INSTALLATION INSTRUCTION [Tir er 7 Cy-7 2
(commie) Flexible Sprinkler Hose Fittings
- diameter of the reducer needed. See equivalent length(in feet) of 1”
Introduction Table 1. Schedule 40 steel pipe.
Fire-fighting Flexible Sprinkler Hose . ; ;
Fittings are intended for direct Mai ppaEEOa ees Largest K factor of Sprinkler
connection (ofthe branch line) to the Ttsiiadinbe Catnmtad Oiittng?
hm sate wiggle Mima Ambient Temperatures. FS er
and U2" or 3/4” outlet reducer. Each 225°F(107.2°0) seaeeny
Flexible Sprinkler Hose Fittings
system installs easily and is designed Connection to Branch Line: ‘Table 2-Fretion Loss Data
to save costs and speed project 1" NPYBSPT m=] > pm]
letion. ‘
= ‘Minimum Bend Radius of Se erg ote coe
Ithasa merit of bending by hand for Flexible Tube: ¢° we yn [oe | | [ee
placement of sprinkler head at the Wet System and Dry = ae
desired location, and has a merit that it amet tee et
canbe tightly secured easily tothe ybjet-Syrinker Mexle Hos itings |e 0 za
ceiling grid(bar) by using wing nutand Model waese| 2 parse] 2
flange tapping screw of the side a 70 | ow “
brackets at both ends, for both general wese] 3 moss]
ceiling tile system and special os. 4° | ms =
construction of ceiling suspension vues] a rwose| 3
system as far as the ceiling grid(bar) ws #0 | ww ne
for supporting celing tiles are installed. mer] > | a, ws] | a,
Both general ceiling tile system and Lot | 28
special construction of ceiling rs a a
suspension system are for use with ~ =.
intermediate or heavy duty ceiling =
arids manufactured according to ASTM =
C635 and installed in accordance with
ASTM C636.
Fire-fighting sprinkler flexible hose ‘This is Flexible Sprinkler Hoses with
siti aré syailible i asin fittings having limited flexibility (to 100 ;
different lengths from 2.30feet to Gfeet, SYS) Installation
#° and” NPTIBSPT sprinkler head is ire
available. Sprinkler Hoses are UL Parts Included aaa ee
Listed and approved by the New York Each Flexible Sprinkler Hose Fitting set 3 in eSB 13, 13D or IBR
City MEA Department of Buildings. consists ofthe following parts:each SG BAN f
one-piece of stainless steel flexible tube Senso a ela govern!
and reducer and 1" nipple ready to ee baapags
‘mount to branch line; and the assembly A"Y ae ee
. of one square tube, two side brackets quirement or st ESaDY,
Technical Data hes bniead dat eoe sine Aten comply with the ;
Product Identification Ahan 0 Ce ack eoeiein aston nie
Fire-fighting flexible sprinkler hose Which fix the reducer to the square tube. ayant een.
fittings are available in different i ae
models, depending on the length of the FrictionLossData =
getllekicscinipple and outlet: ‘Table 2 shows the hydraulic friction
Joss expressed in terms of the average‘Step 1: Connect the 1” nipple to the
branch line using the NPT/BSPT
tapered threads of the nipple.
Figure 1. Apply anon hardening
pipe joint compound or Teflon tape to
the NPT/BSPT male threads of the
nipple. Tighten firmly with pipe
wrench for leak proof connection,
(Torque 99-95N.m)
Step 2: Connect sprinkler hose to
nipple. Figure 2.
Do not use joint compound or Teflon
‘tape on the fine PF threads of the
nipple. ‘The nut on the end of the
flexible tube contains a gasket which
provides the leak proof connection.
‘The connection is designed so that the
gasket achieves the proper amount of
compression by tightening the nut(nut
torque 20N.m.) until the end of fine
thread on the nipple, as the thread is
limited thread.
Step 3: Attach the side brackets to the
rails of the suspended ceiling and the
square bar using the setscrews.
(Gorque 3Nm.)
Step 4: Attach the reducer to the square
tube using the center bracket. The
reducer can be adjusted vertically by
raising or lowering the reducer and
center bracket can be adjusted from side
to side before tightening the bracket
setscrews. (Torque is 4Nm.)
Step 5: Connect sprinkler head to
reducer. Apply a nonhardening pipe
joint compound or Teflon tape to the
male threads of the sprinkler head
‘and connect with nut to the reducer
according to the sprinkler head
~ manufacturer's instructions, using
a special wrench supplied by the head
manufacturer. Figure 3.
After installation is completed, test
the sprinkler system for leaks pursuant
to NFPA Guidelines.
Warranty
‘This Fire-Fighting Sprinkler
Flexible Hose Fittings are designed
to meet high quality and durability
standards, and warrants to the
original purchaser that its products
are free from defects in materials
and workmanship according to this
installation instruction and use for
a period of two years from the date
of sale by us. This warranty does.
not apply to damage due directly or
indirectly to misuse, abuse, or
negligence, and does not apply to
products that have been installed,
used or maintained in a manner
‘contrary to our recommendations
or instructions.
‘To take advantage of this
warrafity, the product or part must
be returned to us. This warranty
onlyextends to the original
purchaser, and may not be
assigned. Proof of purchase date
and an explanation of the
complaint with photo of job site
‘must aeeompany the defect
‘merchandise. If we verify the
defectand determine that the
product is covered by this
warranty, we will either repair or
replace the product at our election,
or we may elect to refund the
purchase price. (Floss occurs to
the consumer due to our fault, that
loss would also be compensated.)
We will return repaired products at
our expense, but if we determine
that the defect resulted from
causes;notwithin the scope of our
warranty, then we are not liable for
warranty.
‘THIS WARRANTY IS IN LIEU OF
ALL IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED
‘TO WARRANTIES OF
MERCHANTABILITY AND.
WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE,
WE SHALL NOT BE
PESPONSIBLE FOR ANY
INCIDENTAL OR
CONSEQUENTIAL DAMAGES,
WHETHER ARISING FROM ANY
BREACH OF THIS LIMITED
WARRANTY OR ARISING OUT OF
‘THE SALE OF, USE OF, OR
DEFECT IN ANY OF OUR.
PRODUCTS. This warranty gives
you specific legal rights, and you
may also have other rights which
vary from state to state.
Our products are insured for
products/eompleted operations
liability insurance.
NO Flexible tube should not be
bent or fluctuated up and down
or side to side, when itis
pressurized for test.
4® Flexible tube should not be
bent within 2% inches of
connection nut at both ends..