Professional Documents
Culture Documents
Manual
WARNING
The power supply cable must be connected directly to the battery or to a regulated
feeder.
! If it is not the case, DG is not responsible for damages to the micro computer..
Disconnect the power supply cable from the micro computer when the battery is
! undergoing recharge.
If it is not the case, DG is not responsible for damages to the micro computer.
Disconnect all lines from the local plant before undertaking welding on the lorry.
! If it is not the case, DG is not responsible for damages to the micro computer.
For a correct functioning, please make sure that the battery has always a higher
! voltage than 10,5 Volt.
Before cleaning the machine with jets of water under high pressure, protect the
equipment from possible ingress of water. In addition, take great care not to subject
! the indicator, load cell, junction box, audible alarm, cables or any options to direct jets
of water.
If the equipment needs to be cleaned, use a soft, damp, lint-free cloth. Never use
! sprays, solvents, abrasives, or sharp or pointed objects that could damage the
indicator
1
INDEX
WARNING...........................................................................................................................................................1
INDEX .................................................................................................................................................................2
1 GENERAL DESCRIPTION ......................................................................................................................3
2 GENERAL CONNECTION SCHEME ......................................................................................................3
3 MOTORS CONNECTION SCHEME .......................................................................................................4
4 TECHNICAL FEATURES ........................................................................................................................5
4.1 ELECTRONIC FEATURES OF THE RELAYS CONTACT..................................................................5
5 NOTES FOR INSTALLATION .................................................................................................................5
6 CONFIGURATION...................................................................................................................................6
6.1 CONFIGURATION OF THE BOARD ...................................................................................................7
6.2 SETTING MODE JUMPERS (CN17) ...................................................................................................8
6.2.1 Address configuration ...................................................................................................................8
6.2.2 Configuration outputs management..............................................................................................8
6.3 SETTING CONFIGURATION JUMPERS ............................................................................................9
6.3.1 Configuration BANK 0 INPUT .......................................................................................................9
6.3.2 Configuration BANK 1 INPUT .......................................................................................................9
6.4 SETTING CONTACT JUMPERS ...................................................................................................... 10
7 FUNCTIONING ..................................................................................................................................... 11
7.1 USING THE SERVICE OUTPUTS.................................................................................................... 11
7.2 USING THE OUTPUTS IN FUNCTION OF COMPONENTS ........................................................... 12
7.2.1 16 Loading Components............................................................................................................ 12
7.2.2 8 Loading Components + 8 Loading Components Pre-alarms ................................................. 13
7.3 USING OUTPUTS IN FUNCTION OF UNLODING POINTS............................................................ 14
7.3.1 16 Unloading Points................................................................................................................... 14
7.3.2 8 Unloading Points + 8 Unloading Points Pre-alarms ............................................................... 15
7.4 USING OUTPUTS IN SPECIAL CONFIGURATIONS ...................................................................... 16
7.4.1 8 Loading Components + 8 Service Outputs............................................................................. 16
7.4.2 8 Service Outputs + 8 Unloading Points .................................................................................... 17
7.4.3 8 Loading Components + 8 Unloading Points ........................................................................... 18
8 COMPLIANCE CLAIM .......................................................................................................................... 19
9 GUARANTEE........................................................................................................................................ 20
2
1 GENERAL DESCRIPTION
The complete system is composed by the weighing microcomputer Top Scale, having 99 loading programs
(24 components/ingredients for each program) and 48 unloading programs (48 elements for each program),
and by the BOX MOTOR DRIVER.
The BOX MOTOR DRIVER system contains the boards for the control of the OUTS that drive the relays.
Every relay is independent and places at disposition a contact which is normally open (or closed) for the
driving of the control devices of the power system. In parallel to the coil of every relay, a LED is available to
highlight when the relay is operative
The weighing microcomputer Top Scale in combination with the kit Motor control gives the possibility to
have a serie of relays contacts activated by components and/or by the unloading point of execution
programs. With these contacts it’s possible to drive a motor obtaining in this way the automatic start of
functions like the opening of a door, the movement of a belt and so on.
All relays are independent, and gives a contact normally opened (or closed).
In parallel to the coil of every relays a LED is available and shows when the driving is activated.
