Chiller 2 Circuit A:
FINDINGS:
FINDINGS:
2. Chiller 2 Circuit B super Heat is on higher side (22C), And Expansion valve is
fully open (100%). Refrigerant Top-up required.
RECOMMENDATIONS:
Required Maintenance:
MANPOWER REQUIRED:
1 Expert Engineer with 2 Technician for 6 days for Technical Maintenance Works
Troubleshooting:
a. Further troubleshooting required to find the root cause of the low economizer
Pressure in circuit B
b. Further troubleshooting required to find the root cause of high compressor motor
temperature of compressor B1