Professional Documents
Culture Documents
presented by
Bill de Blasio, Mayor
Melanie La Rocca, Commissioner
ACKNOWLEDGEMENTS
One City: Built to Last
We wish to acknowledge Mayor Bill de Blasio for his commitment to
80% reduction of Greenhouse Gas Emissions by 2050, over 2005
levels.
■ A sweeping plan to retrofit public and private buildings to reduce the
City’s contributions to climate change.
■ This makes New York the largest city to commit to the 80% reduction
by 2050.
■ It charts a long-term path for investment in renewable sources of
energy and a total transition from fossil fuels.
The Menu icon takes you to the main menu page within
each module.
AIR-SIDE SYSTEMS
System Requirements ● VAV System Types
1. MULTI-ZONE SYSTEMS 12
& Schematics
build safe | live safe 28 Fan VFD & Static Pressure controls: C403.4
4. CHILLERS: OVERVIEW
Slides 29 to 39
2016 NYCECC
Partial Table C403.2.3(7)
Chiller Efficiency Requirements:
build safe | live safe 33 Table C403.2.3(7)
& NPLV: C403.2.3 .1
4. CHILLERS: EFFICIENCY METRICS
Which Chiller Efficiency Metrics Apply for Non-Standard Operating Conditions?
NPLV (Non-standard Part-Load Value):
■ Single number part-load efficiency
metric analogous to IPLV
■ Different rating conditions (non-
standard) than for IPLV
■ Applicable only for centrifugal
chillers within limits:
Minimum evaporator leaving
temperature: 36°F
Maximum condensing leaving
temperature: 115°F
■ Calculation formula: Refer to Code
Air-cooled Condenser:
■ Packaged or separate air-cooled
condenser
■ Chiller ratings must include
condenser fan energy
NYCECC requires
Vapor air-cooled chillers
Compression without
- Schematic
Cooling devices (Vapor compression
condensers to be rated with matching condensers & Absorption) use Condensers to
and must then comply with the air-cooled chiller reject heat
efficiency requirements. The code, however, does
include separate efficiency requirements for air-
cooled condensing units.
Water-cooled Condenser:
■ Need condenser water loop and
ASHRAE 90.1 provides efficiency requirement for cooling tower (or ground)
air-cooled chillers without condensers, and allows ■ Chiller ratings don’t include
them to be rated as such. ASHRAE also includes condenser water system energy (i.e.,
efficiency requirements for remote air–cooled pumps and tower fans)
condensers.
Air-cooled Condenser:
■ Packaged or separate air-cooled
condenser
■ Chiller ratings must include
condenser fan energy
Pros:
■ Simple
■ Low maintenance
■ Inexpensive
■ No freeze issues
Cons:
An air-cooled condenser is a ■ Low efficiency
type of dry cooler.
Pros:
■ More efficient than Dry Coolers
■ Typically more efficient than Evap Coolers
Cons:
■ Requires make-up water
■ Condenser water must be filtered to control
contamination
■ Higher maintenance than Dry Cooler or
Evaporative Cooler
■ Code Requirements:
Two-pipe Reverse Return Deadband of 15°F between heating and cooling
modes based on OA temperature
4-hour delay before changing modes
AND
Difference between changeover temperatures
must be no more than 30°F
Intent: To avoid heating previously chilled water
or cooling previously heated water
■ Code Requirements:
Two-pipe Reverse Return Deadband of 15°F between heating and cooling
modes based on OA temperature
4-hour delay before changing modes
AND
Difference between changeover temperatures
must be no more than 30°F
Intent: To avoid heating previously chilled water
or cooling previously heated water
■ Cons:
Simultaneous heating & cooling due to mixed
return
■ Performance Requirements;
■ Control Requirements;
Temperature
Heat Traps
Hot Water System Controls
■ Pipe Insulation; and
■ Swimming Pools.
