Professional Documents
Culture Documents
C CS NonstructuralComp Bachman Dowty July081
C CS NonstructuralComp Bachman Dowty July081
E
between nonstructural components and nonbuilding struc-
tures, many generalizations need to be made so that the
discussion can be simplified as much as possible. Common
R
sense also needs to be exercised, as these generalizations
don’t always apply. Also, it should be noted, that the guid-
ance provided herein represents only the collective opinion
U
of the authors at this point in time. It is hoped that as the
nonstructural component and nonbuilding structure code Figure 1: Nonbuilding Structure Similar to Building.
ght ob-
T
provisions evolve, some of these guidelines willy r ibecome
Copissues.
solete as the code will directly address these
C
Nonstructural Components
e
U
Traditionally, nonstructural components system similar to build-
have been identified as architectural, me- ings and the other type
chanical and electrical components found has a structural system
i n
R
in buildings. Prior to adoption of the that is not similar to
International Building Code (IBC), the buildings (Figures 1 and
z
T a
focus had been on the design of anchor- 2). The focus of this
age and bracing of these components article is on nonbuild-
g
and not the components themselves. The ing structures which are Figure 2: Nonbuilding Structure Not Similar to Building.
S
components themselves had been treated not similar to build-
a
Codes and Standards
as a “black box” and whatever was inside ings, and the determination of when “big” now need to be described in a more
the “black box” was not required to be the design rules of ASCE 7-05 Chapter definitive way. Mechanical and electrical
m
designed for seismic loads. Exceptions
to this “black box” approach were items
such as towers on tops of buildings (radio
and cell towers), heavy cladding, battery
15 apply and when the design rules of equipment components are typically
ASCE 7-05 Chapter 13 apply. small enough to fit within a building;
Figure 3 provides a visual illustration something on the order of less than 10
that shows: feet tall. There are, of course, exceptions
racks, billboards and signage attached to 1) those items which should to the 10 feet, such as signs attached to
buildings. Current IBC seismic code re- be treated as nonstructural buildings and very large generators and
quirements for anchorage and bracing components; turbines. The 10-foot height is obviously
requirements for nonstructural compo- 2) those items which should be treated an arbitrary height. The basis for select-
nents are found in ASCE 7-05 Chapter as nonbuilding structures; and ing 10 feet is twofold:
13. It should be noted that, starting with 3) those items, such as tanks, that 1) it represents a story height which
updates and discussions related to codes and standards
the 2000 IBC, when the component is appear to be ambiguous since will allow installation within a
determined to have an importance factor they are permitted to be treated building, and
of 1.5, the “black box” itself now generally either way. 2) the weight of the component is
needs to be designed, or qualified, to resist It should be noted that most, if not likely small relative to the weight
the effects of seismic forces. all, nonbuilding structures support at- of the supporting structure.
tached nonstructural components of Another obvious difference between
Nonbuilding Structures some type. One item not shown on the nonstructural components and nonbuild-
list that is of interest is skid mounted ing structures is whether they are factory
Self-supporting nonbuilding structures
equipment modules. assembled or field erected. Nonstructural
are structures other than buildings that
carry gravity loads and resist the effects components are typically factory as-
of earthquakes. The concept of provid- Differentiating Between sembled in that they are transported in
ing specific seismic design requirements Nonstructural Components one piece on a truck and require no as-
for nonbuilding structures was first in- sembling at the jobsite. Obviously there
troduced into code requirements in the and Nonbuilding Structures are many nonstructural components that
1988 Uniform Building Code (UBC). The There are a number of obvious differ- are assembled on the site in pieces such
most current seismic design requirements ences between nonstructural components as ceilings, partition walls, exterior curtain
for nonbuilding structures are found in and nonbuilding structures. First is size. walls, exterior siding, masonry veneer,
ASCE 7-05 Chapter 15. To say it simply, nonstructural compo- cable trays, piping systems, ductwork,
There are two types of nonbuilding nents are typically small, and nonbuilding large roof mounted roof handlers, eleva-
structures. One type has a structural structures are typically big. “Small” and tors etc. Fortunately, there is no question
E
Cabinets Manufacturing equipment Bins
Cable trays Motor control centers
Ceilings
Chimneys
Chillers
Motors
Panel boards
Conveyors Amusement structures
Hoppers (elevated)
There is one item listed as a nonstructural
Communication equipment Cooling Towers
component in Figure 3 that may come as a
R
Parapets Monuments
Compressors Stacks
Penthouse (except where Silos (cast-in-place
Computers framed by an extension of
Tanks
concrete having walls surprise: penthouses (except where framed
Ductwork Towers
Electrical conduit
the building frame)
Piping Vessels
to foundation) by an extension of the building frame). A
U
Elevator
Engines
Plumbing penthouse is typically a structure on a roof for
Process equipment
Switch gear Pumps housing elevator machinery, equipment, water
Transformers Wall panel
ht tanks, etc. It can easily be more than 10 feet
yrig
T
Tubing Walls
Cop
Turbines
Veneer
Water heaters in height, and it is most likely constructed at
Vibration isolated components
and systems the jobsite. Because penthouses are typically
C
located at the roof level, are of a small mass
and footprint size compared to the structure
Figure 3: Intersection of Nonstructural Components and Nonbuilding Structures.
