 - Detailed checks to EN40 (no input data)
Baseplate (EN40).. - Baseplate design to EN40 (only used if required)
BD 26_99 Fatigue.. - Detailed column checks to BD 26, except baseplate (no input data)
Baseplate (BD26).. - Baseplate design to BD26 (only used if required)

Support and Enquiries


· Contact SOMERSET Structural Ltd : Tel 01704 549 494
E-mail bb@somerset-structural.co.uk
National Application Document PD 6547:2004
Rationalised Wind Loading Factors Rwf and Max Altitude
Administrative Area Mean Hourly 10 Min Mean Maximum Rationalized Rationalised
Wind Velocity Wind Velocity Altitude Wind Loading Wind Factor
[m/sec] m/sec m Region Rwf [N/m2]
Aberdeen 24.0 25.20 141 Heavy 466
Aberdeenshire 24.5 25.73 117 Heavy 466
Angus 24.0 25.20 250 Extra Heavy 576
Antrim 25.0 26.25 217 Extra Heavy 576
Argyll and Bute 26.0 27.30 170 Extra Heavy 576
Armagh 23.5 24.68 250 Extra Heavy 576
Bath and North East Somerset 21.0 22.05 250 Medium 429
Bedfordshire 22.0 23.10 147 Light 396
Blackburn and Darwen 23.0 24.15 142 Medium 429
Blackpool 23.0 24.15 98 Light 396
Blaenau Gwent 21.0 22.05 250 Medium 429
Bournemouth 23.0 24.15 98 Light 396
Bracknell Forest 20.0 21.00 250 Light 396
Bridgend 21.5 22.58 221 Medium 429
Brighton and Hove 22.0 23.10 147 Light 396
Bristol 20.5 21.53 231 Light 396
Buckinghamshire 21.0 22.05 202 Light 396
Caerphilly 21.0 22.05 250 Medium 429
Carmarthenshire 24.0 25.20 250 Extra Heavy 576
Cambridgeshire 23.5 24.68 117 Medium 429
Cardiff 21.0 22.05 250 Medium 429
Ceredigion 23.0 24.15 142 Medium 429
Channel Islands 24.0 25.20 141 Heavy 466
Cheshire 22.0 23.10 193 Medium 429
Clackmannanshire 23.0 24.15 190 Heavy 466
Conwy 23.0 24.15 250 Extra Heavy 576
Cornwall 24.0 25.20 141 Heavy 466
Cumbria 24.5 25.73 242 Extra Heavy 576
Darlington 24.5 25.73 72 Medium 429
Denbighshire 22.0 23.10 244 Heavy 466
Derby 21.5 22.58 174 Light 396
Derbyshire 22.0 23.10 193 Medium 429
Devon 23.0 24.15 142 Medium 429
Dorset 22.0 23.10 193 Medium 429
Down 24.0 25.20 250 Extra Heavy 576
Dumfries and Galloway 24.5 25.73 117 Heavy 466
Dundee 24.5 25.73 242 Extra Heavy 576
Durham 25.0 26.25 217 Extra Heavy 576
East Dunbartonshire 23.5 24.68 165 Heavy 466
East Lothian 24.0 25.20 141 Heavy 466
East Renfrewshire 24.0 25.20 250 Extra Heavy 576
East Riding of Yorkshire 25.0 26.25 217 Extra Heavy 576
East Sussex 22.0 23.10 147 Light 396
Edinburgh 23.5 24.68 165 Heavy 466
Essex 22.5 23.63 167 Medium 429
Falkirk 23.0 24.15 190 Heavy 466
Fermanagh 24.0 25.20 250 Extra Heavy 576
Fife 24.0 25.20 141 Heavy 466
Flintshire 22.0 23.10 193 Medium 429
Glasgow 23.5 24.68 165 Heavy 466
Gloucestershire 20.5 21.53 231 Light 396
Greater London 21.5 22.58 174 Light 396
Greater Manchester 22.5 23.63 167 Medium 429
Gwynedd 24.0 25.20 250 Extra Heavy 576
Halton 22.0 23.10 147 Light 396
Hampshire 22.0 23.10 147 Light 396
Hartlepool 25.0 26.25 95 Heavy 466
Herefordshire 21.0 22.05 202 Light 396
Hertfordshire 22.0 23.10 147 Light 396
Highland 27.0 28.35 127 Extra Heavy 576
Inverclyde 24.5 25.73 242 Extra Heavy 576
Isle of Anglesey 24.0 25.20 94 Medium 429
Isle of Man 24.0 25.20 94 Medium 429
Isle of Wight 22.0 23.10 147 Light 396
Isles of Scilly 24.0 25.20 52 Light 396
Kent 22.5 23.63 167 Medium 429
Kingston upon Hull 24.0 25.20 52 Light 396
Lancashire 24.0 25.20 141 Heavy 466
Leeds City 23.5 24.68 250 Extra Heavy 576
Leicester 21.5 22.58 174 Light 396
