You are on page 1of 56

System CPX-E

Description

Function
Parameterisation

8071027
2017-07
[8071029]
Original instructions
CPX-E-SYS-EN

CoDeSys®, PI PROFIBUS PROFINET® are registered trademarks of the respective trademark owners in certain
countries.

Symbols used:
Recommendations, tips, references to other documentation

2 Festo – CPX-E-SYS-EN – 2017-07 –


Table of Contents

1 About this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


1.1 Further applicable documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Product version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Product labelling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Specified standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.1 Function example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.2 Modules CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.3 System CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.4 Power supply concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2 Influencing signal statuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.1 Influencing output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.2 Influencing input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.3 Forcen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.4 Signal status when there is a fault (Fail safe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.5 Signal status in Idle status (Idle mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Diagnostics options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.1 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.2 Status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.3.3 I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.3.4 Diagnostic memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3.5 Error classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.3.6 Error numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3 Parameterisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.1 Parameterisation using Festo software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2 Parameterisation using the higher-order controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3 Types of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.4 Parameters and data for the system CPX-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.2 Function numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.5 System parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.1 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.2 Fail safe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.3 Force mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.4 Idle mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5.5 System start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5.6 Analogue process value representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6 Module parameters (module-specific) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.1 Module monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.2 Behaviour after short circuit/overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.3 Input debounce time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.4 Signal extension time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.5 Data format for analogue value of inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Festo – CPX-E-SYS-EN – 2017-07 – English 3


3.7 Module parameters (channel-specific) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.7.1 Signal extension channel x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.7.2 Fail safe channel x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.7.3 Idle mode channel x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.7.4 Forcen channel x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.8 Diagnostic memory parameters (Trace parameters) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.8.1 Entries saved retentively with Power On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.8.2 Run/Stop filter 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.8.3 Run/Stop filter 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.8.4 Error end filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.8.5 Error number filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.8.6 Module/channel filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.8.7 Module number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.8.8 Channel number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.8.9 Error number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.9 Diagnostic memory data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.9.1 Number of entries in the diagnostic memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.9.2 Overflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.9.3 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.9.4 Diagnostic memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.10 System diagnostic data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.10.1 Status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.10.2 Module number and diagnostic status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.10.3 Error number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.11 Module diagnostic data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.11.1 Number of the first faulty channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.11.2 Error number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.11.3 Info 2 and 3 (reserved) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.12 System data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.12.1 Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.12.2 Force mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.12.3 System start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.12.4 Fail safe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.12.5 Idle mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.12.6 System monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.13 Module data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.13.1 Module code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.13.2 Revision code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.13.3 Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

A Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

B Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

4 Festo – CPX-E-SYS-EN – 2017-07 – English


1 About this document

1 About this document


This document describes the function and parameterisation of the product series stated in the title.
Use of and further information on handling the products are described in other documents
è 1.1 Further applicable documents.

1.1 Further applicable documents


Document Contents
Instructions for use of system CPX-E (CPX-E-SYS) Instructions and important notes on mounting,
electrical installation and maintenance tasks in a system
CPX-E
Documentation for the components in a system CPX-E Information on use of the components
and the connected peripherals
Special documentation on ATEX Information on the use of the product in explosive gas
atmospheres
Device description files Definition of the modules of a system CPX-E for
integration into the higher-order controller
Documentation of the higher-order controller and Information on commissioning and parameterisation
additional participants in the network ofthe components
Tab. 1.1

For all available product documentation è www.festo.com/pk.

1.2 Target group


This document is intended for qualified specialised personnel. Experience with electrical control systems is required
in order to understand this documentation.

1.3 Product version


This document refers to the system consisting of modules CPX-E. The product version can be identified from the
product label or with the help of appropriate software from Festo.
Appropriate software for identifying the product version can be found in the Festo Support Portal
è www.festo.com/sp.
Information on using the software can be found in the integrated Help function.

1.4 Product labelling


The modules CPX-E are labelled on the side. The product labelling is described in the documentation supplied with
the product.

1.5 Specified standards


Version
DIN 46228-1:1992-08 EN 60529:2013-10
DIN 46228-4:1990-09 EN 60715:2001-09
EN 60068-2-27:2010-02 IEC 60204-1:2014-10
Tab. 1.2

Festo – CPX-E-SYS-EN – 2017-07 – English 5


2 Function

2 Function

2.1 Overview
The system CPX-E is a modular system for the connection of electrical periphery and designed for use in a protected
environment. A system CPX-E can be connected to a higher-order controller via a network using a bus module or
controller, or operated autonomously.
The behaviour of the system CPX-E can be adapted to the respective requirements through parameterisation.
Byaccessing the internal parameters it is possible to influence the following, for example:
– Behaviour of the outputs in the event of communication errors (Fail-safe settings)
– Behaviour following fault clearance
– Debounce times and signal extension times for digital input signals
– Force settings (force signal status)
– Operating method of the diagnostic memory
Modules CPX-E are supplied with preset parameters. You can find the module-specific parameters in the
corresponding module documentation.

2.1.1 Function example

6 4

5
3

1 Higher-order controller 4 Flow sensor


2 Valve terminal VTUG 5 Signal lamp
3 Standards-based cylinder with proximity sensors 6 System CPX-E with bus module and I/O modules
forposition sensing
Fig. 2.1

6 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

2.1.2 Modules CPX-E


This section presents an overview of the various modules CPX-E which can be used to construct a system CPX-E and
describes their functions.
You can find detailed information about the individual modules in the documentation supplied with
eachproduct.

Bus module
A bus module is the interface between a system CPX-E and the fieldbus/network, and performs the following
functions:
– Connection of the system CPX-E to the fieldbus/network
– Data transfer between the system CPX-E and the higher-order controller
– Transmission of control signals to the connected modules
– Monitoring the functionality of the connected modules
– Read and write access to system parameters, input and output signals and diagnostic data (dependent on the
bus module)
– Control of the system CPX-E

Examples of bus modules:


– CPX-E-PB (PROFIBUS DP)
– CPX-E-PN (PROFINET IO)
– CPX-E-EP (EtherNet/IP, Modbus TCP)
– CPX-E-EC (EtherCAT)

Overview (using CPX-E-EC as an example)


1 LED indicators
2 DIL and/or rotary switches1)2)
3 Terminal block (coded, removable)
4 Terminal block lock 6
5 Module lock
1
6 Network connection 8
7 Linking element 2
8 Functional earth contact FE 7

5
1) Dependent on the bus module
2) Not present on all bus modules 4 3
Fig. 2.2

Festo – CPX-E-SYS-EN – 2017-07 – English 7


2 Function

Controller
A controller is used to control a system CPX-E:
– Stand-alone system controller
– Incorporation into higher-order plant controllers via integrated communication interfaces (e.g. PROFINET) or
Ethernet.
Using a controller provides the option of implementing process visualisation via CODESYS in addition to
programming.

Examples of controllers:
– CPX-E-CEC-C1-PN
– CPX-E-CEC-M1-PN
Overview (using CPX-E-CEC-C1-PN as an example)
1 Cover (removable)
2 Slot for SD memory card
3 USB interface
4 Ethernet interfaces
5 Terminal block (coded, removable)
6 Terminal block lock 8
1
7 LED indicators
8 Network connection
9 Linking element 9
2
8
3
7
4
6 5
Fig. 2.3

Input/output modules
Input or output modules are used to process digital or analogue signals, depending on the module.
Examples of input and output modules:
– Digital input modules CPX-E-16DI-...
– Digital output modules CPX-E-8DO-...
– Analogue input modules CPX-E-4AI-U-I
– Analogue output modules CPX-E-4AO-U-I
– IO-Link master module CPX-E-4IOL-...
– Counter module CPX-E-1CI
Overview (using IO-Link master module CPX-E-4IOL as an example)
1 LED indicators
2 Terminal blocks (coded, removable)
3 Terminal block lock 7
4 Module lock 1
6
5 Linking element
6 Functional earth contact FE
5 2
7 DIL switch1)

4
2
1) Not present on all modules
3
Fig. 2.4

8 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

2.1.3 System CPX-E


Rules for set-up
A system CPX-E essentially comprises a bus module or controller and a maximum of 10 further modules. The bus
module or controller is always positioned within a system CPX-E as the first module on the left. The other modules
can be added in any sequence.

Example set-up of system CPX-E


1 Bus module (here: CPX-E-PN)
2 Input and output modules
– Digital input module CPX-E-16DI
– Digital output module CPX-E-8DO
– Analogue input module CPX-E-4AI-U-I
– Analogue output module CPX-E-4AO-U-I 1
– IO-Link master module CPX-E-4IOL

Fig. 2.5

H-rail mounting
The modules are mounted on an H-rail 35 × 7.5 mm to EN 60715.
When selecting screws for H-rail mounting, a distance between the H-rail and the linking elements of
3 mm must be observed.
The distance between the screws for mounting the H-rail may be a maximum of 50 mm.

Mounting distances
To guarantee sufficient dissipation of heat from the modules, the following minimum distances must be observed
when mounting the system CPX-E è Fig. 2.6.

Minimum distances for the


systemCPX-E for vertical/horizontal
mounting
1
1 System CPX-E
2 End supports
2
Dimensions [mm]: a = 40
b = 20
c = 30
d = 106
e = 195

Fig. 2.6

Festo – CPX-E-SYS-EN – 2017-07 – English 9


2 Function

2.1.4 Power supply concept


The system CPX-E uses separate voltages to supply the electronics and sensors (UEL/SEN) and to supply outputs
(UOUT). The equivalent voltage potentials (+24 V DC and 0 V DC) are respectively connected to each other in the
terminal blocks. This enables the respective voltage to be transferred from one module to the next.
Operating voltage supply UEL/SEN
The operating voltage supply UEL/SEN to supply the electronics and sensors is fed in at the bus module or controller
and distributed internally to the entire system CPX-E by means of the linking.
Load voltage supply UOUT
The load voltage supply UOUT to supply the outputs is fed directly into the module, separately for each module
having outputs.

1 Bus module CPX-E-PN 1 2 3 4 5 6


2 Digital input module CPX-E-16DI
3 Digital output module CPX-E-8DO
4 Analogue input module CPX-E-4AI-U-I
5 Analogue output module CPX-E-4AO-U-I
6 IO-Link master module CPX-E-4IOL
7 Load voltage supply UOUT
8 Operating voltage supply UEL/SEN
9
9 Linking

8 7

Fig. 2.7

The operating voltage supply UEL/SEN and load voltage supply UOUT are routed separately from each
other within a system CPX-E. If this separation is not required for the respective use case, both voltages
can also be supplied from a common voltage source. In this case, it must be possible to disconnect the
load voltage supply separately.

