Professional Documents
Culture Documents
• 24 V DC operating voltage
• Dual-channel system with electronic self-
monitoring
• LED bar flame intensity indicator and
4 (0) ... 20 mA measuring output
• Selectable trend indicator allowing opti-
mum adjustment to the flame direction
-2-
8 Guarantee and delivery terms.................................................................................. 23
9 Layout of the operational controls .......................................................................... 24
9.1 F 200 K1 … (in the state as delivered)..................................................................................................... 24
9.2 F 200 K2 … (Ex-proof), (in the state as delivered) .................................................................................. 25
10 Dimensional drawings .............................................................................................. 26
10.1 F 200 K … and F 200 K Compact Flame Detectors... Z2 (hazardous area II)......................................... 26
10.2 F 200 K2 … Compact Flame Detector Ex (hazardous area I) ................................................................. 27
10.3 Connection housing FG 24 Ex ................................................................................................................. 27
11 Pin configuration....................................................................................................... 28
11.1 F 200 K1 … .............................................................................................................................................. 28
11.2 F 200 K2 ... (Ex) ....................................................................................................................................... 29
12 Examples of application ........................................................................................... 30
12.1 Interconnection with Etamatic .................................................................................................................. 30
12.2 Interconnection with FMS......................................................................................................................... 30
13 Accessories ............................................................................................................... 31
13.1 FN 20 mains supply unit........................................................................................................................... 31
13.1.1 Purpose .................................................................................................................................................... 33
13.1.2 Technical parameters............................................................................................................................... 33
13.1.3 Pin configuration....................................................................................................................................... 35
13.2 Adjustable holding devices....................................................................................................................... 36
13.2.1 FS 19-10 (for IR and UV, without ball-and socket-joint, with purge air connection) ................................ 38
13.2.2 FS 20-10 (for IR and UV, with ball-and socket-joint and purge air connection)....................................... 38
13.2.3 FV 19-10 (for IR and UV, without socket-and-ball-joint, with purge air connection) ................................ 39
13.2.4 FV 20-10 (for IR and UV, with ball-and-socket-joint and purge air connection)....................................... 39
13.2.5 FS 50 (without ball-and-socket-joint and cooling air housing) ................................................................. 40
13.2.6 FS 51 (with ball-and-socket joint and cooling air housing)....................................................................... 41
13.3 Installation in the cooling air housing ....................................................................................................... 40
14 EG Certificate of Conformity .................................................................................... 41
15 EC Prototype testing certificate............................................................................... 42
16 TÜV Certificate .......................................................................................................... 43
-3-
1 General remarks
-4-
2 Safety instructions
This operator manual uses the following symbols to mark important safety instructions
to be complied with by the user. In the following sections, this symbols appear in texts
at places where the information is required. Make sure to comply with these safety in-
structions, in particular note the warnings.
WARNING
marks possible risks for persons, especially emanating from electrical equipment.
WARNING
makes reference to possible risks for persons if system components are handled im-
properly.
CAUTION!
makes reference to dangers for system components or to a possible deterioration of
the equipment's operability.
NOTE:
comprises additional information of importance for the user on the system or system
components, and provides additional hints.
-5-
3 Operating instructions
3.1 Application
These operating instruction apply to the F 200 K compact flame detector.
The devices comply with the following standards and rules:
DIN EN 230
DIN EN 298
DIN VDE 0116
97/23/EG (directive on pressurised equipment)
90/396/EWG (directive on gas equipment)
DIN EN 60730, part 1 and IEC 801, part 5 (leakage paths and sparking-distance in air
as well as interference susceptibility)
- OIL
- GAS
- BIO-MASS
- DUST COAL
- CHEMICALS AND OTHER WASTE PRODUCTS.
3.3 Design
The compact-type flame detector is composed of a cylindrical casing comprising a
light incidence aperture that is in line with the axis a processing status indicator on its
rear side as well as operational controls, which can be accessed there when removing
the cover.
When closed the flame detector complies with the requirements of IP 67 protection
degree.
The detector is installed at the burner by optionally using the FS 19, FV 19, FS 20, FV
20 adjustable holding devices or with an air-cooled housing of the FS 50 or FS 51
types.
The device is connected through an integrated standard plug and using the a connec-
tion cable required for this (8 pins, static screen,
cable type LiYCY 8x1x0,5 mm²) with coupler.
