Professional Documents
Culture Documents
CLASS PRESSU SUITABLE FOR ST PR. LIMIT MAX. VEL AIR LEAK LIMIT
RE +VE -VE
(Pascal) (m/s) (L/s/m²)
A LOW Branch & outlet 500 500 10 0.027Xp⅔
B MEDIUM Zone main duct 1000 750 20 0.009Xp⅔
C HIGH Plant room/riser 2000 750 40 0.003Xp⅔
Where 'p' is differential pressure.
Drop rod 6 8 10 12
Ref: DW144