10 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

2.2 Influencing signal statuses


Functions for influencing signal statuses
Function Priority 1) Brief description Signals that can be
influenced
Forcen2) 1 Influences signal statuses independently of actual Input and output signals
signal statuses è 2.2.3.
Fail safe 2 Specifies signal statuses that take effect in the event Output signals
ofcommunication errors in the network è 2.2.4.
Idle mode3) 3 Specifies signal statuses that take effect when Output signals
switching to Idle status è 2.2.5.
1) If several functions are active at the same time
2) Primarily for test purposes during commissioning
3) Only relevant for certain network protocols
Tab. 2.1

2.2.1 Influencing output signals


The basic settings for the respective function are preset using system parameters. By setting the system parameter
appropriately, you can specify the desired signal status for each channel individually, using channel-specific module
parameters.
Output signal (e.g. via network)

Idle mode Memory


1 0
Hold last state

Module parameter
Idle mode channel x Idle mode is only relevant for certain
network protocols.
Assume idle mode Reset outputs 0
System parameters
Idle mode

Yes No
Idle mode status

Fail safe Memory


1 0
Hold last state

Module parameter
Fail safe channel x

Assume fault mode Reset outputs 0


System parameter
Fail safe

Yes No
Network communication faults

Force 0 1
Disable
Module parameter
Force channel x
Enable Disable
System parameter
Force mode
1
Output

1 Status LED for the respective output


Fig. 2.8

Festo – CPX-E-SYS-EN – 2017-07 – English 11


2 Function

2.2.2 Influencing input signals


Input
1
Force 0 1
Disable
Module parameter
Force channel x

Enable Disable
System parameter
Force mode

Input signal

1 Status LED for the respective input


Fig. 2.9

Forcen an input does not modify the input signal itself and cannot be observed at the relevant status LED.
Thelogical status of the input only changes internally and may be effective in a program.
2.2.3 Forcen
Fundamentals
The Forcen function permits the manipulation of signal statuses independently of the actual operating conditions.
Forcen enables input and output signals to be overwritten. Input signals actually present or changes in status by
program will be ignored. The input signals actually present and the output signals generated by the user program
only become valid again when the Forcen function is deactivated.
The Forcen function is used mainly in the commissioning phase in order to set certain signals to the desired status
for test purposes even if the wiring is not complete.
Parameterisation
In the system CPX-E, Force parameterisation is possible for:
– Digital inputs and outputs
– Solenoid coils (only in combination with CPX-E-4IOL)
– Inputs and outputs of the I/O diagnostic interface and status bits
– Analogue inputs and outputs
Forcen is enabled or disabled globally for the system CPX-E using the “Force mode” system parameter.
System parameters Settings Description
Force mode Disabled (presetting) Forcen disabled1)
Enabled Forcen enabled1)
1) Applies to the entire system CPX-E
Tab. 2.2

The signal status can be specified according to the channel (input/output) for each module.
Module parameter Settings Description
Force mode Disabled (presetting) Forcen is disabled for the channel
Force state Adopt the signal status defined
by Force state
Force state
Digital signal Reset signal (presetting) Reset input/output signal
Set signal Set input/output signal
Analogue signal Analogue value (0 = presetting) Value of the analogue signal
Tab. 2.3

12 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Mode of operation
Input information actually present will be replaced by the values entered in the Force table in the process image for
the inputs.
Information actually present in the process image for the outputs will be replaced by the values entered in the Force
table and transmitted to the physical outputs.
Force parameterisation – example for binary signals

1 1 1 0 1 0 1 0
1

Force mode
0 = Force disabled 1 1 0 0 1 0 0 0
2 1 = Force state
Force state
0 = Reset signal 0 1 0 1 0 1 1 0
1 = Set signal

3
0 1 1 0 0 0 1 0

1 Signal status previously 3 Signal status afterwards


2 Module parameter (according to channel)
Fig. 2.10

Force parameterisation – example for analogue signals

321 288 333 432 400 505 11 500


1

Force mode
0 = Force disabled 1 1 0 0 1 0 0 0
2 1 = Force value
Force state
100 505 100 321 202 110 80 50

3
100 505 333 432 202 505 11 500

1 Analogue signal previously 3 Analogue signal afterwards


2 Module parameter (according to channel)
Fig. 2.11

Festo – CPX-E-SYS-EN – 2017-07 – English 13


2 Function

2.2.4 Signal status when there is a fault (Fail safe)


Fundamentals
The Fail-safe parameterisation is used to help specify the signal status which the outputs are to assume in the event
of communication errors in the network (Fail-safe status). This should establish a defined machine/system status in
the event of communication errors in the network (e.g. failure of the higher-order controller).
Parameterisation
In the system CPX-E, Fail-safe parameterisation is possible for:
– Digital outputs
– Analogue outputs
– Solenoid coils (only in combination with CPX-E-4IOL or digital outputs)
The “Fail safe” system parameter can be used to globally specify the signal status which the outputs are to assume
in the event of communication errors in the network, e.g. in the event of:
– Communication failure (network interruption, PLC failure)
– Communication stop
System parameter Settings Description
Fail safe Reset outputs (presetting) Reset all outputs
Hold last state Retain current signal status for all outputs
Assume Fault-mode value Adopt the signal status defined for the
relevant channel
Tab. 2.4

“Reset outputs” means the following:


– Monostable valves move to the initial position.
– Bistable valves remain in the current position.
– Mid-position valves go into mid-position (pressurised, exhausted or closed, depending on
valvetype).

If “Assume Fault mode value” is activated, the signal statuses defined by module parameter for the relevant channel
will take effect è Tab. 2.5.
Module parameter Settings Description
Fault mode Hold last state Retain current signal status
Fault state (presetting) Adopt the signal status defined
by Fault state
Fault state
Digital signal Reset output (presetting) Reset output signal
Set output Set output signal
Analogue signal Analogue value Value of the analogue signal
Tab. 2.5

14 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Mode of operation
The Fault mode parameter is used to determine whether the current signal status is to be retained or whether the
signal status defined by the Fault state parameter is to be assumed.
Fail-safe parameterisation – example for binary signals

1 1 0 0 1 1 1 0
1

Fault mode
0 = Hold last state 0 1 0 1 1 1 0 0
2 1 = Fault state
Fault state
0 = Reset output 0 0 0 1 0 1 0 0
1 = Set output

3
1 0 0 1 0 1 1 0

1 Signal status before the fault 3 Signal status after the fault
2 Module parameter (according to channel)
Fig. 2.12

Fail-safe parameterisation – example for analogue signals

100 321 444 230 700 604 0 333


1

Fault mode
0 = Hold last state 0 1 0 1 1 1 0 0
2 1 = Fault state
Fault state
222 500 500 500 333 321 100 200

3
100 500 444 500 333 321 0 333

1 Signal status before the fault 3 Signal status after the fault
2 Module parameter (according to channel)
Fig. 2.13

Festo – CPX-E-SYS-EN – 2017-07 – English 15


2 Function

2.2.5 Signal status in Idle status (Idle mode)


This function is only relevant for certain network protocols è Description for the respective bus module.

Fundamentals
The Idle-mode parameterisation is used to help specify the signal status which the outputs are to assume when
switching to Idle status. This should establish a defined machine/system status.
Parameterisation
In the system CPX-E, Idle-mode parameterisation is possible for:
– Digital outputs
– Analogue outputs
– Solenoid coils (only in combination with CPX-E-4IOL or digital outputs)
The Idle mode system parameter can be used to globally specify the signal status which the outputs are to assume
when switching to Idle status.
System parameters Settings Description
System Idle mode Reset outputs (presetting) Reset all outputs
Hold last state Retain current signal status for all outputs
Assume Idle-mode value Adopt the signal status defined for the
relevant channel
Tab. 2.6

If “Assume Idle mode value” is activated, the signal statuses defined by module parameter for the relevant channel
will take effect è Tab. 2.7.
Module parameter Settings Description
Idle mode Hold last state Retain current signal status
Idle state (presetting) Adopt the signal status defined
by Idle state
Idle state
Digital signal Reset output (presetting) Reset output signal
Set output Set output signal
Analogue signal Analogue value Value of the analogue signal
Tab. 2.7

Mode of operation
The mode of operation is identical to Fail-safe parameterisation è Fig. 2.12 and Fig. 2.13.

16 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

2.3 Diagnostics options


For the diagnostics of errors, various possibilities are available depending on the parameterisation and network
protocol used.
Diagnostics option Description Detailed information
LED display components
System-specific System status and errors are displayed directly on the è 2.3.1
module via LED indicators.
Module- or Module or network status and errors are displayed directly è Documentation for
network-specific on the module via LED indicators. respective module
Internal system diagnostics
Status bits Common diagnostic messages (global error messages) are è 2.3.2
displayed by means of 8 internal inputs (8 status bits).
I/O diagnostic interface Diagnostic information for the system CPX-E is made è 2.3.3
available via the I/O diagnostic interface. The I/O
diagnostic interface enables bus-independent read access
to diagnostic information, data and parameters via
16internal inputs and 16 internal outputs.
Network-specific Special diagnostic functions or communication services è Description for the
diagnostic functions may be available, such as DPV1 for PROFIBUS, depending respective bus module
on the network used.
Tab. 2.8

2.3.1 LED indicators


Various LED indicators are available on every module for the visualisation of the statuses and errors. A distinction is
made here between system-specific LED indicators and those specific to the module or network.
The system-specific LED indicators of the controllers and bus modules are described in this document.
LED indicators specific to the module or network are described in the documentation for the respective
module.