Leicestershire 22.0 23.10 193 Medium 429
Lincolnshire 24.0 25.20 94 Medium 429
Londonderry 25.0 26.25 217 Extra Heavy 576
Luton 21.0 22.05 202 Light 396
Medway 21.5 22.58 174 Light 396
Merseyside 23.0 24.15 142 Medium 429
Merthyr Tydfil 21.5 22.58 250 Heavy 466
Mid Lothian 24.0 25.20 141 Heavy 466
Middlesbrough 25.0 26.25 95 Heavy 466
Milton Keynes 21.0 22.05 202 Light 396
Monmouthshire and Newport 21.0 22.05 202 Light 396
Moray 24.0 25.20 250 Extra Heavy 576
Neath Port Talbot 22.0 23.10 193 Medium 429
Norfolk 25.0 26.25 95 Heavy 466
North Ayrshire 25.0 26.25 217 Extra Heavy 576
North East Lincs 24.0 25.20 52 Light 396
North Lanarkshire 23.0 24.15 190 Heavy 466
North Lincs 24.0 25.20 94 Medium 429
North West Somerset 21.0 22.05 202 Light 396
North Yorkshire 25.0 26.25 95 Heavy 466
Northamptonshire 22.0 23.10 147 Light 396
Northumberland 25.0 26.25 50 Medium 429
Nottingham 22.0 23.10 147 Light 396
Nottinghamshire 23.0 24.15 142 Medium 429
Orkney 28.0 29.40 87 Extra Heavy 576
Oxfordshire 20.0 21.00 250 Light 396
Pembrokeshire 23.0 24.15 142 Medium 429
Perth and Kinross 23.5 24.68 165 Heavy 466
Peterborough 23.0 24.15 98 Light 396
Plymouth 23.0 24.15 142 Medium 429
Poole 22.0 23.10 147 Light 396
Portsmouth 22.0 23.10 147 Light 396
Powys 22.0 23.10 193 Medium 429
Reading, 20.0 21.00 250 Light 396
Redcar and Cleveland 25.0 26.25 95 Heavy 466
Renfrewshire 24.0 25.20 250 Extra Heavy 576
Rhondda Cynon Taff 21.5 22.58 250 Heavy 466
Rutland 22.5 23.63 122 Light 396
Scottish Borders 24.5 25.73 117 Heavy 466
Shropshire 21.5 22.58 250 Heavy 466
Slough 20.0 21.00 250 Light 396
Somerset 22.0 23.10 193 Medium 429
South and East Ayrshire 24.5 25.73 117 Heavy 466
South Gloucester 20.5 21.53 231 Light 396
South Lanarkshire 23.5 24.68 165 Heavy 466
South Yorkshire 23.0 24.15 142 Medium 429
Southampton 21.5 22.58 174 Light 396
Southend 22.0 23.10 147 Light 396
Staffordshire 21.5 22.58 221 Medium 429
Stirling 24.0 25.20 250 Extra Heavy 576
Stockton on Tees 24.5 25.73 72 Medium 429
Stoke-on-Trent 21.5 22.58 221 Medium 429
Suffolk 24.0 25.20 94 Medium 429
Surrey 21.5 22.58 250 Heavy 466
Swansea 22.5 23.63 167 Medium 429
Swindon 20.0 21.00 250 Light 396
Telford and Wrekin 21.0 22.05 202 Light 396
Thurrock 21.5 22.58 174 Light 396
Torbay 22.5 23.63 122 Light 396
Torfaen 21.0 22.05 250 Medium 429
Tyne and Wear 25.0 26.25 217 Extra Heavy 576
Tyrone 24.0 25.20 250 Extra Heavy 576
Vale of Glamorgan 21.5 22.58 221 Medium 429
Warrington 22.0 23.10 147 Light 396
Warwickshire and Coventry 21.0 22.05 250 Medium 429
West Berkshire and Newbury 20.0 21.00 250 Light 396
West Dunbartonshire 24.0 25.20 141 Heavy 466
West Lothian 23.0 24.15 190 Heavy 466
West Midlands 20.5 21.53 231 Light 396
West Sussex 22.0 23.10 147 Light 396
West Yorkshire 23.5 24.68 250 Extra Heavy 576
Western Isles 28.0 29.40 87 Extra Heavy 576
Wiltshire 21.0 22.05 202 Light 396
Windsor and Maidenhead 20.0 21.00 250 Light 396
Wokingham 20.0 21.00 250 Light 396
Worcestershire 20.5 21.53 231 Light 396
Wrexham 21.5 22.58 221 Medium 429
York 24.0 25.20 52 Light 396
Shetland 30.0 31.50 Special Case – seek specialist assistance
Note : The rationalised wind loading factors Rwf are all stated at 10m above ground level, and for a mean return period
of 25 years
NOTE
Tyne and Wear includes: Gateshead, Newcastle, North and South Tyneside and Sunderland.