3
4
Relay Motor 1
Relay Motor 2
Relay Motor 3
Relay Motor 4
Relay Motor 5
BANK 0 OUTPUTS
Relay Motor 6
Relay Motor 7
Relay Motor 8
Relay MOTOR 1
Max 125 Volts, 2A
Relè
Inside box
Maximum current: 2 A
Relay Motor 9
Relay Motor 13
∼
BANK 1 OUTPUTS
Relay Motor 14
3 MOTORS CONNECTION SCHEME
relay
Relay Motor 15
Power
MOTOR 1
Relay Motor 16
4 TECHNICAL FEATURES
Weighing system TOP SCALE: see Top Scale manual
ATTENTION: if the external circuit exceeds these characteristics Dinamica Generale declines every
responsibility for malfunctions or damages of this device.
5
6 CONFIGURATION
Every box is composed by 2 outputs banks which control 8 relays each, for a total of 16 outputs per
each box.
Every output bank can be programmed in only one the following options:
8 service outputs
Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Relay 8
Closed Closed Closed Closed Closed Closed Closed Closed
Alarm in Pre-alarm Always During the Always free free free
Partial in Partial during a mixing time during an
weighing weighing load unload
execution execution
8 loading components
Comp. 1 Comp. 2 Comp. 3 Comp. # Comp. 8
Execution Execution Execution Execution Execution
Relay 1 ON up to Relay 2 ON up to Relay 3 ON up to Relay # ON up to Relay 8 ON up to
the weight is 0 the weight is 0 the weight is 0 the weight is 0 the weight is 0
8 unloading points
Same logic of the component but referred to the unloading points
The banks are set independently one from the other and cannot have crossed outputs (4 load and 4
unload, 6 load and 2 unload, etc…)
6
6.1 CONFIGURATION OF THE BOARD
CONTACT JUMPERS
MODE JUMPERS
IN7 IN7
CONFIGURATION JUMPERS
7
6.2 SETTING MODE JUMPERS (CN17)
The Motors Control board to communicate with the TOP SCALE must be set on the same address that on
the scale is defined by the parameter “Handy Address” while on the Motors Control board is set through PIN
1-6 of the MODE JUMPERS according to the following table:
ADDRESS
PIN 1-2 PIN 3-4 PIN 5-6
(Parameter “Handy Address” value on TOP SCALE)
OPEN OPEN OPEN 0
SHORT OPEN OPEN 1
OPEN SHORT OPEN 2
SHORT SHORT OPEN 3
OPEN OPEN SHORT 4
SHORT OPEN SHORT 5
OPEN SHORT SHORT 6
SHORT SHORT SHORT 7
The outputs of the Motors Control board can be driven by the load components, by the unloading points or
as service outputs. The configuration is through PIN 7-14 of the MODE JUMPERS according to the following
table:
8
6.3 SETTING CONFIGURATION JUMPERS
The first input group is used in case it’s necessary to have the outputs driven by the pre-alarm signal of
components/unloading points (signal active according to the percentage of intervention posed in parameter
“Alarm threshold%” of the scale).
Outputs set in pre-alarm functioning will be active during the intermittent sound of the alarm.
Configuration is through PIN 0-1 while PIN 2-7 aren’t used.
* the pre-alarm management is NOT enabled, obviously, if outputs are set in SERVICE but is
enabled only if outputs have been programmed in LOAD or UNLOAD
The second input group is used to indicate to which components/unloading points must be referred the
outputs.
Through PIN 0-3 is set the management of outputs of BANK 0, with PIN 4-7 is set the management of
outputs of BANK 1
9
IDENTIFICATION OF COMPONENTS / UNLOADING POINTS
IN7 IN6 IN5 IN4
IN BANK 1 OUTPUTS
OPEN OPEN OPEN OPEN Outputs driven by components / unloading points 1-8
OPEN OPEN OPEN SHORT Outputs driven by components / unloading points 9-16
OPEN OPEN SHORT OPEN Outputs driven by components / unloading points 17-24
OPEN OPEN SHORT SHORT Outputs driven by components / unloading points 25-32
OPEN SHORT OPEN OPEN Outputs driven by components / unloading points 33-40
OPEN SHORT OPEN SHORT Outputs driven by components / unloading points 41-48
OPEN SHORT SHORT OPEN Outputs driven by components 49-56
OPEN SHORT SHORT SHORT Outputs driven by components 57-64
SHORT OPEN OPEN OPEN Outputs driven by components 65-72
SHORT OPEN SHORT OPEN Outputs driven by components 73-80
SHORT OPEN OPEN SHORT Outputs driven by components 81-88
SHORT OPEN SHORT SHORT Outputs driven by components 89-96
SHORT SHORT OPEN OPEN Outputs driven by components 97-99
PIN 1-2 SHORT Contact NO. Activating the component / loading point the contact closes.