Power System [PS] – Operating voltage supply UEL/SEN


LED (green) Meaning Remedy
ON Voltage supply present. No error. –
OFF

lights up
ON Voltage supply present, but outside of the  Eliminate undervoltage.
OFF
tolerance range.
flashes Linking on the bus module is missing or  Check linking.
incomplete.
ON The internal fuse of the voltage supply has  Eliminate short circuit/overload.
OFF
tripped. Depending on the parameterisation,
flashes the voltage supply is then switched on
again automatically (factory setting)
or it must be switched off and then on
again.
ON Voltage supply not present.  Check connection of the power supply.
OFF
off
Tab. 2.9

Festo – CPX-E-SYS-EN – 2017-07 – English 17


2 Function

Power Load [PL] – Load voltage supply UOUT


LED (green) Meaning Remedy
ON Voltage supply present. No error. –
OFF

lights up
ON Voltage supply present, but outside of the  Eliminate undervoltage.
OFF
tolerance range.
flashes
ON Voltage supply not present.  Check connection of the power supply.
OFF
off
Tab. 2.10

System Failure [SF] – System fault


LED (red)1) Meaning Remedy
ON
Simple error/information è 2.3.5 Error classes
OFF
(error class 1)
flashes ON
Error
OFF
(Error class 2)
ON
Serious error
OFF
(Error class 3)
ON No error –
OFF
off
1) The system error LED flashes as a function of the error class in question.
Tab. 2.11

Modify [M] – Parameterisation modified or Force active


LED (yellow) Meaning
ON System start with saved parameterisation and saved expansion set; parameters and
OFF
expansion are saved to retentive memory; external parameterisation is blocked.1)
lights up Caution when replacing systems with saved parameterisation.
In the case of these systems, parameterisation is not carried out automatically by the
higher-order controller on replacement.
 Before replacement, note required settings and restore them after replacement,
ifrequired.
ON The Forcen function is enabled.1)
OFF

flashes
ON System start with default parameterisation (factory setting) and current expansion set;
OFF
off external parameterisation is possible (presetting).
1) The indication of the Forcen function (LED flashing) has priority over indication of the setting for the system start with the saved
parameterisation and saved extension (LED lights up).
Tab. 2.12

18 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

2.3.2 Status bits


Irrespective of the bus module used, the system CPX-E provides 8 status bits for displaying common diagnostic
messages (global error messages).
Status bits are configured like inputs. The input addresses which are to be assigned to status bits depend on the
network protocol used è Description for the respective bus module.
The status bits supply coded diagnostic information in form of 0 or 1 signals. If all bits supply a logic 0, no error is
reported.
– Bits 0 to 3 specify the module type in which errors have occurred.
– Bits 4 to 7 specify the type of error.
Bit Diagnostic information with logic 1 Description
0 Error at valve Module type in which an error has occurred
1 Error at output
2 Error at input
3 Error in analogue, function or technology module
4 Undervoltage Error type
5 Short circuit/overload
6 Wire break
7 Other error
Tab. 2.13

Examples of typical status information


No error signalled
Error type Module type
Other Wire break Short Under­ Analogue, Input Output Valve
error circuit voltage function
Bit 7 6 5 4 3 2 1 0
Status 0 0 0 0 0 0 0 0
Tab. 2.14

Short circuit at the output


Error type Module type
Other Wire break Short Under­ Analogue, Input Output Valve
error circuit voltage function
Bit 7 6 5 4 3 2 1 0
Status 0 0 1 0 0 0 1 0
Tab. 2.15

Undervoltage of sensor supply


Error type Module type
Other Wire break Short Under­ Analogue, Input Output Valve
error circuit voltage function
Bit 7 6 5 4 3 2 1 0
Status 0 0 0 1 0 1 0 0
Tab. 2.16

If different errors occur simultaneously on different module types, errors cannot be assigned.
The I/O diagnostic interface can be used to distinguish errors clearly è 2.3.3 I/O diagnostic interface.

Festo – CPX-E-SYS-EN – 2017-07 – English 19


2 Function

2.3.3 I/O diagnostic interface


For networks that do not have extensive diagnostic functions, the diagnostic information for the system CPX-E is
available via the I/O diagnostic interface. The I/O diagnostic interface enables network-independent read access to
diagnostic information, data and parameters via internal inputs and outputs (16 I/16 O).
Organisation of internal data and parameters
Internal data and parameters of the modules and of the system CPX-E are stored in a common memory area. The I/O
diagnostic interface can provide read access to individual bytes of this memory area with the aid of the function
number.
Parameters can be modified with the aid of network-specific functions, depending on the network used
è 3 Parameterisation.

Mode of operation of the I/O diagnostic interface


Detailed diagnostic information can be accessed via the I/O diagnostic interface. For example, it is possible to
ascertain on exactly which module and which channel an error has occurred. 16 input bits and 16 output bits,
through which all diagnostic data can be retrieved, are available for accessing the system diagnostics.
The addresses of the input and output bits of the I/O diagnostic interface depend on the network used
è Description for the respective bus module.

Output bits
The function number of the desired data is specified in binary coded form using the output bits O0 ... O12 of the I/O
diagnostic interface. The function number is applied when control bit O15 supplies a logic 1.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
2
Function number

Reserved
Control bit

1 Bit number 2 Outputs


Fig. 2.14

Input bits
The reply data are output by the system CPX-E via the input bits I0 ... I7 when the acknowledgement bit I15 supplies
a logic 1.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
2
Reserved Diagnostic data

Acknowledgement bit

1 Bit number 2 Inputs


Fig. 2.15

If control bit O15 supplies a logic 0, acknowledgement bit I15 will be reset automatically and the status
byte will be shown with the diagnostic data bits.

20 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Reading out diagnostic data


The function number is applied if there is a rising edge at control bit O15. The input bits I0 ... I7 supply the diagnostic
data when the acknowledgement bit supplies a logic 1.

Reading out the diagnostic data flow diagram


Start the read process

Start timeout

Set function number

Set control bit (O15)

No

Acknow­ No Timer Yes


ledgement
bit =1? expired?

Yes

Apply data
Reset control bit

Reset control bit O15

No

Acknow­ No Timer Yes


ledgement Timeout
bit =0? expired?

Yes

Fig. 2.16

Festo – CPX-E-SYS-EN – 2017-07 – English 21


2 Function

Example 1: Check whether diagnostic data is available


Function number 1937 specifies whether there are diagnostic data and contains, where applicable, the number of
the first module on which an error has occurred è Tab. 3.38.
– Function number = 1937
– 1937 dec. = 11110010001 bin

Reading out function number 1937


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
1 0 0 0 0 1 1 1 1 0 0 1 0 0 0 1
2
Function number
Reserved
Control bit

1 Bit number of the outputs 2 Signal status of the outputs


Fig. 2.17

Diagnostic data are available if bit 6 supplies a logic 1. Bits 0 ... 5 then contain the module number of the first faulty
module è Tab. 3.38.
If, for example, there were a fault on module 5 (5 dec. = 101 bin), the following input data would be available:

Reply data (example – error on module 5)


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
1 0 1 0 0 0 1 0 1
2
Reserved Diagnostic data

Acknowledgement bit

1 Bit number of the inputs 2 Signal status of the inputs


Fig. 2.18

Detailed information on the module diagnostic data è 3.11 Module diagnostic data.

22 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Example 2: Reading out current error numbers of module 5


Using the module number of the faulty module, it is possible to ascertain the function numbers of the relevant
module diagnostic data è 3.11 Module diagnostic data.
Module diagnostic data can be e.g.:
– The number of the faulty channel
– The module error number.
The following function number can be used to ascertain e.g. the module error number of module 5:
– Function number = 2008 + 4 * 5 + 1 = 2029
– 2029 dec. = 11111101101 bin

Reading out the module error number of module 5


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
1 0 0 0 0 1 1 1 1 1 1 0 1 1 0 1
2
Function number
Control bit

1 Bit number 2 Signal status of the outputs


Fig. 2.19

Fig. 2.20 shows by way of example the reply data in the case of error number 4 (4 dec. = 100 bin).
Reply data with error number 4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
1 0 0 0 0 0 1 0 0
2
Reserved Diagnostic data

Acknowledgement bit

1 Bit number of the inputs 2 Signal status of the inputs


Fig. 2.20

Festo – CPX-E-SYS-EN – 2017-07 – English 23


2 Function

2.3.4 Diagnostic memory


Fundamentals
The diagnostic memory is used for logging error statuses. Recording the time when errors occur and error
sequences makes it easier to find the cause of errors which are otherwise difficult to locate. Errors which occur
during operation are entered in the diagnostic memory. Depending on parameterisation, the first or the last
40entries are saved, as well as the respective time measured from the moment the power supply was switched on.
Parameterisation
Various diagnostic memory filters can be parameterised by means of diagnostic memory parameters
(è3.8 Diagnostic memory parameters (Trace parameters)). These filters can be used to suppress the recording of
certain system statuses, and to control both starting and stopping. The mode of operation of the diagnostic memory
filters is shown in the following figure è Fig. 2.21.

The mode of operation of the diagnostic memory filters


Start: Error

Run/stop filter 1 The first 40 errors or the last 40 errors

Error end filter Register end of fault or not

Error number filter Record defined FN or not

Module/channel filter Record FN of a module/channel only

Run/
stop
Filter 2

0 = Always record

1 = Record up to the defined FN

2 = Record up to the defined FN + MN


Diagnostic
memory

3 = Record up to the defined FN + MN + CN

4 = Record as from the defined FN

5 = Record as from the defined FN + MN


6 = Record as from the defined FN + MN + CN

MN = Module number FN = Error number


CN = Channel number
Fig. 2.21

24 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Mode of operation
A maximum of 40 diagnostic messages can be saved in the diagnostic memory. Using appropriate software from
Festo or using a controller CPX-E-CEC... via CoDeSys, it is possible to parameterise which messages are saved and
how these are saved, among other things. This includes how long they are stored for or the diagnostic memory
mode (“Entries remanent at Power ON”) and the memory procedure (“Run/Stop” setting). An explanation of the
major settings can be found in the following sections.
Suitable software for parameterisation can be found on the Festo Support Portal è www.festo.com/sp.
Detailed information on using the software can be found in the integrated Help function.

Memory duration or diagnostic memory mode


(“Trace parameters” > “Entries remanent at Power ON” or “Diag.Buffer – Mode”):
– “Active” or “remanent”:
The diagnostic messages remain saved when the operating voltage UEL/SEN is switched off or after a power
failure.
– “Inactive” or “not remanent”:
The diagnostic messages are lost after the operating voltage UEL/SEN is switched off or after a power failure.

Memory procedure
(“Trace parameters” > “Run/Stop 1” or “Diag.Buffer – Mode”):
– “Save first 40 entries” or “Stop after 40 records...”: (Stop after 40 entries...):
The bus module saves the first forty diagnostic messages. Additional, subsequent messages are not saved.
– “Save last 40 entries” or “Record continually...”:
Continuous saving of the diagnostic messages. After the fortieth message, the oldest message will be
overwritten.

