Professional Documents
Culture Documents
SPECIFICATION 5 660-4
First edition
2016-12-15
Reference number
ISO/TS 5660-4:2016(E)
ii
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Contents Page
Foreword .......................................................................................................................................................................................................................................... v
1 Scope ................................................................................................................................................................................................................................. 1
2 Normative re ferences ...................................................................................................................................................................................... 1
3 Terms and definitions ..................................................................................................................................................................................... 2
4 Symbols and units ............................................................................................................................................................................................... 3
5 Principle ........................................................................................................................................................................................................................ 4
6 Apparatus ..................................................................................................................................................................................................................... 4
6.1 General ........................................................................................................................................................................................................... 4
6.2 Cone-shaped radiant electrical heater ............................................................................................................................... 6
6.3 Radiation shield ..................................................................................................................................................................................... 6
6.4 Irradiance control ................................................................................................................................................................................. 6
6.5 Weighing device ..................................................................................................................................................................................... 6
6.6 Specimen holder .................................................................................................................................................................................... 6
6.7 Retainer frame ......................................................................................................................................................................................... 7
6.8 Exhaust gas system with flow measuring instrumentation ............................................................................. 8
6.9 Gas sampling apparatus ............................................................................................................................................................... 10
6.10 Ignition circuit ...................................................................................................................................................................................... 10
6.11 Ignition timer ........................................................................................................................................................................................ 10
6.12 Oxygen analyser .................................................................................................................................................................................. 11
6.13 Heat flux meters .................................................................................................................................................................................. 11
6.14 Calibration burner ............................................................................................................................................................................ 11
6.15 Data collection and analysis system .................................................................................................................................. 11
6.16 Optional side screens ..................................................................................................................................................................... 11
7 Suitability o f a product for testing .................................................................................................................................................. 12
7.1 Surface characteristics .................................................................................................................................................................. 12
7.2 Asymmetrical products ................................................................................................................................................................ 12
7.3 Materials of short burning time ............................................................................................................................................ 12
7.4 Composite specimens..................................................................................................................................................................... 12
7.5 Products with unknown burning behaviour .............................................................................................................. 12
8 Specimen construction and preparation.................................................................................................................................. 13
8.1 Specimens ................................................................................................................................................................................................ 13
8.2 Conditioning of specimens ........................................................................................................................................................ 13
8.3 Preparation ............................................................................................................................................................................................. 13
8.3.1 Specimen wrapping.................................................................................................................................................... 13
8.3.2 Specimen preparation .............................................................................................................................................. 14
9 Test environment .............................................................................................................................................................................................. 14
10 Calibration ............................................................................................................................................................................................................... 14
10.1 Initial calibrations ............................................................................................................................................................................. 14
10.1.1 General................................................................................................................................................................................... 14
10.1.2 Weighing device response time ....................................................................................................................... 15
10.1.3 Weighing device output drift.............................................................................................................................. 15
10.1.4 Oxygen analyser delay and response times ........................................................................................... 15
10.1.5 Oxygen analyser output noise and dri ft.................................................................................................... 15
10.2 Operating calibrations ................................................................................................................................................................... 16
10.2.1 General................................................................................................................................................................................... 16
10.2.2 Weighing device accuracy ..................................................................................................................................... 16
10.2.3 Oxygen analyser............................................................................................................................................................. 16
10.2.4 Heat release rate calibration .............................................................................................................................. 16
10.2.5 Heater calibration ........................................................................................................................................................ 17
10.3 Less frequent calibrations .......................................................................................................................................................... 17
10.3.1 Working-standard heat flux meter calibration ................................................................................... 17
© ISO 2016 – All rights reserved
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
iii
ISO/TS 5660-4:2016(E)
11 Test procedure . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . 17
1 1 .1 General p recautions . . . . .. . . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . 1 7
1 1 .2 I nitial preparation . . . . . . . .. . . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . 1 8
1 1 .3 Test p rocedure . . . . .. . . . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . 1 8
14 Test report. . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . . 21
Annex A (informative) Overview . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . 23
Annex B (informative) Calibration o f the working heat flux meter .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . 26
Annex C (informative) Calculation o f heat release with additional gas analysis . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . 27
Annex D (informative) Data obtained in initial round robin. . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . 31
Bibliography . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. . . . . . . . . .. 34
iv
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work o f preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters o f
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
di fferent types o f ISO documents should be noted. This document was dra fted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some o f the elements o f this document may be the subject o f
patent rights. ISO shall not be held responsible for identi fying any or all such patent rights. Details o f
any patent rights identified during the development o f the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is in formation given for the convenience o f users and does not
constitute an endorsement.
For an explanation on the meaning o f ISO specific terms and expressions related to con formity assessment,
as well as information about ISO’s adherence to the World Trade Organization (WTO) principles in the
Technical Barriers to Trade (TBT) see the following URL: www.iso.org/iso/foreword.html.
The committee responsible for this document is ISO/TC 92, Fire safety, Subcommittee SC 1, Fire initiation
and growth .
A list of all parts in the ISO 5660 series can be found on the ISO website.
1 Scope
This document specifies a method for evaluating materials and products that produce low levels o f heat
release when exposed to high irradiance levels typical o f fully developed fires. It di ffers from ISO 5660-1
by prescribing items such as specific specimen size, specimen holder, specimen orientation, volumetric
flow rate for O 2 analyses and irradiance levels at which testing is conducted.
The test method described in this document is intended for use on products and materials that contain
only small amounts o f combustible elements, e.g. test specimens that yield a total heat release o f
0,75 MJ/m2 to 15 MJ/m 2 .
NOTE 1 The test method for specimens that yield moderate to high total heat release is described in
ISO 5660-1. The in formation obtained from this test method in this document can also be used for fire sa fety
engineering purposes.
NOTE 2 As in ISO 5660-1, the heat release rates are not measured directly and absolute but are theoretically
calculated using the empirically derived constant o f proportionality that links heat released and measured
oxygen consumed.
2 Normative references
The following documents are re ferred to in text in such a way that some or all o f their content
constitutes requirements o f this document. For dated re ferences, only the edition cited applies. For
undated re ferences, the latest edition o f the re ferenced document (including any amendments) applies.
ISO 291, Plastics — Standard atmospheres for conditioning and testing
ISO 554, Standard atmospheres for conditioning and/or testing — Specifications
ISO 5660-1:2015, Reaction-to-fire tests — Heat release, smoke production and mass loss rate — Part 1 :
Heat release rate (cone calorimeter method)
ISO 5660-3,
Reaction-to- fire tests — Heat release, smoke production and mass loss rate — Part 3: Guidance
on measurement
I SO/ TR 1469 7, Reaction-to- fire tests — Guidance on the choice of substrates for building and transport
products
I SO 1493 4 -2 , Fire tests — Calibration and use of heat flux meters — Part 2: Primary calibration methods
I SO 1493 4 -3 : 2 01 2 , Fire tests — Calibration and use of heat flux meters — Part 3: Secondary calibration
method
— I E C E lec trop edia: avai lable at http://www. elec trop edia. org/
3.1
emissivity
ratio o f the radiation emitted by a radiant source to the radiation that would be emitted by a black body
radiant source at the s ame temp erature
3.2
flashing
existence o f flame on or over the sur face o f the specimen for periods o f less than 1 s
3.3
ignition
ons et of sustained flaming (3 .10)
3.4
irradiance
<at a point on a sur face> quotient o f the radiant flux incident on an infinitesimal element o f sur face
containing the p oint, and the area of that element
Note 1 to entry: Convective heating is minimized in the horizontal specimen orientation. For this reason, the
term “irradiance” is used instead o f “heat flux” throughout this document as it best indicates the essentially
rad iative mo de of he at tran s fer.
3.5
material
single substance or uni formly dispersed mixture
EXAMPLE Metal, stone, timber, concrete, mineral fibre and polymers.
