Professional Documents
Culture Documents
Description
Function
Parameterisation
8071027
2017-07
[8071029]
Original instructions
CPX-E-SYS-EN
CoDeSys®, PI PROFIBUS PROFINET® are registered trademarks of the respective trademark owners in certain
countries.
Symbols used:
Recommendations, tips, references to other documentation
2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.1 Function example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.2 Modules CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.3 System CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.4 Power supply concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2 Influencing signal statuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.1 Influencing output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.2 Influencing input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.3 Forcen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.4 Signal status when there is a fault (Fail safe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.5 Signal status in Idle status (Idle mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Diagnostics options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.1 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.2 Status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.3.3 I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.3.4 Diagnostic memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3.5 Error classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.3.6 Error numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3 Parameterisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.1 Parameterisation using Festo software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2 Parameterisation using the higher-order controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3 Types of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.4 Parameters and data for the system CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.2 Function numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.5 System parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.1 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.2 Fail safe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.3 Force mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.4 Idle mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5.5 System start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5.6 Analogue process value representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6 Module parameters (module-specific) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.1 Module monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.2 Behaviour after short circuit/overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.3 Input debounce time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.4 Signal extension time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.5 Data format for analogue value of inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
A Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2 Function
2.1 Overview
The system CPX-E is a modular system for the connection of electrical periphery and designed for use in a protected
environment. A system CPX-E can be connected to a higher-order controller via a network using a bus module or
controller, or operated autonomously.
The behaviour of the system CPX-E can be adapted to the respective requirements through parameterisation.
Byaccessing the internal parameters it is possible to influence the following, for example:
– Behaviour of the outputs in the event of communication errors (Fail-safe settings)
– Behaviour following fault clearance
– Debounce times and signal extension times for digital input signals
– Force settings (force signal status)
– Operating method of the diagnostic memory
Modules CPX-E are supplied with preset parameters. You can find the module-specific parameters in the
corresponding module documentation.
6 4
5
3
Bus module
A bus module is the interface between a system CPX-E and the fieldbus/network, and performs the following
functions:
– Connection of the system CPX-E to the fieldbus/network
– Data transfer between the system CPX-E and the higher-order controller
– Transmission of control signals to the connected modules
– Monitoring the functionality of the connected modules
– Read and write access to system parameters, input and output signals and diagnostic data (dependent on the
bus module)
– Control of the system CPX-E
5
1) Dependent on the bus module
2) Not present on all bus modules 4 3
Fig. 2.2
Controller
A controller is used to control a system CPX-E:
– Stand-alone system controller
– Incorporation into higher-order plant controllers via integrated communication interfaces (e.g. PROFINET) or
Ethernet.
Using a controller provides the option of implementing process visualisation via CODESYS in addition to
programming.
Examples of controllers:
– CPX-E-CEC-C1-PN
– CPX-E-CEC-M1-PN
Overview (using CPX-E-CEC-C1-PN as an example)
1 Cover (removable)
2 Slot for SD memory card
3 USB interface
4 Ethernet interfaces
5 Terminal block (coded, removable)
6 Terminal block lock 8
1
7 LED indicators
8 Network connection
9 Linking element 9
2
8
3
7
4
6 5
Fig. 2.3
Input/output modules
Input or output modules are used to process digital or analogue signals, depending on the module.
Examples of input and output modules:
– Digital input modules CPX-E-16DI-...
– Digital output modules CPX-E-8DO-...
– Analogue input modules CPX-E-4AI-U-I
– Analogue output modules CPX-E-4AO-U-I
– IO-Link master module CPX-E-4IOL-...
– Counter module CPX-E-1CI
Overview (using IO-Link master module CPX-E-4IOL as an example)
1 LED indicators
2 Terminal blocks (coded, removable)
3 Terminal block lock 7
4 Module lock 1
6
5 Linking element
6 Functional earth contact FE
5 2
7 DIL switch1)
4
2
1) Not present on all modules
3
Fig. 2.4
Fig. 2.5
H-rail mounting
The modules are mounted on an H-rail 35 × 7.5 mm to EN 60715.