Error end filter


(“Trace parameters” > “Fault end filter” or “Diag.Buffer – Error end”):
– “Record outgoing faults” or “Record coming/going” (record incoming/outgoing errors):
When an error occurs and is eliminated, the error number and the time of the event are recorded.
– “Do not record outgoing faults” or “Record coming only” (record incoming errors only):
The error number and the time of the event are recorded only when an error occurs. If the error is eliminated, the
time of the event will not be recorded.
2.3.5 Error classes
Possible errors of the system CPX-E are divided into three error classes (1 ... 3) with different priority, depending on
the seriousness of the error. If an error occurs, the system error LED (SF) flashes as a function of the error class in
question.
Error class Flashing sequence of the system error LED (SF) Error weighting Priority
1 1x flash, pause Minor Low
2 2x flash, pause Medium Medium
3 3x flash, pause High High
Tab. 2.17

If several errors occur together, the error with the highest priority will have precedence, in other words:
– The system error LED flashes according to the higher priority.
– The number of the error with the higher priority will be entered in the system diagnostic data under function
number 1938 (error number).
Within an error class, errors of modules with a lower module number have higher priority. That means that, within an
error class, errors on
– Module number 0 have the highest priority
– Module number 1 have the second highest priority
– etc.

Festo – CPX-E-SYS-EN – 2017-07 – English 25


2 Function

2.3.6 Error numbers


Error numbers (error class 2)
Error Meaning Remedy
number
0 No error –
1 General diagnostics (module-specific errors) è Description for the respective module
2 Short circuit/overload in sensor supply (SCS) or at Eliminate short circuit/overload è Description
output (SCO) for the respective module.
3 Wire break/idling at current input/output  Check cables and sensors/actuators and
replace where required.
4 Failure of load voltage supply UOUT due to short  Check actuators and their connections.
circuit/overload (on output side)
5 Undervoltage in the operating voltage supply  Eliminate undervoltage.
UEL/SEN (on input side)
6…8 Reserved –
9 Value falling below nominal range  Check signal range and parameterised limit
10 Value exceeding nominal range value.
11 Short circuit at valve  Check valve and pneumatic interface.
12 Reserved –
13 Wire break at valve (open load)  Check valve and pneumatic interface.
14 Limit value of the condition counter exceeded  Set or delete the limit value of the condition
counter by parameterising.
15 Module/channel failed  Check module/peripherals and replace if
necessary.
16 Saved configuration is different to the actual For the system:
expansion of the system.  Check expansion and save again if necessary
è Tab. 3.13.
For the bus module:
 Modify the System Start parameter to
“System start with default parameterisation
and current CPX-E expansion”.
For the controller:
 Save the actual configuration as the set
configuration using the CoDeSys software.
17 Saved I/O length of the module is different to the è Error number 16
actual system expansion.
18 Number of I/O points exceeded  Check DIL switch position and system
expansion è Description for the respective
bus module/controller.
19 Nominal service life/life cycle exceeded  Replace module or spare part è Description
for the respective module.
20 Error in Signal range  Check the parameterisation and if necessary
21 parameterisation Data format repeat using the correct parameters.
22 Linear scaling
23 Measured value
smoothing
24 Lower limit value
25 Upper limit value
26 Error on actuator supply  Eliminate short circuit and check actuators
and actuator supply.
27 Missing or incorrect spare part  Replace module or spare part è Description
for the respective module.

26 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Error numbers (error class 2)


Error Meaning Remedy
number
28 Alarm value reached  Check operating conditions è Description
for the respective module.
29 Error in parameterisation  Check the parameterisation and if necessary
repeat using the correct parameters.
30 Error in internal communication  Replace module if switching on and off does
(no new output data) not remedy problem.
31 Bus connection interrupted  Make bus connection or check configuration.
32 STI read access defective  Repeat STI read access.
33 Read access parameter defective  Repeat read access parameter.
34 … 36 Reserved –
37 Defect in the controller function  Check pressure and actuator supply.
(e. g. setpoint value cannot be reached)
38 No valve recognised  Check valve (function/installation), replace if
necessary.
39 Maintenance required è Description for the respective module
40 … 47 Reserved –
48 Calibration error (factory adjustment missing)  Replace module.
49 Current loop is in the lower drop-out range  Check the installation/parameterisation of
the actuator è Description for the respective
50 Current loop is in the upper drop-out range
module.
51 Physical limit value for a sensor exceeded:  Check structure (compliance with module
– Process value invalid specification), check module for damage and
– Possible hardware damage replace if necessary.
52 Short circuit at cold junction compensation  Eliminate short circuit and check connected
CJC sensors if necessary.
53 Wire break at cold junction compensation  Check cables and connected CJC sensors and
replace where required.
54 Calibration data is faulty  Replace module.
55 Formation of the process value is invalid due to  Check structure (compliance with module
faulty structure specification).
56 … 63 Reserved –
64 The number of modules in the current system  Correct expansion or save new expansion.
expansion does not match the saved expansion
65 … 69 Reserved –
70 System expansion is greater than the number of  Check DIL switch position (increase number
stations set of stations).
71 Bus connection interrupted  Check wiring.
72 … 79 Reserved –
80 Module-specific malfunction è Description for the respective module
81 … 99 Reserved –
100 Error in configuration/parameterisation  Check configuration/parameterisation,
correct if necessary or repeat commissioning.
101 Error executing a positioning job  Check the positioning task and correct if
102 Error executing a positioning record necessary.
103 Error in control or in the parameters of a
positioning job
104 Error in the process control or the system  Check system configuration, positioning job,
configuration I/O signals or system status and correct as
necessary.

Festo – CPX-E-SYS-EN – 2017-07 – English 27


2 Function

Error numbers (error class 2)


Error Meaning Remedy
number
105 Error in the peripherals (power supply, operating  Check peripherals, power supply and
pressure, etc.) operating pressure.
106 Error in valve or on axis string  Check valves and cables and replace where
required.
107 Error in the controller or drive regulator  Check controller or drive regulator and
replace if necessary.
108 Error in measuring system or on axis string  Check measuring system and cables and
replace where required.
109 Error in the motor or power section  Check motor or power section and replace if
necessary.
110 … 114 Reserved –
115 Module/channel in a subordinate system has  Check subordinate module
failed (function/installation) and replace if
necessary è Description for the respective
module.
Tab. 2.18

Error numbers (error class 3)


Error Meaning Remedy
number
128 Hardware defective  Check hardware and replace if necessary.
129 Bus module faulty  Replace bus module.
130 System error on bus module  Replace module if switching on and off does
not remedy problem.
131 Error in internal communication during start-up  Check system and replace if necessary.
132 System error  Replace module if switching on and off does
not remedy problem.
133 … 134 Module faulty  Replace module.
135 Error in internal configuration, module out of order  Check system and replace if necessary.
136 System error  Replace module if switching on and off does
not remedy problem.
137 Error in internal configuration, module out of order  Check system and replace if necessary.
138 Error in internal configuration, e.g.:  Check module mounting/arrangement
– Module not correctly mounted, plugged in (nogaps in system expansion), check module
– Module faulty and replace if necessary.
139 Error when processing cyclical services  Check control program, check system and
(e.g.parameters) replace if necessary.
140 Hardware defective  Identify and replace faulty module.
141 Malfunction in internal communication;  Check application environment, check system
142 systemwas not yet operational and replace if necessary.
143 System error  Replace module if switching on and off does
not remedy problem.
144 Module does not have a valid licence  Procure licence or replace module.
145 … 149 Reserved –
150 System error  Replace module if switching on and off does
not remedy problem.
151 … 199 Reserved –
Tab. 2.19

28 Festo – CPX-E-SYS-EN – 2017-07 – English


2 Function

Error numbers (error class 1)


Error Meaning Remedy
number
200 Error in parameterisation (parameter transfer  Replace module if switching on and off does
failed) not remedy problem.
201 Address incorrect  Check DIL switch position and correct if
necessary.
202 Initialisation of the protocol chip defective  Replace module if switching on and off does
not remedy problem.
203 Reserved –
204 Invalid switch position  Check DIL switch position and correct if
necessary.
205 … 253 Reserved –
254 Undervoltage of electronics and sensors  Eliminate undervoltage.
255 Unknown error –
Tab. 2.20

Festo – CPX-E-SYS-EN – 2017-07 – English 29


3 Parameterisation

3 Parameterisation
With the aid of parameterisation, the behaviour of the system CPX-E or the behaviour of individual modules and
channels can be adapted to the particular application. Parameterisation can be performed using suitable software
from Festo or using the higher-order controller. The parameters are preset at the factory.
The parameterisation options depend on the bus module or controller used è Description of the
respective bus module/controller.

3.1 Parameterisation using Festo software


Suitable software for parameterisation can be found on the Festo Support Portal è www.festo.com/sp.
Information on using the software can be found in the integrated Help function.