-6-
The cable provides for the following connections:
The compact flame detector converts the flame radiation pulses of the burner flame
into electrical signals. These representative signals are routed to an electronic
changeover switch, which alternately applies them to one of the independently work-
ing processing channels, where the signals are digitised. This reduces the initial signal
quantity to the information "pulse period" (information carrier: pulse frequency of the
flame radiation). The digitised signals are compared with the related reference signals
by means of a digital frequency evaluation unit. This makes sure that only those flame
signals that are within the pre-selected frequency transmission range will be included
in a continued processing, irrespective of their original amplitude. A control switch (for
the F 200 K2 only) located below the removable cover allows to change the lower fre-
quency limit if required. After evaluation, the flame signal is routed to the switching
amplifier, which also controls the related shut-down time. A safe monitoring of the
antivalent control states as well as the response and shut-down periods is performed
at the output of the signal processing channels, before an activation of the output re-
lays at the end of each signal processing channel is carried out. Antivalence faults and
deviation in time delays going beyond the admissible limit values result in the control
state "Flame out". The control states “Flame out“ and “Flame in“ are indicated on the
rear side of the device by means of a red and/or green LED, the change-over between
the two signal processing channels being indicated by pulsation of the green LED dur-
ing the “Flame in“ control state. Moreover, one or two six-step control switches provide
for a sensitivity adjustment to adapt the system to the flames to be monitored, this be-
ing indicated by means of a six-step chain of green LEDs designed to be the device's
flame intensity indicator.
Miscellaneous
Self-monitoring principle
Signal processing is carried out by means of two transmission channels working inde-
pendently of each other and alternately triggered. The output levels are permanently
checked for antivalence within a given time grid.
The turning knob controls of the F 200 K1 / F 200 K2 compact flame detectors allow to
set 6 to 12 sensitivity levels, the F 200 K version providing an increased sensitivity
level in range II. A six-step green LED indicator indicates the evaluated flame intensity
on the rear side of the device. The transmission range of the digital flame frequency
evaluation allows for signal passage between10 ... 190 Hz (F 200 K1) and/or 10 / 30 /
45 ... 190 Hz (F 200 K2).
-7-
3.5 Basic circuit diagram
Flame sensor
Detector
Switch-over
contact
Stabilisation
UB Cycle
7...1 7...1
1...6 1...6
2 2
Channel A Channel B
Sensitivity
selector switch
0/4...20mA
Intensity remote Visual intensity
indicator indicator
GND
GND GND
cycl
Self- e
monitoring
Monitoring
Output relay cycle
Output
contacts
-8-
4 Technical parameters
4.1 Characteristics
The compact flame detector is available in 2 basic versions, apart from an ex-proof enclosure type with several
spectral varieties (IR / UV).
Signals lying in the mains frequency range or its multiples are suppressed for 50 Hz
mains generally. For 60 Hz application, please indicate separately in your order form.
The related stop ranges are changed in factory. The compact flame detector is ac-
cordingly marked by a type plate.
- F 200 K1 UV-1 and F 200 K2 UV-1 (Ex) 260 ... 400 nm about 8°
- F 200 K1 UV-2 and F 200 K2 UV-2 (Ex) 210 ... 380 nm about 8°
- F 200 K1 IR-2 and F 200 K2 IR-2 (Ex) 850 … 1200 nm about 50°
- F 200 K1 IR-1 and F 200 K2 IR-1 (Ex) 1200 ... 2800 nm about 60°
Response sensitivity 25 mV AC
Output parameters
-9-
- admissible switching current 0.5 A maximally
10 mA minimally, at a limit
load of 50 mA
Dynamic characteristics
Taking into account the electrical basic conditions, it also possible to bridge major dis-
tances using smaller cable core sections. An important criterion is the compliance with
the supply voltage limits at the compact flame detector, and thus the voltage drop in
supply voltage coming through the supply line.
Technical stressability
Operating mode DB
Creepage distances and clearances DIN EN 60730 part 1
Interference susceptibility DIN EN 60730-1, EN 61000-4
Emitted interference DIN EN 55011/A1
The output contacts of the flame detector have no radio interference suppression. The
user is required to take the appropriate radio interference suppression measures on
the basis of the overall installation design. In order to ensure the required safety, carry
out the installation circuitry in such a way as to avoid shorting-out of the contacts by
defective components of the interference suppression unit.
