You are on page 1of 1

Steel Duct Temp Estimation

without With mineral Wool Insulation


Insulation
Gas Temp in the duct Deg C 600 600 600 600
Ambient Temp Deg C 30 30 30 30
Wind velocity m/s 1 1 1 1
Assumed surface Temp Deg C 92.7 57.1 47.8 43.4
Surface heat transfer coeff W/m2 K 19.5 16.1 14.9 14.2
Mineral Wool Thickness mm 0 50 100 150
Thermal Conductivity of mineral wool W/m K 0.06 0.06 0.06 0.06
Insulyte K Thickness mm 60 60 60 60
Thermal Conductivity of insulyte 7 w /m K 0.16 0.16 0.16 0.16
Whteheat K Thickness mm 40 40 40 40
Thermal Conductivity of Whyteheat K w /m K 1.9 1.9 1.9 1.9
Thermal resistances
Outside surface m2 K/W 0.051 0.062 0.067 0.070
Mineral Wool Layer m2 K/W 0.000 0.833 1.667 2.500
Insulyte 7 Layer m2 K/W 0.369 0.369 0.369 0.369
Whyteheat K Layer m2 K/W 0.021 0.021 0.021 0.021
Inside heat transfer coeff m2 K/W 0.025 0.025 0.025 0.025
Total thermal resistance m2 K/W 0.466 1.310 2.148 2.985
Heat Flux W/m2 1223.4 435.1 265.3 191.0
Surface Temp Deg C 92.7 57.1 47.8 43.4
Steel Duct metal Temp Deg C 92.7 419.6 490.0 520.8
Whyteheat K / Insulyte 7 interface temp Deg C 543.7 580.0 587.8 591.2
Whyteheat K inside surface temp Deg C 569.4 589.1 593.4 595.2
Gas Temp (Calculated) Deg C 600.0 600.0 600.0 600.0

Difference to be made '0' by changing 0.0 0.0 0.0 0.0


assumed surface temp