615 Series General Presentation - 756700 - ENh
615 Series General Presentation - 756700 - ENh
© ABB Group
November 12, 2015 | Slide 1 | 1MRS756700 H
Relion® 615 series
Contents
© ABB Group
November 12, 2015 | Slide 2 | 1MRS756700 H
Relion® 615 series
Products
© ABB Group
November 12, 2015 | Slide 3 | 1MRS756700 H
Main customer benefits
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 4 | 1MRS756700 H
Relion® 615 series
Main customer benefits 1(5)
© ABB Group
November 12, 2015 | Slide 5 | 1MRS756700 H
Relion® 615 series
Main customer benefits 2(5)
© ABB Group
November 12, 2015 | Slide 6 | 1MRS756700 H
Relion® 615 series
Main customer benefits 3(5)
© ABB Group
November 12, 2015 | Slide 7 | 1MRS756700 H
Relion® 615 series
Main customer benefits 4(5)
© ABB Group
November 12, 2015 | Slide 8 | 1MRS756700 H
Relion® 615 series
Main customer benefits 5(5)
© ABB Group
November 12, 2015 | Slide 9 | 1MRS756700 H
New features
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 10 | 1MRS756700 H
Relion® 615 series
IEC 61850 Edition 2
© ABB Group
November 12, 2015 | Slide 11 | 1MRS756700 H
Relion® 615 series
IEC 61850 conformance
© ABB Group
November 12, 2015 | Slide 12 | 1MRS756700 H
Relion® 615 series
Multifrequency admittance-based E/F protection 1(3)
© ABB Group
November 12, 2015 | Slide 13 | 1MRS756700 H
Relion® 615 series
Multifrequency admittance-based E/F protection 2(3)
_+90 deg
Im(Yo) Easy setting principles based on basic
network data
REVERSE FORWARD
Operation characteristic valid both in
compensated and unearthed networks
Fault direction indication both in operate
_0 deg
Re(Yo) direction and non-operate direction
Yosum_CPS
© ABB Group
November 12, 2015 | Slide 14 | 1MRS756700 H
Relion® 615 series
Multifrequency admittance-based E/F protection 3(3)
© ABB Group
November 12, 2015 | Slide 15 | 1MRS756700 H
Relion® 615 series
Process bus with sampled values of currents and voltages
The relay can act as a merging unit and measure currents and
voltages in the substation and send them as Sampled Measured
Values (SMV) over Ethernet.
Other relays in the substation having phase voltage-based
functions can receive the SMVs over Ethernet and use them for
the following purposes:
Instead of physically (VT or voltage sensor) measured phase voltages
For synchro-check
The SMVs are transferred using the IEC 61850-9-2 LE (light
edition) protocol.
The relay uses IEEE 1588 V2 Precision Time Protocol (PTP) with
Power Profile for high-accuracy time synchronization.
Benefits:
Simplicity (reduces wiring and terminals)
Flexibility
Improved diagnostics
Longer maintenance cycles
© ABB Group
November 12, 2015 | Slide 16 | 1MRS756700 H
Relion® 615 series
System example of utilizing process bus
© ABB Group
November 12, 2015 | Slide 17 | 1MRS756700 H
Relion® 615 series
Other functional enhancements 1(3)
© ABB Group
November 12, 2015 | Slide 18 | 1MRS756700 H
Relion® 615 series
Other functional enhancements 2(3)
RED615
HSR and PRP-1 with fiber-optic redundant Ethernet
IEC 61850-9-2 LE and IEEE 1588 v2 with fiber-optic
redundant Ethernet
REF615 standard configurations L and N
Optional interconnection protection functions
Reverse power/directional overpower
Standard configuration N can alternatively be used for
high-impedance based differential protection
Non-directional overcurrent and earth-fault protection
added to standard configuration L
Frequency and voltage protection instances added
© ABB Group
November 12, 2015 | Slide 19 | 1MRS756700 H
Relion® 615 series
Other functional enhancements 3(3)
REV615
Optional residual current input 0.2/1 A
Transient/intermittent earth-fault protection
RET615
Frequency measurements added to standard
configurations with voltage inputs
REM615
One non-directional overcurrent protection instance
