GENERAL NOTES

-:DIVERSITY FACTOR #

AC =0.9 , W.H = 0.3 , COOKER = 0.4 , G.L =0 .6 , OTHER = 0.5,


MACHINES=0.8 ( IN CASE WE HAVE MACHINES IN OUR PROJECT WE CONSIDER
DIVERSITY OF OTHERS AND MACHINE THE SAME)

AC >> AC UNITS , VENTLATION ( EX. FAN AND FA FAN ) ( AT PUMP ,GENERATOR , LV ,


MV , SERVICES ROOMS , BASEMENTS , PRESSURIZATION FANS AT STAIRS AND LIFT
LOBBIES ) , AHU , ERU , CHLILED WATER PUMP

WH >> CENTRAKL WATER HEATER , INDIVIDUAL WATER HEATER

COOKER >> COOKER AT KITCHEN ( 3000 W )

GL >> LIGHTING , POWER , SMALL EX FAN AT KITCHEN AND TOILETS

OTHERS >> PUMPS , LIFTS

STANDARD OF DB CIRCUIT IS 4, 6 , 8 , 10 , 12 , 14 , 16 -

IN QATAR SINGLE PHASE VOLTAGE =240V & THREE PHASE VOLTAGE = 415 V -

DB LOAD DOESN'T EXCEED 60KW AND 125 A CB -

OOREDOO ROOM MUST BE 125A C.B &CABLE ( 4X70+35 )mm2 ,10 CIRCUIT -

MAIN CB OF DB MUST BE BIGGER THAN THE BIGGEST CB AT THE DB -

MINIMUM CB CURRENT RATING OF DB FROM LVP >> 40 A-

BUS RISER SUPPLY MAXIMUM 6 FLOORS-

.BUS RISER IN CASE OF (G+5) BUILDING WILL START FROM FOURTH FLOOR -