PRESSURE CLASSIFICATION OF DUCTS

CLASS PRESSU SUITABLE FOR ST PR. LIMIT MAX. VEL AIR LEAK LIMIT
RE +VE -VE
(Pascal) (m/s) (L/s/m²)
A LOW Branch & outlet 500 500 10 0.027Xp⅔
B MEDIUM Zone main duct 1000 750 20 0.009Xp⅔
C HIGH Plant room/riser 2000 750 40 0.003Xp⅔
Where 'p' is differential pressure.

SPECIFICATIONS FOR LOW & MED PRESSURE RECTANGULAR DUCTS


Longer Side 400 600 800 1000 1250 1500 2000 2500 3000
Sheet thickness 0.6 0.8 1 1.2

Drop rod 6 8 10 12

Bearer angle 25X25X1.6 25X25X3 30X30X3 40X40X3 50X50X3 60X60X3

Spacing 3000 2500

Ref: DW144