3.2 Parameterisation using the higher-order controller


There are various options for parameterisation of the system CPX-E using the higher-order controller è Tab. 3.1.
Parameterisation options Description/benefits
Interface module or Parameterisation can be ensured e.g. in the start-up phase or after network
scanner/master interruptions.
User program in the higher-order The parameters can be modified during run-time.
controller
Network-specific configurators Parameters can be modified during the commissioning phase or during the
troubleshooting.
Tab. 3.1

3.3 Types of parameters


A distinction is made between the following types of parameters:
Parameter type Description Overview of
parameters
System parameters Influence the behaviour of the complete system CPX-E. è Tab. 3.3
Module parameters
Module-specific Influence the behaviour of a particular module. è Tab. 3.4
Channel-specific Influence the behaviour of a particular channel.
Diagnostic memory parameters Influence the mode of operation of the internal diagnostic è Tab. 3.5
memory.
Tab. 3.2

30 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

System parameters Brief description


Diagnostics and monitoring for: Switches monitoring of short circuit/ overload and undervoltage for the entire
– Short circuit/overload system CPX-E on or off.
– Undervoltage at outputs
Signal status when there is a Defines the status which digital output signals are to assume in the event of
malfunction (Fail-safe parameter) communication errors on the network.
Signal status in Idle mode1) Defines the status which digital output signals are to assume when switching
to Idle status.
Force signal status Manipulation of signal statuses separate from actual operating conditions
(Force parameter) and independent of the higher-order controller.
System start Specifies the start-up behaviour of the system CPX-E.
Analogue process value Switches the data format for displaying analogue process values (I/O signals).
representation (data format)2)
1) This function is only relevant for certain network protocols è Description for the respective bus module.
2) Special parameter, only available on certain bus modules
Tab. 3.3

Module parameters Brief description


Module-specific
Diagnostics and monitoring for: Switches monitoring of short circuit/overload and undervoltage on the
– Short circuit/overload module on or off.
– Undervoltage
– Wire break
Behaviour after: Specifies, after a short circuit/overload or wire break, whether the power is to
– Short circuit/overload remain switched off or whether it is to be switched on again automatically.
– Wire break
Input debounce time Serves for trouble-free recognition of digital input signals.
Signal extension time Serves for recognising short signals.
Data format of analogue values è Description for the respective analogue module
Channel-specific
Signal extension Serves for recognising short signals.
Monitoring of wire break Serves for recognising connection errors.
Fault mode Defines the status that the relevant channel is to assume in the event of
Fault state communication errors on the network.
Idle mode1) Defines the status which digital output signals are to assume when the Idle
Idle state1) function is accessed.
Force mode Actual signals are replaced in the process image by the Force settings.
Force state
1) This function is only relevant for certain network protocols è Description for the respective bus module.
Tab. 3.4

Diagnostic memory parameters Brief description


Entries, saved retentively Specifies whether the contents of the diagnostic memory are to be retained
after the power supply is switched on again or whether they are to be deleted.
Diagnostic memory filters: The diagnostic memory filters can be used to suppress the recording of certain
– Run/stop filter 1 + 2 error messages, and to control both the start and stop of the error recording.
– Error end filter
– Error number filter
– Module/channel filter
Tab. 3.5

Festo – CPX-E-SYS-EN – 2017-07 – English 31


3 Parameterisation

3.4 Parameters and data for the system CPX-E

3.4.1 Overview
Parameters Description
System parameters Specify global system functions for the entire system, e.g.:
– Diagnostic monitoring
– System start
Module parameters Specify module-specific and channel-specific functions for the respective
module, e.g.:
– Input debounce time
– Signal extension time
Diagnostic memory parameters Specify the mode of operation of the diagnostic memory
Tab. 3.6

Data Description
System diagnostic data Global information about the system status
(e.g. error number, common diagnostic message)
Module diagnostic data Information on locating errors (e.g. error number, number of the first faulty
channel etc.)
Diagnostic memory data Entries in the diagnostic memory (maximum 40)
System data Information on global system settings
Module data Serial number, revision code and module code of the modules used
Tab. 3.7

3.4.2 Function numbers


Function number1) Description Data/parameters Detailed
information
0 Expansion System data è Tab. 3.44
Force mode è Tab. 3.45
System start è Tab. 3.46
1 Fail safe è Tab. 3.47
Idle mode è Tab. 3.48
2 System monitoring è Tab. 3.49
16 + 16 m + 0 Module code Module data è Tab. 3.50
16 + 16 m + 13 Revision code è Tab. 3.51
784 + 4m + 0 … 3 Serial number è Tab. 3.52
1936 Status bits System diagnostic data è Tab. 3.37
1937 Module number and diagnostic status è Tab. 3.38
1938 Error number è Tab. 3.39
2008 + 4 m + 0 Number of the first faulty channel Module diagnostic data è Tab. 3.40
2008 + 4 m + 1 Module error number è Tab. 3.41
2008 + 4 m + 2 Info 2 (reserved) è Tab. 3.42
2008 + 4 m + 3 Info 3 (reserved) è Tab. 3.43
3480 Entries saved retentively with Power On Diagnostic memory parameters è Tab. 3.24
Run/stop filter 1 è Tab. 3.25
1) m = module number (counting from left to right, beginning with 0)
2) d = Diagnostic event
3) Access is protocol-specific è Description of bus module
4) Only relevant for certain network protocols è Description of bus module

32 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

Function number1) Description Data/parameters Detailed


information
3482 Number of entries in the diagnostic Diagnostic memory data è Tab. 3.33
memory
3483 Overflow è Tab. 3.34
Status è Tab. 3.35
3484 Run/stop filter 2 Diagnostic memory parameters è Tab. 3.26
Error end filter è Tab. 3.27
Error number filter è Tab. 3.28
Module/channel filter è Tab. 3.29
3485 Module number è Tab. 3.30
3486 Channel number è Tab. 3.31
3487 Error number è Tab. 3.32
3488 + 10d + 0 … 9 Diagnostic memory Diagnostic memory data è Tab. 3.36
4401 Monitoring System parameters è Tab. 3.9
4402 Fail safe è Tab. 3.10
Force mode è Tab. 3.11
Idle mode è Tab. 3.12
System start è Tab. 3.13
Analogue process value representation è Tab. 3.14
4828 + 64 m + 0 Module monitoring Module parameters è Tab. 3.15
4828 + 64 m + 1 Behaviour after short circuit/overload (module-specific) è Tab. 3.16
Input debounce time è Tab. 3.17
Signal extension time è Tab. 3.18
4828 + 64 m + 3 Data format for analogue value of è Tab. 3.19
inputs
Data format for analogue value of
outputs
4828 + 64 m + 6 Signal extension channel x Module parameters è Tab. 3.20
3) Fail safe channel x (channel-specific) è Tab. 3.21
Idle mode channel x è Tab. 3.22
Forcen channel x è Tab. 3.23
4) Number of input bytes (Rx size) System data –
Number of output bytes (Tx size) (network-specific) –
1) m = module number (counting from left to right, beginning with 0)
2) d = Diagnostic event
3) Access is protocol-specific è Description of bus module
4) Only relevant for certain network protocols è Description of bus module
Tab. 3.8

Festo – CPX-E-SYS-EN – 2017-07 – English 33


3 Parameterisation

3.5 System parameters

3.5.1 Monitoring
System parameter – Monitoring
Activates or deactivates (suppresses) monitoring of short Selection via parameters
circuit/overload and undervoltage for the entire system.1)
If monitoring is active, an error reported by the module will be: F no.2) Bit
– Sent to the higher-order master
– Entered in the diagnostic memory3) 4401 7 6 5 4 3 2 1 0
– Entered in the module diagnostic data and, if applicable, in the
status bits
– Indicated by the red common error LED on the module
Short circuit/overload in sensor supply (SCS) 0
1

Short circuit/overload at the outputs (SCO) 0


1

Undervoltage at outputs (UOUT) 0


1

1) Values: 1 = active (presetting); 0 = inactive


2) Function number
3) Dependent on filter settings
Tab. 3.9

Monitoring can also be set separately for each module using the module parameter “Module monitoring”
è Tab. 3.15. The mode of operation of the channel error LED remains unaltered.

3.5.2 Fail safe


System parameter – Fail safe
Specifies which signal status the outputs are to assume in the event of Selection via parameters
communication errors in the network, e.g. in the event of network F no.1) Bit
interruption, failure of the higher-order controller, communication stop.
4402 7 6 5 4 3 2 1 0

Reset all outputs (presetting) 0 0


Hold last state (retain signal status) 0 1
Assume Fault mode 1 0
1) Function number
Tab. 3.10

When changing from “Assume Fault mode” to “Reset all outputs” or to “Hold last state”, the
channel-orientated Fail-safe settings (module parameters “Fault mode” and “Fault state”) are reset
automatically for safety reasons in order to avoid undesired signal statuses.
The Fault-mode status is set using the channel-specific module parameters è Tab. 3.21.

3.5.3 Force mode


System parameter – Force mode
Specifies for the entire system whether the Forcen function is disabled Selection via parameters
or enabled. F no.1) Bit
4402 7 6 5 4 3 2 1 0

Force mode disabled (presetting) 0 0


Force mode enabled (retain signal status) 0 1
1) Function number
Tab. 3.11

34 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

By changing this parameter, the channel-orientated Force settings (module parameters “Force mode” and
“Force state”) are reset automatically for safety reasons in the following cases in order to avoid undesired
signal statuses:
– Change using Festo software: when switching from “enabled” to “disabled”
– Change via the network: When changed from “disabled” to “enabled”
Force signals have priority over Fail-safe signals.

3.5.4 Idle mode


System parameter – Idle mode1)
Establishes which signal status outputs are to assume when the system Selection via parameters
switches to Idle status. F no.2) Bit
4402 7 6 5 4 3 2 1 0

Reset all outputs (presetting) 0 0


Hold last state (retain signal status) 0 1
Assume Idle mode 1 0
1) This parameter is only relevant for certain network protocols è Description for the respective bus module.
2) Function number
Tab. 3.12

When changing from “Assume Idle mode” to “Reset all outputs” or to “Hold last state”, the
channel-orientated Idle-mode settings (module parameters “Idle mode” and “Idle state”) are reset
automatically for safety reasons in order to avoid undesired signal statuses.

3.5.5 System start


System parameter – system start
Specifies the starting behaviour of the system and saves all current Selection via parameters
parameter settings and the current expansion. F no.1) Bit
4402 7 6 5 4 3 2 1 0

System start with default parameterisation (factory setting) and current CPX 0
expansion; external parameterisation is possible (presetting)
System start with saved parameterisation and saved CPX expansion; parameters 1
and expansion are saved to retentive memory; external parameterisation is
blocked; the Modify LED (M) on the bus module lights up
1) Function number
Tab. 3.13

If bit 6 is set to 1, the current parameter settings will be write-protected and the current expansion will be
saved, except for bit 6 itself and the module parameters “Forcen channel X”.
Recommendation: “System start with default parameterisation and current CPX expansion”. The desired
parameterisation can then be created in the start-up phase or after a network interruption, e.g. by the
interface module or the scanner/master (depending on the network used). If “System start with default
parameterisation and current CPX expansion” is active, the factory settings for all module and system
parameters will be applied after switching on and off.

