FM EXGas HazardPoster
Division 1, Groups A, B, C, D T5
IEC classification per IEC 60079-10-1
Ex eb EU EPL Gb EN IEC 60079-7 EU classification per EN 60079-10-1
US classification per ANSI/NFPA 70 National Electrical Code® (NEC®) Article 500 or Article 505
Ex eb IEC EPL Gb IEC 60079-7 CA classification per CSA C22.1 Canadian Electrical Code (CE Code) Section 18 or Annex J
No arcs,
AEx ec US Class I, Zone 2 ANSI/UL 60079-7 sparks or
Permitted Division Temperature Class Ex ec CA Zone 2 CSA C22.2 No. 60079-7 hot surfaces
(optional except for Division 2)
Permitted Group
(T5 and T6 optional) Ex ec
Ex ec
EU
IEC
Category 3G
EPL Gc
EN IEC 60079-7
IEC 60079-7 Equipment Grouping
Non-Incendive (NI) US Class I, Division 2 FM 3611 US (NEC® 505)
Ambient temperature ranges other than standard (-25°C ≤ Ta ≤ +40°C) must be marked.
(NI) CA Class I, Division 2 CSA C22.2 No. 213 CA (CE Code Section 18)
US (NEC® 505) Explosionproof (XP)
(XP)
US
CA
Class I, Division 1
Class I, Division 1
FM 3615
CSA C22.2 No. 30
EU US (NEC® 500)
American Typical gas IEC CA (CE Code Annex J18)
National Standard
Flameproof AEx da US Class I, Zone 0 ANSI/UL 60079-1
Permitted Class Ex da CA Zone 0 CSA C22.2 No. 60079-1 Acetylene Group IIC Class I/Group A
Type of Equipment Protection Level
(optional) Protection (optional) Ex da EU Category 1G EN 60079-1 Hydrogen (Group IIB + H2) Class I/Group B
Ex da IEC EPL Ga IEC 60079-1
Ethylene Group IIB Class I/Group C
AEx db (or AEx d) US Class I, Zone 1 ANSI/UL 60079-1
Class I, Zone 1, AEx db [ia Ga] IIC T5 Gb Ex db (or Ex d) CA Zone 1 CSA C22.2 No. 60079-1 Contain
Propane Group IIA Class I/Group D
Ex db EN Category 2G EN 60079-1 the explosion Methane Group I* Mining*
Explosion-Protected Gas Group Ex db IEC EPL Gb IEC 60079-1 and extinguish
*Not within scope of NEC . Under jurisdiction of MSHA. Not within scope of CE Code.
®
2809 II 2(1) G Ex ic
Ex ic
EU
IEC
Category 3G
EPL Gc
EN 60079-11
IEC 60079-11
120°C T4A
Note 1: For associated intrinsically safe apparatus suitable for installation in a hazardous location, the symbols for the type of protection
100°C T5 T5
“ia” or “ib” are enclosed within square brackets (e.g., Class I, Zone 1 AEx db [ia Ga] IIC T4 Gb).
85°C T6 T6
Identification Number of Notified Body Category for I.S. Output Note 2: For associated intrinsically safe apparatus not suitable for installation in a hazardous location, both the symbol “Ex” or “AEx” and
the symbol for the type of protection “ia”, “ib” or “ic” are enclosed within the same square brackets (e.g., [AEx ia Ga]); in this case, a temperature
Involved in Production Control Stage Category class is not included.