3.6
orientation
plane in which the exp osed face of the s p ecimen is lo cated during tes ting
3.7
oxygen consumption principle
proportional relationship between the mass o f oxygen consumed during combustion and the heat
released
3.8
product
material, composite or assembly about which in formation is required
2
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
3.9
specimen
repre s entative pie ce o f the pro duc t th at i s te s te d to ge ther with a ny s ub s trate or tre atment
N o te 1 to entr y: Fo r cer ta i n typ e s o f pro duc t, for e xa mp le pro duc ts th at co nta i n a n a i r gap o r j oi nts , it m ight no t
be possible to prepare a specimen that is representative of the end-use conditions; see Clause 7.
3.10
sustained flaming
exi s tence o f fla me on or over the s u r face o f the s p e c i men for p erio d s o f over 10 s
3.11
transitory flaming
exi s tence o f fla me on or over the s u r face o f the s p e c i men for p erio d s o f b e twe en 1 and 10 s
m e
m a s s flow rate i n e x h au s t duc t kg s −1
q A,max
maximum value of the heat release rate per unit area kW m −2
average heat release rate per unit area over the period starting at kW m −2
t9 0 ti me at 9 0 % of to ta l ma s s lo s s s
ε emissivity
5 Principle
The measurement o f the heat release rate and total heat release is used to quanti fy the test specimen’s
ability to ignite and contribute heat to the fire. It is based on the observation that, generally, the net heat
o f combustion o f a material is directly related to the quantity o f oxygen required for its combustion.
This relationship is such that approximately 13,1 × 10 kJ o f heat are released per 1,0 kg o f oxygen
3
consumed. Optionally, additional measurements o f carbon dioxide and carbon monoxide can be made
and used in calcu lation of heat release. T he app aratus procedures and calculation metho ds describ ed
Specimens are exposed in ambient air conditions, while being subjected to an irradiance o f 50 kW·m−2
in the presence o f a spark ignition source. Alternatively, testing may be conducted at an exposure o f
75 kW· m−2 . The changes in oxygen, O , concentration o f gases and exhaust gas mass flow rate are
2
monitored and, from these data, the heat release is calculated. Additionally, the time to sustained
flaming is observed and mass-loss rate is measured.
In this document, the heat release is measured from the moment the specimen is subjected to the
radiant thermal exposure o f a conical heater and is continued for 20 min. The primary measurements
are oxygen concentration and exhaust-gas mass flow rate. Provision is also made for the time to
sustained flaming. This test method is used to evaluate specimens in a horizontal orientation under an
external irradiance.
I n order to meas ure heat release of material s or pro duc ts that produce low level s of heat release
when exposed to high irradiances typical o f fully developed fires, this part di ffers from ISO 5660-1
by prescribing a larger specimen size (150 mm × 150 mm), a 50 % lower exhaust gas volumetric flow
rate, direc t connec tion b etween the plenum and heater to ens ure col lec tion of al l the combus tion gases ,
more stringent specifications for the oxygen analyser to improve accuracy, and a specified irradiance
level at which to conduc t tes ting. T his document is des igned to tes t s amples with p eak heat release
PMMA is typically used to check the general operation o f a cone calorimeter in ISO 5660-1. PMMA shall
not b e used with this tes t metho d as the heat releas e rate is to o high .
6 Apparatus
6.1 General
T he app aratus shal l b e set up as shown in Figure 1 , with the individual comp onents as describ ed in
detai l in 6 . 2 to 6 . 6 .
4
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Key
1 pressure ports 8 spark plug
2 o rifice p lates 9 vertical connection
3 thermocouple (located on stock centreline) 10 blower motor
4 plenum with extension piece 11 retainer frame and specimen
5 blower 12 specimen holder
6 heater 13 weighing device
7 gas sampling probe 14 exp ans io n flange
Figure 1 — Apparatus
and cons truc ted s uch that it b e cap able of producing irradiance on the s urface of the s p ecimen of up to
T he i rrad iance from the he ater sh a l l be mai ntai ne d at a pre s e t level by control l i ng the average
temp erature of th re e thermo couple s (typ e K s ta i n le s s s te el- she athe d thermo couple s have b e en
proven s uitable but I nconel or o ther h igh-p er forma nce materia l s are a l s o accep table) , s ym me tric a l ly
dis p osed and in contac t with, but not welded to, the heater element, either 3 ,0 mm outs ide diameter
she athe d thermo couple s with e xp o s e d ho t j u nc tion or 1 , 0 m m to 1 , 6 m m outs ide d i ame ter s he athe d
NO T E A heater havi ng a to ta l leng th of 1 2 m, lower outer d iame ter of 3 5 0 m m and top outer d iameter of
irradiance prior to the s tar t of a tes t. T he shield shal l b e made of non- combus tible material, with a total
thicknes s not exceeding 1 2 mm . T he shield shal l b e one of the fol lowing, either:
a) water- co ole d a nd co ate d with a du rable matte black fi n i s h o f s u r face em i s s ivity, ε, e qua l to
0 ,95 ± 0 , 0 5;
b) no t water- co ole d , either me ta l with a refle c tive top s u r face or cera m ic in order to m i ni m i z e
T he shield shal l b e equipp ed with a handle or other s uitable means for quick inser tion and removal . T he
cone heater b ase plate shal l b e equipp ed with a mechanis m for moving the shield into p os ition .
the heater thermo couples during the calibration describ ed in 10 . 2 . 5 at the preset level to within ±10 °C .
pro cedure describ ed in 10 . 2 . 2 . T he weighing device shal l be cap able of meas uring the mas s of
s p ecimens of at leas t 2 ,0 kg. T he weighing device shal l have a 10 % to 9 0 % res p onse time of 4 s or les s ,
as determined according to the cal ibration describ ed in 10 .1 . 3 . T he output of the weighing device shal l
T he holder shal l b e cons truc ted of s tain les s s teel with a thicknes s of (2 ,4 ± 0 ,1 5 ) mm . I t shal l include a
handle to faci l itate ins er tion and removal, and a mechanis m to en s ure central lo cation of the s p ecimen
under the heater and prop er alignment with the weighing device. T he b ottom of the holder shal l b e lined
with a layer o f low den s ity (nom i na l den s ity o f 6 5 kg/m 3 ) re frac tor y fibre bla n ke t with a th ickne s s o f at
leas t 1 3 mm . T he dis tance b etween the b ottom s urface of the cone heater and the top of the s p ecimen
sha l l b e adj u s te d to b e (2 5 ± 1) m m .
6
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
All dimensions in mm
Key
1 stainless (mill smooth)
2 spot weld, four corners
3 2,4 ± 0,15mm stainless steel
Figure 2 — Specimen holder
Key
1 1,9 ± 0,1 mm stainless steel
2 M4 screws (4 pcs)
8
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
A gas sampling ring probe (sample holes face blower) sampler shall be located in the fan intake duct
for gas sampling, (685 ± 15) mm from the plenum (see Figure 4). The gas sampling ring probe (sample
holes face blower) shall contain 12 small holes with a diameter of (2,2 ± 0,1) mm, to average the stream
composition, with the holes facing away from the flow to avoid clogging with soot.
The temperature of the gas stream shall be measured using a 1,0 mm to 1,6 mm outside diameter
sheathed-junction thermocouple or a 3 mm outside diameter exposed-junction thermocouple positioned
in the exhaust stack on the centreline and (100 ± 5) mm upstream from the measuring orifice plate.
The mass flow rate shall be determined by measuring the di fferential pressure across a sharp edge
orifice (internal diameter (57 ± 3) mm, thickness (1,6 ± 0,3) mm) in the exhaust stack, at least 350 mm
downstream from the fan, if the latter is located as shown on Figure 4. The fan shall be located as
indicated in Figure 5.
