IEC60870-5-101/104 PROTOCOL
Technical Manual
ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
Copyright © 2006 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Release Note:
ENHANCED TECHNOLOGY i
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
TABLE OF CONTENTS
A. Introduction ………………………..…………………………………………………………...1
ii ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
A. Introduction
IEC 60870-5 provides a communication method to send basic telecontrol messages between two
systems. The IEC Technical Committee 57 have developed a protocol standard for Telecontrol,
Teleprotection, and associated telecommunications for electric power systems.
IEC 60870-5-101/-104 are applied to telecontrol equipment and systems with coded bit serial data
transmission for monitoring and controlling geographically widespread processes.
IEC 60870-5-101 protocol uses the standard of asynchronous serial tele-control channel interface
between DTE(Data Terminal Equipment) and DCE(Data Commincation Equipement). The
standard is suitable for multiple configurations like point-to-point and multipoint.
IEC 60870-5-104 protocol is an extension of IEC 60870-5-101 protocol with the changes in terms
of transport, network, link & physical layer services for the complete network access. The standard
uses an open TCP/IP interface to network to have connectivity to the LAN(Local Area Network)
and routers with different facility(ISDN, X.25, Frame relay etc) can be used to connect to the WAN
(Wide Area Network). Application layer of IEC 60870-5-104 is preserved same as that of IEC
60870-5-101 with some of the data types and facilities not used. There are two separate link layers
defined in the standard and suitable for data transfer over Ethernet & serial line(PPP - Point-to-
Point Protocol).
ENHANCED TECHNOLOGY 1
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Time Out(t0) Timeout for connection establishment 1~255 sec 120 sec
Time Out(t1) Timeout for send or test APDUs 1~255 sec 15 sec
Time Out(t2) Timeout for acknowledgements in case of no data message 1~255 sec 10 sec
Time Out(t3) Timeout for sending test frame in case of a long idle state 1~255 sec 20 sec
Max. value
Limit High
variation
Time
variation
Limit Low
Min. value t1 t2 t3 t4
∆t = 1sec
2 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 3
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
C. Interoperability Document
1. SYSTEM OR DEVICE:
□ System Definition
□ Controlling Station Definition (Master)
▣ Controlled Station Definition (Slave)
2. NETWORK CONFIGURATION:
▣ Point-to-Point ▣ Multipoint
□ Multiple Point-to-Point □ Multipoint Star
3. PHYSICAL LAYER
Transmission Speed (control direction):
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
▣ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec
4 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
▣ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec
4. LINK LAYER
■ Structured
▣ Unstructured
Frame Length :
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:
9 <1>
※ Note) In response to a class 2 poll, a controller station may respond with class 1 data when there is no
class 2 data available.
ENHANCED TECHNOLOGY 5
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-1, is used exclusively in
this companion stanadard.
■ Three Octets
Cause of Transmission:
▣ One Octet
■ Two Octets (with originator address). Originator address is set to zero if not used.
▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.
