CLTD METHOD
BAGSAO, Yancy A.
FALLORINA, Brian F. November 19, 2021
Submitted by: Date Performed:
BSME- IV December 2, 2021
Course/Year: Date Due:
November 30, 2021
Date Submitted:
Indoor Design
69.8 ⁰F
Temperature
Room Height 9 ft
COMPUTATION OF SENSIBLE COOLING LOAD FROM INFILTRATION/VENTILATION
• Single Family Residence
• Located at Zambales, Philippines
• Month of May (Hottest month in Philippines)
• Design dry bulb temperature for the hottest month is 35.3 ⁰C (95.54 ⁰F)
• DB range for the hottest month is 5.3⁰C or 9.64⁰F (Low)
• Inside Desired Temperature Condition = 21⁰C (69.8 ⁰F)
I. Bedroom 1
Given:
Solution:
Given:
III. Bedroom 3
Given:
Given:
V. Living Room
Given:
VI. Kitchen
Given:
Given:
Given Data:
• Single Family Residence
• Located at Zambales, Philippines
• Month of May (Hottest month in the Philippines)
• Design dry bulb temperature for the hottest month is 35.3 ⁰C
• DB range for the hottest month is 5.3 ⁰C or 9.64 ⁰F (Low)
• Inside Desired Temperature Condition = 21 ⁰C (69.8 ⁰F)
• Number of Persons in the house = 4 Persons
• Cooling load per person = 230 BTU/hr/person
• Relative humidity desired inside the building = 40 %
• Cooling load of appliances for whole building = 1600 BTU/hr/person
Solution:
q Internal Heat Gain (Whole Building) = (# of occupants)(cooling load per person) +
cooling load of appliances for whole building
𝐵𝑇𝑈
q Internal Heat Gain (Whole Building) = (4 persons) (230 /𝑝𝑒𝑟𝑠𝑜𝑛) + 1600 BTU/hr
ℎ𝑟
Given Data:
• Single Family Residence
• Located at Luzon Island, Philippines
• Month of May (Hottest month in the Philippines)
• Design dry bulb temperature for the hottest month is 35.3 ⁰C(
• DB range for the hottest month is 5.3 ⁰C or 9.64 ⁰F (Low)
• Inside Desired Temperature Condition = 21 ⁰C (69.8 ⁰F)
• Number of Persons in the house = 4 Persons
• Cooling load per person = 230 BTU/hr/person
• Relative humidity desired inside the building = 40 %
• Cooling load of appliances for whole building = 1600 BTU/hr/person
• Humidity Ratio (W) from Psychrometric Chart = 0.001437 lb /lb da
• Actual LF is less than 2% from the computed LF
Solution:
LF = 0.58 + 42W
lb
LF = 0.58 + (42)(0.001437 )
lb𝑑𝑎
LF = 𝟎. 𝟔𝟒𝟎𝟒
Actual LF = LF − 0.02LF
Actual LF = 0.6404 − 0.02(0.6404)
Actual LF = 𝟎. 𝟔𝟐𝟕𝟔
Given Data:
• Total Sensible Load = 51,446.7366 BTU
• Total Latent Load = 32,300.5239 BTU
Solution:
Total Cooling Load = Total Sensible Load + Total Latent Load
Total Cooling Load = 51,446.7366 BTU + 32,300.5239 BTU