NOTE As an alternative, the fan can be located further downstream and the measuring orifice located be fore
the fan.
The exhaust system shall be checked for proper operation be fore testing and shall discharge into a
building exhaust system with adequate capacity. Provision shall be made for collecting and venting any
combustion products that shall for whatever reason fail to be collected by the normal exhaust system
of the apparatus.
Key
1 gas sampling ring probe 5 gas sampling ring probe (sample holes face blower)
2 thermocouple 6 fan
3 plenum with extension piece 7 vertical connection
4 orifice plate
A schematic view of an example of the gas s ampl ing app aratus is shown in Figure 5 . O ther arrangements
which satis fy the requirements may be used. The transport delay time o f the oxygen analyser, t d, shal l
NO T E I f an (op tiona l) CO 2 analyser is used, the equations to calculate the heat release rate can be di fferent
from tho s e for the s tandard cas e (s ee C lau s e 1 3 and Annex C ) .
Key
1 gas sampling ring pro be (sample ho les face b lower) 5 mo isture trap
elec trode length and lo cation of the s p ark plug shal l b e s uch that the s p ark gap is lo cated (1 3 ± 2 ) mm
to within 1 s in 1 h.
10
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
ox ygen . T he ana lys er s ha l l exh ibit a d ri ft o f no t more tha n 3 0 μl/ l d ri ft o f ox ygen over a p erio d o f
to 10.1.5 . Si nce ox ygen a na lys ers a re s en s itive to s tre am pre s s u re s , the s tre am pre s s ure s ha l l be
regu late d (up s tre am o f the a na lys er) to m i n i m i ze flow fluc tuation s , and the re ad i ngs
f rom the ana lys er
compensated with an absolute pressure transducer to allow for atmospheric pressure variations. The
ana lys er and the ab s olute pre s s u re tra n s ducer sh a l l b e lo cate d i n an i s o therma l envi ron ment.
The temperature of the environment shall be maintained to within 2 °C of a preset value between 30 °C
and 70 ° C . T he ox ygen ana lys er sha l l have a 10 % to 9 0 % o f
f f u l l- s c a le re s p on s e ti me o le s s than 1 2 s , a s
location equivalent to the centre of the specimen face during this calibration.
T he he at-flu x me ter sh a l l b e o f the S ch m idt-B o elter (thermopi le) typ e with a de s ign ra nge o f (10 0 ± 0)
kW·m −2
f and a d i ame ter o f
approxi mately 1 2 , 5 m m . T he s en s i ng s u r ace s ha l l b e co ate d with a du rab le
f f
matte black fi n i s h o s ur ace em i s s ivity, ε, e qua l to 0 ,9 5 ± 0 , 0 5 . T he he at-flu x me ter s ha l l b e water- co ole d .
The water temperature should be kept above the dew point of the ambient air to avoid condensation of
water on the s en s i ng s ur face o f the he at flu x me ter.
Rad i ation sh a l l no t p a s s th rough any wi ndow b e fore re ach i ng the s en s i ng s u r face . T he i n s tru ment sh a l l
b e robu s t, s i mple to s e t up a nd u s e, and s table i n c a l ibration . T he i n s tru ment sh a l l h ave a n acc u rac y o f
of (500 ± 100) mm2 covered with wire gauze through which the methane diffuses. The tube shall be
p acke d with re frac tor y fibre to i mprove un i form ity o f flow. T he c a l ibration bu rner sh a l l b e con ne c te d
the re adout corre s p ond i ng to a he at rele a s e rate o f 1 kW. T he acc u rac y veri fic ation sha l l b e p er forme d
according to 10.3.3.
6.15 Data collection and analysis system
T he data col le c tion and ana lys i s s ys tem s ha l l have fac i l itie s for re cord i ng the output from the ox ygen
ana lys er, the ori fice me ter, the thermo couple s and the weigh i ng device . T he data col le c tion s ys tem
sh a l l h ave an acc u rac y corre s p ond i ng to at le a s t 5 0 μl/ l o f ox ygen for the ox ygen chan nel, 0 , 5 ° C for
the temperature measuring channels, 0,01 % of full-scale instrument output for all other instrument
cha n nel s , and at le as t 0 ,1 % for ti me . T he s ys tem sh a l l b e c ap able o f re cord i ng data ever y s e cond . T he
s ys tem sha l l b e c ap ab le o f s tori ng m i n i mu m o f 7 2 0 data p er p a rame ter. T he raw data re corde d for e ach
te s t s ha l l b e s tore d s o that they c a n b e re covere d and u s e d to che ck the acc u rac y o f the s o ftware .
For operational or sa fety reasons, the heater and sample holder may be guarded with side screens.
However, it shal l b e demons trated that the pres ence of the screens do es not affec t the ignition time and
b) a sur face irregularity that is evenly distributed over the exposed sur face, provided that
1) at leas t 5 0 % of the s urface of a representative 2 2 5 mm 2 area lies within a dep th of 10 mm from
a plane taken acros s the highes t p oints on the exp osed s urface, or
2) for sur faces containing cracks, fissures or holes not exceeding 8 mm in width or 10 mm in
depth, the total area o f such cracks, fissures or holes at the sur face does not exceed 30 % o f a
representative 2 2 5 mm 2 area of the exp os ed s urface.
When an exp osed s urface do es not meet the requirements of either 7.1 a) or 7.1 b) , the pro duc t shal l
be tested in a modified form complying as nearly as possible with the requirements given in 7.1 . T he
test report shall state that the product has been tested in a modified form, and clearly describe the
modification.
materials arranged in a different order in relation to the two faces . I f either of the faces can b e exp osed
in use within a room, cavity or void, then both faces shall be tested.
at not more than 2 s intervals. For longer burning times, 5 s intervals may be used.
of 0 ,75 M J/m 2 to 1 5 M J/m 2 . I f there is no previous exp erience in tes ting the pro duc t and it is not known
what the peak and total heat release rate is at the given test conditions, the product shall first be tested
in accordance with I S O 5 6 60 -1 .
12
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
8.1 Specimens
8.1.1 Unless otherwise specified, a minimum o f three specimens shall be tested at each level o f
irradiance selected and for each different exposed surface.
8.1.2 The specimens shall be representative of the product and shall be square with sides
measuring 150 −20 mm.
8.1.3 Products with normal thickness of 50 mm or less shall be tested using their full thickness.
8.1.4 For products with a normal thickness greater than 50 mm, the requisite specimens shall be
obtained by cutting away the unexposed face to reduce the thickness to 50 mm.
8.1.5 When cutting specimens from products with irregular surfaces, the highest point on the surface
shall be arranged to occur at the centre of the specimen.
8.1.6 Assemblies shall be tested as specified in 8.1.3 or 8.1.4, whichever is appropriate.
Where thin materials or composites are used in the fabrication o f an assembly, the nature o f any
underlying construction can significantly a ffect the ignition and burning characteristics o f the exposed
sur face. The influence o f the underlying layers should be understood and care taken to ensure that the
test result obtained on any assembly is relevant to its use in practice.
When the product is a material or composite which would normally be attached to a well-defined
substrate, it shall be tested in conjunction with that substrate using the recommended fixing technique,
for example bonded with the appropriate adhesive or mechanically fixed. In the absence o f a unique
or well-defined substrate, an appropriate substrate for testing shall be selected in accordance with
ISO/TR 14697.
8.1.7 Products that are thinner than 6 mm shall be tested with a substrate representative of end-use
conditions, such that the total specimen thickness is 6 mm or more.
8.2 Conditioning o f specimens
Before the test, specimens shall be conditioned to constant mass at a temperature of (23 ± 2) °C, and a
relative humidity o f (50 ± 5) % in accordance with ISO 554.
Constant mass shall be considered to have been reached when two successive weighing operations,
carried out at an interval o f 24 h, do not di ffer by more than 0,1 % o f the mass o f the test piece or 0,1 g,
whichever is greater.