West Yorkshire includes: Calderdale, Bradford, Kirklees and Wakefield

South Yorkshire includes: Barnsley, Doncaster, Rotherham and Sheffield.

Greater Manchester includes: Bolton, Bury, Manchester, Oldham, Rochdale, Salford, Stockport,
Tameside, Trafford and Wigan.
West Midlands includes: Birmingham, Coventry, Dudley, Sandwell, Solihull, Walsall and
Wolverhampton.
Greater London includes: All London Boroughs.
This worksheet is by CORUS Tubes and for information only
[unchecked by Somerset Consulting]
Corus Tubes
S&C Business, Special Products
Lighting Columns, door reinforcement
parameter calculation

Input Data Output Data


(Enter Information into Green cells)

L = (mm) mx = 0.00 (mm)

t = (mm) my = 0.00 (mm)

tw = (mm) mox = -4.62 (mm)

dw = (mm) moy = 1.91 (mm)

Door width must be less than -18.48 or greater than 0.00

Door (d) = (mm) Door Width OK

0 0
Client Sheet no / 01
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

DESIGN SUMMARY
Octagonal Steel Lighting Column

Codes : EN 40
BD 26/99

Wind Loading

Location

General Mean Return Period 25 yrs

Topography factor f 1.00


Terrain Category II

Site-Specific Wind Site altitude 10 m


Site ref wind speed Vref (*) 27 m/s
mean hourly (1)
(*) (2)
or 10 min mean (2)

Rationalised Wind Factor

EN 40 Parameters

Partial Load Factors Class gf ()wind)


gf ()DL)
B 1.2 1.2

Partial Material Factors Material gm


Steel (e>15%) 1.05

Deflection Class Class Max Horizontal Deflection


EN 40 3.0
Client Sheet no / 02
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

COLUMN REF / TYPE :


Location :

Actual Height Ref Drawings :


5.00 m
(to lantern)

Sections (tapered, octagonal)