as a whole thus not affecting the dynamics
e
U
that these all should be treated as nonstructural equation in ASCE 7-05 Chapter 15, and of the entire structure, they are classified as
n
components and the design criteria in ASCE using the most conservative design. nonstructural components provided they are
7-05 Chapter 13 apply. Nonbuilding struc- The design force equation for nonstructural
R z
tures are most likely field erected, as they are components is indirectly dependent on the pe- argue that their framing system is similar to
constructed at the jobsite. Exceptions to this riod of the item (is it flexible or rigid?) whereas that of a building; however, they also can be
T a
rule would be large vertical vessels, hoppers the design force equation for non-building viewed as a small appendage to a structure
and bins which can be shipped on trucks or structures is directly dependent on the period similar to a tower. If the penthouse is framed
g
S
railcars to the site. Essentially every by an extension of the building frame,
a
other type of nonbuilding structure then it needs to be designed as part of
is constructed at the jobsite. Nonstructural Components: the building as a whole.
( )
m
Another major difference between z
0.4apSDSWp 1+2
a nonstructural component and a Fp = h Nonbuilding Structures
nonbuilding structure is the basis
for its design and construction.
Nonstructural components are typ-
Rp
Ip ( ) Supported Within a
Building or
ically constructed to function for Fp shall not be taken as less than: Fp = 0.3SDSIpWp Other Structures
architectural, mechanical or elec- Fp is not required to be taken as greater than: Fp = 1.6SDSIpWp Sometimes a nonbuilding structure
trical purposes. The primary func- needs to have its seismic design forces
tion of nonbuilding structures is to Nonbuilding Structures determined using the same equations
SDS
maintain structural stability, and Not Similar to Buildings: Cs = for T≤ Ts used to determine forces as specified
they are typically constructed to
resist gravity and lateral loads and
the structural system is typically
R
I ( ) for a nonstructural component. This
happens when, rather than being sup-
ported on the ground, the nonbuilding
very carefully designed for seismic SD1
Cs = for TL ≥ T > Ts structure is supported within a building
( )
loads. For example, a communica- R or by another nonbuilding structure.
tions tower is designed to maintain T
I ASCE 7-05 Section 15.3 provides clear
structural stability whereas a motor instructions for this condition.
is primarily designed for mechanical
functionality and seismic design Cs = SD1TL for T > TL Where the weight of the supported
nonbuilding structure is “relatively
may be inherent and therefore not
rigorously evaluated (other than
for anchorage).
T2
R
I ( ) small” compared to the weight of the
supporting structure, the assumption is
For nonbuilding systems that have an R value provided in that the supported nonbuilding struc-
Table 15.4-2, Cs shall not be taken as less than: ture will have a relatively small effect
Designer’s Option on the overall nonlinear earthquake
Cs = 0.03 response of the primary structure dur-
When in doubt, the designer
always has the option of calculating For nonbuilding structures located where S1 ≥ 0.6g, Cs shall ing design level ground motions. In
not be taken as less than: these cases, the code allows such struc-
the force demand in accordance Cs = 0.8S1 tures to be considered as nonstructural
( )
with the nonstructural component R
equation in ASCE 7-05 Chapter components and they can therefore
I utilize the requirements for Chapter
13 and the nonbuilding structure
E
the nonbuilding structure and supporting
structure), it is expected that the combined because of transportation loadings. It is the Design of Items Which Can
response could be significantly affected by authors’ opinion that transportation design
Be Either a Nonstructural
R
the combined response of the supported and loads are usually sufficient to assure adequate
supporting nonbuilding structure. There are seismic performance in lower areas of seis- Component or a
micity (structures assigned to Seismic Design Nonbuilding Structure
U
two analysis options that are permitted to be
used for this situation, and they are set forth Categories A, B or C) if the module is not
Now that the differences between nonstruc-
in ASCE 7-05 Section 15.3.2. stiffened or bracedhin t anyway for transporta-
ig of seismicity (structures tural components and nonbuilding structures
T
tion. In higher y rareas
assigned C
op
to Seismic Design Categories D, E
have been described, it is appropriate to take
Equipment Modules or F), seismic design of the primary structural
a look at the apparently ambiguous items (the
C
(Equipment Skids) frame of the modular unit should be demon-
overlap items in Figure 3, page 19). Table 1
provides discussion on these items.