Materials such as polyamides, which require more than one week in conditioning to reach equilibrium,
may be tested a fter conditioning in accordance with ISO 291. This period shall be not less than one
week, and shall be described in the test report.
8.3 Preparation
A conditioned specimen shall be wrapped in a single layer o f aluminium foil, o f 0,025 mm to 0,04 mm
thickness, with the shiny side towards the specimen. The aluminium foil shall be pre-cut to a size to
cover the bottom and sides o f the specimen and extend 3 mm or more beyond the upper sur face o f
the specimen. The specimen shall be placed in the middle of the foil and the bottom and sides shall
© ISO 2016 – All rights reserved
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
13
ISO/TS 5660-4:2016(E)
be wrapped. The excess foil above the top sur face shall be cut i f necessary so that it does not extend
more than 3 mm above the top surface of the specimen. The excess foil at the corners shall be folded
around the corners to form a seal around the top surface of the specimen. After wrapping, the wrapped
specimen shall be placed in the specimen holder and covered by a retainer frame. No aluminium foil
shall be visible after the procedure is completed.
For so ft specimens, a dummy specimen having the same thickness as the specimen to be tested may be
used to preshape the aluminium foil.
All specimens shall be tested with the retainer frame shown in Figure 4. The following steps shall be
taken to prepare a specimen for testing:
a) put the retainer frame on a flat sur face facing down;
b) insert the foil-wrapped specimen into the frame with the exposed surface facing down;
c) put layers o f re fractory fibre blanket (nominal thickness 13 mm, nominal density 65 kg/m 3 ) on top
until at least one full layer, and not more than two layers extend above the rim o f the frame;
d) fit the sample holder into the frame on top o f the re fractory fibre and press down;
e) secure the retainer frame to the specimen holder.
9 Test environment
It is imperative that the following good laboratory and operating procedures are practised at all times.
a) The cone calorimeter shall be in a draught- free environment, with an atmosphere relative humidity
between 20 % and 80 % and temperature between 15 °C and 30 °C.
b) The oxygen analyser and the pressure transducer shall be located in an isothermal environment.
c) The CO 2 trap and the moisture traps shall be checked daily and the sorbents shall be replaced daily
as o ften as necessary.
d) Any accumulated water shall be removed from the cold trap daily be fore testing day and
subsequently when necessary.
e) Calibrations of all operating instruments, including calculation of the “C” constant C, shall be
per formed at least once daily.
10 Calibration
10.1.1 General
The calibrations in this subclause shall be per formed, when first commissioning a cone calorimeter; or
a fter maintenance, repair or replacement o f the heater assembly the weighing device (10.1.3 and 10.1.4),
the oxygen analyser or other major components o f the gas analysis system (10.1.5). The calibration
tests to determine the effect of side screens in 6.16 are conducted at the time the screens are installed.
For a new instrument that is delivered with side screens, this shall be done by the manu facturer.
14
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
The cone heater shall not be turned on for this calibration. Place an empty specimen holder with a
(750 ± 50) g non-combustible weight piece on the weighing device.
NOTE The weight piece accounts for the retainer frame, which is not used during this calibration.
Measure the weighing device output, and mechanically or electronically adjust the value to zero. Gently
add a second non-combustible weight piece with a mass of (750 ± 50) g on the holder and record the
weighing device output. A fter equilibrium is reached, gently remove the second weight piece from the
holder, and again record the weighing device output. Determine the response time of the weighing
device as the average of the times for the weighing device output to change from 10 % to 90 % of its
ultimate deflection.
Set the height of the cone heater to the same position as when testing a specimen with the retainer
frame. Place a thermal barrier on the weighing device. Turn on power to the exhaust fan and cone heater.
Set an exhaust volumetric flow rate o f (0,012 ± 0,002) m 3/s and an irradiance of (50 ± 1) kW·m−2 . Once
the heater temperature has reached its equilibrium, remove the thermal barrier and place an empty
specimen holder with a (750 ± 50) g weight piece on the weighing device.
NOTE The weight piece accounts for the retainer frame, which is not used during this calibration.
A fter equilibrium is reached, measure the weighing device output and mechanically or electronically
adjust the value to zero. Gently add a second weight piece with a mass o f (1 500 ± 500) g on the
specimen holder. After equilibrium is reached, record the weighing device output. After 30 min, record
the weighing device output. Calculate the drift of the weighing device output as the absolute value of
the di fference o f the initial and final values.
The cone heater shall not be turned on for this calibration. Turn on the exhaust fan, and set an exhaust
volumetric flow rate o f (0,012 ± 0,002) m 3/s. Determine the delay time o f the oxygen analyser by
delivering a methane mass flow rate equivalent to 1 kW to the calibration burner. Light the burner
outside the hood and allow flame to stabilize. Quickly introduce the burner underneath the hood, and
leave the burner in position for 3 min. Then, remove the burner from underneath the hood and turn
o ff the methane supply. Record the output o f the analyser from the moment o f insertion o f the burner
underneath the hood, until 3 min a fter removal o f the burner. The turn-on delay is determined by the
time di fference between insertion o f the burner and the oxygen reading reaching 50 % o f its ultimate
deflection. Calculate the turn-o ff delay similarly. The delay time td shall be determined using the
average o f at least three turn-on and turn-o ff delays. The oxygen concentration at a given time shall be
taken as the concentration registered after the time interval, t . d
The response time o f the oxygen analyser shall be calculated as the average for the turn-on and turn-
o ff experiments o f the time for the oxygen analyser output to change from 10 % to 90 % o f its ultimate
deflection.
NOTE 1 For the purpose o f measurement o f the oxygen analyser delay and response time, the methane mass
flow rate need not be controlled accurately, because the delay and response time is not sensitive to the oxygen level.
NOTE 2 This procedure should be repeated if the test is repeated at (0,018 ± 0,002) m3/s
10.1.5 Oxygen analyser output noise and dri ft
The cone heater shall not be turned on for this calibration. Turn on the exhaust fan and set an exhaust
volumetric flow rate o f (0,012 ± 0,002) m 3/s. Feed the oxygen analyser with oxygen- free nitrogen gas.
A fter 60 min, switch to dried ambient air from the exhaust duct at the normal volumetric flow rate
and pressure as for the sample gases. A fter reaching equilibrium, adjust the oxygen analyser output
to (20,95 ± 0,01) %. Start recording the oxygen analyser output at 5 s intervals for a period o f 30 min.
Determine the dri ft by use o f a least squares fitting procedure to fit a straight line through the data
points. For the straight line fit, the absolute value o f the di fference between the reading at 0 and at
30 min establishes the short-term dri ft. Determine the noise by computing the root-mean-square
deviation around the linear trend line according to Formu la (1) :
∑ xi 2
i =1
rms = (1)
n
where xi is the ab solute difference b etween the data p oint and the linear trend l ine.
Record this rms noise value in terms o f parts per million o f oxygen.
10.2.1 General
The following calibrations shall be per formed at the start o f testing each day, in the order given below.
T he heater cal ibration shal l also b e p erformed when changing to a di fferent irradiance level .
T he weighing device shal l b e calibrated with s tandard weight pieces in the range of tes t s p ecimen mas s .