PIN 2-3 SHORT Contact NC. Activating the component / loading point the contact opens.
PIN 1-3 SHORT NOT POSSIBLE.
Outputs can be set independently one from each other, since on the board there is a CONTACT JUMPER
for each output relay.
10
7 FUNCTIONING
7.1 USING THE SERVICE OUTPUTS
To set the outputs as service outputs:
11
7.2 USING THE OUTPUTS IN FUNCTION OF COMPONENTS
7.2.1 16 Loading Components
Considering of driving the outputs according to the loading components, thinking to have for each loading
program up to 16 components each, it’s necessary to have:
Short-circuit PIN 7 and 8 and open PIN 9 and 10 of MODE JUMPERS (see 6.2)
Short-circuit PIN 11 and 12 and open PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way both the output banks are driven from the components of the loading programs.
Considering a loading program composed by 16 components from 1 to 16, with the first 8 we drive the BANK
0 Outputs and with the other the BANK 1 Outputs, to do this we have to configure the CONFIGURATION
JUMPERS in the following way:
Relay Motor 11
Relay Motor 12
Relay Motor 13
Relay Motor 14
Relay Motor 15
Relay Motor 16
Relay Motor 1
Relay Motor 2
Relay Motor 3
Relay Motor 4
Relay Motor 5
Relay Motor 6
Relay Motor 7
Relay Motor 8
Relay Motor 9
12
7.2.2 8 Loading Components + 8 Loading Components Pre-alarms
Considering of driving the outputs according to the loading components, and controlling also pre-alarms for
each component, it’s necessary to have:
Short-circuit PIN 7 and 8 and open PIN 9 and 10 of MODE JUMPERS (see 6.2)
Short-circuit PIN 11 and 12 and open PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way both the output banks are driven by the components of the load programs
Considering a loading program composed by 8 components that drive the BANK 0 Outputs and all the pre-
alarm phases of these components that drive the BANK 1 Outputs, to do this we have to configure the
CONFIGURATION JUMPERS in the following way:
Example:
Component 1 set at 200 Kg
Parameter Alarm Threshold% set at 10
Enter the recipe, activating component 1 relay 1 of BANK 0 activates (correspondent led on), the weight
starts from 200 and charging the material, the weight on the display decreases.
When the weight on the display reaches 20 Kg (10% of 200 Kg) automatically the relay 1 of BANK 1
activates (correspondent led on) and the relay 1 of BANK 0 deactivates (correspondent led off).
The same procedure will be applied to all components.
13
7.3 USING OUTPUTS IN FUNCTION OF UNLODING POINTS
7.3.1 16 Unloading Points
Considering of driving the outputs according to the unloading points, thinking to have for each unloading
program up to 16 unloading points each, it’s necessary to have:
Open PIN 7 and 8 and short-circuit PIN 9 and 10 of MODE JUMPERS (see 6.2)
Open PIN 11 and 12 and short-circuit PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way both the output banks are driven by the unloading points of the correspondent
unloading programs
Considering the unloading program composed by 16 unloading points, from 1 to 8 we drive the BANK 0
Outputs and with the others the BANK 1 Outputs; to do this we have to configure the CONFIGURATION
JUMPERS in the following way:
Relay Motor 11
Relay Motor 12
Relay Motor 13
Relay Motor 14
Relay Motor 15
Relay Motor 16
Relay Motor 1
Relay Motor 2
Relay Motor 3
Relay Motor 4
Relay Motor 5
Relay Motor 6
Relay Motor 7
Relay Motor 8
Relay Motor 9
14
7.3.2 8 Unloading Points + 8 Unloading Points Pre-alarms
Considering of driving the outputs according to the unloading points, and controlling also pre-alarms for each
unloading point, it’s necessary to have:
Open PIN 7 and 8 and short-circuit PIN 9 and 10 of MODE JUMPERS (see 6.2)
Open PIN 11 and 12 and short-circuit PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way both the output banks are driven by the unloading points of the correspondent
unloading programs
Considering the unloading program composed by 8 unloading points that drive the BANK 0 Outputs, and all
the pre-alarm phases of these unloading points that drive the BANK 1 Outputs; to do this we have to
configure the CONFIGURATION JUMPERS in the following way:
Example:
Unloading point 1 set at 200 Kg
Parameter Alarm Threshold% set at 10
Enter the unloading program, activating unloading point 1 relay 1 of BANK 0 activates (correspondent led
on), the weight starts from 200 and unloading the material the weight on the display decreases.