Festo – CPX-E-SYS-EN – 2017-07 – English 35


3 Parameterisation

3.5.6 Analogue process value representation


System parameter – Analogue process value recommendation1)
Switches the data format or byte sequence for displaying analogue Selection via parameters
process values. F no.2) Bit
4402 7 6 5 4 3 2 1 0

INTEL byte sequence (presetting): 0


Least significant bit on the left, most significant bit on the right (LSB-MSB)3)
MOTOROLA byte sequence: 1
Most significant bit on the left, least significant bit on the right (MSB-LSB)3)
1) This parameter is only relevant for certain bus modules è Description for the respective bus module.
2) Function number
3) LSB = Least Significant Bit; MSB = Most Significant Bit
Tab. 3.14

36 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.6 Module parameters (module-specific)


Module parameters refer to module-specific or channel-specific functions. 64 bytes are available for parameters in
each module.
You can find detailed information on the module parameters supported by the module used, as well as
parameter values and their presettings, in the description for the relevant module.

3.6.1 Module monitoring


Module parameter – Module monitoring
Monitoring of the possible errors can be activated or deactivated Selection via parameters
(suppressed) independently for each module.1) F no.2) Bit
If monitoring is active, an error will be:
4828 7 6 5 4 3 2 1 0
– Sent to the bus module
– Indicated by the common error LED on the module + 64m
Short circuit/overload in sensor supply (SCS) +0 0
1

Short circuit/overload at the outputs (SCO) 0


1

Undervoltage at outputs (UOUT) 0


1

Monitoring of parameterisation errors 0


1

1) Values: 1 = active (presetting); 0 = inactive


2) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.15

Monitoring can also be set for the entire system via the “Monitoring" system parameter è Tab. 3.9.

3.6.2 Behaviour after short circuit/overload


Module parameter – Behaviour after short circuit/overload
Specifies, after a short circuit/overload in the sensor supply or the Selection via parameters
outputs, whether the relevant voltage is to remain switched off or F no.2) Bit
whether it is to be switched on again automatically.1) 4828 7 6 5 4 3 2 1 0
+ 64m
Short circuit/overload in sensor supply (SCS) +1 0
1

Short circuit/overload at the outputs (SCO) 0


1

Short circuit/overload at the analogue signal 0


1

1) Values: 1 = Switch voltage back on; 0 = Voltage remains switched off


2) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.16

With the setting “Voltage remains switched off ”, you must switch the power off and back on or set/reset
the relevant signals to recover the voltage.

Festo – CPX-E-SYS-EN – 2017-07 – English 37


3 Parameterisation

3.6.3 Input debounce time


Module parameter – Input debounce time
Specifies when a change of edge of the sensor signal on the relevant Selection via parameters
module is to be accepted as a logical input signal. F no.1) Bit
4828 7 6 5 4 3 2 1 0
+ 64m
Input debounce time 0.1 ms +1 0 0
3 ms (typical presetting) 0 1
10 ms 1 0
20 ms 1 1
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.17

You can find more information on this parameter in the description for the respective module.

3.6.4 Signal extension time


Module parameter – Signal extension time
Specifies the signal extension time for the respective module. Selection via parameters
Signal statuses accepted as logical input signals usually remain valid at F no.1) Bit
least until the specified signal extension time (minimum signal duration) 4828 7 6 5 4 3 2 1 0
has expired. Changes of edge within the extension time are ignored. + 64m
Signal extension time 0.5 ms +1 0 0
15 ms (typical presetting) 0 1
50 ms 1 0
100 ms 1 1
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.18

The signal extension time can be activated channel-by-channel è Tab. 3.20. You can find more
information on this parameter in the description for the respective module.

3.6.5 Data format for analogue value of inputs/outputs


Module parameter – Data format for analogue value of inputs/outputs
Specifies the data format for internal processing of the relevant Selection via parameters
analogue values.1) F no.2) Bit
The choice of data format depends on the network or master used and 4828 7 6 5 4 3 2 1 0
simplifies evaluation of the analogue values. + 64m
Data format for analogue value of inputs +3 0
1
0
1

Data format for analogue value of outputs 0


1
0
1

1) Values è Description for the respective module


2) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.19

38 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.7 Module parameters (channel-specific)

3.7.1 Signal extension channel x


Module parameter (channel-specific) – Signal extension channel x
Specifies whether the signal extension for the relevant channel is to be Selection via parameters
enabled or disabled.1) F no.2) Bit
The signal extension time can be specified separately for each module 4828 7 6 5 4 3 2 1 0
è Tab. 3.18. + 64m
Signal extension Channel 0 +6 0
1

Channel 1 0
1

Channel 2 0
1

Channel 3 0
1

Channel 4 0
1

Channel 5 0
1

Channel 6 0
1

Channel 7 0
1

1) Values: 1 = enabled; 0 = disabled


2) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.20

3.7.2 Fail safe channel x


Module parameters (channel-specific) – Fail safechannel x
The Fail-safe parameterisation can be used to specify the signal status Selection via parameters
which the outputs are to assume in the event of communication errors
è 2.2.4 Signal status when there is a fault (Fail safe).
Fault mode channel x Hold last state Access is via protocol-specific functions
Fault state (presetting) è Description for the bus module.
Fault state channel x Reset output (presetting)
Set output
Tab. 3.21

3.7.3 Idle mode channel x


Module parameters (channel-specific) – Idle modechannel x1)
The Idle-mode parameterisation can be used to specify the signal status Selection via parameters
which the outputs are to assume when switching to Idle status
(è 2.2.5 Signal status in Idle status (Idle mode)).
Idle mode channel x Hold last state Access is via protocol-specific functions
Idle state (presetting) è Description for the bus module.
Idle state channel x Reset output (presetting)
Set output
1) Not supported by all bus modules
Tab. 3.22

Festo – CPX-E-SYS-EN – 2017-07 – English 39


3 Parameterisation

3.7.4 Forcen channel x


Module parameters (channel-specific) – Forcenchannel x
The Forcen function permits the manipulation of signal statuses Selection via parameters
independently of the actual operating conditions è 2.2.3 Forcen.
Force mode inputs, channel x Disabled (presetting) Access is via protocol-specific functions
Force state è Description for the bus module.
Force state inputs, channel x Set signal
Reset signal (presetting)
Force mode outputs, channel x Disabled (presetting)
Force state
Force state outputs, channel x Set signal
Reset signal (presetting)
Tab. 3.23

40 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.8 Diagnostic memory parameters (Trace parameters)


The mode of operation of the diagnostic memory can be adapted to individual requirements using the diagnostic
memory parameters. The diagnostic memory parameters retain their last setting after the power supply has been
switched off and on again and are saved so as to be protected against mains failure.
You can find more information about the mode of operation of the diagnostic memory in the Function
chapter è 2.3.4 Diagnostic memory.

3.8.1 Entries saved retentively with Power On


Diagnostic memory parameter – Entries saved retentively with Power On
Specifies whether the contents of the diagnostic memory are to be Selection via parameters
retained after the power supply is switched on again or whether they are F no.2) Bit
to be deleted. 1) 3480 7 6 5 4 3 2 1 0
The diagnostic memory will be deleted if the mode is changed.
Entries saved retentively with renewed switch-on 0
1

1) Values: 1 = active (presetting); 0 = inactive


2) Function number
Tab. 3.24

3.8.2 Run/Stop filter 1


Diagnostic memory parameter – Run/Stop filter 1
Diagnostic memory filter which is used to specify whether the first Selection via parameters
40 errors or the last 40 errors are to be saved. F no.1) Bit
The diagnostic memory will be deleted if the mode is changed. 3480 7 6 5 4 3 2 1 0

Save the first 40 entries; stop after 40 entries 0


Save the last 40 entries; overwrite old entries (presetting) 1
1) Function number
Tab. 3.25

3.8.3 Run/Stop filter 2


Diagnostic memory parameter – Run/Stop filter 2
Diagnostic memory filter which is used to determine when the recording Selection via parameters
of errors is to be started or stopped. F no.2) Bit
MN = module number, CN = channel number, FN = error number1) 3484 7 6 5 4 3 2 1 0

Run/Stop filter 2 inactive (presetting) 0 0 0


Record up to the defined FN 0 0 1
Record up to the defined FN + MN 0 1 0
Record up to the defined FN + MN + CN 0 1 1
Record from the defined FN 1 0 0
Record from the defined FN + MN 1 0 1
Record from the defined FN + MN + CN 1 1 0
Reserved 1 1 1
1) The appropriate numbers are specified by means of the diagnostic memory parameters “Module number” (è Tab. 3.30), “Channel number”
(è Tab. 3.31) and “Error number” (è Tab. 3.32).
2) Function number
Tab. 3.26

Festo – CPX-E-SYS-EN – 2017-07 – English 41


3 Parameterisation

3.8.4 Error end filter


Diagnostic memory parameters – Error end filter
Diagnostic memory filter which is used to specify whether outgoing Selection via parameters
errors are to be recorded or not. F no.1) Bit
3484 7 6 5 4 3 2 1 0

Record outgoing errors (end of error); filter inactive (presetting) 0


Do not record outgoing errors (end of error); filter active 1
1) Function number
Tab. 3.27

By recording the outgoing errors it can be determined how long an error has existed. Incoming and
outgoing errors each represent one entry. With outgoing errors, the error number “0” is entered.
Amaximum of 40 entries are saved in total.