T he cone heater shal l b e turned off and the app aratus shal l b e cooled down to ambient temp erature
be fore this calibration is per formed. Place an empty specimen holder with a (750 ± 50) g weight piece
on the weighing device. T he retainer frame is not used during this calibration. Meas ure the weighing
device output, and mechanically or electronically adjust the value to zero. Gently add a calibrated
weight piece with a mas s b etween 5 0 0 g to (6 0 0 ± 10) g on the holder and meas ure the weighing device
output a fter it reaches a steady value. Repeat this procedure at least four times a fter adding calibrated
weight pieces of the s ame mas s . At the end of the calibration, the total mas s of al l weight pieces on
the holder shall not exceed 2 500 g. The accuracy o f the weighing device shall be determined as the
ma ximum di fference b etween the mas s of the weight pieces and the weighing device output recorded
Zero and calibrate the oxygen analyser. This calibration may be per formed with the cone heater
op erating or not, but shal l not b e p erformed during heater warm-up . Turn on the exhaus t fan, and set
an exhaust volumetric flow rate o f (0,012 ± 0,002) m /s. For zeroing, feed the analyser with oxygen-
3
free nitrogen gas, with the same volumetric flow rate and pressure as for the sample gases. Adjust the
analyser response to (0,00 ± 0,01) %. Calibration shall be similarly achieved using dried ambient air
and adjusting for a response o f (20,95 ± 0,01) %. Care fully monitor analyser volumetric flow rate and
set to be equal to the volumetric flow rate used when testing specimens. A fter each specimen has been
tes ted, ens ure that a res p onse level of (2 0 ,95 ± 0 ,01) % is ob tained us ing dried ambient air.
Per form a heat release rate calibration to determine the orifice constant C. T his calibration shal l b e
p erformed with the cone heater op erating or not, but shal l not b e p erformed during heater warm-up .
Turn on the exhaust fan, and set an exhaust volumetric flow rate o f (0,012 ± 0,002) m 3 /s . Star t col lec ting
b asel ine data at 5 s inter val s for a p erio d of at leas t 1 min . I ntro duce methane into the cal ibration
burner using a calibrated flow meter at a mass flow rate corresponding to q = (1 ± 0 ,1) kW b ased on
b
the net heat o f combustion o f methane (50,0 × 103 kJ/ kg). Allow 3 min for the methane flow to reach a
cons tant rate then col lec t data at 5 s inter val s over a 3 min p eriod.
16
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
The orifice constant C shall be calculated according to Formula (2), using averages over the 3 min period
of the measured values of q b , Te, Δ P, and XO . XO0 is determined as the average of the oxygen analyser
2 2
output measured during the 1 min baseline measurements.
An alternate procedure for performing this calibration consists of burning a suitable liquid fuel
(e.g. ethanol) in a special pan that is placed on the weighing device. The average theoretical heat release
rate is then obtained as the total mass o f fuel burnt multiplied by the net heat o f combustion o f the fuel,
and divided by the duration o f flaming.
10.2.5 Heater calibration
At the start o f testing each day or when changing to a di fferent irradiance level, adjust the irradiance
control system so that the conical heater produces the required irradiance to within ±2 %, as measured
by the heat flux meter. No specimen or specimen holder shall be used when the heat flux meter is
inserted into the calibration position. Allow 10 min for the cone heater to reach thermal stability at the
set point.
10.3 Less frequent calibrations
10.3.1 Working-standard heat flux meter calibration
At maximum intervals o f 100 working hours, check the working-standard heat flux meter against the
secondary-standard heat flux meter according to ISO 14934-3. The operating heat flux meter shall be
calibrated in accordance with ISO 14934-3:2012, Annex D.
10.3.2 Linearity o f heat release rate measurements
At maximum intervals of 100 working hours, with the instrument calibrated at 1 kW according to 10.2.4,
per form a further calibration with a mass flow rate corresponding to 2 kW ± 10 % and 3 kW ± 10 %,
using the basic procedure as described in 10.2.4. With the value for C from the 1 kW calibration, the
measured heat release rate at 2 kW and 3 kW shall be within ±5 % of the set value.
10.3.3 Accuracy o f calibration burner flow meter
The accuracy o f the calibration burner flow meter shall be verified every 6 months or when the
calibration factor determined according to 10.2.2 di ffers by more than 5 % from the value obtained
during the first heat release rate calibration following the previous flow meter verification. To veri fy
the accuracy o f the flow meter, per form the burner calibration described in 10.2.4, with a reference
flow meter in series with the operating flow meter. During the 3 min period o f data collection, both flow
meters shall agree to within ±3 %. If the difference between the two measurements exceeds ±3 %, the
operating flow meter shall be re-calibrated as recommended by the manu facturer.
11 Test procedure
11.1 General precautions
WARNING — So that suitable precautions are taken to sa feguard health, the attention of all
concerned in fire tests is drawn to the possibility that toxic or harm ful gases can be evolved
during exposure of test specimens.
The test procedures involve high temperatures and combustion processes. Therefore, hazards can exist
such as burns or the ignition o f extraneous objects or clothing. The operator shall use protective gloves
for insertion and removal o f test specimens. Neither the cone heater nor the associated fixtures shall
be touched while hot except with the use of protective gloves. Care shall be taken never to touch the
spark igniter which carries a substantial potential (10 kV). The exhaust system o f the apparatus shall
be checked for proper operation be fore testing and shall discharge into a building exhaust system with
adequate capacity. The possibility o f the violent ejection o f molten hot material or sharp fragments
from some types o f specimens when irradiated cannot be discounted and it is there fore essential that
eye protection be worn.
11.2.1 Check the CO 2 trap and both moisture traps. Replace the chemical i f necessary. Drain any
accumulated water in the cold trap separation chamber. The normal operating temperature of the cold
I f any o f the traps or filters in the gas sampling line have been opened during the check, the gas sampling
should be checked for leaks (with the sample pump on), e.g. by introducing pure nitrogen, at the same
volumetric flow rate and pressure as for the sample gases, from a nitrogen source connected as close
as possible to the gas sampling ring probe (sample holes face blower). The oxygen analyser shall then
read zero .
11.2.2 Adjust the distance between the base plate o f the cone heater and the upper surface o f the
specimen as specified in 6.5 or 7 .5 .
11.2.3 Turn on power to the cone heater and the exhaust fan. Power to the gas analysers, weighing
device and pressure transducer shall not be turned o ff on a daily basis.
11.2.5 Perform the required calibration procedures specified in 1 0 .2 . Put a thermal barrier on top of the
weighing device (for example, an empty specimen holder with refractory fibre blanket or water cooled
radiation shield) in place during warm up and between tests to avoid excessive heat transmission to the
weighing device.
11.2.6 Set the irradiance level of 5 0 kW· m −2 . Alternatively, testing may be conducted at an exposure
of 7 5 kW· m −2 provided that there is no ignition of the sp ecimen at the 5 0 kW· m −2 irradiance level, and
there is evidence of continued comb ustion after the 2 0 min test duration.
11.3.1 Start data collection. C ollect at least 60 s of b aseline data prior to starting a test. The scan interval
shall be as per 7 .3 .
11.3.2 I nsert the radiation shield (which must be cooler than 1 0 0 °C) in p osition. Remove the thermal
11.3.3 Place the specimen, held in the specimen holder, onto the sample mount assembly. The holder
shall be at room temperature initially.
11.3.4 Remove the radiation shield. Start the test and ignition timer. M ove the sp ark plug into place, and
11.3.5 Record the times when flashing or transitory flaming occurs. When sustained flaming occurs
(reported as the time at which flaming was initially observed, not when the 10 s period elapsed) record
the time, turn o ff the spark, and remove the spark igniter. I f the flame extinguishes in less than 60 s after
18
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
turning o ff the spark, reinsert the spark igniter and turn on the spark. I f flaming recurs, stop the test,
discard the test data, and repeat the test without removing the spark until the entire test is completed.
Report these events in the test report. Continue the test until a total of 20 min have elapsed since the
start of the test.
If smoke is being lost through the cone heater, the test should be repeated at 18 l/s, with a note
explaining that this will reduce the resolution.
11.3.6 At the end o f the time period specified in 11.3.5, put back the radiation shield position, remove
the specimen holder with specimen from the test position and remove the sample from the holder and
wait until all combustion products are gone. Record the end o f test value for the oxygen analyser. The
value should be within 100 ppm from the value recorded at the beginning of the test. If the value is not
within the 100 ppm value, the test shall be run again.
