GENERAL NOTES: FRONT EDGE OF TOILET SEAT.

FRONT EDGE OF TOILET SEAT. DISPENSERS THAT CONTROL DELIVERY OR THAT DO NOT PERMIT CONTINUOUS PAPER FLOW SHALL NOT BE
4. WHEN THE SLOPE IN THE DIRECTION OF TRAVEL OF ANY % GRADIENT WALK EXCEEDS 1 VERTICAL TO 20 HORIZONTAL 5 IT SHALL USED.
UNLESS OTHERWISE NOTED, PLAN DIMENSIONS ARE TAKEN FROM:
COMPLY WITH THE PREVISIONS FOR PEDESTRIAN RAMPS.
1. ROUGH FACE OF STUD TO ROUGH FACE OF STUD.
C.
GENERAL CONTRACTOR SHALL COORDINATE IN FIELD AND SHALL FURR OUT OF WALLS WHERE IN CONFLICT WITH EXISTING STRUCTURE
5. SURFACES ACROSS SLOPES SHALL NOT EXCEED 1: 50 SLOPE.
OR UTILITIES AS REQUIRED.
SIGNAGE AND IDENTIFICATION:
6. WALKS, SIDEWALKS, AND PEDESTRIAN WAYS SHALL BE FREE OF GRATINGS WHENEVER POSSIBLE. FOR GRATINGS LOCATED IN THE
2. FACE TO FACE OF CONCRETE MASONRY UNIT OR FACE OF CONCRETE MASONRY UNIT TO ROUGH FACE OF STUD.
A.
3.
7.
MEASUREMENTS ARE TO ROUGH OPENINGS. GENERAL CONTRACTOR SHALL VERIFY ACTUAL ROUGH OPENING SIZE WITH DOOR AND/OR
DIFFERENT FROM THE COLOR AND CONTRAST OF THE DOOR. IN ADDITION, THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL BE
WINDOW MFR.
8. USAGE SHALL BE FLOOR PLACED DIRECTLY BELOW THE SYMBOL AND ACCOMPANIED BY GRADE 2 BRAILLE AS DESCRIBED IN NOTE C.
4. STUD DIM. ARE ROUNDED OFF TO NEAREST INCH. FOR ACTUAL STUD SIZES REFER TO PARTITION TYPE DETAILS.
9. WALKS SHALL BE PROVIDED WITH A LEVEL AREA NOT LESS THAN 60 INCHES AT A DOOR OR GATE THAT SWINGS TOWARD THE WALK, AND
THE GENERAL CONTRACTOR SHALL CONSTRUCT THE BUILDING IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL CODES, LAWS AND
NOT LESS THAN 48 INCHES WIDE BY 44 INCHES DEEP AT A DOOR OR GATE THAT SWINGS AWAY FROM THE WALK. SUCH WALKS SHALL B. WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, PROVIDE BRAILLE SIGN. SIGN SHALL BE ADJACENT TO THE
REGULATIONS IN ORDER TO INSURE A FINAL CERTIFICATE OF OCCUPANCY FROM GOVERNING AUTHORITIES. THE GENERAL CONTRACTOR
EXTEND 24 INCHES TO THE SIDE OF THE STRIKE EDGE OF A DOOR OR GATE THAT SWINGS TOWARD THE WALK.
AND SUB-CONTRACTOR(S) SHALL FULLY AND CAREFULLY INFORMED HIMSELF/HERSELF REGARDING ALL INFORMATION ON ALL DRAWINGS
AND SPECIFICATIONS DURING THE BID PROCESS AND SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH WORK OF
ACCESSIBLE FLOOR AND LEVEL REQUIREMENTS: C.
CONTRACT IS TO BE PERFORMED INCLUDING TOPOGRAPHY, APPROACHES AND IMPROVEMENTS ON OR ABOUT SITE, PROTECTION OF
ADJACENT BUILDINGS AND PROPERTY. THE GENERAL CONTRACTOR SHALL NOT ASSUME ON INFORMATION THAT IS OR SEEMS INCOMPLETE
1. IN BUILDINGS AND FACILITIES, FLOORS OF A GIVEN STORY SHALL BE COMMON LEVEL THROUGHOUT, OR SHALL BE CONNECTED BY