When selecting screws for H-rail mounting, a distance between the H-rail and the linking elements of
3 mm must be observed.
The distance between the screws for mounting the H-rail may be a maximum of 50 mm.
Mounting distances
To guarantee sufficient dissipation of heat from the modules, the following minimum distances must be observed
when mounting the system CPX-E è Fig. 2.6.
Fig. 2.6
8 7
Fig. 2.7
The operating voltage supply UEL/SEN and load voltage supply UOUT are routed separately from each
other within a system CPX-E. If this separation is not required for the respective use case, both voltages
can also be supplied from a common voltage source. In this case, it must be possible to disconnect the
load voltage supply separately.
Module parameter
Idle mode channel x Idle mode is only relevant for certain
network protocols.
Assume idle mode Reset outputs 0
System parameters
Idle mode
Yes No
Idle mode status
Module parameter
Fail safe channel x
Yes No
Network communication faults
Force 0 1
Disable
Module parameter
Force channel x
Enable Disable
System parameter
Force mode
1
Output
Enable Disable
System parameter
Force mode
Input signal
Forcen an input does not modify the input signal itself and cannot be observed at the relevant status LED.
Thelogical status of the input only changes internally and may be effective in a program.
2.2.3 Forcen
Fundamentals
The Forcen function permits the manipulation of signal statuses independently of the actual operating conditions.
Forcen enables input and output signals to be overwritten. Input signals actually present or changes in status by
program will be ignored. The input signals actually present and the output signals generated by the user program
only become valid again when the Forcen function is deactivated.
The Forcen function is used mainly in the commissioning phase in order to set certain signals to the desired status
for test purposes even if the wiring is not complete.
Parameterisation
In the system CPX-E, Force parameterisation is possible for:
– Digital inputs and outputs
– Solenoid coils (only in combination with CPX-E-4IOL)
– Inputs and outputs of the I/O diagnostic interface and status bits
– Analogue inputs and outputs
Forcen is enabled or disabled globally for the system CPX-E using the “Force mode” system parameter.
System parameters Settings Description
Force mode Disabled (presetting) Forcen disabled1)
Enabled Forcen enabled1)
1) Applies to the entire system CPX-E
Tab. 2.2
The signal status can be specified according to the channel (input/output) for each module.
Module parameter Settings Description
Force mode Disabled (presetting) Forcen is disabled for the channel
Force state Adopt the signal status defined
by Force state
Force state
Digital signal Reset signal (presetting) Reset input/output signal
Set signal Set input/output signal
Analogue signal Analogue value (0 = presetting) Value of the analogue signal
Tab. 2.3
Mode of operation
Input information actually present will be replaced by the values entered in the Force table in the process image for
the inputs.
Information actually present in the process image for the outputs will be replaced by the values entered in the Force
table and transmitted to the physical outputs.
Force parameterisation – example for binary signals
1 1 1 0 1 0 1 0
1
Force mode
0 = Force disabled 1 1 0 0 1 0 0 0
2 1 = Force state
Force state
0 = Reset signal 0 1 0 1 0 1 1 0
1 = Set signal
3
0 1 1 0 0 0 1 0
Force mode
0 = Force disabled 1 1 0 0 1 0 0 0
2 1 = Force value
Force state
100 505 100 321 202 110 80 50
3
100 505 333 432 202 505 11 500
If “Assume Fault mode value” is activated, the signal statuses defined by module parameter for the relevant channel
will take effect è Tab. 2.5.
Module parameter Settings Description
Fault mode Hold last state Retain current signal status
Fault state (presetting) Adopt the signal status defined
by Fault state
Fault state
Digital signal Reset output (presetting) Reset output signal
Set output Set output signal
Analogue signal Analogue value Value of the analogue signal
Tab. 2.5
Mode of operation
The Fault mode parameter is used to determine whether the current signal status is to be retained or whether the
signal status defined by the Fault state parameter is to be assumed.