The test may be stopped i f explosive spalling or excessive swelling occurs. The specimen holder and
weighing device may become very hot during operation. Care should be taken by the operator when
removing the specimen.
11.3.7 Insert the thermal barrier to protect the weighing device from irradiance.
11.3.8 Collect data at least 3 min after the specimen removal.
11.3.9 Make three determinations and report as specified in Clause 14.
13.1 General
The formulae in this subclause assume that only O 2 is measured using the gas analysis system in
Figure 5 . Appropriate formulae for cases where additional gas analysis equipment (CO2 , CO and possibly
H 2 O) is used and CO2 is not removed from the O2 sampling lines can be found in ISO 5660−1:2015,
Annex F. If CO2 is removed from the O2 sampling lines (even when CO2 is separately measured), then
Formulae (2) to (4) shall be used.
13.2 Calibration constant for oxygen consumption analysis
The heat release rate calibration specified in 10.2.4 shall be per formed daily to check for the proper
operation o f the instrument and to compensate for minor changes in determination o f mass flow. The
calibration constant, C, is calculated using Formula (2):
q b Te 1, 105 − 1, 5 X O
C = ⋅ 2
(2)
( 12, 54 × 10 3
) ( 1, 10 ) ∆p X0 − XO
O2 2
where
corres p onds to the rate of heat release (in kW) of the methane s upplied (see 10 . 2 .4) ;
q b
ma l func tion .
13.3.1 Prior to performing other calculations, calculate the oxygen analyser reading from the recorded
analyser data and the delay time, t , using Formula (3 ) : d
XO (t) = X1 (t + td ) (3 )
2 O2
13.3.2 Calculate the heat release rate, q t() , from Formula (4) :
X0 − XO
∆p O2 2
q ( t ) = ∆h c / ro ) ( 1, 10 ) C ⋅ (4)
Te 1, 105 − 1, 5 X O
2
where Δ h c /ro for
the specimen is taken as (13,1 × 10 ) kJ/ kg, un les s a more accurate value is known,
3
0
and X
O2
is determined as the average o f the oxygen analyser output measured during the last 1 min o f
the b aseline meas urements .
NOTE The value o f Δ h c /ro = 1 3 ,1 M J/ kg O 2 i s given with in 5 % accord ing to I S O 5 6 6 0 -3 . H owever, th i s va lue
i s adap ted to the c arb onaceous fuel and a con s is tent combus tion . For the pur p o s e of th i s s tandard, materia l s and
products with very low levels o f heat release are tested. This means that the value o f Δ h /r can significantly c o
deviate from the theoretical value, well beyond the 5 %. Also, i f a value o f Δ h /r i s no t known for the tes ted fuel, c o
13.3.3 H eat release per unit area can b e ob tained from Formula (5 ) :
() ()
q A t ? = ? q t ? /? A
s
(5 )
20
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
13.5.1 The mass loss rate, − m , at each time interval may b e calculated us ing the fo llowing five- p o int
25 m 0 − 48 m 1 + 36 m 2 − 16 m 3 + 3 m 4
−[ m ] i = 0 = (7)
12 ∆t
3 m 0 + 10 m 1 − 18 m 2 + 6 m 3 − m 4
−[ m ] i = 0 = (8)
12 ∆t
For a ny s c an for wh ich 1 < I < n −1 (where n is the total number of scans):
−m i − 2 + 8 mi −1 − 8 m i + 1 + mi + 2
−[ m ] i = (9)
12 ∆t
−3 m n − 10 m n − 1 + 18 m n − 2 − 6 m n − 3 + m n − 4
−[ m ] i = n − 1 = (10)
12 ∆t
−25 m + 48 m n − 1 − 36 m n − 2 + 16 m n − 3 − m n − 4
−[ m ] i = n = (11)
12 ∆t
where
Δm = m s m f; −
m10 = m s m; − 0 ,10 Δ
m 90 = m s m. − 0 ,9 0 Δ
NO TE E qu atio n s for the e ffe c tive he at o f comb u s tion , Δ h c,eff, are given in A.1.8 and ISO 5660–1:2015,
Annex C.
14 Test report
The test report shall contain the following information for each specimen:
a) name of manufacturer (and submitter where applicable);
b) name of operator
© ISO 2016 – All rights reserved
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
21
ISO/TS 5 660-4: 2 01 6(E)
c) date of test;
i) irradiance, in kW·m −2
a nd exhau s t flow rate, i n m 3 /s;
j) ti me to s u s tai ne d flam i ng , i n s;
22
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Annex A
(informative)
Overview
A.1 Background
A.1.1 Overview
A brie f history to give insight into the development o f the method described in this document and to
provide a rationale for the design of the various features of the apparatus is discussed in Reference [14].
More recent work on the development of the larger conical heater to be used in this document can be
found in in Reference [17].
A.1.2 Heat release rate measurements
A.1.2.1 The rate o f heat release is one o f the most important variables, in many cases the single most
important variable, in determining the hazard from a fire. This rate o f heat release is the total rate,
as a function o f time and irradiance. With many items, composed o f many surfaces, contributing to a
fire, the evaluation o f rate o f heat release is quite complex. For each separate surface, it should first be
determined when, i f at all, it will become ignited. The size o f the fire from any already burning items
should be known, since that constitutes the external irradiance to nearby items. Next, the flame spread
over the surface in question should be evaluated. The rate of heat release from the whole surface can
then be evaluated knowing the rate of heat release per unit area for a given irradiance, as a function of
time. This last quantity is the only one that can be measured in a bench-scale test.
A.1.2.2 The total heat release from a fire then involves a summation o f the heat release per unit area
over the surface. Also to be considered is the fact that some elements may burn out and then no longer
contribute to the fire. This procedure is conceptually straightforward but can be very cumbersome to
compute.
A.1.2.3 Many common combustibles do not have the geometrically simple surfaces that are required
to make computations of this kind. Other complications, such as melting, dripping, or collapsing can also
preclude a detailed mathematical analysis. In such cases a simpler, more empirical model is appropriate.
An example o f the use o f bench-scale heat release rate measurements in deriving a fire hazard assessment
is available. [1] A number o f apparatus have been developed over the years for measuring rate o f heat
release; most of these have been reviewed in detail. [2] Traditionally, the simplest measurement scheme
is a direct measurement o f flow enthalpy from a chamber thermally lagged to present an adiabatic
environment. A truly adiabatic apparatus, with the use o f guard heaters, would be possible but would
also be prohibitively expensive and has not been implemented. A combustion chamber that is insulated in
a simpler manner leads to a significant under measurement o f the heat release, so that only an empirical
calibration is possible. An example of such an insulated chamber method is ASTM Test Method E906.
Furthermore, that calibration may be sensitive to the radiant fraction (or sootiness) o f the combustible.
[3][4] A more advanced scheme is an isothermal instrument, rather than an adiabatic one, with the heat
release rate taken to be that which should be supplied by a substitution burner to maintain isothermal
conditions. [5] This scheme gives better results, since only second-order heat loss error terms remain;
however, its practical implementation is complex and costly.
A.1.2.4 It can be concluded that it is di fficult to measure heat directly without losing some o f it.
However, it is simple to capture all combustion products without losing any and to measure the oxygen
levels in that stream. Heat release can be computed from such measurements with the availability o f the
oxygen consumption principle. [6] This principle states that for most common combustibles an amount of
heat equal to 13,1 kJ × 10 kJ is released for each kilogram o f oxygen consumed from the air stream. This
3
constant varies only about ±5 % for most common combustibles; certain exceptions are given in. The [6]
method remains use ful even i f a significant fraction o f the products become CO or soot, rather than CO ; 2
in these cases, correction terms are known [6] [7 ] and can be ap plied.