PRIMITIVO E. CONDE, RA ARCHITECT AR0014406 W W W . S D C O L L A B O R A T I V E . C O M


FL 33176
A A 2 6 0 0 3 9 0 2
OR NOT PROPERLY COORDINATED WITHIN DIFFERENT TRADES. THE GENERAL CONTRACTOR SHALL CONTACT ARCHITECT/ENGINEERS OF
PEDESTRIAN RAMPS, PASSENGER ELEVATORS, OR SPECIAL ACCESS LIFTS
RECORD THROUGH THE CONSTRUCTION PROJECT MANAGER FOR CLARIFICATIONS DURING BID PROCESS FOR PROPER AND REALISTIC
ESTIMATE AS REQUIRED.
2. FLOOR SURFACES SHALL BE SLIP-RESISTANT. D. ALL BLDG ENTRANCES THAT ARE ACCESSIBLE TO AND USABLE BY PERSONS WITH DISABILITIES AND AT EVERY MAJOR JUNCTION ALONG

11410 N. KENDAL DRIVE - UNIT 208 MIAMI,


OR LEADING TO AN ACCESSIBLE ROUTE OF TRAVEL, SHALL BE IDENTIFIED WITH A SIGN DISPLAYING THE INTERNATIONAL SYMBOL OF
THE GENERAL CONTRACTOR(S), BY BIDDING, CERTIFY THAT THE DRAWINGS AND THE SPECIFICATION BOOK HAVE BEEN REVIEWED AND THAT
ACCESSIBILITY.
LABOR AND MATERIALS REQUIRED FOR A COMPLETE AND PROPER INSTALLATION ARE INCLUDED IN THEIR SUBMITTED BIDDING
ADDITIONAL ACCESSIBLE REQUIREMENTS:
DOCUMENTS. UNLESS OTHERWISE NOTED, THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE BUILDING PERMIT COST AS
E. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL CONSIST OF A WHITE FIGURE ON A BLUE BACKGROUND. THE BLUE SHALL EQUAL

P : 3 0 5 7 4 0 6 9 4 8
WELL AS THE PERMITS REQUIRED BY ALL TRADES THAT ARE NECESSARY TO COMPLETE THE WORK AS DESCRIBED IN THE CONSTRUCTION
1. THE CENTER OF RECEPTACLE OUTLETS SHALL BE NO LESS THAN 12 INCHES ABOVE THE FLOOR OR WORKING PLATFORM. THE COLOR NO. 15090 IN FEDERAL STANDARD 599B.
DOCUMENTS.
2. THE CENTER OF THE GRIP OF THE OPERATING HANDLE OF SWITCHES INTENDED TO BE USED BY THE OCCUPANT OF THE ROOM OR AREA F. EACH PARKING SPACE RESERVED FOR PERSONS WITH DISABILITIES SHALL BE IDENTIFIED BY A REFLECTORIZED SIGN PERMANENTLY
FLORIDA BUILDING CODES (FBC):
TO CONTROL LIGHTING OR RECEPTACLE OUTLETS, APPLIANCES, OR COOLING, HEATING AND VENTILATING EQUIPMENT SHALL BE NOT LESS POSTED IMMEDIATELY ADJACENT TO, AND VISIBLE FROM EACH STALL OR SPACE, CONSISTING OF THE INTERNATIONAL SYMBOL OF
- FLORIDA BUILDING CODE - BUILDING (2020 / 7TH EDITION)
THAN 3 FEET NOR MORE THAN 4 FEET ABOVE THE FLOOR OR WORKING PLATFORM. ACCESSIBILITY IN WHITE ON A DARK BLUE BACKGROUND (AS PER FEDERAL STANDARD 599B). THE SIGN SHALL NOT BE SMALLER THAN 70
- FLORIDA BUILDING CODE - MECHANICAL (2020 / 7TH EDITION)
- FLORIDA BUILDING CODE - PLUMBING (2020 / 7TH EDITION)
3. THE CENTER OF THE FIRE ALARM INITIATING DEVICES (BOXES) SHALL BE LOCATED 48 INCHES ABOVE THE LEVEL OF THE FLOOR, SIGN TO THE PARKING SPACE FINISHED GRADE.
- FLORIDA FIRE PREVENTION CODE (2018 / 7TH EDITION)
WORKING PLATFORM, GROUND SURFACE OR SIDEWALK.
SHOP DRAWINGS:
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA):
4. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL BE STANDARD USE TO IDENTIFY FACILITIES THAT ARE ACCESSIBLE TO AND