3.8.5 Error number filter


Diagnostic memory parameter – Error number filter
This diagnostic memory filter can be used to suppress recording of Selection via parameters
adesired error message or to record a desired error message only.1) F no.2) Bit
3484 7 6 5 4 3 2 1 0

Error number filter inactive (presetting) 0 0


Record only defined error number 0 1
Do not record defined error number 1 0
Reserved 1 1
1) The relevant numbers are specified by means of the diagnostic memory parameter “Error number” (è Tab. 3.32).
2) Function number
Tab. 3.28

3.8.6 Module/channel filter


Diagnostic memory parameter – Module/channel filter
This diagnostic memory filter can be used to suppress the recording of Selection via parameters
errors of other modules or channels so that errors in a particular module F no.2) Bit
or channel can be analysed.1) 3484 7 6 5 4 3 2 1 0

Module/channel filter inactive (presetting) 0 0


Record the error number of a given module only 0 1
Record the error number of a given channel only 1 0
Reserved 1 1
1) The relevant numbers are specified by means of the diagnostic memory parameters “Module number” (è Tab. 3.30) and “Channel number”
(è Tab. 3.31).
2) Function number
Tab. 3.29

42 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.8.7 Module number


Diagnostic memory parameter – Module number
Module number for the diagnostic memory filter Selection via parameters
Only effective if an appropriate diagnostic memory filter is active. F no.1) Bit
3485 7 6 5 4 3 2 1 0

Module number 0 ... 47 (0 = presetting) 0


1
0
1
0
1
0
1
0
1
0
1

1) Function number
Tab. 3.30

3.8.8 Channel number


Diagnostic memory parameter – Channel number
Channel number for the diagnostic memory filter Selection via parameters
Only effective if an appropriate diagnostic memory filter is active. F no.1) Bit
3486 7 6 5 4 3 2 1 0

Channel number 0 ... 63 (0 = presetting) 0


1
0
1
0
1
0
1
0
1
0
1

1) Function number
Tab. 3.31

3.8.9 Error number


Diagnostic memory parameter – Error number
Error number for the diagnostic memory filter Selection via parameters
Only effective if an appropriate diagnostic memory filter is active. F no.1) Bit
3487 7 6 5 4 3 2 1 0

Error number 0 ... 255 (0 = presetting) 0


1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number
Tab. 3.32

Festo – CPX-E-SYS-EN – 2017-07 – English 43


3 Parameterisation

3.9 Diagnostic memory data

3.9.1 Number of entries in the diagnostic memory


Diagnostic memory data – Number of entries in the diagnostic memory
Specifies the number of entries in the diagnostic memory. Selection via parameters
Can be used as a loop counter if the complete diagnostic memory is to F no. Bit
be read out by PLC program. 34821) 7 6 5 4 3 2 1 0

Number of entries in the diagnostic memory (0 ... 40) 0


1
0
1
0
1
0
1
0
1
0
1

1) Function number
Tab. 3.33

3.9.2 Overflow
Diagnostic memory data – Overflow
Indicates whether the diagnostic memory has overflowed. Overflow Selection via parameters
means that more than 40 errors have occurred. F no.1) Bit
The overflow is displayed when the first 40 errors are recorded as well as 3483 7 6 5 4 3 2 1 0
when the last 40 errors are recorded.
No overflow 0
Overflow 1
1) Function number
Tab. 3.34

3.9.3 Status
Diagnostic memory data – Status
Indicates whether error recording is active or inactive. Selection via parameters
Error recording can be stopped and started with the Run/Stop filters. F no.1) Bit
3483 7 6 5 4 3 2 1 0

Recording active 0
Recording inactive 1
1) Function number
Tab. 3.35

44 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.9.4 Diagnostic memory


Diagnostic memory data – Diagnostic memory (10 bytes per entry, 40 entries)
The diagnostic memory contains a maximum of 40 diagnostic entries, Selection via parameters
with each diagnostic entry consisting of 10 bytes.
F no.1) Bit
The first 5 bytes contain information on the time of the error and the
last 5 byes contain information about the error. 3488 7 6 5 4 3 2 1 0
Byte Description Value + 10d
1 Days 0 … 255 +0 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

Number of days2)
2 Hours 0 … 23 +1 0
1
0
1
0
1
0
1
0
1

Number of hours2)
3 Minutes 0 … 59 +2 0
1
0
1
0
1
0
1
0
1
0
1

Number of minutes2)
4 Seconds 0 … 59 +3 0
1
0
1
0
1
0
1
0
1
0
1

Number of seconds2)
5 Milliseconds 0 … 99 +4 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

Number of 10 milliseconds2) or
Bit 7 is additionally set if it is the first entry 128 … 227
after a switch-on.
6 Module code3) 0 … 255 +5 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

Module code of the module which reported


the error
7 Module position 0 … 47; +6 0
1
0
1
0
1
0
1
0
1
0
1

Module number of the module which 63


reported the error; 63 = error not
module-related
8 Channel number3)
Number of first faulty output channel 0 … 255 +7 0 0 0
1
0
1
0
1
0
1
0
1
0
1

(bits0 ... 5; values: 0 ... 63)


Number of first faulty input channel 1 0 0
1
0
1
0
1
0
1
0
1
0
1

(bits0 ... 5; values: 0 ... 63)


Module error (bits 0 ... 5; values: 0 ... 63) 0 1 0
1
0
1
0
1
0
1
0
1
0
1

Reserved 1 1 0
1
0
1
0
1
0
1
0
1
0
1

9 Error number 0 … 255 +8 0


1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

(possible error messages è 2.3.5)


10 Subsequent channels 0 … 63 +9 0
1
0
1
0
1
0
1
0
1
0
1

Number of subsequent channels with the


same error
1) Function number; d = Diagnostic event = 0 … 39; current diagnostic event = 0
2) Measured from the moment the power supply is switched on
3) If the error number = 0, the content of these bytes is also 0. If the error number lies between 128 ... 199 (error class 3), the content of these
bytes is not relevant (servicing required).
Tab. 3.36

Festo – CPX-E-SYS-EN – 2017-07 – English 45


3 Parameterisation

3.10 System diagnostic data

3.10.1 Status bits


System diagnostic data – Status bits
The 8 status bits display common diagnostic messages.1) Selection via parameters
– Bit 0 … 3: source of error F no.2) Bit
– Bit 4 … 7: type of error 1936 7 6 5 4 3 2 1 0

Source of error Valve 0


1

Outlet 0
1

Input 0
1

Analogue/technology module 0
1

Type of error Undervoltage 0


1

Short circuit/overload 0
1

Wire break 0
1

Other error 0
1

1) Values: 1 = error present; 0 = no error


2) Function number
Tab. 3.37

3.10.2 Module number and diagnostic status


System diagnostic data – Module number and diagnostic status
Indicates whether there are diagnostic data and contains, where Selection via parameters
applicable, the number of the first module on which an error has F no. Bit
occurred.1)
1937 7 6 5 4 3 2 1 0
With the aid of the module number of the faulty module, you can
ascertain the function number of the relevant diagnostic data.
Module number of the first faulty module (0 ... 47) 0
1
0
1
0
1
0
1
0
1
0
1

Diagnostic status 0
1

1) Values: 1 = Diagnostic data available; 0 = no diagnostic data


Tab. 3.38

3.10.3 Error number


System diagnostic data – Error number
Current error number (possible error messages è 2.3.5) Selection via parameters
Function number 1937 indicates whether diagnostic data are available F no.1) Bit
è Tab. 3.38. 1938 7 6 5 4 3 2 1 0

Error number (0 … 255) 0


1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number
Tab. 3.39

46 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.11 Module diagnostic data


The module diagnostic data are attributed to the function numbers 2008 … 2199. A total of 4 items of diagnostic
information are available in 4 consecutive bytes for each module.
The function number of the diagnostic data for the faulty module is therefore calculated as follows:
– Function number = 2008 + (4 x module number) + information number
The module number of the first faulty module can be determined with the aid of the system diagnostic
data (function number 1937) è Tab. 3.38.

3.11.1 Number of the first faulty channel


Module diagnostic data – Number of the first faulty channel
Indicates the number of the first faulty channel. Selection via parameters
F no.1) Bit
2008 7 6 5 4 3 2 1 0
+ 4m
Channel number (0 … 63) +0 0
1
0
1
0
1
0
1
0
1
0
1

Number of first faulty output channel 0 0


Number of first faulty input channel 1 0
Module error 0 1
Reserved 1 1
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.40

3.11.2 Error number


Module diagnostic data – Error number
Error number (possible error messages è 2.3.5) Selection via parameters
F no.1) Bit
2008 7 6 5 4 3 2 1 0
+ 4m
Error number (0 … 255) +1 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.41

3.11.3 Info 2 and 3 (reserved)


Module diagnostic data – Info 2 (reserved)
Info 2 (reserved) Selection via parameters
F no.1) Bit
2008 7 6 5 4 3 2 1 0
+ 4m
Reserved +2 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.42

Module diagnostic data – Info 3 (reserved)


Info 3 (reserved) Selection via parameters
F no.1) Bit
2008 7 6 5 4 3 2 1 0
+ 4m
Reserved +3 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.43

Festo – CPX-E-SYS-EN – 2017-07 – English 47


3 Parameterisation

3.12 System data


System data provide information about global system settings and the system status. The system data are not
saved to retentive memory and are lost on switching off.
3.12.1 Expansion
System data – Expansion
Indicates whether the current expansion of the system corresponds to Selection via parameters
the saved expansion. F no.1) Bit
See also system parameter “System start” è Tab. 3.13. 0 7 6 5 4 3 2 1 0

Uniform expansion 0
Non-uniform expansion 1
1) Function number
Tab. 3.44

3.12.2 Force mode


System data – Force mode
Indicates whether Forcen is disabled or enabled. Selection via parameters
See also system parameter “Force mode” è Tab. 3.11. F no.1) Bit
0 7 6 5 4 3 2 1 0

Forcen disabled 0
Forcen enabled 1
1) Function number
Tab. 3.45

3.12.3 System start


System data – System start
Indicates how the system start is to be carried out. Selection via parameters
See also system parameter “System start” è Tab. 3.13. F no.1) Bit
0 7 6 5 4 3 2 1 0

System start with default parameterisation (factory setting) and current expansion 0
System start with saved parameterisation and saved equipment status 1
1) Function number
Tab. 3.46

3.12.4 Fail safe


System data – Fail safe
Indicates whether Fail safe is active or inactive. Selection via parameters
F no.1) Bit
1 7 6 5 4 3 2 1 0

Reset all outputs 0 0


Hold last state (retain signal status) 0 1
Assume Fault mode 1 1
1) Function number
Tab. 3.47

48 Festo – CPX-E-SYS-EN – 2017-07 – English


3 Parameterisation

3.12.5 Idle mode


System data – Idle mode
Indicates whether Idle mode is active or inactive. Selection via parameters
F no.1) Bit
1 7 6 5 4 3 2 1 0

Reset all outputs 0 0


Hold last state (retain signal status) 0 1
Assume Idle mode 1 1
1) Function number
Tab. 3.48

3.12.6 System monitoring


System data – System monitoring
Indicates whether monitoring of short-circuit/overload and Selection via parameters
undervoltage is active or inactive.1) F no.2) Bit
See also system parameter “Monitoring” è Tab. 3.9. 2 7 6 5 4 3 2 1 0

Short circuit/overload in sensor supply (SCS) 0


1

Short circuit/overload at the outputs (SCO) 0


1

Undervoltage at outputs (UOUT) 0


1

1) Values: 1 = active; 0 = inactive


2) Function number
Tab. 3.49

Festo – CPX-E-SYS-EN – 2017-07 – English 49


3 Parameterisation

3.13 Module data


Module data contain information appropriate to the respective modules and are thus used to identify modules.
3.13.1 Module code
Module data – Module code
Indicates the module code of the module. You can find the module codes Selection via parameters
in the corresponding module documentation. F no.1) Bit
16 7 6 5 4 3 2 1 0
+ 16m
Reserved (0) +0 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