Number of sides : 8
Level Diameter(*) Thickness fy r (**)
(mm) (mm) (N/mm2) (mm)
'A' 170
3.0 275 3.0
'B' 68
'C' 157 (**) corner rad

'D' 140
'E' 132
(*) across flats

Sections (circular)
Item Diameter Thickness fy
(mm) (mm) (N/mm2)
Non-tapered : S6 0.0 0.0
Bracket arm 300.0 3.0 235

Dimensions
Height of tapered section (total) h1 5000 mm
Height of tapered sections : Base h1_0 2000 mm
S1 h1_1 600 mm
S2 h1_2 600 mm
S3 h1_3 600 mm
S4 h1_4 600 mm
S5 h1_5 600 mm
Height of non-tapered section S6 h2 0 mm
Projection of bracket arm w 0 mm
Rise of bracket arm h3 0 mm
Height to bottom of door h4 1000 mm
Lantern length 1 mm
Planted depth 700 mm

Attachments
Item Height above Offset from Wind Area Mass Shape
GL Column C/L Coefficient
(mm) ± (mm) (m2) (kg)
Lantern 5000 0 0.200 15.0 1.0
Sign Class : A 2500 0 0.300 5.0 1.8
Client Sheet no / 03
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

COLUMN REF / TYPE :


(cont'd)

Door Details Un-Reinforced


Reinforced (type 4)

Door opening Reinforcement (Type 4)


Length a 400 mm Plate dim's dw 50 mm > 4tw OK
Width b 100 mm tw 6.0 mm > t OK
Corner radius N 6.0 mm Length of col wall acting with reinf't 0 mm <= 10t OK
Orientation to wind A v 1.73 mm (incl. col wall)
S 10 mm
mox 53.0 mm
moy 50.0 mm
mx 40.0 mm
my 47.0 mm
Shear strength of fasteners in length S 1.1 kN
Shear strength of fasteners in length C 21.6 kN
(b) (t)
R/L 0.17 0.16
q 47.1 50.6 deg
Fig 8 f7 3.83 3.51
(t) / (b) = top / bottom of door opening

RESULTS - SUMMARY

EN 40 CHECKS
Strength Deflection
Item Unity Direction Unity
Check Check
Tapered : Base (GL) 0.24 PASS Horizontal 0.00 0
Base (door) Vertical 0.00 0
0.37 PASS
Reinforced (type 4)
S1 0.13 PASS Planted Root Depth (mm) 700
S2 0.09 PASS Ground Resistance Diameter of Root Req'd
S3 0.08 PASS Type G (kN/m3) (mm)
S4 0.06 PASS Poor 230 706
S5 0.03 PASS Avg 390 416
Non-tapered : S6 #VALUE! ### Good 630 258
Bracket arm 0.00 0
EN40 Found'n Loads Unfactored
Moment at GL 3.8 kNm
Shear at GL 1.4 kN
Client Sheet no / 04
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

WIND LOADING TO EN 40-3-1


A) Site-specific method B) Rationalised method
Site altitude 10 m Category N/A
Altitude factor CALT 1.01 Wind load factor (basic) Rwf N/A
Vb 27.0 m/s Correction for return period N/A
Factor to convert to 10 minute mean 1.00 Wind load factor (corrected) Rwf' N/A
Site ref wind speed Vref,0 27.0
Alt adjusted Vref 27.3 m/s
Ref wind pressure q(10) 428 N/m2
Site-specific Wind (1) or
1
Mean return period 25 years Rationalised Wind Factor (2)
Probability factor Cs 0.96
Column size factor d 0.95
Dynamic factor freq 3.30 Hz
T 0.30 sec
b 1.19
Topography factor f 1.00
Terrain category II
kr 0.19
zo 0.05
zmin 4.00
(*)
Height above ground z 5.00 m
(*)
Cr(z) 0.87
(*)
Exposure coefficient Ce(z) 1.93
(*)
Characteristic wind pressure q(z) 0.935 kN/m2
(*) max - for info only