Fail-safe parameterisation – example for binary signals
1 1 0 0 1 1 1 0
1
Fault mode
0 = Hold last state 0 1 0 1 1 1 0 0
2 1 = Fault state
Fault state
0 = Reset output 0 0 0 1 0 1 0 0
1 = Set output
3
1 0 0 1 0 1 1 0
1 Signal status before the fault 3 Signal status after the fault
2 Module parameter (according to channel)
Fig. 2.12
Fault mode
0 = Hold last state 0 1 0 1 1 1 0 0
2 1 = Fault state
Fault state
222 500 500 500 333 321 100 200
3
100 500 444 500 333 321 0 333
1 Signal status before the fault 3 Signal status after the fault
2 Module parameter (according to channel)
Fig. 2.13
Fundamentals
The Idle-mode parameterisation is used to help specify the signal status which the outputs are to assume when
switching to Idle status. This should establish a defined machine/system status.
Parameterisation
In the system CPX-E, Idle-mode parameterisation is possible for:
– Digital outputs
– Analogue outputs
– Solenoid coils (only in combination with CPX-E-4IOL or digital outputs)
The Idle mode system parameter can be used to globally specify the signal status which the outputs are to assume
when switching to Idle status.
System parameters Settings Description
System Idle mode Reset outputs (presetting) Reset all outputs
Hold last state Retain current signal status for all outputs
Assume Idle-mode value Adopt the signal status defined for the
relevant channel
Tab. 2.6
If “Assume Idle mode value” is activated, the signal statuses defined by module parameter for the relevant channel
will take effect è Tab. 2.7.
Module parameter Settings Description
Idle mode Hold last state Retain current signal status
Idle state (presetting) Adopt the signal status defined
by Idle state
Idle state
Digital signal Reset output (presetting) Reset output signal
Set output Set output signal
Analogue signal Analogue value Value of the analogue signal
Tab. 2.7
Mode of operation
The mode of operation is identical to Fail-safe parameterisation è Fig. 2.12 and Fig. 2.13.
lights up
ON Voltage supply present, but outside of the Eliminate undervoltage.
OFF
tolerance range.
flashes Linking on the bus module is missing or Check linking.
incomplete.
ON The internal fuse of the voltage supply has Eliminate short circuit/overload.
OFF
tripped. Depending on the parameterisation,
flashes the voltage supply is then switched on
again automatically (factory setting)
or it must be switched off and then on
again.
ON Voltage supply not present. Check connection of the power supply.
OFF
off
Tab. 2.9
lights up
ON Voltage supply present, but outside of the Eliminate undervoltage.
OFF
tolerance range.
flashes
ON Voltage supply not present. Check connection of the power supply.
OFF
off
Tab. 2.10
flashes
ON System start with default parameterisation (factory setting) and current expansion set;
OFF
off external parameterisation is possible (presetting).
1) The indication of the Forcen function (LED flashing) has priority over indication of the setting for the system start with the saved
parameterisation and saved extension (LED lights up).
Tab. 2.12
If different errors occur simultaneously on different module types, errors cannot be assigned.
The I/O diagnostic interface can be used to distinguish errors clearly è 2.3.3 I/O diagnostic interface.
Output bits
The function number of the desired data is specified in binary coded form using the output bits O0 ... O12 of the I/O
diagnostic interface. The function number is applied when control bit O15 supplies a logic 1.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
2
Function number
Reserved
Control bit
Input bits
The reply data are output by the system CPX-E via the input bits I0 ... I7 when the acknowledgement bit I15 supplies
a logic 1.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
2
Reserved Diagnostic data
Acknowledgement bit
If control bit O15 supplies a logic 0, acknowledgement bit I15 will be reset automatically and the status
byte will be shown with the diagnostic data bits.
Start timeout
No
Yes
Apply data
Reset control bit
No
Yes
Fig. 2.16
Diagnostic data are available if bit 6 supplies a logic 1. Bits 0 ... 5 then contain the module number of the first faulty
module è Tab. 3.38.
If, for example, there were a fault on module 5 (5 dec. = 101 bin), the following input data would be available:
Acknowledgement bit
Detailed information on the module diagnostic data è 3.11 Module diagnostic data.