Module code (1 … 245)


Reserved (246 … 255)
1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.50

3.13.2 Revision code


Module data – Revision code
Indicates the module version (è Product labelling). Selection via parameters
F no.1) Bit
16 7 6 5 4 3 2 1 0
+ 16m
Revision code (0 … 255) + 13 0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.51

3.13.3 Serial number


Module data – Serial number
Indicates the serial number of the module (in hexadecimal). Selection via parameters
F no.1) Bit
784 7 6 5 4 3 2 1 0
+ 4m
8th figure +0 0
1
0
1
0
1
0
1

7th figure 0
1
0
1
0
1
0
1

6th figure +1 0
1
0
1
0
1
0
1

5th figure 0
1
0
1
0
1
0
1

4th figure +2 0
1
0
1
0
1
0
1

3rd figure 0
1
0
1
0
1
0
1

2nd figure +3 0
1
0
1
0
1
0
1

1st figure 0
1
0
1
0
1
0
1

1) Function number; m = module number (counting from left to right, beginning with 0)
Tab. 3.52

50 Festo – CPX-E-SYS-EN – 2017-07 – English


A Technical Data

A Technical Data
General
Feature Specification/value
Mounting position Vertical/horizontal
Ambient temperature [°C] –5 … +60 (–5 … +50)1)
Storage temperature [°C] –20 … +70
Air humidity (non-condensing) [%] 0 … 95
Max. permissible setup altitude above sea level [m] 2000
Max. number of modules per system CPX-E, 11
including the bus module or controller
Address volume of the inputs/outputs [byte] 64/64 (maximum)
Degree of protection in accordance with EN 60529 IP20
Protection against electric shock (protection against Through the use of PELV circuits
direct and indirect contact to IEC 60204-1) (protectedextra-low voltage)
CE marking (see declaration of conformity) To EU EMC Directive
è www.festo.com
Explosion prevention and protection (IECEx/ATEX) è Special documentation on ATEX
Certification RCM compliance mark
Contamination level 2
Vibration and shock resistance in accordance with EN 600682)
Vibration (part 2-6) H-rail SL1
Shock (part 2 - 27) H-rail SL1
Continuous shock (part 2-27) H-rail SL1
1) For horizontal mounting position
2) Explanation of the severity levels è Tab. A.2 … Tab. A.4
Tab. A.1

Vibration load
Frequency range [Hz] Acceleration [m/s2] Deflection [mm]
SL1 SL2 SL1 SL2 SL1 SL2
2…8 2…8 – – ±3.5 ±3.5
8 … 27 8 … 27 10 10 – –
27 … 58 27 … 60 – – ±0.15 ±0.35
58 … 160 60 … 160 20 50 – –
160 … 200 160 … 200 10 10 – –
Tab. A.2

Shock load
Acceleration [m/s2] Duration [ms] Shocks per direction
SL1 SL2 SL1 SL2 SL1 SL2
±150 ±300 11 11 5 5
Tab. A.3

Continuous shock load


Acceleration [m/s2] Duration [ms] Shocks per direction
±150 6 1000
Tab. A.4

Festo – CPX-E-SYS-EN – 2017-07 – English 51


A Technical Data

Power supply
Feature Specification/value
Operating voltage supply UEL/SEN
Nominal operating voltage [V DC] 24 ± 25 %
Trigger level, undervoltage identification [V DC] 17.5
Max. current load of terminal strip [A] 8
Mains buffering time Module-dependent 1)
Load voltage supply UOUT
Nominal operating voltage [V DC] 24 ± 25 %2)
Trigger level, undervoltage identification Module-dependent 1)
Max. current load of terminal strip [A] 8
1) è Documentation of the modules
2) The indication of tolerance deviates in case of some modules.
Tab. A.5

Connection data of the terminal strips


Feature Specification/value
4-pin 6-pin
Conductor cross section
Solid [mm²] 0.14 … 1.5
Flexible [mm²] 0.14 … 2.5 0.14 … 1.5
Flexible with wire end sleeve
Without plastic sleeve [mm²] 0.14 … 1.5
With plastic sleeve [mm²] 0.14 … 1.5 0.14 … 1.5
Length of the wire end sleeve without plastic sleeve1)
Conductor cross section 0.14 … 1.0 mm2 [mm] 8 … 10
Conductor cross section 1.5 mm2 [mm] 8 … 10 10
Length of the wire end sleeve with plastic sleeve2)
Conductor cross section 0.14 … 0.34 mm2 [mm] 8 … 10
Conductor cross section 0.5 … 1.0 mm2 [mm] 8 … 10 10
1) In accordance with DIN 46228-1
2) In accordance with DIN 46228-4
Tab. A.6

52 Festo – CPX-E-SYS-EN – 2017-07 – English


B Terminology

B Terminology
Term/abbreviation Description
Bus module Connects a system CPX-E to the network; transmits control signals to the
connected modules CPX-E and monitors their functionality.
Device description file Protocol-specific file for configuring the bus module in the control software for
the higher-order controller. This contains all the information required to
parameterise the system CPX-E via control software.
DIL switch Switch consisting of several switch elements with which settings can be made
(dual in-line).
I/O Input and output
I/O diagnostic interface Network-independent diagnostic interface at I/O level, which enables access to
the internal data of the system CPX-E.
I/O module Collective term for modules that provide analogue or digital inputs and/or
outputs.
Modules CPX-E Collective term for the various modules which can be incorporated in a
systemCPX-E.
PLC Programmable logic controller
Status bits Internal status information (common diagnostic messages) of the system CPX-E,
provided as input signals via the network.
System CPX-E Complete system consisting of modules CPX-E.
Tab. B.1 Terms and abbreviations

Festo – CPX-E-SYS-EN – 2017-07 – English 53


Index
A F
Abbreviations, 53 Fail safe, 34, 48
Analogue process value representation, 36 Fail safe channel x, 39
Force, 12
B Force channel x, 40
Behaviour after short circuit/overload, 37 Force mode, 34, 48
Bus module, 7 Function example, 6
Function numbers, 32
C Further applicable documents, 5
Channel number, 43
Controller, 8 H
H-rail mounting, 9
D
Data, 32 I
– Diagnostic memory data, 32 I/O diagnostic interface, 20
– Module data, 32 Idle mode, 35, 49
– Module diagnostic data, 32 Idle mode channel x, 39
– System data, 32 Influencing signal statuses
– System diagnostic data, 32 – Fail safe, 11
Data format for analogue value of inputs/outputs, 38 – Force, 11
Diagnostic memory, 24, 45 – Idle mode, 11
Diagnostic memory data, 32, 44 Input debounce time, 38
– Diagnostic memory, 45 Input module, 8
– Number of entries in the diagnostic memory, 44
– Overflow, 44 L
– Status, 44 LED indicators, 17
Diagnostic memory parameters, 31, 32, 41 – Modify [M], 18
– Channel number, 43 – Power load [PL], 18
– Entries saved retentively with Power On, 41 – Power system [PS], 17
– Error end filter, 42 – System failure [SF], 18
– Error number, 43 Load voltage supply, 10
– Error number filter, 42
– Module number, 43 M
– Module/channel filter, 42 Module code, 50
– Run/stop filter 1, 41 Module data, 32, 50
– Run/stop filter 2, 41 – Module code, 50
Diagnostics options, 17 – Revision code, 50
– I/O diagnostic interface, 20 – Serial number, 50
– LED indicators, 17 Module diagnostic data, 32, 47
– Status bits, 19 – Error number, 47
– Number of the first faulty channel, 47
E Module monitoring, 37
Entries saved retentively with Power On, 41 Module number, 43
Error classes, 25 Module number and diagnostic status, 46
Error end filter, 42 Module parameters, 31, 32
Error number, 43, 46, 47 Module parameters (channel-specific), 39
Error number filter, 42 – Fail safe channel x, 39
Error numbers, 26 – Force channel x, 40
Expansion, 48 – Idle mode channel x, 39
– Signal extension channel x, 39

54 Festo – CPX-E-SYS-EN – 2017-07 – English


Module parameters (module-specific), 37 S
– Behaviour after short circuit/overload, 37 Serial number, 50
– Data format for analogue value of inputs/outputs, 38 Signal extension channel x, 39
– Input debounce time, 38 Signal extension time, 38
– Module monitoring, 37 Status, 44
– Signal extension time, 38 Status bits, 19, 46
Module/channel filter, 42 System CPX-E, 9
Modules CPX-E, 7 – H-rail mounting, 9
– Bus module, 7 – Mounting distances, 9
– Controller, 8 – Rules for set-up, 9
– Input module, 8 System data, 32, 48
– Output module, 8 – Expansion, 48
Monitoring, 34 – Fail safe, 48
Mounting distances, 9 – Force mode, 48
– Idle mode, 49
N – System monitoring, 49
Number of entries in the diagnostic memory, 44 – System start, 48
Number of the first faulty channel, 47 System diagnostic data, 32, 46
– Error number, 46
O – Module number and diagnostic status, 46
Operating voltage supply, 10 – Status bits, 46
Output module, 8 System monitoring, 49
Overflow, 44 System parameters, 31, 32, 34
– Analogue process value representation, 36
P
– Fail safe, 34
Parameters, 32
– Force mode, 34
– Diagnostic memory parameters, 31, 32
– Idle mode, 35
– Module parameters, 31, 32
– Monitoring, 34
– System parameters, 31, 32
– System start, 35
Power supply, 10
System start, 35, 48
– Load voltage, 10
– Operating voltage, 10 T
Power supply concept, 10 Target group, 5
Technical data, 51
R
Terminology, 53
Revision code, 50
Trace parameter, 41
Rules for set-up, 9
Types of parameters, 30
Run/stop filter 1, 41
Run/stop filter 2, 41

Festo – CPX-E-SYS-EN – 2017-07 – English 55


Copyright:
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany

Phone:
+49 711 347-0

Fax:
+49 711 347-2144

e-mail:
Reproduction, distribution or sale of this document or communication of service_international@festo.com
its contents to others without express authorization is prohibited. Offend­
ers will be liable for damages. All rights reserved in the event that a pat­ Internet:
ent, utility model or design patent is registered. www.festo.com

You might also like