DULCE M. CONDE, RA ARCHITECT AR0015803


- NATIONAL SPRINKLERS CODE (NFPA 13, 2016 EDITION)
USABLE BY PHYSICALLY DISABLED PERSONS AS SET FORTH IN THESE BUILDING STANDARDS. THE SYMBOL SPECIFIED ABOVE SHALL 1. CONTRACTOR SHALL SUBMIT A MINIMUM OF SEVEN (7) COPIES OF ALL REQUIRED SHOP DRAWINGS. IF THE SHOP DRAWINGS CONSIST OF
- NATIONAL ELECTRIC CODE (NFPA 70, 2017 EDITION)
CONSIST OF A WHITE FIGURE ON A BLUE BACKGROUND. THE BLUE SHALL BE EQUAL TO COLOR NO. 15090 IN FEDERAL STANDARDS 595A. SAMPLES, THEN THE CONTRACTOR SHALL SUBMIT THREE (3) SAMPLES. SHOP DRAWING SUBMITTAL SHALL HAVE THE FOLLOWING MINIMUM
- NATIONAL FIRE ALARM (NFPA 72, 2016 EDITION)
INFORMATION SHOWN ON THE COVER SHEETS:
- LIFE SAFETY CODE (NFPA 101, 2018 EDITION)
5. IF EMERGENCY WARNING SYSTEMS ARE REQUIRED, THEY SHALL ACTIVATE A MEANS OF WARNING THE HEARING IMPAIRED. FLASHING
- ALL OTHER APPLICABLE NFPA CHAPTERS, CODES, STANDARDS AND
VISUAL WARNINGS SHALL HAVE A FREQUENCY OF NOT MORE THAN 60 FLASHES PER MINUTE. 1.1. PROJECT NUMBER
RECOMMENDED PRACTICES
1.2. PROJECT NAME
ACCESSIBLE RAMP REQUIREMENTS: 1.3. PROJECT ADDRESS
OTHER GUIDELINES, CODES AND REGULATIONS:
1.4. CONTRACTOR'S SHOP DRAWING NUMBER
SAFETY CODE FOR ELEVATORS AND ESCALATORS (ANSI/ASME A17.1) (IF APPLICABLE)
1. ANY PATH OF TRAVEL SHALL BE CONSIDERED A RAMP IF ITS SLOPE IS GREATER THAN 1 FOOT RISE IN 20 FEET OF HORIZONTAL RUN. 1.5. REVISION NUMBER
FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD DETAILS.
1.6. DATE RECEIVED
FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION.
2. THE MAXIMUM SLOPE OF A RAMP THAT SERVES ANY EXIT WAY, PROVIDES HANDICAP ACCESS OR IS IN THE PATH OF TRAVEL SHALL BE 1 1.7. DESCRIPTION OF SHOP DRAWING
STATE AND LOCAL OCCUPATIONAL SAFETY AND HEALTH AGENCIES. FOOT RISE IN 12 FEET OF HORIZONTAL RUN. 1.8. SUB-CONTRACTOR NAME
STATE AND LOCAL ENVIRONMENT PROTECTION AGENCIES.
1.9. LAST DATE FOR RETURN TO CONTRACTOR
FEDERAL GOVERNMENT LEGISLATION, REGULATIONS, STANDARDS AND GUIDELINES: 3. DOORS IN ANY POSITION SHALL NOT REDUCE THE MINIMUM DIMENSION OF THE RAMP LANDING TO LESS THAN 42 INCHES AND SHALL
ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAAG) NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 3-1/2 INCH WHEN FULLY OPENED. 2. SHOP DRAWING REVIEW IS ONLY FOR GENERAL CONFORMANCE WITH DESIGN CONCEPT AND INTENT OF CONTRACT DOCUMENTS.
UNIFORM FEDERAL ACCESSIBILITY STANDARDS (UFAS)