Fig. 2.20 shows by way of example the reply data in the case of error number 4 (4 dec. = 100 bin).
Reply data with error number 4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
1 0 0 0 0 0 1 0 0
2
Reserved Diagnostic data
Acknowledgement bit
Run/
stop
Filter 2
0 = Always record
Mode of operation
A maximum of 40 diagnostic messages can be saved in the diagnostic memory. Using appropriate software from
Festo or using a controller CPX-E-CEC... via CoDeSys, it is possible to parameterise which messages are saved and
how these are saved, among other things. This includes how long they are stored for or the diagnostic memory
mode (“Entries remanent at Power ON”) and the memory procedure (“Run/Stop” setting). An explanation of the
major settings can be found in the following sections.
Suitable software for parameterisation can be found on the Festo Support Portal è www.festo.com/sp.
Detailed information on using the software can be found in the integrated Help function.
Memory procedure
(“Trace parameters” > “Run/Stop 1” or “Diag.Buffer – Mode”):
– “Save first 40 entries” or “Stop after 40 records...”: (Stop after 40 entries...):
The bus module saves the first forty diagnostic messages. Additional, subsequent messages are not saved.
– “Save last 40 entries” or “Record continually...”:
Continuous saving of the diagnostic messages. After the fortieth message, the oldest message will be
overwritten.
If several errors occur together, the error with the highest priority will have precedence, in other words:
– The system error LED flashes according to the higher priority.
– The number of the error with the higher priority will be entered in the system diagnostic data under function
number 1938 (error number).
Within an error class, errors of modules with a lower module number have higher priority. That means that, within an
error class, errors on
– Module number 0 have the highest priority
– Module number 1 have the second highest priority
– etc.
3 Parameterisation
With the aid of parameterisation, the behaviour of the system CPX-E or the behaviour of individual modules and
channels can be adapted to the particular application. Parameterisation can be performed using suitable software
from Festo or using the higher-order controller. The parameters are preset at the factory.
The parameterisation options depend on the bus module or controller used è Description of the
respective bus module/controller.
3.4.1 Overview
Parameters Description
System parameters Specify global system functions for the entire system, e.g.:
– Diagnostic monitoring
– System start
Module parameters Specify module-specific and channel-specific functions for the respective
module, e.g.:
– Input debounce time
– Signal extension time
Diagnostic memory parameters Specify the mode of operation of the diagnostic memory
Tab. 3.6
Data Description
System diagnostic data Global information about the system status
(e.g. error number, common diagnostic message)
Module diagnostic data Information on locating errors (e.g. error number, number of the first faulty
channel etc.)
Diagnostic memory data Entries in the diagnostic memory (maximum 40)
System data Information on global system settings
Module data Serial number, revision code and module code of the modules used
Tab. 3.7
3.5.1 Monitoring
System parameter – Monitoring
Activates or deactivates (suppresses) monitoring of short Selection via parameters
circuit/overload and undervoltage for the entire system.1)
If monitoring is active, an error reported by the module will be: F no.2) Bit
– Sent to the higher-order master
– Entered in the diagnostic memory3) 4401 7 6 5 4 3 2 1 0
– Entered in the module diagnostic data and, if applicable, in the
status bits
– Indicated by the red common error LED on the module
Short circuit/overload in sensor supply (SCS) 0
1
Monitoring can also be set separately for each module using the module parameter “Module monitoring”
è Tab. 3.15. The mode of operation of the channel error LED remains unaltered.
When changing from “Assume Fault mode” to “Reset all outputs” or to “Hold last state”, the
channel-orientated Fail-safe settings (module parameters “Fault mode” and “Fault state”) are reset
automatically for safety reasons in order to avoid undesired signal statuses.
The Fault-mode status is set using the channel-specific module parameters è Tab. 3.21.
By changing this parameter, the channel-orientated Force settings (module parameters “Force mode” and
“Force state”) are reset automatically for safety reasons in the following cases in order to avoid undesired
signal statuses:
– Change using Festo software: when switching from “enabled” to “disabled”
– Change via the network: When changed from “disabled” to “enabled”
Force signals have priority over Fail-safe signals.