Equipment modules are currently not ex- strated. Obviously if a modular unit doesn’t
e
U
plicitly (but implicitly) covered by ASCE weigh much, for example 400 pounds, it does
7-05, and therefore a suggested seismic design not make sense to require a design. On the Conclusion
approach is provided in this article. Some- other hand, if a modular unit weighs 2000
i n
The foregoing article provides guidance on
R
times these modules have exterior coverings pounds, it is prudent to design for seismic how the authors believe items that could be
and one could consider them as very large loads. In such a case, the primary support
z identified as either nonstructural components
T a
“black boxes”. There’s a certain inherent rug- members should be designed in accordance or nonbuilding structures can be treated from
gedness of equipment modules because these with ASCE 7-05 Chapter 13, and ap and Rp a seismic design perspective. Because of the
g
preassembled modular units are typically values should be the same as that for the en- wide variety of items, it is extremely difficult
S
transported on a truck and therefore must try from ASCE 7-05 Table 13.6-1 shown in to write all-inclusive definition rules within
have a certain level of inherent ruggedness Figure 4.
a the code. It is hoped that the guidance pro-
vided along with the application of a good
Ch 13 Ch 15
Item Discussion
Rp-value R-value
Billboards If the item is attached to a structure, then it is considered a nonstructural component and
2.5 3.5
and Signs Chapter 13 is used. If the item is attached and supported by another structure, it may be of
such a size and weight that it needs to be treated as a nonbuilding structures supported by ®
E
other structures with the seismic design forces determined in accordance with Section 15.3
Bins 1.0 2 or 3 which refers back to Chapter 13. If the item is assembled and is a free standing, ground-
supported structure, then it should be treated as a nonbuilding structure and Chapter 15
R
should be used.
There are many types of chimneys ranging from residential to industrial chimneys. A
U
chimney attached to a structure may be of such a size and significance that it can be
considered an architectural nonstructural component and designed in accordance with
t institutional and commercial chimneys that are attached and
igh
Chapter 13. Industrial,
T
Chimneys varies 3 supported p y
by
rother structures may be of such a size and weight that they need to be
Co
considered nonbuilding structures supported by other structures with the seismic design forces
C
determined in accordance with Section 15.3 which refers back to Chapter 13. Freestanding
industrial, institutional, and commercial chimneys, on the other hand, are typically of a size
that they are considered nonbuilding structures and designed in accordance with Chapter 15.
e
U
They are usually The support structures for conveyors which are used in large industrial complexes such as
considered
n
surface mining facilities typically qualify as nonbuilding structures similar to buildings. There
i
R
“nonbuilding are, however, smaller manufacturing, processing and material handling conveyors which can
z
Conveyors 2.5 structures similar be transported in a truck in one piece and would qualify as a nonstructural component. In
T
to buildings” the case where conveyors are designed as nonbuilding structures in accordance with Chapter
except for the
mechanical parts.
g a
15, the bracing and anchorage for the actual mechanical workings should be designed in
accordance with Chapter 13.
S
If the cooling tower is shop fabricated and transported in a truck, it is considered a
Cooling Tower 2.5 or 1.0 3.5
a
nonstructural component and designed in accordance with Chapter 13. If it is self-
supporting and field erected, then it is considered a nonbuilding structure and designed in
If the vessel is less than 10 feet tall, it can typically fit within a building and is considered
a nonstructural component. If the vessel is more than 10 feet tall, it most likely should
be considered a nonbuilding structure. Vessels that are power boilers typically qualify as a
Vessels 2.5 or 1.0 varies nonbuilding structure. Free standing vessels should typically be considered nonbuilding
structures. If the vessel is attached and supported by another structure, it may be of such a
size and weight that design forces may need to be determined in accordance with Section 15.3
which refers back to ASCE 7-05 Chapter 13.
Reprinted with permission from ICC Building Safety Journal, April/May 2008.