CONTRACTOR IS SOLELY RESPONSIBLE FOR VERIFYING DIMENSIONS, FOR ESTABLISHING FABRICATION PROCESSES, MEANS, TECHNIQUES, OWNERSHIP AND USE OF THESE
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) 4. INTERMEDIATE LANDINGS AT A CHANGE OF DIRECTION IN EXCESS OF 30 DEGREES AND BOTTOM LANDINGS SHALL HAVE A DIMENSION IN DOCUMENTS & SPECIFICATIONS AS
SEQUENCES AND PROCEDURES OF CONSTRUCTION, AND FOR COORDINATION OF WORK OF ALL TRADES. EXCEPTIONS TAKEN AND NOTED INSTRUMENTS OF SERVICE ARE AND SHALL
ICC/ANSI A117.1-1998 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES THE DIRECTION OF RAMP RUN OF NOT LESS THAN 60 INCHES. TO INFORMATION SHOWN DOES NOT AUTHORIZE WORK RESULTING IN CONTRACT COST REVISIONS UNLESS SO STATED IN SEPARATE REMAIN THE PROPERTY OF THE ARCHITECT
WHETHER THE PROJECT THEY ARE MADE
LETTER OR CHANGE ORDER. FOR IS EXECUTED OR NOT. THEY SHALL
1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL THE FOLLOWING ITEMS: 5. OTHER INTERMEDIATE LANDINGS SHALL HAVE A DIMENSION IN THE DIRECTION OF RAMP RUN OF NOT LESS THAN 60 INCHES. THE NOT BE USED BY THE OWNER OR OTHERS
ON OTHER PROJECTS OR FOR ADDITIONS
LANDING SHALL BE AT LEAST AS WIDE AS THE RAMP RUN LEADING TO IT. 3. SHOP DRAWINGS WILL NOT BE REVIEWED BY THE ARCHITECT UNLESS THE SHOP DRAWINGS HAVE BEEN PREVIOUSLY REVIEWED BY THE TO THIS PROJECT BY OTHERS, EXCEPT BY
AWNING CANOPIES AGREEMENT IN WRITING AND WITH
CONTRACTOR AND STAMPED APPROVED. THE CONTRACTOR SHALL STAMP AND INITIAL EACH DRAWING, PAGE, CUT SHEET, ETC. OF THE
CEILINGS 6.
APPROPRIATE COMPENSATION TO
SUBMITTAL, INDICATING THEY HAVE REVIEWED THE SUBMITTAL FOR COMPLIANCE WITH THE PLANS AND SPECIFICATIONS. IN THE CASE THE ARCHITECT.
CIVIL - ASPHALT MIX DESIGN CIVIL - CONCRETE MIX DESIGN FOOT OF HORIZONTAL RUN 1:50. THAT THERE IS NO PLACE FOR THE STAMP ON THE FRONT, THE CONTRACTOR SHALL STAMP THE BACK SIDE OF EACH SHEET, INDICATING
CIVIL - SEWER SYSTEM CIVIL - STORM WATER SYSTEM
THE PAGE NUMBER ( I.E. BACK OF PAGE 1 OF 6)
CIVIL - STRIPPING CIVIL - TRAFFIC SIGNAGE 7. HANDRAILS ARE REQUIRED ON RAMPS THAT PROVIDE HANDICAP ACCESS IF THE SLOPE EXCEEDS ONE FOOT RISE IN FIFTEEN FEET OF
CIVIL - WATER SYSTEM CLADDING HORIZONTAL RUN. SEE 4.8.5. 4. GENERAL CONTRACTOR SHALL ALLOW THE ARCHITECT A MINIMUM OF 2 WEEKS FOR SHOP DRAWING REVIEW FOR EACH SHOP
CONCRETE MASONRY BLOCKS CRUSHED STONE AGGREGATE
DRAWING. MULTIPLE SUBMITTAL WILL NOT BE ACCEPTED FOR REVIEW AT THE SAME TIME. IF THE CONTRACTOR SUBMITS MULTIPLE SHOP
CURTAIN WALLS DOORS