When changing from “Assume Idle mode” to “Reset all outputs” or to “Hold last state”, the
channel-orientated Idle-mode settings (module parameters “Idle mode” and “Idle state”) are reset
automatically for safety reasons in order to avoid undesired signal statuses.
System start with default parameterisation (factory setting) and current CPX 0
expansion; external parameterisation is possible (presetting)
System start with saved parameterisation and saved CPX expansion; parameters 1
and expansion are saved to retentive memory; external parameterisation is
blocked; the Modify LED (M) on the bus module lights up
1) Function number
Tab. 3.13
If bit 6 is set to 1, the current parameter settings will be write-protected and the current expansion will be
saved, except for bit 6 itself and the module parameters “Forcen channel X”.
Recommendation: “System start with default parameterisation and current CPX expansion”. The desired
parameterisation can then be created in the start-up phase or after a network interruption, e.g. by the
interface module or the scanner/master (depending on the network used). If “System start with default
parameterisation and current CPX expansion” is active, the factory settings for all module and system
parameters will be applied after switching on and off.
Monitoring can also be set for the entire system via the “Monitoring" system parameter è Tab. 3.9.
With the setting “Voltage remains switched off ”, you must switch the power off and back on or set/reset
the relevant signals to recover the voltage.
You can find more information on this parameter in the description for the respective module.
The signal extension time can be activated channel-by-channel è Tab. 3.20. You can find more
information on this parameter in the description for the respective module.
Channel 1 0
1
Channel 2 0
1
Channel 3 0
1
Channel 4 0
1
Channel 5 0
1
Channel 6 0
1
Channel 7 0
1
By recording the outgoing errors it can be determined how long an error has existed. Incoming and
outgoing errors each represent one entry. With outgoing errors, the error number “0” is entered.
Amaximum of 40 entries are saved in total.
1) Function number
Tab. 3.30
1) Function number
Tab. 3.31
1) Function number
Tab. 3.32
1) Function number
Tab. 3.33
3.9.2 Overflow
Diagnostic memory data – Overflow
Indicates whether the diagnostic memory has overflowed. Overflow Selection via parameters
means that more than 40 errors have occurred. F no.1) Bit
The overflow is displayed when the first 40 errors are recorded as well as 3483 7 6 5 4 3 2 1 0
when the last 40 errors are recorded.
No overflow 0
Overflow 1
1) Function number
Tab. 3.34
3.9.3 Status
Diagnostic memory data – Status
Indicates whether error recording is active or inactive. Selection via parameters
Error recording can be stopped and started with the Run/Stop filters. F no.1) Bit
3483 7 6 5 4 3 2 1 0
Recording active 0
Recording inactive 1
1) Function number
Tab. 3.35
Number of days2)
2 Hours 0 … 23 +1 0
1
0
1
0
1
0
1
0
1
Number of hours2)
3 Minutes 0 … 59 +2 0
1
0
1
0
1
0
1
0
1
0
1
Number of minutes2)
4 Seconds 0 … 59 +3 0
1
0
1
0
1
0
1
0
1
0
1
Number of seconds2)
5 Milliseconds 0 … 99 +4 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Number of 10 milliseconds2) or
Bit 7 is additionally set if it is the first entry 128 … 227
after a switch-on.