Climatic stressability
Mass 0.6 kg
5 Selection criteria
- 11 -
6 Installation and assembly instructions
- is to be aligned in such a way as to cover the first third of the flame for single mo-
nitoring.
- has to cover the flame root area for a simple selection during the "Flame in" control
state (area of high flame frequencies), and during the "Flame out" state to only de-
tect the residual radiation caused by the "off-shoots" of the other flames in the
combustion chamber (area of low flame frequencies) or by reflection.
- If possible avoid to arrange the compact flame detector in parallel with the flame
axis, since in this position, a flame rupture can hardly be detected.
In order to reach a high availability and a high selection quality, it is very important to
place the compact flame detector at the appropriate location.
Make sure in every case that the aperture angle for the UV solutions is only about 8°.
That's why we recommend to use the FS 20 and/or FV20 adjustable holding device
(ball-and-socket joint), unless already in place. A correct alignment is of paramount
importance in particular in such cases where there is an additional viewing tube in-
side the burner or where the visibility of the flame is considerably restricted. The instal-
lation site must be easily accessible to allow a perfect observation of the visual opera-
tional controls even during operation of the furnace. When replacing the compact
flame detector, make sure to install a device having the same identification marking.
Make sure that the maximum admissible ambient temperature of 60 °C is not ex-
ceeded at the installation site. This applies in particular to radiant heat.
For the installation of an extension cable on site, make sure to use a separate,
shielded extensionable. Moreover, provide for good continuity of the shield and
make sure that the shield and functional earthing (FPE) are connected properly.
We recommend to lay the supply cable, including extension cable, on separate cable
trays to keep mains and control lines as well as high-energy power lines and equip-
ment separated from each other (e.g. ignition lines, ignition transformer, electrical mo-
tors, contactor). Moreover, avoid any parallel cable routing together with mains cables
in trays.
CAUTION!
Very high levels of electromagnetic radiated noise may result in sporadic problems in
flame detection, or may even avoid proper detection at all.
- 12 -
6.2 Installation
Output contacts
The flame detector ready for operation delivers the "Flame in" or "Flame out" status
message to a floating output contact. Further signal processing has to be carried out
by the controller adapted to the related furnace.
To guarantee a high safety level make sure when installing the output contacts to lay
out the circuitry of the radio interference suppression system to be provided by the
user in such a manner as to avoid shorting-out of the contacts due to faulty compo-
nents of the radio interference suppression unit.
Only potential-free devices may be connected complying with the requirements for
protective low voltage (SELV) (safe insulation according to DIN EN 50178).
- 13 -
7 Instructions on commissioning and maintenance
7.0.1 Intensity indicator including the “Adjust“ function / section 9.1 + 9.2, items 3 and 6
Intensity indication is effected by means of a roaming light dot in 6 levels. The indica-
tion is delayed in accordance with switch-off time (1s and/or 3s) and fulfils 2 functions.
The Adjust switch has to be in the ON position in any case. The function of the
Serv. switch is not active in this case. The direct flame signal is now shown at the
probe element without evaluation of the flame frequency. The Adjust function is
used to align the compact flame detector to the maximum of the flame radiation
using a ball-and-socket joint (refer to section 7.1.3). Normally, the display should
be in the green LED row. If the flame is stable, a reliable operation may be possible
in this function even if the two upper yellow LEDs light up. This display mode only
represents the trend of the orientation at a good accuracy, thus it is no exact
measuring device.
This display type only exists in the F 200 K2 execution type. The display shows the
sensitivity ranges I or II activated by external selection. The range I (normal sensitivity)
is mainly used for high flame intensities, while range II (higher sensitivity) is used for
weaker flame intensities.
The red LED shows the Flame OUT operating state, the green LED showing the
Flame IN state. In the “Flame in“ state, the green LED shows a pulsating intensity at
the rhythm of the self-monitoring cycle (1.5 s and/or 3 s). If the green LED is not pul-
sating, this may be due to a e.g. excessive interference radiation (EMV) or to a defect
of the compact flame detector. (refer to 7.1.2 and 7.2)
- 14 -
7.0.4 Sensitivity – Switch/ sections 9.1 + 9.2, items 4 and 5
Depending on the solution type (F 200 K1 or F 200 K2), there are 1 or 2 sensitivity se-
lector switches. The sensitivity selector switches can be set in 6 steps. The switches
serve to adapt the device to the existing flame intensity. (refer to 7.1.3)
The Serv. service switch serves to suppress the indication during start-up and star-
ting time of the flame detector. In the state as delivered, the Serv. is in the ON posi-
tion. This function does not display any short flame signals of other radiation sources
(e.g. adjacent burners or background fire), which are not to result in a switch-on of the
flame detector.