(A) (B)
Item Ht to centr. q(z) q(z)
z (m) Cr(z) Ce(z) kN/m2 kN/m2
Tapered sect : Base 1.000 0.83 1.80 0.872 N/A
S1 2.300 0.83 1.80 0.872 N/A
S2 2.900 0.83 1.80 0.872 N/A
S3 3.500 0.83 1.80 0.872 N/A
S4 4.100 0.84 1.81 0.879 N/A
S5 4.700 0.86 1.89 0.917 N/A
Non-tapered sect : S6 5.000 0.87 1.93 0.935 N/A
Bracket arm 5.000 0.87 1.93 0.935 N/A
Lantern 5.000 0.87 1.93 0.935 N/A
Sign 2.500 0.83 1.80 0.872 N/A
0.000 0.00 0.00 0.000 N/A
0.000 0.00 0.00 0.000 N/A
0.000 0.00 0.00 0.000 N/A
0.000 0.00 0.00 0.000 N/A
Client Sheet no / 05
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

CHECK TO EN 40-3-3
Sections
(octagonal) Radius of corners r 3.0mm
Item Length D (*) D (**) t fy
(mm) (mm) (mm) (mm)(N/mm2)
Tapered sect : Base 2000 157.5 139.6 3.0 275
S1 600 121.7 116.3 3.0 275
S2 600 110.9 105.6 3.0 275
S3 600 100.2 94.8 3.0 275
S4 600 89.5 84.1 3.0 275
S5 600 78.7 73.4 3.0 275
(*) across flats, bottom of section

(**) across flats, average

Sections
Item Length D t fy
(mm) (mm) (mm)(N/mm2)
Non-tapered sect : S6 0 0.0 0.0
Bracket arm 0 300.0 3.0 235

Wind Loading
Item Area q(z) Re c Wind Force Dead Load Offset from
Ht to centr.
(mm) (m2) kN/m2 (kN) (kN) Col C/L(mm)
Tapered sect : Base 1000 0.302 0.872 3.38 1.30 0.343
S1 2300 0.076 0.872 2.82 1.33 0.088
S2 2900 0.069 0.872 2.56 1.38 0.083
S3 3500 0.062 0.872 2.30 1.43 0.077
S4 4100 0.055 0.879 2.05 1.45 0.070
S5 4700 0.048 0.917 1.82 1.45 0.063
Non-tapered sect : S6 5000 0.000 0.935 0.00 1.20 0.000
Bracket arm 5000 0.000 0.935 7.53 0.56 0.000 0.000 0
Lantern 5000 0.200 0.935 N/A 1.00 0.187 0.147 0
Sign 2500 0.300 0.872 N/A 1.80 0.471 0.049 0
0 0.000 0.000 N/A 0.00 0.000 0.000 0
0 0.000 0.000 N/A 0.00 0.000 0.000 0
0 0.000 0.000 N/A 0.00 0.000 0.000 0
0 0.000 0.000 N/A 0.00 0.000 0.000 0
Client Sheet no / 06
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

Bending Moments Class gf ()wind)


gf ()DL)
B 1.2 1.2
Unfactored Factored
Item Height DL Wind Moment Tors Moment Tors
above GL Mom Mom MDL MW MDL MW
(mm) (kNm) (kNm) (kNm) (kNm) (kNm) (kNm) (kNm) (kNm)
Tapered : Base (GL) 0 0.00 3.77 0.00 3.77 0.00 0.00 4.53 0.00
Base (door,bot) 1000 0.00 2.38 0.00 2.38 0.00 0.00 2.86 0.00
Base (door,top) 1400 0.00 1.83 0.00 1.83 0.00 0.00 2.19 0.00
S1 2000 0.00 1.33 0.00 1.33 0.00 0.00 1.60 0.00
S2 2600 0.00 0.78 0.00 0.78 0.00 0.00 0.94 0.00
S3 3200 0.00 0.52 0.00 0.52 0.00 0.00 0.62 0.00
S4 3800 0.00 0.30 0.00 0.30 0.00 0.00 0.36 0.00
S5 4400 0.00 0.13 0.00 0.13 0.00 0.00 0.16 0.00
Non-tapered : S6 5000 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Bracket arm 7000 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Section Capacities gm =1.05