6 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
■ <14> := Measured value, short floating point value with time tag M_NE_TC_1
■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
■ <20> := Packed single-point information with status change detection M_SP_NA_1
□ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
□ <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
□ <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
□ <40> := Packed output circuit information of protection equipment
with time tag CP56Time2a M_EP_TF_1
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the
ENHANCED TECHNOLOGY 7
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
File transfer
□ <120> := File Ready F_FR_NA_1
8 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
ENHANCED TECHNOLOGY 9
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1 X X X X X
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
10 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<106> C_CD_NA_1
<110> P_ME_NA_1 X X X
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*
* Blank or X only
6. BASIC APPLICATION
FUNCTIONS Station Initialization:
▣ Remote initialization
ENHANCED TECHNOLOGY 11
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Read Procedure:
▣ Read procedure
Spontaneous Transmission:
▣ Spontaneous transmission
Station interrogation:
▣ Global
▣ Group 1 ▣ Group 5 ▣ Group 9 ▣ Group 13
Clock synchronization:
▣ Clock synchronization (optional)
□ Day of week used
12 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Command transmission:
▣ Direct command transmission
□ No additional definition
▣ Short pulse duration (duration determined by a system parameter in the outstation)
▣ Long pulse duration (duration determined by a system parameter in the outstation)
□ Persistent output
Parameter loading:
▣ Threshold value
□ Smoothing factor
▣ Low limit for transmission of measured values
Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
ENHANCED TECHNOLOGY 13
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Test procedure:
□ Test procedure
File transfer:
File transfer in monitor direction:
□ Transparent file
□ Transmission of disturbance data of protection equipment
□ Transparent file
Background scan:
□ Background scan
1. SYSTEM OR DEVICE:
□ System Definition
□ Controlling Station Definition (Master)
2. NETWORK CONFIGURATION:
■ Point-to-Point ■ Multipoint
■ Multiple Point-to-Point ■ Multipoint Star
14 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
3. PHYSICAL LAYER
Transmission Speed (control direction):
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
4. LINK LAYER
■ Two Octets
■ Structured
■ Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
ENHANCED TECHNOLOGY 15
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:
5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in
this companion stanadard.
▣ Three Octets
Cause of Transmission:
■ One Octet
▣ Two Octets (with originator address). Originator address is set to zero if not used.
Maximum Length of APDU: 253 (the maximum length may be reduced by the system.)
▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.
16 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the
ENHANCED TECHNOLOGY 17
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
□ <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
File transfer
□ <120> := File Ready F_FR_NA_1
□ <121> := Section Ready F_SR_NA_1
□ <122> := Call directory, select file, call file, call section F_SC_NA_1
18 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1
ENHANCED TECHNOLOGY 19
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
20 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1 X X X X X
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
<61> C_SE_TA_1 X X X X X
<62> C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1 X X
ENHANCED TECHNOLOGY 21
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<110> P_ME_NA_1 X X X
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*
* Blank or X only
6. BASIC APPLICATION
FUNCTIONS Station Initialization:
▣ Remote initialization
22 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Read Procedure:
▣ Read procedure
Spontaneous Transmission:
▣ Spontaneous transmission
Station interrogation:
▣ Global
▣ Group 1 ▣ Group 5 ▣ Group 9 ▣ Group 13
Clock synchronization:
▣ Clock synchronization (optional)
Command transmission:
▣ Direct command transmission
ENHANCED TECHNOLOGY 23
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
□ No additional definition
□ Persistent output
▣ Supervision of maximum delay in command direction of commands and set point commands
▣ Counter read
□ Counter freeze without reset
□ Counter freeze with reset
□ Counter reset
▣ General request counter
□ Request counter group 1
□ Request counter group 2
Parameter loading:
▣ Threshold value
□ Smoothing factor
Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
□ Test procedure
24 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
File transfer:
File transfer in monitor direction:
□ Transparent file
□ Transmission of disturbance data of protection equipment
□ Transparent file
Background scan:
□ Background scan
VALUE VALUE
VALUE VALUE
ENHANCED TECHNOLOGY 25
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Portnumber:
standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.
▣ Ethernet 802.3
□ Serial X.21 interface
□ Other selection(s) from RFC 2200 (list below if selected)
26 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Single-point information
1011 27 Target ٧ ٧ 5
1012 59 Target ٧ ٧ 5
1013 25 Target ٧ ٧ 5
1014 81 Target ٧ ٧ 5
ENHANCED TECHNOLOGY 27
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
1030 79 RESET ٧ ٧ 4
1031 79 CYCLE ٧ ٧ 4
1032 79 LOCKOUT ٧ ٧ 4
1038 Contact(52a) ٧ ٧ 2
28 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 29
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
30 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
Group1: Panel (Other) Function Section
Group2: Tank(Recloser) related
Group3: Protection elements
ENHANCED TECHNOLOGY 31
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Single Command
Object
Description Notes
Address
CLOSE OFF
21000
OPEN ON
Protection Disable OFF
21001
Protection Enable ON
Ground Disable OFF
21002
Ground Enable ON
SEF Disable OFF
21003
SEF Enable ON
Reclose Disable OFF
21004
Reclose Enable ON
Control Unlock OFF
21005
Control Lock ON
Primary Setting Enable OFF
21006
Alternate Setting Enable ON
Program 1 Disable OFF
21007
Program 1 Enable ON
Program 2 Disable OFF
21008
Program 2 Enable ON
Hot Line Tag Disable OFF
21009
Hot Line Tag Enable ON
21010 Target Reset ON
21011 Battery test ON
21012 Reset Max demand value ON
21013 Reset energy ON
21014 Change Setting ON Note 1)
21015 Opto Input 1 operate ON
21016 Opto Input 2 operate ON
21017 Opto Input 3 operate ON
21018 Opto Input 4 operate ON
32 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
1) As changed value by Single Command signal, changed present setting value and restart a system.