For commissioning it is recommendable to set the Serv. switch to OFF. Short
flame signal of other sources are thus indicated even during the start-up phase. This
information is important for a probably required change of the start-up suppression
setting (refer to 7.1.3).
The Adjust switch serves to feed in the unevaluated flame intensity (direct signal at
the probe element) on the intensity display of the compact flame detector. The activa-
tion of the Adjust switch (ON position) suppresses the function of the Serv. switch
(refer to 7.1.3).
The potentiometer serves to vary the setting of the start-up (switch-on) behaviour of
the flame detector. This setting has an influence on the switch-on behaviour of the
flame detector with regard to the flame to be monitored. (refer to 7.1.3)
These measuring points serve to directly measure the flame signals at the probe ele-
ment and can be used to determine the optimal alignment, apart from intensity indica-
tion. (refer to 7.1.3).
- 15 -
7.1 Commissioning
Check the compact flame detector for correct positioning on the burner. Before switch-
ing on the supply voltage, check the connections on the basis of the pin configuration as
specified herein. Refer to section 12.
The switches of the compact flame detector as delivered are set according to section
10, unless otherwise agreed. The potentiometer for start-up suppression is set to 50 %.
“Flame out" state
After switching on the auxiliary energy, the flame detector is ready for operation after
approximately 5 s. The following display has to be shown:
To check the monitoring parameters, install the compact flame detector in the speci-
fied mounting place before starting the operation of the furnace. If the flame burns
naturally, the display should change as follows:
The flame detector can be checked for proper functioning without any burning flame.
1. Carry out the complete electrical installation of the flame detector and connect it to
the supply voltage.
A LAMTEC test emitter of the FFP 02 type (IR + UV) can be used as an auxiliary
means for flame simulation.
2. Simulation of a flame radiation in front of the flame detector's viewing port. This
can be done using a lighter or any other type of a modulated-light source (don't
use the mains frequency) having a sufficiently high intensity. For example, you
can modulate in a sufficient way the light of a lamp by moving your fingers splayed
out in front of the light source and the flame detector. However, start-up suppres-
sion requires a stable signal to do this. If necessary and if the signal is not suffi-
cient, the Serv. switch (section 9) should be set to OFF in order to make the re-
action to the simulated flame signal visible.
The flame detector has to switch on its output contacts if the flame signal is simulated
for a sufficient period of time. This is shown by the extinction of the red LED and the
pulsating light of the green LED. The 6-level intensity indicator lights up.
- 16 -
If no flame signal is delivered in spite of an apparently correct functioning, check the
output contact (refer to 7.2).
Alignment
IR- flame detectors should be installed / aligned in such a way that possible reflec-
tions form the combustion chamber are already largely suppressed by constructive
measures. A ball-and-socket joint for the alignment of the sensor to the flame is nor-
mally not required, since the optics of the flame detector is characterised by a wide
viewing angle.
UV- flame detectors should generally be used with one ball-and-socket joint only,
since the optics of the flame detector has a narrow viewing angle. That's why an opti-
mum alignment towards the flame is of utmost importance.
.
Optics
There are no special requirements for locking discs or similar components when using
IR- flame detectors. Small accumulations of dirt due to dust and similar materials are
mainly not critical for flame detection.
In UV- flame detectors, the requirements to locking discs are more strict. Make sure
to use a material that lets UV light pass (e.g. quartz) without problems. They are al-
ready contained in the LAMTEC-UV adjustable holding device (FS 19, FS 20, FV 19
and FV 20). Small accumulations of dust, water etc. are considerably more likely to
lead to problems in flame detection than IR radiation.
7.1.3 Adjustment
Sensitivity
If for the 1st burner start, there is no reaction, the sensitivity switch (flame amplitude)
can be set towards the right-hand stop position to allow a stable flame detection. The
positions 1 – 6 and/or 7 – 12 are allocated to the internal amplification of the flame
signal. Position 1 and/or 7 means lowest amplification / sensitivity as well as 6 and/or
12 highest amplification / sensitivity in the related sensitivity range.