System Controls:
■ Circulating Systems
Automatic or manual shut-off for
circulating pump during periods when
system not in use
■ COMcheck software
■ Energy Modeling
■ Alternative Formats
C403.2.3
HVAC Equipment Performance
HVAC Equipment Performance Requirements
Supporting Documentation for
Requirements
Unitary air conditioners, condensing units, EACH item within the Tabular
Table Split System 5 ton air cooled AC Split System AC units schedule,
C403.2.3(1)
electrically operated, minimum efficiency
requirements
unit, AC-1
13.5 SEER
Analysis.
13.0 SEER
drawing M-300
Unitary air conditioners, condensing units,
Table Through the Wall AC unit, 1 ton, Through the wall AC units schedule,
electrically operated, minimum efficiency 12.5 SEER 12.0 SEER
C403.2.3(1) AC-2 drawing M-300
requirements
Unitary and applied heat pumps,
Table 3 ton air cooled heat pump, single
electrically operated, minimum efficiency 14.2 SEER 14.0 SEER AC units schedule, drawing M-300
C403.2.3(2) package, HP-1
requirements
Table Packaged Terminal Air Conditioners and PTAC (Cooling Mode) Replacement, PTAC AC units schedule, drawing M-
10.6 EER 14.0-(0.300xCap/1000)EER = 10.4 EER
C403.2.3(3) Packaged Terminal Heat Pumps 12,000 BTU, PTAC-1 301
Dual duct and mixing VAV systems, Terminal devices shall be capable of reducing air from
C403.4.4.2 N/A N/A N/A
terminal devices one duct to a minimum before mixing takes place
Individual dual duct or mixing heating and cooling
Single fan dual duct and mixing VAV systems with a single fan and capacities greater than
C403.4.4.3 N/A N/A N/A
systems, economizers 90,000 Btu/h shall not be equipped with air
economizers
Control system shall automatically reset supply-air
VAV System with Multiple Zone, supply-
C403.4.4.5 N/A N/A temperature in response to building load or O.A. N/A
air temperature reset controls*
temperature
Provide condenser water heat recovery, required for 24
Heat Recovery for Service Water Heating
C403.4.5 N/A N/A hr/day operations, with water cooled systems over 6 N/A
for systems*
million btu/h
Hot gas bypass is allowed only on systems with
C403.4.6, Table
Hot Gas Bypass Limitation N/A N/A multiple steps of unloading or continuous capacity N/A
C403.4.6
modulation. Allowed Bypass capacity per table 503.4.7
ROOF PLAN
Mechanical Schedules
Shutoff dampers: Dampers for stair and elevator shaft vents and other outdoor air intakes and exhaust
openings integral to the building envelope shall be visually inspected to verify that such dampers, except As required Approved construction documents; C403.2.4.3; ASHRAE
IIB2
where permitted to be gravity dampers, comply with approved construction drawings. Manufacturer’s during installation AMCA 500D 90.1 – 6.4.3.4
literature shall be reviewed to verify that the product has been tested and found to meet the standard.
C403.2, C404.2,
HVAC-R and service water heating equipment: Equipment sizing, efficiencies, pipe sizing and other C404.5, C404.9,
Approved construction documents;
performance factors of all major equipment units, as determined by the applicant of record, and no less than Prior to final plumbing and C406.2, ASHRAE 90.1
IIB3 ASHRAE 183, ASHRAE HVAC
15% of minor equipment units, shall be verified by visual inspection and, where necessary, review of construction inspection – 6.3, 6.4.1, 6.4.2,
Systems and Equipment Handbook
manufacturer’s data. Pool heaters and covers shall be verified by visual inspection. 6.4.5, 6.4.6, 6.5.11,
6.8, 7.4, 7.8
HVAC-R and service hot water system controls: No less than 20% of each type of required controls and After installation and prior to final
economizers shall be verified by visual inspection and tested for functionality and proper operation. Such electrical and construction C403.2, C404.3,
Approved construction documents,
controls shall include, but are not limited to: Thermostatic, Off-hour, Zones, Freeze protection/Snow- and ice- inspection, except that for controls C403.4, C403.5,
including control system
melt system, Ventilation System and Fan Controls, Energy recovery systems, Kitchen/lab exhaust systems, Fan with seasonally dependent C404.6, C404.7,
IIB4 narratives; ASHRAE Guideline 1:
systems serving single and multiple zones, Outdoor heating systems, HVAC control in hotel/motel guest functionality, such testing shall be C404.9; ASHRAE 90.1
The HVAC Commissioning Process,
rooms, Air/Water Economizers & controls, Hydronic systems, Heat rejection systems, Hot gas bypass performed before sign-off for – 6.3, 6.4, 6.5, 6.6,
where applicable
limitation, Refrigeration systems, Door switches, Computer room systems, Service water heating systems, issuance of a Final Certificate of 7.4.4, 7.4.5
Pool heater and time switches. Occupancy
C403.2.9, C403.2.10,
Approved construction
HVAC-R insulation and sealing: Installed duct and piping insulation shall be visually inspected to verify proper C404.4; MC 603.9;
After installation and prior to closing documents; SMACNA Duct
IIB5 insulation placement and values. Joints, longitudinal and transverse seams and connections in ductwork shall ASHRAE 90.1 – 6.3,
shafts, ceilings and walls Construction Standards, Metal and
be visually inspected for proper sealing. 6.4.4, 6.8.2, 6.8.3;
Flexible
7.4.3
TR8:
https://www1.nyc.gov/assets/buildings/pdf/tr8.pdf
Shutoff dampers: Dampers for stair and elevator shaft vents and other outdoor air intakes and exhaust
openings integral to the building envelope shall be visually inspected to verify that such dampers, except As required Approved construction documents; C403.2.4.3; ASHRAE
IIB2
where permitted to be gravity dampers, comply with approved construction drawings. Manufacturer’s during installation AMCA 500D 90.1 – 6.4.3.4
literature shall be reviewed to verify that the product has been tested and found to meet the standard.
C403.2, C404.2,
HVAC-R and service water heating equipment: Equipment sizing, efficiencies, pipe sizing and other C404.5, C404.9,
Approved construction documents;
performance factors of all major equipment units, as determined by the applicant of record, and no less than Prior to final plumbing and C406.2, ASHRAE 90.1
IIB3 ASHRAE 183, ASHRAE HVAC
15% of minor equipment units, shall be verified by visual inspection and, where necessary, review of construction inspection – 6.3, 6.4.1, 6.4.2,
Systems and Equipment Handbook
manufacturer’s data. Pool heaters and covers shall be verified by visual inspection. 6.4.5, 6.4.6, 6.5.11,
6.8, 7.4, 7.8
HVAC-R and service hot water system controls: No less than 20% of each type of required controls and After installation and prior to final
economizers shall be verified by visual inspection and tested for functionality and proper operation. Such electrical and construction C403.2, C404.3,
Approved construction documents,
controls shall include, but are not limited to: Thermostatic, Off-hour, Zones, Freeze protection/Snow- and ice- inspection, except that for controls C403.4, C403.5,
including control system
melt system, Ventilation System and Fan Controls, Energy recovery systems, Kitchen/lab exhaust systems, Fan with seasonally dependent C404.6, C404.7,
IIB4 narratives; ASHRAE Guideline 1:
systems serving single and multiple zones, Outdoor heating systems, HVAC control in hotel/motel guest functionality, such testing shall be C404.9; ASHRAE 90.1
A Progress Inspections Table must be included in the Supporting Documentation
rooms, Air/Water Economizers & controls, Hydronic systems, Heat rejection systems, Hot gas bypass performed before sign-off for
The HVAC Commissioning Process,
where applicable
– 6.3, 6.4, 6.5, 6.6,
limitation, Refrigeration systems, Door switches, Computer room systems, Service water heating systems, issuance of a Final Certificate of 7.4.4, 7.4.5
Pool heater and time switches. drawings, noting all applicable inspections to be performed based on the scope of
Occupancy
work, plus Reference Standards and NYCECC Citations. Approved construction C403.2.9, C403.2.10,
HVAC-R insulation and sealing: Installed duct and piping insulation shall be visually inspected to verify proper C404.4; MC 603.9;
insulation placement and values. Joints, longitudinalThe design applicant must alsoshallinclude contract
After installation and prior language
to closing requiring
documents; SMACNAtheDuctcontractor to
IIB5 and transverse seams and connections in ductwork ASHRAE 90.1 – 6.3,
shafts, ceilings and walls Construction Standards, Metal and
be visually inspected for proper sealing.