E (N/mm2) = 210000

Item D t fy R e f1 f2 Zp Mux/Muy Tu
(mm) (mm) (N/mm2) (mm) (cm3) (kNm) (kNm)
Tapered : Base (GL) 157.5 3.0 275 77.2 0.932 0.948 1.000 77.3 19.20 14.73
S1 121.7 3.0 275 59.3 0.716 1.000 1.000 45.6 11.95 8.69
S2 110.9 3.0 275 54.0 0.651 1.000 1.000 37.8 9.89 7.19
S3 100.2 3.0 275 48.6 0.586 1.000 1.000 30.6 8.02 5.83
S4 89.5 3.0 275 43.2 0.522 1.000 1.000 24.2 6.35 4.61
S5 78.7 3.0 275 37.9 0.457 1.000 1.000 18.6 4.87 3.54
Non-tapered : S6 0.0 0.0 0.0 0.000 1.000 #DIV/0! 0.0 #VALUE! 0.00
Bracket arm 300.0 3.0 235 148.5 1.656 0.775 1.000 264.6 45.91 46.52

Un-Reinforced Door Capacities


Item D t fy R q b0 g N L f1
(mm) (mm) (N/mm2) (mm) (deg) (mm) (mm) (mm)
Tapered : Base (door,bot) 139.6 3.0 275 68.3 47.069 57.8 0.860 6.0 397.4 0.990
Base (door,top) 132.4 3.0 275 64.7 50.594 54.9 0.888 6.0 397.4 1.000
f3 f4 f5 F Zpn Zpy Mux Muy Tu
(cm3) (cm3) (kNm) (kNm) (kNm)
0.783 0.879 2.847 2.16 33.3 50.8 5.88 8.97 1.35
0.792 0.884 2.563 2.16 28.1 44.4 5.18 8.18 1.08

Reinforced Door Capacities (Type 4)


Item D t fy R q L v As Ae tw
(mm) (mm) (N/mm2) (mm) (deg) (mm) mm mm2 mm3 mm
Tapered : Base (door,bot) 139.6 3.0 275 68.3 47.069 397.4 1.7 300 4.0 6.0
Base (door,top) 132.4 3.0 275 64.7 50.594 397.4 1.7 300 4.0 6.0
Bx By f5 f6 f7 P Zpnr Zpyr
(cm3) (cm3)
0.026 0.021 2.847 0.927 3.832 0.020 31.6 47.5
0.027 0.022 2.563 0.930 3.505 0.021 26.7 41.5
Mux Muy Tu
(kNm) (kNm) (kNm)
7.67 11.52 1.70
6.52 10.11 1.31

Client Sheet no / 07
Project Rev
Contract No By
Details Date
Authorised User :
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

Capacity checks Factored


Item Moment Tors Mux Muy Tu Unity
MDL MW Check
(kNm) (kNm) (kNm) (kNm) (kNm) (kNm)
Tapered : Base (GL) 0.00 4.53 0.00 19.20 19.20 14.73 0.24 PASS
0.00
0.00
Base (door,bot) - reinf't 0.00 2.86 0.00 7.67 11.52 1.70 0.37 PASS
Base (door,top) - reinf't 0.00 2.19 0.00 6.52 10.11 1.31 0.34 PASS
S1 0.00 1.60 0.00 11.95 11.95 8.69 0.13 PASS
S2 0.00 0.94 0.00 9.89 9.89 7.19 0.09 PASS
S3 0.00 0.62 0.00 8.02 8.02 5.83 0.08 PASS
S4 0.00 0.36 0.00 6.35 6.35 4.61 0.06 PASS
S5 0.00 0.16 0.00 4.87 4.87 3.54 0.03 PASS
Non-tapered : S6 0.00 0.00 0.00 0.00 #VALUE! 0.00 #VALUE! ###
Bracket arm 0.00 0.00 0.00 45.91 45.91 46.52 0.00