A.1.4.1 Exp erience with various rate-of-heat-release measurement techniques suggests that for
c) op en air.
Nearby solid sur faces, i f they are not temperature-controlled, can rise in temperature due to specimen
flame heating and then act as further sources o f radiation back to the specimen. Further, when oxygen
consumption is used as the measurement principle, a gas-fired heater is not desirable because it can
contribute a noisy baseline to the oxygen readings, even though it can be subtracted out in steady-state.
A.1.4.2 A heater in the shape o f a truncated cone was first explored for use in an ignitability apparatus
by ISO (see ISO 5657). The heater adopted in the present method is similar, but not identical to the
device described in I SO 5 65 7 . The main differences include higher irradiances, temperature control, and
more rugged design details. In the horizontal orientation, the conical shape approximately follows the
fire plume contours while the central hole allows the stream to emerge without impacting on the heater.
A thin layer o f cool air is pulled along and the flames do not make contact with the sides o f the cone. The
central hole has a further function; in its absence the middle of the sp ecimen would receive a higher
irradiance than the edges. With the hole, the irradiance is uniform to within ± 2 %.
can be made by using a layer o f an insulating material. This is easier to do for the horizontal orientation
case, in which case a very low density re fractory blanket is used.
24
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
approxi mately ± 2 5 ppm ox ygen . O ther typ e s o f a na lys ers (for e xample, ele c tro chem ic a l and c ata lytic)
genera l ly c an no t me e t th i s re qu i rement. Para magne tic a na lys ers a l s o exh ibit an i ntri n s ic a l ly l i ne ar
Si nce an ox ygen a na lys er i s s en s itive to s tre am pre s s ure s , either the re ad i ngs h ave to b e comp en s ate d
with an ab s olute pre s s u re tra n s ducer, con ne c te d to the a na lys er, or the pre s s u re h as to b e me cha n ic a l ly
regu late d b o th aga i n s t flow fluc tuation s and atmo s pheric pre s s u re variation s . T he a na lys er and the
as noise and drift, it is suggested that 10.1.4 and 10.1.5 b e p er for me d for one day, thereb y pro vid i ng a b e tter
Examples of a material with a single mode of degradation and, therefore, a constant effective heat of
combu s tion i nclude mo s t organ ic l iqu id s . C el lu lo s ic pro duc ts , by contra s t, typic a l ly s how more th an one
mo de o f degradation and a var yi ng e ffe c tive he at o f combu s tion . For materia l s havi ng more than one
mode of degradation, or for composites or non-homogeneous materials, the effective heat of combustion
i s no t ne ce s s a ri ly con s tant.
o f pro duc ts and materia l s . T he s e a re no t the on ly s p e ci men mou nti ng me tho d s ava i l able to the te s ti ng
lab orator y. 9 Re ference [ ] s ugge s ts s ome add itiona l pro ce du re s . For more unu s ua l s p e ci men typ e s ,
the te s ti ng lab orator y wi l l have to devi s e appropri ate mou nti ng me tho d s . Si nce d i fferent mou nti ng
methods could give different test results, the method used should be documented in the test report.
Si nce te s t re s u lts a re i nevitably a ffe c te d b y s uch mou nti ng device s , they s hou ld no t b e u s e d u n le s s prior
te s ti ng i nd ic ate s that they a re ne ce s s a r y to a l levi ate anoma lou s burn i ng cond ition s .
Annex B
(informative)
The inter-comparison o f working and re ference standard heat flux meters specified in 6.13 , may be
made using the conical heater (6.2 ), with each heat flux meter mounted in turn in the calibration
position. Care should be taken to allow the whole apparatus to attain thermal equilibrium. Alternatively,
a specially built comparison apparatus may be used (for example, devices specified in BS 6809:1987).
The use o f two, instead o f just one re ference standard, provides a greater sa feguard against change in
sensitivity o f the re ference instruments.
26
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Annex C
(informative)
Calculation o f heat release with additional gas analysis
C.1 General
The formulae in Clause 13 used to calculate heat release rate assume CO2 /CO are removed from the
gas sample in a chemical scrubber before O2 is measured, as indicated in Figure 5. Some laboratories
are equipped to measure CO2 2 /CO from the O 2
/C O i n wh ich c a s e it i s no t ne ce s s a r y to remove the C O
f
l i ne givi ng the advantage th at the u s e o f
chem ic a l s c rubbi ng agent, wh ich i s co s tly and re qu i re s c are u l
requirement cannot be met, this annex shall not be used for obtaining the heat release rate. Silica
2
gel/D rierite sh a l l no t b e u s e d as the d r yi ng agent i f a C O /C O ana lys er i s u s e d i n the s ys tem .
In this annex, formulae are given which are to be used when CO2/CO is measured but not scrubbed out
of the sampling lines. Two cases are considered:
— f
i n the fi rs t ca s e, p a r t o f 2 and CO
the d rie d a nd fi ltere d s ample s tre a m i s d iver te d i nto i n rare d C O
Figure 5);
a na lys ers (s e e op tion i n
To avoid condensation, the measuring of H 2 O concentration i n the flow o f combu s tion pro duc ts re qu i re s
a s ep a rate s ampl i ng s ys tem with he ate d fi lters , he ate d s a mpl i ng l i ne s , a nd he ate d ana lys er.
C.2 Symbols
T he fol lowi ng new s ymb ol s are u s e d i n th i s an nex:
p ambient pressure Pa
Ta ambient temperature K
1 del ay ti me o f the C O 2 a n a l ys er s
td
2 del ay ti me o f the C O a n a l ys er s
td
3 del ay ti me o f the H 2 O a n a l ys er s
td
C.3.1 Instrumentation
The CO 2 analyser shall be o f the IR type and capable o f measuring a range o f at least 0 % to 10 % carbon
dioxide. The linearity o f the analyser shall be 1 % o f full scale or better. The response time o f the
analyser shall be not more than 12 s (as measured in accordance with 10.1.4).
The output from the analyser to the data acquisition system shall have a resolution o f 100 ppm or better.
The CO analyser shall be o f the IR type and capable o f measuring a range o f at least 0 % to 1 % carbon
monoxide. The linearity o f the analyser shall be 1 % o f full scale or better. The response time o f the
analyser shall be not more than 12 s. The output from the analyser to the data acquisition system shall
have a resolution of 10 ppm or better.
C.3.2 Carbon dioxide analyser adjustment
The carbon dioxide analyser shall be adjusted for zero and span each day on which tests are per formed.
The analyser output for carbon dioxide- free nitrogen gas shall be (0,00 ± 0,02) %. The span width shall
be within 0,02 % VCO2 /Vair o f the width defined by the calibration gases used. A possible procedure to
per form the adjustment is given below.
a) For zeroing, feed the analyser with carbon dioxide- free nitrogen gas, with the same volumetric flow
rate and pressure as for sample gases. When the analyser reaches equilibrium, adjust the analyser
output to (0,00 ± 0,02) %.
b) For span calibration, a specified gas with a carbon dioxide content between 5 % and 10 % should
be used. Feed the analyser with the gas, with the same volumetric flow rate and pressure as for
28
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
sample gases. When the analyser reaches equilibrium, adjust the analyser output to the carbon
dioxide content o f the specified gas ± 0,02 %.
C.3.3 Carbon monoxide analyser adjustment
The carbon monoxide analyser shall be adjusted for zero and span each day on which tests are
per formed. The analyser output for carbon monoxide- free nitrogen gas shall be (0,000 ± 0,002) %.
The span width shall be within 0,002 % VCO/Vair of the width defined by the calibration gases used. A
possible procedure to per form the adjustment is given below.
a) For zeroing, feed the analyser with carbon monoxide- free nitrogen gas, with the same volumetric
flow rate and pressure as for sample gases. When the analyser reaches equilibrium, adjust the
analyser output to (0,000 ± 0,002) %.
b) For span calibration, a specified gas with a carbon monoxide content between 0,5 % and 1,0 %
should be used. Feed the analyser with the gas, with the same volumetric flow rate and pressure as
for sample gases. When the analyser reaches equilibrium, adjust the analyser output to the carbon
monoxide content o f the specified gas ± 0,002 %.