Caution!
Make sure to react otherwise in a sufficient way to a flame not burning correctly or an
extinguishing flame next to the flame detector until successful switch-off test will have
been carried out.
After having carried out a correct burner adjustment, reduce the sensitivity again to
such an extent as to allow for a stable and safe operation. The measurable signals
should have at least 2 to 3 times the switching threshold value of 25 mV AC to al-
low a reliable recognition.
To allow an optimum alignment of the compact flame detector towards the flame
(maximum flame amplitude), the intensity indicator of the device can be used by
activating the “Adjust“ function switch. The activation of the “Adjust“ switch
(ON position) suppresses the function of the Serv. switch. The intensity indicator
now represents flame amplitude detected. If the intensity has already been set to
maximum in this function, reduce the sensitivity of the active sensitivity switch to such
a level that a reaction of the intensity indicator can be noticed, in order to find the best
possible view to the flame by alignment. After having completed the adjustment work
and/or before optimisation set the Adjust switch back to OFF.
- 17 -
Measuring points
Apart from the Adjust function, the measuring points (section 10) of the device can be
used. This allows to continuously measure the unevaluated intensity.
Use a commercial potential-free measuring device, such as a manual multimeter
complying with EN 61010-1 (safe insulation), and having a measuring resistance
> 5 MΩ.
The trigger threshold for the F 200 K is at ≥ 25 mV AC , while the measured sig-
nal voltage can amount to maximally 3 V AC.
Frequency setting
An adaptation to the burner flame can additionally be effected in the F 200 K2 (ex-
proof) as to the lower frequency limit (section 9.2, item 6). This frequency allows no
remote switch-over. Generally, a low frequency limit means a higher availability, how-
ever a reduction of the selectivity.
3 levels are provided for.
The setting (changeover to another frequency range) has always to be carried out for
both processing channels A and B in an identical way.
Moreover, always make sure that only one frequency range in ON position is selected
each time.
Start-up suppression
If on burner start, there are short flame pulses in the set transmission range due to in-
tense background fire and/or adjacent burners, thus likely to cause problems with
burner start ( light emitted by other sources ), a change of start-up suppression ac-
cording to the technological circumstances can be used to suppress the undesired
flame pulses.
The start-up suppression function (refer to section 7.0.8, separately adjustable) allows
to suppress short pulse rates, which may occur on burner start in connection with the
fan operation (pre-ventilation) and background fire. The values can be set between 0
and 100 % at a continuous start-up delay of 1s, i.e. that short pulse rates that may re-
sult in extraneous light signalling during the burner start phase, but don't represent no
continued flame signal, are excluded from evaluation (suppressed) with differently in-
tensive ways. When 0% has been set, the flame detector is activated even on im-
proper flame signals, at a setting of 100% however, an activation requires very proper
and stable flame signals.
In case of improperly starting flames, an excessive start-up suppression impedes a
timely recognition of the flame.
The devices are delivered with start-up suppression of 50 % factory pre-set 50 % and
the Serv. switch pre-set to the ON position (deactivated).
- Set the Serv. switch to the OFF position, this allowing to make the pulses visible
during the start-up time via the devices' intensity indicator
- Set the start-up suppression (section 10, item 9) according to the amplitude of the
pulse rates between 0 and 100 %
After completion of the settings and/or optimisation, reset the Serv. switch to the ON
position.
- 18 -
Caution!
However, this setting operation should only be used if the alignment of the flame
sensor, as well as sensitivity and frequency settings as to reliability have fully been
used.
Simulate a flame rupture or flame extinction. To this end, shut off the fuel supply to the
burner to be monitored by the flame detector. Check that the signal for shutting-off the
safety valve is triggered off within the period of TS< 1 s (on safety period “Operation“ at
tVOff = 1 s) after extinction of the flame.
For the IR compact flame detectors of the F 200 K1(2) IR-1 and/or F 200 K1(2) IR -2
types, take into account the special reflection effects caused by the combustion
chamber. Consequently, switch-off tests have to be carried out when the boiler has
the operating temperature. In particular, make sure that the sensitivity of the compact
flame detector is increased only to such a value required to safely and reliably monitor
the flame throughout the operating range of the burner.