COMMENTS
8. HANDRAILS SHALL BE PLACED ON EACH SIDE OF EACH RAMP AND SHALL BE CONTINUOUS THE FULL LENGTH OF THE RAMP AND SHALL DRAWINGS THAN THE ARCHITECT RESERVES THE RIGHT TO ALLOW AMPLE TIME FOR REVIEW, AND IT IS THE RESPONSIBILITY OF THE
EQUIPMENT - ALL TYPES EQUIPMENT - KITCHEN BE THIRTY INCHES TO THIRTY FOUR INCHES ABOVE THE RAMP SURFACE AND SHALL EXCEED A MINIMUM OF ONE FOOT BEYOND THE TOP CONTRACTOR TO SUBMIT A SCHEDULE TO LET THE ARCHITECT KNOW WHICH SHOP DRAWINGS HAVE PRECEDENCE.
ELECTRICAL - DATA AND TELEPHONE ELECTRICAL - FLOOR BOXES AND BOTTOM OF THE RAMP AND THE ENDS SHALL BE RETURNED.
ELECTRICAL - GROUNDING ELECTRICAL - LIGHTING FIXTURES
5. SUBMIT SHOP DRAWINGS FOR REINFORCEMENT STEEL PLACEMENT AND DETAILS FOR ARCHITECT'S APPROVAL. DRAWINGS AND
ELECTRICAL - LIGHTING PROTECTION ELECTRICAL - OUTLETS PULL AND JUNCTION BOXES 9. HANDRAILS PROJECTIONS FROM A WALL HAVE A SPACE OF NOT LESS THAN 1-1/2 INCHES BETWEEN THE WALL AND THE HANDRAIL. CALCULATIONS SHALL BE SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER IN THE STATE OF FLORIDA.
ELECTRICAL - RACEWAYS AND CONDUITS ELECTRICAL - SITE LIGHTING
ELECTRICAL - SWITCH GEAR AND ELECT. PANELS ELECTRICAL - TERMINAL CABINETS 10. THE GRIP PORTION OF THE HANDRAIL SHALL BE NOT LESS THAN 1-1/4 INCH NOR MORE THAN TWO INCHES IN CROSS SECTIONAL 6. CONTRACTOR WILL NOT USE SHOP DRAWING SUBMITTALS FOR OBTAINING CLARIFICATION REGARDING CONTRACT PLANS OR
ELECTRICAL - WIRES AND CABLES ELECTRICAL - WIRING DEVICES DIMENSIONS AND THE SURFACES SHALL BE SMOOTH WITH NO SHARP CORNERS. SPECIFICATION REQUIREMENTS. SUCH CLARIFICATIONS REQUIRED FOR PREPARATION OF COMPLETE AND CORRECT SHOP DRAWINGS
FASTENERS FIRE ALARM
WILL BE REQUESTED BY REQUEST FOR INFORMATION (RFI) THROUGH MIAMI DADE COUNTY PROJECT MANAGER.
FIRE PROTECTION FIRE SPRINKLERS