added
© ABB Group
November 12, 2015 | Slide 20 | 1MRS756700 H
Common features
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 21 | 1MRS756700 H
Relion® 615 series
Designed for IEC 61850
© ABB Group
November 12, 2015 | Slide 22 | 1MRS756700 H
Relion® 615 series
Standard conf. for rapid setup and commissioning
Ready-made adaptations
(standard configurations)
Adjusting of standard signal
configuration settings possible with the
setting and configuration tool PCM600
Rapid relay setup and commissioning
after tailoring according to application-
specific requirements
© ABB Group
November 12, 2015 | Slide 23 | 1MRS756700 H
Relion® 615 series
Application-specific tailoring of standard configurations
© ABB Group
November 12, 2015 | Slide 24 | 1MRS756700 H
Relion® 615 series
Control of primary devices with dedicated push-buttons
© ABB Group
November 12, 2015 | Slide 25 | 1MRS756700 H
Relion® 615 series
Patented and compact plug-in unit design
© ABB Group
November 12, 2015 | Slide 26 | 1MRS756700 H
Relion® 615 series
Disturbance recorder for in-depth analysis
Example:
© ABB Group
November 12, 2015 | Slide 27 | 1MRS756700 H
Relion® 615 series
Operation traceability for pre and post-fault analysis
© ABB Group
November 12, 2015 | Slide 28 | 1MRS756700 H
Relion® 615 series
Condition monitoring for ensured protection availability
© ABB Group
November 12, 2015 | Slide 29 | 1MRS756700 H
Relion® 615 series
Authorized relay access control
PCM600
© ABB Group
November 12, 2015 | Slide 30 | 1MRS756700 H
Relion® 615 series
Versatile tools supporting engineering and operation
PCM600
One single tool for managing settings, signal
configuration and disturbance handling
Web browser-based user interface
Local or remote relay access using a web
browser
Internet Explorer version 8.0, 9.0, 10.0 and 11.0
are verified
Relay-specific connectivity packages
For automatic configuration via MicroSCADA
Pro SYS600, Substation Management Unit
COM600 or PCM600
Substation Management Unit COM600
MicroSCADA Pro
PCM600 2.6 (with Rollup 20150626) or later
© ABB Group
November 12, 2015 | Slide 31 | 1MRS756700 H
Relion® 615 series
Single line diagrams (SLD) for bay-level overview
© ABB Group
November 12, 2015 | Slide 33 | 1MRS756700 H
Relion® 615 series
Thermal overload protection with RTD/mA measuring
Oli temperature
Ambient temperature
Pressure
© ABB Group
November 12, 2015 | Slide 34 | 1MRS756700 H
Relion® 615 series
Extended control of primary network devices
© ABB Group
November 12, 2015 | Slide 35 | 1MRS756700 H
Relion® 615 series
Fault records and events
© ABB Group
November 12, 2015 | Slide 36 | 1MRS756700 H
Relion® 615 series
Parallel protocols
© ABB Group
November 12, 2015 | Slide 37 | 1MRS756700 H
Relion® 615 series
Redundancy solutions
© ABB Group
November 12, 2015 | Slide 38 | 1MRS756700 H
Relion® 615 series
IEC 61850 Ethernet redundancy HSR
© ABB Group
November 12, 2015 | Slide 39 | 1MRS756700 H
Relion® 615 series
IEC 61850 Ethernet redundancy HSR - operation principle
© ABB Group
November 12, 2015 | Slide 40 | 1MRS756700 H
Relion® 615 series
IEC 61850 Ethernet redundancy PRP
© ABB Group
November 12, 2015 | Slide 41 | 1MRS756700 H
Relion® 615 series
Self-healing Ethernet ring
© ABB Group
November 12, 2015 | Slide 42 | 1MRS756700 H
Relion® 615 series
High-speed outputs for time-critical applications
400
Sheet steel burn-up
Copper burn-up
Available as an option
Cable fire
0
0 100 200 300 400
ms
© ABB Group
November 12, 2015 | Slide 43 | 1MRS756700 H
Relion® 615 series
Load profile recorder
© ABB Group
November 12, 2015 | Slide 44 | 1MRS756700 H
Relion® 615 series
Profibus DPV1 protocol
© ABB Group
November 12, 2015 | Slide 45 | 1MRS756700 H
Relion® 615 series
IEEE 1588 time synchronization
© ABB Group
November 12, 2015 | Slide 46 | 1MRS756700 H