1. Interference
Generally, interference becomes apparent by the fact that the intensity indicator of the
device may indicate 100 %, but the green LED (“Flame in“) doesn't light up. Or, the
green LED lights up for a moment, but then it doesn't change its intensity according to
the cycle rhythm and goes out again. This is a cycle synchronisation fault (signal in
both evaluation channel present at the same time). This may chiefly be due to the in-
terference emission of the ignition transformer during ignition.
- Check the shielding and FPE for proper connection to the F 200 K
- Carry out a proper grounding of the ignition transformer
- Check the cables for laying and if required untangle / separate them spa-
tially
2. Excessive temperatures
Make sure that the maximum admissible ambient temperature of 60 °C is not ex-
ceeded at the installation site. In case temperatures are expected to be higher, take
appropriate cooling measures (e.g. cooling air enclosure FS 50 or FS 51, section
14.3). Moreover, make sure that the flame detector casing doesn't heat up beyond this
temperature value due to the impact of the heat radiated by the boiler. Overheating
will result in a sensitivity loss in the first line, or will cause damage to the sensor ele-
ments and with it may result in a total failure of the system.
- 19 -
7.1.6 Faults during ignition
1. In case of additionally monitoring the pilot flame, the pilot flame may not suffi-
ciently be detected.
Check the pilot flame for stable operation
Check that the pilot flame is sufficiently visible within the viewing scope of the
compact flame detector, and change pilot burner adjustment if required.
Realign the flame detector and check for cleanness of the viewing port
Measure the flame radiation captured by the compact flame detector (section
7.1.4), and optimise alignment if required.
Increase sensitivity if required.
2. Interference
3. If the flame has trouble to start-up, a timely recognition of the flame may be ham-
pered by an excessive start-up suppression.
7.2 Troubleshooting
- 20 -
2. Check the supply voltage
- 21 -
7.3 Commissioning flow chart
Burner start Check if there are sufficient visibility of the main flame or pilot flame in
the viewing zone of the flame detector, if required change the burner
adjustment.
no
Check the viewing port for accumulation of dirt
Flame „In“ Check the compact flame detector for proper alignment
- for UV: maximise the signal strength by readjusting the alignment
and by consequently increasing the sensitivity if required
yes - for IR: increase the sensitivity step by step by turning the selector
switch towards the right-hand stop
- Check the viewing situation (e. g. direct view towards the glowing refractory
lining or adjacent flames)
- Reduce sensitivity if required
- Increase the lower frequency limit (for F 200 K2 only)
- Use the start-up suppression in the range between 50 ... 100 % (section 7.1.4)
Set values, measured values and manufacture number of the compact flame
detector, and note down the approximate maximum ambient temperature in the IB
documents.
- 22 -
7.4 Maintenance
Provisions shall be made to ensure that the light entry port of the flame sensor and the
viewing port on the furnace, where the sensor is to be fit in, are regularly cleaned, i.e.
at regular intervals, which depend on the operating conditions of the furnace. The
compact flame detector needs no maintenance. The flame failure induced switch-off
check is to be integrated into maintenance cycle.
The manufacturer's conditions of guarantee shall apply. Any changes to and opera-
tions on components of the compact flame detector effected by unauthorised persons
will result into refusal of claims under guarantee.
Delivery will comply with ordering details. The terms of deliveries and services of
LAMTEC, and the general terms of delivery for products and services made or ren-
dered by companies of the electrical industry, shall apply.