Deflection
Class 3.0 (EN 40)
Allowable horizontal = (h + w)
Allowable vertical = 0.025 w

Direction Allowed Actual


(mm) (mm)
Horizontal 0 #DIV/0! ###
Vertical 0 0

Planted Root
Unfactored
Moment at GL = 3.77 kNm FOS = 1.25
Shear at GL = 1.38 kN Planted depth = 700 mm
O/turning Moment = 4.46 kNm

Ground Resistance Diameter of Root Req'd


G (kN/m3) (mm)
230 706
390 416
630 258
Client Sheet no / 08
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

BASEPLATE CHECK TO EN 40 & BS 5400-3 (4-BOLTS, SQUARE CRS ONLY)

Design Loads
Moment MR = 5.3 kNm (incl gf = 1.4)
Shear FR = 1.9 kN (incl gf = 1.4)

Bolts Size M 20 Baseplate Thickness t 12 mm


(Gr 8.8) Aet 245 mm2 Grade S275J0
sy = 275 N/mm2
O/all size c 400 mm
Column Diameter D 157 mm Bolt crs a 300 mm
fy 275 N/mm2

Weld Weld leg 6 mm


k factor 1.0

FOUNDATION DESIGN LOADS


EN 40 Found'n Design Loads
M = 3.8 kNm Mfd = 3.8 kNm
F = 1.4 kN Ffd = 1.4 kN

FLANGE PLATE

R= 77.2 mm

Design moments Mu-u = 2.1 kNm


Mv-v = 2.4

Capacity (u-u) Mp = 2.4 kNm > 2.1 PASS


Capacity (v-v) Mp = 3.0 kNm > 2.4 PASS

Bearing stress (u-u) = 0.6 N/mm2 < 20 PASS (check based on typical bedding mortar)
(v-v) = 0.8 N/mm2 < 20 ### (check based on typical bedding mortar)

BOLTS

Design tensile stress s = 61.0 N/mm2 Allowable st=560 N/mm2


Design shear stress t = 2.4 N/mm2 Allowable sq=640 N/mm2

[(s/st)2 +2(t/sq)2]1/2 0.11 < 1/(1.3x1.0) = 0.77 PASS

WELD

Applied stress t1 = 67.1 N/mm2


Applied stress t2 = 0.9 N/mm2
Resultant tR =67.1 N/mm2 < Allowable tD =175.6 N/mm2 PASS
Client Sheet no / 08
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

FATIGUE CHECK TO BD 26/99 DETAILS TYPE 7, 9 & 10

Weld / Section to be checked Class (1)


Detail

7 Intermediate weld 80 - 3

9 End weld 50 - 3

10 Flame cut edge 112 - 4

(1) No fatigue stress calculations need be undertaken provided the


geometric and fabrication constraints of 3.10 have been met.
Otherwise, the above classification should be adopted in conjunction with a
detailed stress analysis incorporating stress concentration factors

Geometrical configuration checks Check


Distance - bottom of door to ground / flange ≥300 1000
Door radius ≥20 100
PASS

Fabrication quality checks Check


Sharp irregularities to edges ground out Yes 0
All welding > 10mm from edges of door opening Yes 0
Client Sheet no / 09
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

BASEPLATE CHECK TO BD 26/99 (4-BOLTS, SQUARE CRS ONLY)


Design Loads
Moment MR = 19.2 kNm
Shear FR = 38.4 kN

Bolts Size M 20 Baseplate Thickness t 16 mm


(Gr 8.8) Aet = 245 mm2 Grade S355J0
sy = 355 N/mm2
O/all size c 500 mm
Column Diameter D 157 mm Bolt crs a 250 mm
Thickness t 3 mm
fy 275 N/mm2

