eee eC Nows & Articles Events Classified Ads Jobs Discussion Tools Advertise Allied Trade Directory Login Register ©» Production » Brewery Equipment » Refrigeration » Chiler Troubleshooting 101 Chiller Troubleshooting 101 Production + Refigeation posta Aor 24h, 2014 by Stan Heronymus “There is a good chance your glycol chiller system is often completely forgotton about, until that dreaded day you arrive to find high fermenter temperatures and your glycol chiller system is not sunning Prvay & Cookie This sa uses ceils By contin owe ie web, ou areal close ane accept enna continents b ws repair, The goal ofthis article is not to eliminate the services of a Refrigeration Service Technician, but perhaps minimize these cals to save both you and your service technician's time. prowl supponed by G&D Chir, ie FREEZE, FLOW, OR LOW PRESSURE ALARM ‘Sometime during the Ife of your chiler system you may encounter a freeze alarm. The possible ‘causes for this alarm could cause compressor and evaporator failures, and should be investigated {8 soon as the alarm is detected. In extreme cases, evaporator freeze-up can cause calastrophic system falures; for example, a ruptured evaporator can not only ruin your entre chile system, but also contaminate your entire glycol piping loop with refrigerant and oi. Before resetting a freeze alarm, always investigate to see i you can determine what could have possibly caused the alarm to trip. 41) GLYCOL SOLUTION. Not only check the glycol percentage bul also the level, or volume, of