DATE
11. THE SURFACE OF RAMPS SHALL BE STABLE, FIRM AND SLIP RESISTANT.
HARDWARE HVAC SYSTEM
7. TO FACILITY LOGGING AND DISTRIBUTION OF SUBMITTALS AND TO EXPEDITE SHOP DRAWING REVIEW, THE CONTRACTOR SHALL
INSULATION INTERIOR DRYWALL AND TRIM 12. WHERE THE RAMP SURFACE IS NOT BOUNDED BY A WALL OR FENCE AND THE RAMP EXCEEDS THE FEET IN LENGTH, THE RAMP SHALL COMPLY WITH THE FOLLOWING:
LANDSCAPE - IRRIGATION LANDSCAPE - SITE FURNISHING COMPLY WITH ONE OF THE FOLLOWING REQUIREMENTS.
LINTELS MASONRY UNIT
7.1. PROVIDE A SEPARATE TRANSMITTAL LETTER FOR EACH PACKAGE IN A SUBMITTAL. A PACKAGE MAY CONSIST OF ONE OR MORE

REV NO.
MECHANICAL ACCESSORIES MECHANICAL EQUIPMENT a. A GUIDE CURB A MINIMUM OF TWO INCHES IN HEIGHT SHALL BE PROVIDED AT EACH SIDE OF THE RAMP, OR RELATED ITEMS. FOR A MULTIPLE ITEM PACKAGE, LIST EACH ITEM IN THE TRANSMITTAL. INTERRELATED ITEMS SHOULD BE SUBMITTED
METAL FABRICATION MILLWORK b. A WHEEL GUIDE RAIL SHALL BE PROVIDED, CENTERED THREE INCHES, PLUS A MINUS ONE INCH ABOVE THE SURFACE OF THE AS A PACKAGE. EACH TRANSMITTAL LETTER SHALL HAVE A UNIQUE SUBMITTAL NUMBER.
PAINT - ALL TYPES PANELS RAMP. 7.2. FOR EACH SUBMITTED ITEM, INDICATE THE SPECIFICATION SECTION AND/OR PAY ITEM NUMBER AND DRAWING NUMBER OF THE
PLUMBING PLUMBING ACCESSORIES
CONTRACT PLAN TO WHICH THE SUBMITTAL APPLIES.
PLUMBING FIXTURES PRE-CAST CONCRETE
7.3. CONTRACTOR SHALL VERIFY THAT ALL APPLICABLE ITEMS, ON SUBMITTAL CHECKLIST, SEE NOTE #8, ARE COMPILED WITH PRIOR TO
PRE-STRESSED CONCRETE RAILINGS ACCESSIBLE ENTRANCE REQUIREMENTS: TRANSMITTING SUBMITTAL. CONTRACTOR SHALL INCLUDE COMPLETED COPY OF CHECKLIST WITH SUBMITTAL.
READY MIXED CONCRETE ROOFING
ROOFING ACCESSORIES ROOFING FASTENERS 1. ALL ACCESSIBLE ENTRANCES SHALL BE IDENTIFIED WITH AT LEAST ONE STANDARD SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS 8. SHOP DRAWING SUBMITTAL CHECKLIST
SECURITY SYSTEM SHUTTERS REQUIRED, VISIBLE FROM APPROACHING PEDESTRIAN WAYS. SIGNAGE SHALL BE THE INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE
SIGNAGE - INTERIOR AND EXTERIOR STANDS SYMBOL SHALL BE A WHITE FIGURE ON A BLUE BACKGROUND. PROJECT NUMBER: ________________________________________________________________________
STOREFRONTS STORM PANELS
PROJECT NAME:___________________________________________________________________________
STRUCTURAL COMPONENTS STRUCTURAL ROOF FRAMING 2. LATCHING AND LOCKING DOORS ARE HAND ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL, SHALL BE OPERABLE WITH A SINGLE PROJECT ADDRESS:________________________________________________________________________
STRUCTURAL STEEL AND MISC. STEEL STUCCO TRIMS EFFORT BY LEVER TYPE HARDWARE DESIGN TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING SHOP DRAWING NUMBER:___________________________________________________________________