Relion® 615 series
IEEE 1588 time synchronization example using HSR
© ABB Group
November 12, 2015 | Slide 47 | 1MRS756700 H
Feeder protection and control
REF615
© ABB Group
November 12, 2015 | Slide 48 | 1MRS756700 H
REF615
Description
© ABB Group
November 12, 2015 | Slide 49 | 1MRS756700 H
REF615
Area of application
© ABB Group
November 12, 2015 | Slide 50 | 1MRS756700 H
REF615
Standard configurations 1(3)
Standard configuration A
Non-directional overcurrent and directional earth-fault protection
Standard configuration B
Non-directional overcurrent and directional earth-fault protection and
circuit-breaker condition monitoring (RTD option)
Standard configuration C
Non-directional overcurrent and earth-fault protection
Standard configuration D
Non-directional overcurrent and earth-fault protection and circuit-
breaker condition monitoring (RTD option)
Standard configuration E
Non-directional overcurrent and directional earth-fault protection,
voltage-based measurements and circuit-breaker condition
monitoring (RTD option)
Standard configuration F
Directional overcurrent and earth-fault protection, voltage-based
protection and measurements, and circuit-breaker condition
monitoring (RTD option)
© ABB Group
November 12, 2015 | Slide 51 | 1MRS756700 H
REF615
Standard configurations 2(3)
Standard configuration G
Directional overcurrent and earth-fault protection, voltage-based
protection and measurements, and circuit-breaker condition
monitoring (sensor inputs and optional synchro-check with IEC
61850-9-2 LE)
Standard configuration H
Non-directional overcurrent and earth-fault protection, voltage and
frequency-based protection and measurements,
synchro-check and circuit-breaker condition monitoring (RTD option)
Standard configuration J
Directional overcurrent and earth-fault protection, voltage and
frequency-based protection and measurements,
synchro-check and circuit-breaker condition monitoring (optional
power quality and RTD option)
© ABB Group
November 12, 2015 | Slide 52 | 1MRS756700 H
REF615
Standard configurations 3(3)
Standard configuration K
Directional and non-directional overcurrent and earth-fault protection,
high-impedance restricted earth-fault protection, voltage and frequency-
based protection and measurements, synchro-check and circuit-breaker
condition monitoring (optional power quality and fault locator)
Standard configuration L
Directional and non-directional overcurrent and earth-fault protection with
multifrequency neutral admittance, voltage, frequency and power-based
protection and measurements, and circuit-breaker condition monitoring
(sensor inputs, optional power quality, fault locator, interconnection
protection and synchro-check with IEC 61850-9-2LE)
Standard configuration N
Directional and non-directional overcurrent and earth-fault protection with
multifrequency neutral admittance, voltage, frequency and power-based
protection and measurement, high-impedance differential protection,
synchro-check and circuit-breaker condition monitoring (optional power
quality, fault locator and interconnection protection)
© ABB Group
November 12, 2015 | Slide 53 | 1MRS756700 H
RED615
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 54 | 1MRS756700 H
RED615
Description
RED615 is a phase-segregated,
two-end, unit-type line differential
protection and control relay designed for
protection, control, measurement and
supervision in utility and industrial power
distribution systems, including radial,
looped and meshed distribution
networks, with or without distributed
power generation.
RED615 is also suitable for line
differential applications with an in-zone
transformer.
RED615 relays communicate between
substations either over a fiber-optic link
or a galvanic pilot wire connection.