- 23 -
9 Layout of the operational controls
1
2
7 5 8
- 24 -
9.2 F 200 K2 … (Ex-proof), (in the state as delivered)
6 3 9
10 7 4 5 8 11
6 – Serv. Service switch, according to section 7.0.6 / Adj.- Adjust, according to section 7.0.7 /
frequency switch according to section 7.0.5
7/8– Measuring points to measure the flame radiation received by the F 200 K, according to
section 7.1.3
9 – Start-up suppression, according to section 7.0.8 and 7.1.3
10/11 LED (yellow), only for F 200 K2, lights for active range, Pre-selection according to section
12.2 (pin configuration) and 7.0.2
- 25 -
10 Dimensional drawings
10.1 F 200 K … and F 200 K Compact Flame Detectors... Z2 (hazardous area II)
Ø 22
Light entry
port
36
Ø
1,5
40
Ø
75
51
188 ± 2
Ø 26
180
Ø 35 Indication of the
operating state
36
80
Ø
- 26 -
10.2 F 200 K2 … Compact Flame Detector Ex (hazardous area I)
Ex (II 2G EEx d IIC T6, PTB 03 ATEX 1051)
8 15 90
*
Ø 60
G 1½
Ø 90
Ø 60
659 R 0111
1 2 3 4 5 6 7 8 9
45
75
II 2GD-IP67 – T 85 C
SIRA99ATEX3173)
68
80
- 27 -
11 Pin configuration
11.1 F 200 K1 …
4(0)..20 mA PK
without function YE
24 V RT
24V 0V BU
DC
FPE GY
Sch
- 28 -
11.2 F 200 K2 ... (Ex)
4(0)..20 mA PK
Range YE
24 V RT
24V 0V BU
DC
FPE GY
Sch
- 29 -
12 Examples of application
4(0)..20 mA PK
without function YE
23 +24V 24 V RT
L 22 0V BU
N 24V PE FPE GY
DC
PE PE Sch
* Range YE
10 +24V 24 V RT
L 31 0V BU
N 24V PE FPE GY
DC
PE PE Sch
- 30 -
13 Accessories
13.1.1 Purpose
The FN 20 mains supply unit is used to connect the F 200 K to a mains A.C. It has
been designed for top hat rail installation (as an option, it is also available for plate
mounting). Moreover, the unit has the related safely operating output relays for mains
A.C. to couple the relays of the F 200 K.
Make sure to carry out installation as to provide for a protection degree of at least IP
40. As an option, the FN 20 mains supply unit is available in an IP 65 housing.
+10%
Mains alternating voltage 230 V −15%
+10%
optional 115 V −15%
Note: When ordering the FN 20 for 115 V AC, it will be delivered with the
related identification marking on the mains unit. The setting for the mains
supply voltage will only be changed in the factory.
Power consumption ≤ 6 VA
- 31 -
- Admissible switching current max. 0.5 A
min. 10 mA, at a limit load
of 50 mA
- Switching capacity min. 0.1 W
on DC voltage max. 30 W
on AC voltage max. 120 W
- External fuse ≤ 500 mA slow IEC, ≤ 750 mA slow UL
Caution !
Technical stressability
Operating mode Continuous operation
Creepage distances and clearances DIN EN 60730 part 1
Climatic stressability
Installation category Temp. min. - 20 °C
max. +60 °C
rel. air humidity 80 % at 35 °C
Protection type IP 20; without further enclosure
IP 65; built-in in IP 65 enclosure, which is
available for delivery
Weight 0.35 kg
- 32 -
13.1.3 Pin configuration
FN 20
5 22 WH
Flame- 6 23 BN
contact 7 24 GN
3
Signalling-
contact 4 16 PK
12
4(0)..20 mA 11 17 YE F 200 K
13
Sensitivity 14 21 RD 24 V
selector
1 20 BU 0V
Mains
2 24V 19 GY
DC
PE 15 18 Sch
Sch
+24
WH
GN
BU
BN
GY
PK
RT
YE
(IP20 housing)
0
11 12 13 14 15 200mA 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6 7
COM
COM
NO
NO
NC
L
Width 77 mm
Length 90 mm
Height 46 mm, from upper edge for hat top rail
Weight 0.35 kg
- 33 -
Dimensioned drawing IP65 housing Purchase order no.: 659 R 6010/G
Width 100 mm
Length 160 mm
Height 80 mm
Weight 1.15 kg
D4,8
M16 M20
66
0/4..20mA F 200 K
Remote switch-over
146
M20 M20
- 34 -
13.2 FWS 01 weather shield for F 200 K
The weather shield is intended to chiefly protect the electronic parts in outdoor instal-
lations, if the cover has to be opened for commissioning and repair services under in-
clement weather conditions (rain, snow etc.). Moreover, the weather shield offers sun
shade protection on sunny days to improve the visibility of the indicators.