When the weight on the display reaches 20 Kg (10% of 200 Kg) automatically the relay 1 of BANK 1
activates (correspondent led on) and the relay 1 of BANK 0 deactivates (correspondent led off).
The same procedure will be applied to all unloading points.
15
7.4 USING OUTPUTS IN SPECIAL CONFIGURATIONS
Considering of driving outputs in function of components, thinking to have for each loading program up to 8
components each, but using also a bank for service outputs, it’s necessary to have:
Short-circuit PIN 7 and 8 and open PIN 9 and 10 of MODE JUMPERS (see 6.2)
Short-circuit PIN 11 and 12 and short-circuit PIN 13and 14 of MODE JUMPERS (see 6.2)
In this way BANK 0 is driven by components of loading programs, and BANK 1 is managed as
service outputs.
Considering the loading program composed by 8 components, with these it’s possible to drive the BANK 0
Outputs, and BANK 1 Outputs are managed as service outputs; to do this we have to configure the
CONFIGURATION JUMPERS in the following way:
16
7.4.2 8 Service Outputs + 8 Unloading Points
Considering of using a bank for service outputs and of driving a bank output in function of unloading points,
thinking to have for each unloading program up to 8 unloading point each, it’s necessary to have:
Short-circuit PIN 7 and 8 and short-circuit PIN 9 and 10 of MODE JUMPERS (see 6.2)
Open PIN 11 and 12 and short-circuit PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way BANK 0 is managed as service outputs and BANK 1 is driven by the unloading points
of the unloading programs.
Considering the unloading program composed by 8 unloading points, with these it’s possible to drive the
BANK 1 Outputs, and BANK 0 Outputs are managed as service outputs; to do this we have to configure the
CONFIGURATION JUMPERS in the following way:
17
7.4.3 8 Loading Components + 8 Unloading Points
Considering of driving outputs in function both of components and of unloading points, driving BANK 0 with
components and BANK 1 with unloading points it’s necessary to have:
Short-circuit PIN 7 and 8 and open PIN 9 and 10 of MODE JUMPERS (see 6.2)
Open PIN 11 and 12 and short-circuit PIN 13 and 14 of MODE JUMPERS (see 6.2)
In this way BANK 0 is driven by components and BANK 1 is driven by unloading points
Considering that the recipe is composed by 8 components that drive BANK 0 Outputs and that the unloading
program is composed by 8 unloading points that drive the BANK 1 outputs; to do this we have to configure
the CONFIGURATION JUMPERS in the following way:
Relay Motor 11
Relay Motor 12
Relay Motor 13
Relay Motor 14
Relay Motor 15
Relay Motor 16
Relay Motor 1
Relay Motor 2
Relay Motor 3
Relay Motor 4
Relay Motor 5
Relay Motor 6
Relay Motor 7
Relay Motor 8
Relay Motor 9
18
8 COMPLIANCE CLAIM
Dinamica Generale s.r.l Tel. ++39 - 0386 - 52134
Via Mondatori, 15 Fax. ++39 - 0386 - 51523
46025, Poggio Rusco (MN) Italy E-mail: info@dinamicagenerale.com
MODELLO:
MOTORS CONTROL KIT
Model:
DESCRIZIONE: Sistema di automazione
Description: Automation system
19
9 GUARANTEE
The supplier guarantees, for 24 months from the delivery date, the good quality of materials used, the
excellent construction and the steady functioning of the instrument they have manufactured and that bears
the trademark or the production serial number. During the guarantee period the supplier undertakes to repair
or replace, free supplier’s head office, faulty parts due to poor materials or faulty construction, provided that
such parts are delivered free port supplier’s head office.
Shortcomings and defects due to incorrect use of instruments, inadequate maintenance, changes carried out
without the supplier’s approval, normal wear are not included in this guarantee.
Liability and compensations by the supplier due to direct or indirect damages to persons, objects or
production, even as a consequence of faulty functioning of the supplied instruments or of material or
construction defects, are not included in this guarantee.
NOTES:
MotorsControl_Man_RevB2_2Ing.doc
20