5050 RESIDENCES
SUNSHADES TILES HARDWARE. REVISION NUMBER:_________________________________________________________________________
VENTS
WINDOWS

5050 NW 22nd Ave


3. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 30 INCHES AND 44 INCHES ABOVE THE FINISH FLOOR. PRIOR TO TRANSMITTING THE SUBMITTAL, THE CONTRACTOR SHALL VERIFY AND SIGN BELOW, INDICATING THAT ALL APPLICABLE ITEMS

(MIXED-USE)
PROJECT: PERMIT SET
ON THE CHECKLIST ARE COMPILED WITH:
2. CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING ALL ADDITIONAL SHOP DRAWINGS SPECIFIED ON THE PROJECT DRAWINGS AND 4. THE FLOOR OR LANDING ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR SHALL BE LEVEL AND CLEAR. THE LEVEL AND CLEAR AREA
SPECIFICATIONS. SHALL HAVE A LENGTH IN THE DIRECTION OF DOOR SWING OF AT LEAST 60 INCHES AND THE LENGTH OPPOSITE DIRECTION OF DOOR _____ TRANSMITTAL LETTER INDICATES ITEMS ON NOTE #1.
SWING OF 44 INCHES AS MEASURED AT RIGHT ANGLES TO THE PLANE OF THE DOOR ON ITS CLOSED POSITION.
_____ SUBMITTAL PACKAGE CONTAINS ONLY RELATED ITEMS.
ACCESSIBLE PARKING REQUIREMENTS: 5. THE WIDTH OF THE LEVEL AND CLEAR AREA ON THE SIDE TO WHICH THE DOOR SWINGS SHALL EXTEND 24 INCHES PAST TO THE STRIKE
EDGE OF THE DOOR FOR EXTERIOR DOORS AND 18 INCHES PAST THE STRIKE EDGE FOR INTERIOR DOORS. _____ CONTRACTOR APPROVAL STAMP.
1.
6. _____ ALL REVISIONS FROM PREVIOUSLY PROCESSED SUBMITTALS ARE IDENTIFIED BY CLOUDING WITH REVISION NUMBER AND DATE.
LICENSE PLATES ISSUED FOR PHYSICALLY HANDICAPPED PERSONS MAY BE TOWED. VEHICLES MAY BE RECLAIMED BY TELEPHONING
_____ MINOR PLAN DEVIATIONS NOT AFFECTING CONTRACT TIME, COST, DESIGN INTENT (STRUCTURAL INTEGRITY AND LOAD BEARING
7. THE BOTTOM 10 INCHES OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW CAPACITY) OR REDUCING DURABILITY/MAINTAINABILITY ARE IDENTIFIED BY CLOUDING.
2. EACH PARKING SPACE RESERVED FOR A DISABLED SHALL BE IDENTIFIED BY A PERMANANTLY AFFIXED REFLECTORIZED SIGN THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. WHEN NARROE FRAME
CONSTRUCTED OF PORCELAIN ON STEEL, WITH BEADED TEXT, OR EQUAL, DISPLAYING OF INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE DOORS ARE USED, A 10 INCH HIGH SMOOTH PANEL SHALL BE INSTALLED TO THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR _____ SPECIFICATION SECTION AND CONTRACT PLAN NUMBER ARE REFERENCE FOR EACH ITEM IN THE SUBMITTAL.
SIGN SHALL NOT BE SMALLER THAN 70 SQ. IN. IN AREA AND SHALL BE CENTERED EITHER ON A POST OF 80 INCHES FROM THE BOTTOM OF TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION.
_____ DIMENSIONS AND DETAILS CHECKED AND COORDINATED FOR COMPATIBILITY WITH WORK OF ALL SUBCONTRACTORS.
ACCESSIBILITY STENCILED IN BLUE ON THE PARKING SURFACE. 8. ALL INTERIOR DOORS SHALL BE OPERABLE WITH A SIGNLE EFFORT (NO GRASPING OR WRIST MOVEMENT) MOUNTED BETWEEN 30
INCHES AND 44 INCHES ABOVE THE FINISH FLOOR. ALLOWABLE CLOSURE PRESSURE: INTERIOR HINGED DOORS - 5 POUNDS EXTERIOR 1. _____ EXISTING
ALL EXPOSED CONDITIONS
CONCRETE AND DIMENSIONS
- CLASS USED IN DEVELOPING SHOP DRAWING DETAILS ARE FIELD VERIFIED.
B FORMED FINISH.
3. HINGED DOORS - 8.5 POUNDS FIRE DOORS - 1.5 POUNDS.
2. ALL NON EXPOSED CONCRETE - CLASS C FORMED FINISH.
4. URINALS
DIRECTION
3. ALL STAIRS ARE CAST IN PLACE WITH FIELD PAINTED STEEL RAILINGS.
A.
5. DISABLED PARKING SPACE SHALL BE LOCATED SO AS NOT TO REQUIRE ITS USER TO WHEEL OR WALK BEHIND ANY OTHER DISABLED OR
4. TO THE BEST OF THE ARCHITECTS KNOWLEDGE THE PLANS AND SPECIFICATIONS COMPLY WITH APPLICABLE MINIMUM BUILDING CODE
NON-DISABLED PARKING SPACE. B.