EPL/Category
Type Z CA Class I, Division 2 NFPA 496
Protection against solid bodies Protection against liquid
AEx pxb (or AEx px) US Class I, Zone 1 ANSI/UL 60079-2
Ex pxb (or Ex px) CA Zone 1 CSA C22.2 No. 60079-2 0 No protection No protection
IEC EU (ATEX) Typical Zone Ex pxb EU Category 2G EN 60079-2
Definition 1 Objects greater than 50mm Vertical (90˚) dripping water
EPL Group Category Group of Application Ex pxb IEC EPL Gb IEC 60079-2
AEx pyb (or AEx py) US Class I, Zone 1 ANSI/UL 60079-2 2 Objects greater than 12mm 75˚ to 90˚ dripping water
Mines, “very high”
Ma M1 Ex pyb (or Ex py) CA Zone 1 CSA C22.2 No. 60079-2 3 Objects greater than 2.5mm Sprayed water
level of protection
I I N/A Ex pyb EU Category 2G EN 60079-2
Mines, “high”
Mb M2 Ex pyb IEC EPL Gb IEC 60079-2 4 Objects greater than 1mm Splashed water
level of protection
AEx pzc (or AEx pz) US Class I, Zone 2 ANSI/UL 60079-2 5 Dust-protected Water jets
Gas atmospheres, Ex pzc (or Ex pz) CA Zone 2 CSA C22.2 No. 60079-2
“very high” level Ga 1G 0 Ex pzc EU Category 3G EN 60079-2
6 Dust-tight Heavy seas
of protection 7 Temporary immersion
Ex pzc IEC EPL Gc IEC 60079-2
Gas atmospheres,
“high” level of Gb II 2G II 1
Note 3: For associated equipment used with pressurized equipment, such as a pressurization control system installed within the hazardous
location, the symbol for the Type of Protection is enclosed within brackets (e.g., Ex db [pxb] IIC T4 Gb).
8 Continuous immersion
protection Note 4: The associated equipment not suitable for installation in a hazardous location, both the symbol “Ex” or “AEx” and the symbol “pxb”
9 High pressure/temperature water jet
are enclosed within the same square brackets (e.g., [AEx pxb Gb]). In this case, a temperature class is not included.
Gas atmospheres,
“enhanced” level Gc 3G 2 Restricted Breathing AEx nR US Class I, Zone 2 ANSI/UL 60079-15
Keep
of protection Ex nR CA Zone 2 CSA C22.2 No. 60079-15 flammable Approximate US enclosure type equivalent to IPXX
Level of protection assigned to equipment based on its likelihood of becoming a source Ex nR EU Category 3G EN IEC 60079-15 gas out
of ignition Ex nR IEC EPL Gc IEC 60079-15 Type IP Type IP Type IP
Encapsulation AEx ma US Class I, Zone 0 ANSI/UL 60079-18
1 10 3S 54 6 and 6P 67
Ex ma CA Zone 0 CSA C22.2 No. 60079-18
FM Approvals is your global Ex ma
Ex ma
EU
IEC
Category 1G
EPL Ga
EN 60079-18
IEC 60079-18
2 11 4 and 4X 55 12 and 12K 52
Ex mc EU Category 3G EN 60079-18
Ex mc IEC EPL Gc IEC 60079-18
Canada C C US ATEX Atmosphère explosible
Sealed Device AEx nC US Class I, Zone 2 ANSI/UL 60079-15
Ex nC CA Zone 2 CSA C22.2 No. 60079-15 CA Canada
EU (ATEX) Ex nC EU Category 3G EN IEC 60079-15 CE Code Canadian Electrical Code (CSA C22.1)
FM Approvals can also issue IECEx Test Reports, Quality Assessment Reports and Ex nC IEC EPL Gc IEC 60079-15 EPL Equipment Protection Level
Certificates of Conformity.
Liquid Immersion AEx ob (or AEx o) US Class I, Zone 1 ANSI/UL 60079-6 EU European Union
Ex ob CA Zone 1 CSA C22.2 No. 60079-6
Ex ob EU Category 2G EN 60079-6 IEC International Electrotechnical Commission
FM Approvals Ex ob IEC EPL Gb IEC 60079-6 I.S. Intrinsic Safety
1151 Boston-Providence Turnpike, Norwood, MA, US 02062-9102 AEx oc US Class I, Zone 2 ANSI/UL No. 60079-6
Phone: +1 (1)781 255 4851 Fax: +1 (1)781 762 9375
MSHA Mine Safety and Health Administration
Ex oc CA Zone 2 CSA No. 60079-6
E-mail: information@fmapprovals.com Ex oc EN Category 3G EN 60079-6 NFPA National Fire Protection Association
In Europe, FM Approvals Europe Limited Ex oc IEC EPL Gc IEC 60079-6 NEC® National Electrical Code® (NFPA 70)