Weld Weld leg 10 mm


k factor 1.0

FOUNDATION DESIGN LOADS


EN 40 Impact Loads ksi = 0.2 Found'n Design Loads
M = 3.8 kNm Mi = 3.8 kNm Mfd = 3.8 kNm
F = 1.4 kN Fi = 7.7 kN Ffd = 7.7 kN

FLANGE PLATE
R = 77.2 mm

Design moments Mu-u = 7.0 kNm


Mv-v = 8.3 kNm

Capacity (u-u) Mp = 7.5 kNm > 7.0 PASS


Capacity (v-v) Mp = 9.7 kNm > 8.3 PASS

Bearing stress (u-u) = 1.2 N/mm2 < 20 PASS (check based on typical bedding mortar)
(v-v) = 1.7 N/mm2 < 20 PASS

BOLTS
Design tensile stress s = 265.9 N/mm2 Allowable st=560 N/mm2
Design shear stress t = 47.0 N/mm2 Allowable sq=640 N/mm2

[(s/st)2 +2(t/sq)2]1/2 0.49 < 1/(1.3x1.0) = 0.77 PASS

WELD
Deemed to satisfy throat 4.5 mm (external fillet welds in details A or B)
Throat provided 7.0 mm > 4.5 OK - no further calculation required

Applied stress t1 = 146.3 N/mm2


Applied stress t2 = 11.3 N/mm2
Resultant tR =146.8 N/mm2 < Allowable tD =175.6 N/mm2 PASS
Client Sheet no / 10
Project Rev
Contract No By
Details Date
Authorised User : 0
LCol © Somerset Structural Ltd Rel : 2.3 EN40 [Return=25 yrs, f =1.00, Terrain Cat=II, Alt=10m, Wind Speed=27m/s]

FATIGUE CHECK TO BD 26/99 DETAIL TYPE 1

Weld Section to be Class of


checked Parent Kf = Kt Kb Kh
Metal
Kt = S(2/S(t))
1A
A-A 30Kf - 4 (1) Kb = (S(tf)/5)3 but
1B >=0.33 and <=1.45
Kh = 1.0
(1) Provided weld 1A is designed for transfer of the total load and weld 1B is for sealing
only. Otherwise a detailed stress analysis shall be undertaken and the resulting stress
concentration factors used.
(2) No fatigue check need be undertaken on the weld throat provided geometrical
configuration checks are satisfactory

Ht to Centre c Length Top/Bottom Length in c x Length in


(mm) (mm) half Top half Top Half (mm)
Base 1000 1.30 2000 B 0
Shaft - section 1 2300 1.33 600 T 100 133
- section 2 2900 1.38 600 T 600 830
- section 3 3500 1.43 600 T 600 859
- section 4 4100 1.45 600 T 600 870
- section 5 4700 1.45 600 T 600 870
- section 6 5000 1.20 0 T 0 0
Avg shape coeff't for top half of column cstat = 1.42

cvs = 1.45 Stress range multiplier cr = 0.041


b = 1.19

Base thickness t 3.0 mm Kt 1.075


Flange thickness tf 16 mm Kb 0.512 Kf 0.550
Weld 1A leg 10 mm Kh 1.000
Weld 1B leg N/A mm (assumed for sealing only)

Geometrical configuration checks Check


Weld 1A throat > Kt (K=1.10) PASS

Fatigue parameters
Frequency of vibration (Hz) Nf = 3.77 Detail Class Allowable Dynamic
Design life (years) L =0 Stress Range
No. of cycles N = 0.00E+00 s0 m sR (/2)
N/mm2)
17 4 #DIV/0!

Stress Checks (parent metal adjacent to welds)


Weld 6 Top of Base
Unfactored moment (kNm) 3.77
Elastic modulus Z (cm3) 55.2
Bending stress s (N/mm2) 68.4
Dynamic stress range s x cr (N/mm2) 2.9
#DIV/0!