LEGEND GENERAL NOTES & SPECIFICATION

CEILING LIGHT OUTLET


1 . THE ELECTRICAL INSTALLATION SHALL CONFORM TO THE LATEST EDITION OF THE PHILIPPINE
PINLIGHT W/ COMPACT FLUORESCENT ELECTRICAL CODE RULES AND REGULATIONS OF LOCAL AND NATIONAL AUTHORITIES AND THE
BULB REQUIREMENTS OF LOCAL COMPANIES.

S₂ TWO - GANG SWITCH 2.. ELECTRICAL WIRINGS SHALL BE PASSING THROUGH POLYVINYL CHLORIDE CONDUIT (PVC)
WHILE THE ENTRANCE SHALL PASS THROUGH A RIGID STEEL CONDUIT.
S3 THREE - GANG SWITCH
3. THE MINIMUM SIZE OF WIRING AND CONDUIT SHALL BE 3.5 MM² WITH 600V INSULATION.
2x40 WATTS FLUORESCENT LAMP
4. ALL MATERIALS AND EQUIPMENTS TO BE USED SHALL BE BRAND NEW AND APPROVED QUALITY
DUPLEX CONVENIENCE OUTLET AND BRAND.

WP WEATHERPROOF DUPLEX CONV.OUTLET 5. MOUNTING HEIGHT SHALL BE AS FOLLOWS:


A. WALL SWITCHES 1.37 METER ABOVE FLOOR LINE
WH WATER HEATER OUTLET B. CONVENIENCE OUTLETS 0.30 METER ABOVE FLOOR LINE
C. AIRCONDITIONING OUTLETS 2.00 METER ABOVE FLOOR LINE
Ref REFRIGERATOR OUTLET D. PANEL BOARD 1.37 METER ABOVE FLOOR LINE
E. KILOWATT - HOUR METER 1.85 METER ABOVE FLOOR LINE
R THREE - PRONGS COOKING RANGE OUTLET
6. THERE SHALL BE ONLY ONE SERVICE DROP TO THE PROPOSE BUILDING, SECONDARY
GFCI GROUND FAULT CIRCUIT INTERRUPTER SERVICE ENTRANCE SHALL BE 230 V/ SINGLE PHASE

ACU AIRCONDITIONING OUTLET 7. ALL WEATHER EXPOSED INSTALLATIONS


ACU SHALL USE WEATHERPROOF TYPE MATERIALS
ESPECIALLY WEATHERPROOF CONVENIENCE OUTLETS, CAST BOXES, JUNCTION BOXES
3 CIRCUIT HOMERUN FOR LIGHTING SUBMIT SAMPLE FOR APPROVAL

CIRCTUIT HOMERUN FOR APPLIANCES LEGEND / GENERAL NOTES & SPECIFICATIONS


5
OUTLET SCALE 1:100 MTS

CAD DESIGNER: CHECKED BY: SHEET CONTENT: PLATE NO.


NATHANIEL D. LABIANO LEGENDS/ GENERAL
BETCT - NS - 1A
PROF . JANILYN D. SIY
NOTES & SPECIFICATIONS 10