© ABB Group
November 12, 2015 | Slide 55 | 1MRS756700 H
RED615
Selective protection for specified zone
© ABB Group
November 12, 2015 | Slide 56 | 1MRS756700 H
RED615
Line differential protection applications
Parallel feeders
Looped feeder construction
Doubled feeders
© ABB Group
November 12, 2015 | Slide 57 | 1MRS756700 H
RED615
Standard configurations
Standard configuration A
Line differential protection
Standard configuration B
Line differential protection with directional earth-fault
protection and circuit-breaker condition monitoring
Standard configuration C
Line differential protection with non-directional earth-
fault protection and circuit-breaker condition
monitoring
Standard configuration D
Line differential protection with directional overcurrent
and earth-fault protection, voltage and frequency-
based protection and measurements, synchro-check
and circuit-breaker condition monitoring (RTD option,
optional power quality and fault locator)
Standard configuration E
Line differential protection with directional overcurrent
and earth-fault protection, voltage and frequency-
based protection and measurements, and circuit-
breaker condition monitoring (sensor inputs, optional
power quality, fault locator and synchro-check with
IEC 61850-9-2LE)
© ABB Group
November 12, 2015 | Slide 58 | 1MRS756700 H
Motor protection and control
REM615
© ABB Group
November 12, 2015 | Slide 59 | 1MRS756700 H
REM615
Description
© ABB Group
November 12, 2015 | Slide 60 | 1MRS756700 H
REM615
Area of application
Circuit-breaker or contactor-controlled
high-voltage (HV) motors
Contactor-controlled, medium-sized and
large low-voltage (LV) motors
Manufacturing, process and refinery
industry
Protection for a variety of drives
such as:
Pumps and conveyors
Compressors
© ABB Group
November 12, 2015 | Slide 61 | 1MRS756700 H
REM615
Standard configurations
Standard configuration A
Motor protection with circuit-breaker condition
monitoring (RTD option)
Standard configuration B
Motor protection with voltage and frequency-based
protection and measurements, and circuit-breaker
condition monitoring (RTD option)
Standard configuration C
Motor protection with voltage and frequency-based
protection and measurements, and circuit-breaker
condition monitoring
Standard configuration D
Motor protection with voltage and frequency-based
protection and measurements, and circuit-breaker
condition monitoring (sensor inputs)
© ABB Group
November 12, 2015 | Slide 62 | 1MRS756700 H
REU615
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 63 | 1MRS756700 H
REU615
Description
© ABB Group
November 12, 2015 | Slide 64 | 1MRS756700 H
REU615
Voltage protection (standard configuration A)
© ABB Group
November 12, 2015 | Slide 65 | 1MRS756700 H
REU615
Area of application (standard configuration A)
© ABB Group
November 12, 2015 | Slide 66 | 1MRS756700 H
REU615
Voltage regulation (standard configuration B)
© ABB Group
November 12, 2015 | Slide 67 | 1MRS756700 H
REU615
Area of application (standard configuration B)
© ABB Group
November 12, 2015 | Slide 68 | 1MRS756700 H
Transformer protection and control
RET615
© ABB Group
November 12, 2015 | Slide 69 | 1MRS756700 H
RET615
Description
© ABB Group
November 12, 2015 | Slide 70 | 1MRS756700 H
RET615
Area of application
© ABB Group
November 12, 2015 | Slide 71 | 1MRS756700 H
RET615
Standard configurations
Standard configuration A
Transformer differential with low-impedance restricted earth-fault protection on the
HV side
Standard configuration B
Transformer differential with low-impedance restricted earth-fault protection on the
LV side
Standard configuration C
Transformer differential with high-impedance restricted earth-fault protection on the
HV side
Standard configuration D
Transformer differential with high-impedance restricted earth-fault protection on the
LV side
Standard configuration E
Transformer differential with voltage protection and measurements, and
low-impedance restricted earth-fault protection on the HV side
Standard configuration F
Transformer differential with voltage protection and measurements, and
low-impedance restricted earth-fault protection on the LV side
Standard configuration G
Transformer differential with voltage protection and measurements, and
high-impedance restricted earth-fault protection on the HV side
© ABB Group
November 12, 2015 | Slide 72 | 1MRS756700 H
Capacitor bank protection and control
REV615
© ABB Group
November 12, 2015 | Slide 73 | 1MRS756700 H
REV615
Description
© ABB Group
November 12, 2015 | Slide 74 | 1MRS756700 H
REV615
Area of application
© ABB Group
November 12, 2015 | Slide 75 | 1MRS756700 H
REV615
Standard configurations
Standard configuration A
Capacitor bank overload and unbalance protection, non-directional
overcurrent and earth-fault protection and circuit-breaker condition
monitoring
Standard configuration B
Capacitor bank overload and unbalance protection, non-directional
overcurrent and directional earth-fault protection, voltage and
frequency based protection and measurements, and circuit-breaker
condition monitoring
© ABB Group
November 12, 2015 | Slide 76 | 1MRS756700 H
ABB solutions
Relion® 615 series
© ABB Group
November 12, 2015 | Slide 77 | 1MRS756700 H
Relion® 615 series
Supported ABB solutions 1(2)
© ABB Group
November 12, 2015 | Slide 78 | 1MRS756700 H
Relion® 615 series
Supported ABB solutions 2(2)
© ABB Group
November 12, 2015 | Slide 79 | 1MRS756700 H
Relion® 615 series
Supported ABB solutions example
© ABB Group
November 12, 2015 | Slide 80 | 1MRS756700 H
Conclusions
© ABB Group
November 12, 2015 | Slide 81 | 1MRS756700 H
Relion® 615 series
Conclusions