ATC-300 Automatic Transfer Switch Controller Front Panel Display and Operator Functions
Unit Status
The Unit Status LED
is a blinking indicator
for self and system
diagnostics.
LCD-Based Display
The LCD-based
display is a backlit,
Mimic Diagram 2-line, 16-character
Source 1 and Source display. Displayed
2 color-coded LEDs information includes:
provide Available ■ Source voltages
and Connected and frequency
status indication.
■ Time/date stamp
Step/Enter ■ Historical data
Pressing the Step/ ■ Programming and
Enter pushbutton set point
advances the information
information through ■ Password entry
the programming or
display cycle.
Increase and
Help Decrease
Pressing the Help Pressing the Increase
pushbutton in any or Decrease
function mode will pushbuttons effect
bring up display the value of the
messages, function presently
explanations and active on the
prompts to assist LCD-based display.
the operator.
Engine Test
Pressing the Engine
Test pushbutton
twice initiates
engine test cycle.
Alarm Reset
Pressing the Increase
and Decrease
pushbuttons
Lamp Test Bypass TDNE/TDEN
simultaneously
Pressing the Lamp Test Pressing Step and Help/Lamp Test restores automatic
pushbutton lights all LEDs and pushbuttons simultaneously operation in the
then displays ATC-300 controller reduces programmed time delays event of an alarm
information. to zero to simplify test procedures. condition).
Control Power
Inputs
Power Source
Inputs
0.95
(24.1)
Edge of Enclosure
Door Cutout
5.35 7.75
(135.9) (196.9)
0.16 0.16
(22.1) (22.1) 1.45
5.43 (36.8)
(137.9)
5.75
(146.1) ATC-300 Faceplate