AS NOTED
04-05-2021
AND WITH APPLICABLE FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER 633, FLORIDA

PROJECT NO.: 20-004-00


ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND SHALL ACCOMMODATE A SIGNLE STATIONARY WHEELCHAIR AND OCCUPANT.

PEC/JCC
SITUATES AND FBC 110.8.4.4

DC/PEC
6. PEDESTRIAN WAYS WHICH ARE ACCESSIBLE TO THE PHYSICALLY DISABLED SHALL BE PROVIDED FROM EACH DISABLED PARKING SPACE
TO RELATED FACILITIES, INCLUDING CURB CUTS OR RAMPS AS NEEDED. C. 5. ALL SHORING AND RE-SHORING PROCEDURES , PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORD
KEEPING. EACH SHORING AND RE-SHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE WITH
7. IN ADDITION TO THE ABOVE SIGNAGE REQUIREMENTS, THE SURFACE OF EACH PARKING SPAE SHALL HAVE A SURFACE IDENTIFICATION
SHORING DOCUMENTS BY THE CONTRACTOR AS PER FBC 110.8.4.3
D. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND OPERATED CONTROLS AND MECHANISMS SHALL BE OPERABLE
WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE

ISSUE DATE:

DRAWN BY:
ACCESSIBLE WALK AND SIDEWALK REQUIREMENTS:

CHECKED:
FINISHED DOOR.

SCALE:
1. WALKS AND SIDEWALKS SUBJECT TO THESE REGULATIONS SHALL HAVE A CONTINUOUS COMMON SURFACE, NOT INTERRUPTED BY TOILET ROOM ACCESSORIES:

A.
2. SURFACE WITH A SLOPE OF 6 PERCENT GRADIENT SHALL BE AT LEAST AS SLIP-RESISTANT AS THAT DESCRIBED AS A MEDIUM SALTED
FINISH. B.
General Notes
3. SURFACES WITH A SLOPE OF 6 PERCENT GRADIENT OR GREATER SHALL BE SLIP-RESISTANT.

General Notes
1
NTS A001b