ENHANCED TECHNOLOGY 33
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Object
Description Point Property Notes
Address
NOTE
1) 16 bit rollover Counter.
Integrated Totals is achieved by Integrated Totals Command.
34 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Normalized Measurands
ENHANCED TECHNOLOGY 35
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
36 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 37
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
38 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 39
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
Object Address Point of Normalized Measurands has three Parameter normalized Value( Threshold, Low Limit, Hight
10006 99 0х01(Threshold)
To change Value, do Parameter normalized value command and dedicate new Address and Flags.
Each Object Address Point are 2000~2159 and it has three values (Threshold, Low Limit, Hight Limit). Threshold IOA at
address 2000 is 10000 and Hight Limit IOA of Last Fault Current NEQ at address 2159 is, 10521.
Group10: Measuring
Group11: Measuring
40 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6003 Load profile save interval Static 15 DF1 (0:5, 1:10, 2:15, 3:20, 4:30, 5:60 min)
6015 Reset time from autoreclose cycle (sec) Static 15 DF3 (100-60000)
6017 Limit time to waiting closing power (sec) Static 15 DF3 (100-60000)
6026 Select reset method - PHASE FAST Static 15 DF1 (0:INST, 1:LINEAR)
ENHANCED TECHNOLOGY 41
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6031 Select reset method - PHASE DELAY Static 15 DF1 (0:INST, 1:LINEAR)
6036 Select reset method - GROUND FAST Static 15 DF1 (0:INST, 1:LINEAR)
6041 Select reset method - GROUND DELAY Static 15 DF1 (0:INST, 1:LINEAR)
6043 Operations curve - NEG SEQ FAST Static 15 DF1 (0-56) Reference 1)
6045 Constant time adder - NEG SEQ FAST Static 15 DF3 (0-1000)
6046 Minimum response time - NEG SEQ FAST Static 15 DF3 (0-1000)
6047 Select reset method - NEG SEQ FAST Static 15 DF1 (0:INST, 1:LINEAR)
6048 Operations curve - NEG SEQ DELAY Static 15 DF1 (0-56) Reference 1)
6050 Constant time adder - NEG SEQ DELAY Static 15 DF3 (0-1000)
6051 Minimum response time - NEG SEQ DELAY Static 15 DF3 (0-1000)
6052 Select reset method - NEG SEQ DELAY Static 15 DF1 (0:INST, 1:LINEAR)
6053 H/C Trip function - phase Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6056 H/C Trip Active Trip No - phase Static 15 DF1 (0:0FF, 1-5)
6057 H/C Trip function - ground Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6060 H/C Trip Active Trip No - ground Static 15 DF1 (0:0FF, 1-5)
6061 H/C Trip function - NEQ Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
42 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6064 H/C Trip Active Trip No- NEQ Static 15 DF1 (0:0FF, 1-5)
6065 H/C LOCKOUT function - phase Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6068 H/C LOCKOUT Active Trip No - phase Static 15 DF1 (0:0FF, 1-5)
6069 H/C LOCKOUT function - ground Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6072 H/C LOCKOUT Active Trip No - ground Static 15 DF1 (0:0FF, 1-5)
6073 H/C LOCKOUT function - NEQ Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6076 H/C LOCKOUT Active Trip No - NEQ Static 15 DF1 (0:0FF, 1-5)
6077 Cold Load PickUp function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6089 Direction of current Flow - phase Static 15 DF1 (0:OFF, 1:FORWARD, 2:REVERSE)
6091 Minimum polarizing voltage (M.P.V) - phase Static 15 DF3 (0-125 xVT secondary nominal volt)
