1,200VA
20-5,000 Hz
1Ø4 0-150VL-N
2Ø4 0-300VL-L
www.valuetronics.com
FREQUENCY CONVERSION
AEROSPACE R&D MILITARY MANUFACTURING CUSTOM
112AMX
Output Ratings
112AMX
Output Voltage3 Current 4 Frequency Input Unit Height Unit Weight
Rated Power (VA)1 Coupling Mode Form2 VRMSMax
(ARMS) Range Power In/mm/U (Lbs/Kg)
(L-N/L-L)
NOTES:
1. Rated output power is based on a combination of nominal output voltage, rated current and load power factor. Values stated represent the maximum capabilities of a given model. Consult
factory for assistance in determining specific unit capabilities as they might apply to your application.
2. Unit is operable as single phase with dual range capability. Output voltage range and 1/2/3 conversions are selected by front panel or bus commands.
3. Vmax is output voltage with nominal input and full rated load applied.
4. Available current will vary with output voltage and power factor. Current shown is per phase.
AMX Power Source Specifications (PF = 1.0, Vout > 25% F.S.)
Output Frequency Line Regulation Load Regulation Output Distortion Ripple and Noise Response Time
Full Power 0.1% max for a Direct Coupled Ranges: 5 µsec typ. For
0.25% 20 to 2,000 Hz. 0.1% THDAVG 45 to 1,000 Hz
20-5,000 Hz Direct Coupled ±10% line -72dB step load change.
change 0.50% 2,000 to 5,000 Hz. 0.25% THDAVG 20 to 5,000 Hz Small signal
Improves to less than 0.03% with external sense and CSC enabled. bandwidth = 5 Hz
to 40 KHz
Input Voltage 100VAC ±10% 110VAC ±10% 120VAC ±10% 200 or 208VAC±10% 220VAC±10% 230 or 240VAC±10%
Recommended
25A 25A 25A 15A 15A 15A
Input service
Rated Continuous Load Current as a Function of Ambient Temperature and Power Factor and Output Voltage at Nominal Input Line.
www.valuetronics.com
112AMX
www.valuetronics.com
112AMX
19" (483mm)
3U
(5.25",
133 mm)
17" (432mm)
Heat Dissipation 1.3kBTU/ hr (Full kW Load) /G GPIB Interface, IEEE-488.2. (Standard on UPC-32)
Hardware Over-current, short circuit, over- temperature /IR In-Rush Meter. Capture and view peak in-rush current
values via front panel or remote interface (UPC-1 only).
A single RMS programmed, average responding, value is Test MGR UPC Test Manager License: Create, edit, and execute Test
Programmable Current Limit provided for all phases. Limits current by reducing output sequences and reports. Ordered as separate line Item
voltage. Test SEQ Avionics test sequences; DO-160, ABD-0100, ABD-0100 (A350),
Ordered as separate line item, Requires 'Test' Manager License.
Ordering Information
Available Models
Model Controller Options Input Voltage (VIN)
With Manual Controller
112AMX UPC-1M See List Above 100VAC ± 10%
UPC-1 110VAC ± 10%, 112AMX-UPC1M
UPC-12 120VAC ± 10%
200VAC ± 10% With Programmable Controller
208VAC ± 10%
220VAC ± 10% 112AMX-UPC1 112AMX-UPC12
230VAC ± 10%
240VAC ± 10%
www.valuetronics.com