Professional Documents
Culture Documents
APPLICATIONS 6-9
HVAC Design Manual November 1, 2017
direction, as well as ensuring proper pressure reading by the space pressure monitoring
sensors, and avoiding false alarms.
(c) Pressure References / Example
The requirement of building air balance is to create the desired space pressure induced
air flows between spaces for the purposes of infection control, temperature control and
odor control. All clinical and / or functional spaces shall be designed to be positive,
negative, or neutral to the building baseline pressure or other adjacent space pressure.
An example of this is as follows:
1) A protective environment room in a patient ward accessible from main public
corridor. Solution: Ward corridor pressure is greater than main corridor pressure;
PE ante room pressure is greater than ward corridor pressure; PE room pressure is
greater than ante room pressure; and PE toilet room pressure is less than PE room
pressure. Note that air flow is from PE room, to anteroom, to ward corridor, to
public corridor. While designing to meet these conditions the engineer shall as a
minimum consider the following:
x The integrity of the building envelope including doors, ceilings, windows, and
walls to ensure that excessive air flow differentials are not needed to maintain
required air pressure differentials.
x Minimum required pressure differentials and pressure indicating devices as
required by ASHRAE Standard 170-2013 or approved latest edition.
x Maximum pressure relationship between any two spaces which if excessive can
make it difficult to close or open doors between the spaces.
(d) Positive Air Balance
Positive air balance is designated as (+) in the Room Data Sheets. Generally this can be
achieved when supply air flow exceed return and / or exhaust air flow. The excess air
exfiltrates into the adjoining spaces.
(e) Double Positive Air Balance
Double Positive air balance is designated as (++) in the Room Data Sheets. Generally this
can be achieved when supply air flow exceed return and / or exhaust air flow. The
excess air exfiltrates into the adjoining spaces.
(f) Negative Air Balance
Negative air balance is designated as (-) in the Room Data Sheets. Generally this can be
achieved when exhaust and / or return air exceed supply air flow. The air deficiency
infiltrates from the adjoining spaces.
(g) Double Negative Balance
Double Negative air balance is designated as (--) in the Room Data Sheets. Generally this
can be achieved when exhaust and / or return air exceed supply air flow. The air
deficiency infiltrates from the adjoining spaces.
APPLICATIONS 6-10
HVAC Design Manual November 1, 2017
APPLICATIONS 6-11
HVAC Design Manual November 1, 2017
The air handling unit sheets indicate some air handling units as constant volume (CV)
and some as variable air volume (VAV). Through the use of CV terminals which
modulate to maintain a constant air flow volume in response to varying system supply
air pressure and VAV terminals with modulate to change the flow to the space in
response to space temperature, either type of air handling unit (CV and VAV) can be
used for either purpose. The CV and VAV designation for the air handling unit is
provided based on the majority type of terminals connected to that system. VAV air
handling units serve primarily VAV terminals, however, if necessary CV terminals can be
added to the system. For example, an air handling unit serving a patient ward will be a
VAV air handling unit because it mainly serves VAV terminals; however, that unit is also
required to have a CV terminal to serve the satellite sterile storage for that ward.
Conversely CV air handling units serve primarily CV terminals but can also have VAV
terminals added. An example of this is the CV air handling unit that serves the CV
terminals in SPS, but which also serves VAV terminals for the SPS staff offices,
breakroom, conference room etc.
APPLICATIONS 6-12