CURRENT TRANSFORMER PRIMARY INJECTION

Customer Scilife Plant MV Room


Plant 11kV Incoming Panel 10-04-2021
Identificatio Date
n

Technical Data

Circuit breaker VCB


Rated voltage: 11kV
MV
S.NO C.B. Serial Number
Switch Gear
(##) (Panel Name) 11kV Incoming Panel

Primary Injection Test of CTs and Circuit Verification and Ratio Test

Available ratio: 100/5

Primary Measured Current


Sr No. Phase Injected Protection Metering
Current (A) Core-1 Core-2
30 30.4 30.3
1 R-N
30.5 30.6
30 30.1 30.3
2 Y-N
30.5 30.6
30 30.2 30.3
3 B-N
30.4 30.6
4 R-Y 30 30.3 30.1
5 R-B 30 30.5 30.2
6 Y-B 30 30.5 30.7
Check current in neutral point during phase to phase injection (Comments)
Test Instrument Type Current Injector
Make Megger
Model Severker 760
Remarks:

Page 1 of 2
CURRENT TRANSFORMER PRIMARY INJECTION

Since CT Ratio comply with the name plate data. Hence results found satisfactory

ENEGIX ENGINEERING Client

Sign: Sign:

Name: Name:

Desg: Desg:

Date: Date:

Page 2 of 2