6092 Block overcurrent under M.P.V - phase Static 15 DF1 (0:NO, 1:YES)
6093 Direction of current Flow - ground Static 15 DF1 (0:OFF, 1:FORWARD, 2:REVERSE)
ENHANCED TECHNOLOGY 43
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6095 Minimum polarizing voltage (M.P.V) - ground Static 15 DF3 (0-125 xVT secondary nominal volt)
6096 Block overcurrent under M.P.V - ground Static 15 DF1 (0:NO, 1:YES)
6097 Direction of current Flow - SEF Static 15 DF1 (0:OFF, 1:FORWARD, 2:REVERSE)
6099 Minimum polarizing voltage (M.P.V) - SEF Static 15 DF3 (0-125 xVT secondary nominal volt)
6100 Block overcurrent under M.P.V - SEF Static 15 DF1 (0:NO, 1:YES)
6101 Direction of current Flow - NEQ Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)
6103 Minimum polarizing voltage (M.P.V) - NEQ Static 15 DF3 (0-125 xVT secondary nominal volt)
6104 Block overcurrent under M.P.V - NEQ Static 15 DF1 (0:NO, 1:YES)
6106 Under Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6108 Under Voltage 1 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6109 Under Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6111 Under Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6113 Under Voltage 2 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6114 Under Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6116 Over Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6118 Over Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6120 Over Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6122 Over Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
44 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6128 Frequency Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6129 Frequency Minimum current Static 15 DF3 (1-320 xCT Phase ratio)
6138 Time interval Static 15 DF1 (0:5, 1:10, 2:15, 3:20, 4:30, 5:60 minite)
6139 Demand Pickup - phase Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)
6140 Demand Pickup - ground Static 15 DF3 (0:OFF, 2-320 xCT Ground ratio)
6141 Demand Pickup - NEQ Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)
6143 Dead line maximum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)
6144 Live line minimum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)
6145 Maximum voltage difference Static 15 DF3 (0-125 xVT 2nd norminal volt)
ENHANCED TECHNOLOGY 45
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
6157 Voltage response side to TIE Static 15 DF1(0:Line VS, 1:Line VL, 2:Line VS&VL)
DF1(0:3PN, 1:3PP, 2:1PN(A), 3:1PN(B),
6158 Line VS wire Static 15 4:1PN(C), 5:1PP(AB), 6:1PP(BC),
7:1PP(CA))
DF1(2:1PN(A),3:1PN(B), 4:1PN(C),
6159 Line VL wire Static 15
5:1PP(AB), 6:1PP(BC),7:1PP(CA))
Auto change to Alternate Setting at
6160 Static 15 DF1 (0:OFF, 1:ON)
Mid Point
Auto change to Alternate Setting at DF1 (0:OFF, 1:ON(VS), 2:ON(VL),
6161 Static 15
Tie Point 3:ON(BOTH))
6162 LC after manual close Static 15 DF1 (0:DISABLE, 1:ENABLE)
6164 Open time on both dead Line Static 15 DF3 (1-60000 sec)
6168 Dead Line Pickup time delay Static 15 DF3 (1-60000 sec)
6169 Live Line Pickup time delay Static 15 DF3 (1-60000 sec)
6170 Dead Line Reset time delay Static 15 DF3 (1-60000 sec)
6171 Non Recloser Time after LC Action Static 15 DF3 (0-60000 sec)
NOTE
Each Object Address’ : Normalized Measurands Without Quality value change method.
- Do Normalized Measurand command to change new address.
- For example, to change the value at address 6156, conduct Normalized Measurand command so that address can be