ø 80
reverse installation 10
in F200K possible
110
15° 30°
F200K
- 35 -
13.3 Adjustable holding devices
13.3.1 FS 19-10 (for IR and UV, without ball-and socket-joint, with purge air connection)
280 ± 5
188 89 ± 2
78
1"
13.3.2 FS 20-10 (for IR and UV, with ball-and socket-joint and purge air connection)
235 ±5
188 ± 2 110
78 Ball-and-socket-
joint, adjustable
in all levels
A
40°
320 + 5
197 ± 2 125
Stopper disk
Joint not detachable
detachable
180 ± 2 Sealing ring
Screwed connection
75 detachable
not detachable
G 1"
Ø 40
Ø
80
Counter hold SW 38
60
Ø 26 Screwed connection
18
36
SW 54 separable
G½ "
Ø 35 Operating state
Indicator loose gasket 44 x 32 x 1,5
51
13.3.4 FV 20-10 (for IR and UV, with ball-and-socket-joint and purge air connection)
390
± 5
125 67
~
197 ± 2
Joint not detachable Stopper disk Ball-and-socked-
180 ± 2 detachablwe screwed joint ±20° in
Sealing ring Screwed connection two levels
75 detachable not detachable
•
Ø 80
A
Ø 40
40°
Counter-hold SW 38
60
Ø 26
18
36 Screwed connection
View A
SW 54, separable loose gasket G½ "
Ø 35 Operatin state 44 x 32 x 1,5 Ø 11,5
indicator Connecting thread DIN ISO 228/1
51
Ø
Ø 110
89
Purging air
- 37 -
View of the FV 20-10 with F 200 K Ex
299 ±5
6
67 200 ±5 Ball-and-socket-
Operating state joint ± 20°
indicator 11 Stopper disk 10
in two levels
detachable SW
Ø60
A
90
40°
60
Ø
Ø
32
Cable entry not Sleeve nut SW 53
79
Thread G 1½
41
detachable Sensor connection Inner thread G ½"
with purging air purging air connection
separation
4 x cylindrical bolts M5 Connecting cabel
Ø 8 mm, 3 m long Cylindrical bolt DIN 84
ISO 4762 (DIN 912)
cofiguration as in
F 200 K
Connection core section 2,5...6 mm² View A
Connectors-cylindrical Ø 11,5
pipe threads DIN ISO 228/1
* for pipe connector with thread
*G2; 12 tief
Sensor surface: only on special order
Ø 110
Ø 55
withe aluminium RAL 9006 matt
Ø 27
*G1
Ø 89
13.3.5 FS 50 (without ball-and-socket-joint and cooling air housing)
ca. 235
45 175
86
Pipe connector 56 (< 15)
8 Kt SW 48 Sealing ring 56x42x2
(boiler) Rp1"
3x setting screws
6Kt SW 46 M6 - nylon
ø100 Display
20
Detachable connection 8 Kt SW 66
Cooling air
"
½
Rp
22
ø < 10
36
- 38 -
13.3.6 FS 51 (with ball-and-socket joint and cooling air housing)
ca. 335
ca. 52 ca. 20 45 175 < 15
86
Insulated mounting 56
14 15 Sealing ring position of flame sensor
56x42x2
(Galvanic isolation)
Display ø35
ø100
(Lens cleaning) B
Detachable connection
8 Kt SW 66 Cabel connector
View "A" with screwed
connection
45
22
ø < 10
+2,5
-2,5
)
36
20
(ø 89)
Ø108
R½"
1
ø1
View "B" 45
- 39 -
13.3 Installation in the cooling air housing
3x 1.
F200K
56 x 42 x 2
80 x 2,5
2.2 22 x 3
hexagon 2,5
4x
M3
nylon M6
3x
2.
glass cleaned
3. Rp 1/2
3x
Rp 1
F200K
isolated build in
4.
- 40 -
14 EG Certificate of Conformity
Year: 2005
The product named above complies with the regulations of the following European directives:
Number Text
Signature legally i. V.
binding: ................................................
- 41 -
15 EC Prototype testing certificate
- 42 -
16 TÜV Certificate
- 43 -
18 GOST - Zertifikat
- 46 -
19 EG Baumusterprüfbescheinigung, Ex- Zone 1
- 47 -
20 Baumusterprüfbescheinigung, Ex- Zone 2
- 48 -
LAMTEC Meß- und Regeltechnik LAMTEC Leipzig GmbH & Co KG Handed over by:
für Feuerungen GmbH & Co KG
Impexstraße 5 Schlesierstraße 55
D-69190 Walldorf D-04299 Leipzig
Phone (+49) 0 62 27 / 60 52-0 Phone (+49) 03 41 / 86 32 94 00
Telefax (+49) 0 62 27 / 60 52-57 Telefax (+49) 03 41 / 86 32 94 10
Internet http://www.lamtec.de Printed matter no. DLT 7620-05D-0001
E-mail: info@lamtec.de Printed in Germany
- 44 -