6 Module code3) 0 … 255 +5 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Reserved 1 1 0
1
0
1
0
1
0
1
0
1
0
1
Outlet 0
1
Input 0
1
Analogue/technology module 0
1
Short circuit/overload 0
1
Wire break 0
1
Other error 0
1
Diagnostic status 0
1
1) Function number
Tab. 3.39
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.41
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.42
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.43
Uniform expansion 0
Non-uniform expansion 1
1) Function number
Tab. 3.44
Forcen disabled 0
Forcen enabled 1
1) Function number
Tab. 3.45
System start with default parameterisation (factory setting) and current expansion 0
System start with saved parameterisation and saved equipment status 1
1) Function number
Tab. 3.46
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.51
7th figure 0
1
0
1
0
1
0
1
6th figure +1 0
1
0
1
0
1
0
1
5th figure 0
1
0
1
0
1
0
1
4th figure +2 0
1
0
1
0
1
0
1
3rd figure 0
1
0
1
0
1
0
1
2nd figure +3 0
1
0
1
0
1
0
1
1st figure 0
1
0
1
0
1
0
1
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.52
A Technical Data
General
Feature Specification/value
Mounting position Vertical/horizontal
Ambient temperature [°C] –5 … +60 (–5 … +50)1)
Storage temperature [°C] –20 … +70
Air humidity (non-condensing) [%] 0 … 95
Max. permissible setup altitude above sea level [m] 2000
Max. number of modules per system CPX-E, 11
including the bus module or controller
Address volume of the inputs/outputs [byte] 64/64 (maximum)
Degree of protection in accordance with EN 60529 IP20
Protection against electric shock (protection against Through the use of PELV circuits
direct and indirect contact to IEC 60204-1) (protectedextra-low voltage)
CE marking (see declaration of conformity) To EU EMC Directive
è www.festo.com
Explosion prevention and protection (IECEx/ATEX) è Special documentation on ATEX
Certification RCM compliance mark
Contamination level 2
Vibration and shock resistance in accordance with EN 600682)
Vibration (part 2-6) H-rail SL1
Shock (part 2 - 27) H-rail SL1
Continuous shock (part 2-27) H-rail SL1
1) For horizontal mounting position
2) Explanation of the severity levels è Tab. A.2 … Tab. A.4
Tab. A.1
Vibration load
Frequency range [Hz] Acceleration [m/s2] Deflection [mm]
SL1 SL2 SL1 SL2 SL1 SL2
2…8 2…8 – – ±3.5 ±3.5
8 … 27 8 … 27 10 10 – –
27 … 58 27 … 60 – – ±0.15 ±0.35
58 … 160 60 … 160 20 50 – –
160 … 200 160 … 200 10 10 – –
Tab. A.2
Shock load
Acceleration [m/s2] Duration [ms] Shocks per direction
SL1 SL2 SL1 SL2 SL1 SL2
±150 ±300 11 11 5 5
Tab. A.3
Power supply
Feature Specification/value
Operating voltage supply UEL/SEN
Nominal operating voltage [V DC] 24 ± 25 %
Trigger level, undervoltage identification [V DC] 17.5
Max. current load of terminal strip [A] 8
Mains buffering time Module-dependent 1)
Load voltage supply UOUT
Nominal operating voltage [V DC] 24 ± 25 %2)
Trigger level, undervoltage identification Module-dependent 1)
Max. current load of terminal strip [A] 8
1) è Documentation of the modules
2) The indication of tolerance deviates in case of some modules.
Tab. A.5
B Terminology
Term/abbreviation Description
Bus module Connects a system CPX-E to the network; transmits control signals to the
connected modules CPX-E and monitors their functionality.
Device description file Protocol-specific file for configuring the bus module in the control software for
the higher-order controller. This contains all the information required to
parameterise the system CPX-E via control software.
DIL switch Switch consisting of several switch elements with which settings can be made
(dual in-line).
I/O Input and output
I/O diagnostic interface Network-independent diagnostic interface at I/O level, which enables access to
the internal data of the system CPX-E.
I/O module Collective term for modules that provide analogue or digital inputs and/or
outputs.
Modules CPX-E Collective term for the various modules which can be incorporated in a
systemCPX-E.
PLC Programmable logic controller
Status bits Internal status information (common diagnostic messages) of the system CPX-E,
provided as input signals via the network.
System CPX-E Complete system consisting of modules CPX-E.
Tab. B.1 Terms and abbreviations
Phone:
+49 711 347-0
Fax:
+49 711 347-2144
e-mail:
Reproduction, distribution or sale of this document or communication of service_international@festo.com
its contents to others without express authorization is prohibited. Offend
ers will be liable for damages. All rights reserved in the event that a pat Internet:
ent, utility model or design patent is registered. www.festo.com