identify time in the construction schedule for the progress inspections. Flexible
6.4.4, 6.8.2, 6.8.3;
7.4.3
TR8:
https://www1.nyc.gov/assets/buildings/pdf/tr8.pdf
Fireplaces (IIB1)
Prior to final construction inspection
Provisions of combustion air and tight-fitting fireplace doors shall be verified by visual inspection.
TR8:
https://www1.nyc.gov/assets/buildings/pdf/tr8.pdf
Thermostatic
Off-hour Controls with seasonally dependent functionality: Controls whose
Zones complete operation cannot be demonstrated due to prevailing weather
Freeze protection/Snow- and ice-melt system conditions typical of the season during which progress inspections will After installation and prior
Ventilation System and Fan Controls be performed shall be permitted to be signed off for the purpose of a to final electrical and
Energy recovery systems Temporary Certificate of Occupancy with only a visual inspection, construction inspection,
Kitchen/lab exhaust systems provided, however, that the progress inspector shall perform a except that for controls
Fan systems serving single and multiple zones supplemental inspection where the controls are visually inspected and with seasonally dependent
Outdoor heating systems tested for functionality and proper operation during the next immediate functionality, such testing
HVAC control in hotel/motel guest rooms season thereafter. shall be performed before
Air/Water Economizers & controls sign-off for issuance of a
Hydronic systems The owner shall provide full access to the progress inspector within two Final Certificate of
Heat rejection systems weeks of the progress inspector’s request for such access to perform the Occupancy
Hot gas bypass limitation progress inspection.
Refrigeration systems
Door switches For such supplemental inspections, the Department shall be notified by
Computer room systems the approved progress inspection agency of any unresolved deficiencies
Service water heating systems in the installed work within 180 days of such supplemental inspection.
Pool heater and time switches
TR8:
https://www1.nyc.gov/assets/buildings/pdf/tr8.pdf
TR8:
https://www1.nyc.gov/assets/buildings/pdf/tr8.pdf
EN2 Form:
While a specific format is not stated,
inspection records can include: ■ This DOB form is signed by the progress inspector,
certifying that the values in either the last approved
► Logs, reports, meeting minutes Energy Analysis or in the as-built Energy Analysis
► Photographs represent values in the constructed building
► Annotated Drawings
Resource Link
http://www1.nyc.gov/site/buildings/codes/2016-energy-
2016 NYCECC
conservation-code.page
Local Law 91 of 2016 http://www1.nyc.gov/assets/buildings/local_laws/ll91of2016.pdf
Local Law 125 of 2016 http://www1.nyc.gov/assets/buildings/local_laws/ll125of2016.pdf
Code Notes http://www1.nyc.gov/site/buildings/codes/list-code-notes.page
NYCECC FAQ http://www1.nyc.gov/site/buildings/codes/nycecc-faq.page
1 RCNY §5000-01 http://www1.nyc.gov/assets/buildings/rules/1_RCNY_5000-01.pdf
1 RCNY §101-07 http://www1.nyc.gov/assets/buildings/rules/1_RCNY_101-07.pdf
Buildings Bulletins http://www1.nyc.gov/site/buildings/codes/building-bulletins/page
EN1, EN2, and TR8
http://www1.nyc.gov/site/buildings/codes/energy-code-forms.page
Forms
Resource Link
REScheck/COMcheck https://www.energycodes.gov/
Blower Door Testing https://www.energy.gov/energysaver/blower-door-tests
One City: Built to Last https://www1.nyc.gov/site/builttolast/index.page
New York City
https://www1.nyc.gov/site/buildings/codes/nyc-code.page
Construction Codes
Energy Code:
https://www1.nyc.gov/assets/buildings/pdf/h2g_all.pdf
Supporting Documents
How To Guide
EnergyCode@buildings.nyc.gov