C.3.4 Calculations
Just as for the oxygen analyser, measurements o f CO 2 and CO shall be time shifted to take transport
time in the sampling lines into account:
XO
2
(t) = X1
O2
(t + td ) (C.1)
XCO
2
(t) = X1
CO 2
(t + t d1 ) (C.2)
1
XCO ( t ) = XCO 2
(t + t )
d
(C.3)
Here, the delay times, t d1 and t d2 , for the CO 2 and CO analysers, respectively, are usually di fferent
(smaller) than the delay time, td , for the O 2 analyser.
The exhaust duct flow is calculated in the same way as in 13.3:
∆p
m e = C (C.4)
Te
The heat release rate can now be determined from Formula (C.5):
E − E
Φ − CO ( 1 − Φ ) X CO / X CO
2 E 2
q = 1, 10 ⋅ E ⋅ X a
O2
m e (C.5)
( 1 − Φ ) + 1, 105 Φ
The oxygen depletion factor, Φ, follows from
0 0
X (1 − X
CO 2
− X
CO
) − X
O2
(1 − X )
Φ=
O2
0
CO 2
(C.6)
X (1 − X
CO 2
− X
CO
− X
O2
)
O2
where
H 3 816
X0 = exp 23, 2 − (C . 8)
H2O 100 ⋅ p Ta − 46
T he second term in the numerator of the term in brackets in Formu la (C . 5 ) is a correc tion for incomplete
combus tion of some carb on to CO ins tead of CO 2 . I n cone calorimeter tes ts , XC O is usually very small
so that it can b e neglec ted in Formu lae (C . 5 ) and (C . 6) . T he prac tical implication of this is that a CO
analyser will generally not result in a noticeable increase in accuracy o f heat release rate measurements.
Consequently, Formu lae (C . 5 ) and (C . 6) can be used even i f no CO analyser is present, assuming X is CO
the air which is fully depleted o f its oxygen. This expansion depends on the composition o f the fuel and
the actual stoichiometry o f the combustion. A good average value for the volumetric expansion factor is
1 ,10 5 , which is correc t for methane.
This number is already incorporated within the formulae in 12.2.2 and Formu la (C . 5 ) . For cone
calorimeter tes ts , it can b e as s umed that over 9 9 % of the combus tion pro duc ts cons is t of O 2 , CO 2 , CO,
H2 O and non-reacting gases (which enter and leave the system chemically unaltered) denoted as N 2.
I f H 2 O is meas ured in the exhaus t, this , together with the O 2 , CO 2 , and CO meas urements (al l three
re ferred to the dry gas), can be used to determine the expansion. The mass flow rate in the exhaust
duct is then more accurately given by Formu la (C .9) :
Me ∆p
m e = C (C .9)
Ma Te
I n this equation, Ma can b e taken as 2 9 kg/ kmol . T he molecu lar weight of the combus tion pro duc ts , Me ,
can b e calculated from Formu la (C .10) :
M e = 4, 5 + ( 1 − X H ) ( 2, 5 + XO + 4 XCO )
⋅4 (C .10)
2O 2 2
X 0 (1 − X − X )
O2 O2 CO 2
q( t ) = 1, 10 ⋅ E ⋅ ( 1 − X H O )
− XO me (C .11)
2
1 − X0 − X0 2
O2 O2
It shal l b e noted that the H 2 O readings must be time shi fted in a similar way as in Formu lae (C .1) to
30
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Annex D
(informative)
Data obtained in initial round robin
D.1 Background
A small interlaboratory exercise was organized in order to give validating data to support the
test method for low heat release materials. Results from testing using the method described in this
document were compared to those obtained from standard ISO 5660-1 tests on the same specimens.
D.2 Specimens
Three types o f specimen in two sizes were tested:
— plasterboard tile in
— 100 mm × 100 mm, and
— 150 mm × 150 mm;
— mineral fibre ceiling tile in
— 100 mm × 100 mm, and
— 150 mm × 150 mm;
— vinyl- faced mineral fibre ceiling tile in
— 100 mm × 100 mm, and
— 150 mm × 150 mm.
T he s e show the Pe a k H RR and C o e fficients o f Va ria nce (C oV ) were lower for s p e ci men s te s te d accord i ng
to the metho d describ ed in this document than those tes ted according to I SO 5 6 6 0 -1 . T his demons trates
the s ucce s s o f i ncre a s i ng the s igna l ha s le d to b e tter re s olution and i mprove d rep e atabi l ity.
Table D.1 — Test results for mineral fibre tested to ISO 5660-1 configuration
Lab 1 Lab 2 Lab 3 Average
THR (M J/m 2 ) 6,83 5 ,70 5 ,4 8 6,00
Table D.2 — Test results for vinyl- faced mineral fibre tested to ISO 5660-1 configuration
Lab 1 Lab 2 Lab 3 Average
THR (M J/m 2 ) 8 ,43 8 ,4 0 7,1 5 7,9 9
TH R SD (M J/m 2 ) 1,08 2 , 01 0 ,9 5 0 ,7 3
Table D.3 — Test results for plasterboard tested to ISO 5660-1 configuration
Lab 1 Lab 2 Lab 3 Average
THR (M J/m 2 ) 4,4 0 3,30 2 ,70 3 ,47
Table D.4 — Test results for mineral fibre tested to ISO 5660-4 configuration
Lab 1 Lab 2 Lab 3 Average
THR (M J/m 2 ) 6 ,70 7, 8 0 5 ,4 0 6 , 63
32
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5660-4:2016(E)
Table D.5 — Test results for vinyl- faced mineral fibre tested to ISO 5660-4 configuration
Lab 1 Lab 2 Lab 3 Average
THR (MJ/m2 ) 8,77 9,80 6,98 8,51
THR SD (MJ/m 2 ) 0,38 0,10 0,45 1,43
THR CoV (MJ/m2 )(%) 4,32 1,02 6,45 16,79
Peak HRR (kW/m 2 ) 178,10 166,50 188,94 177,85
Peak HRR SD (kW/m 2 ) 22,62 8,33 5,46 11,22
Peak HRR CoV (kW/m2 )(%) 12,70 5,00 2,89 6,31
Table D.6 — Test results for plasterboard tested to ISO 5660-4 configuration
Lab 1 Lab 2 Lab 3 Average
THR (MJ/m2 ) 3,55 5,10 2,20 3,62
THR SD (MJ/m 2 ) 0,35 0,37 0,14 1,45
THR CoV (MJ/m2 )(%) 9,96 7,25 6,43 40,12
Peak HRR (kW/m 2 ) 104,76 101,20 94,41 100,12
Peak HRR SD (kW/m 2 ) 0,68 12,20 6,97 5,26
Peak HRR CoV (kW/m2 )(%) 0,65 12,06 7,38 5,25
Bibliography
[1] B abrauskas V. , & K rasn y J . F. P redic tion of Uphol s tered C hair Heat Releas e Rates from B ench-
Scale Measurements. In: “Fire Sa fety Science and Engineering”, ASTM STP 882. ASTM, 1985,
pp . 2 6 8 .
[2 ] J anssens M. Survey o f Rate o f Heat Release Test Methods and Apparatuses. Fire Saf. J. , I n pres s .
[3 ] K rause R. F. , & G ann R.G. Rate o f Heat Release Measurements Using Oxygen Consumption.
Journal of Fire and Flammability. 19 8 0 , II (Apri l) pp . 117–1 3 0
[4] B abrauskas V. Per formance o f the Ohio State University Rate o f Heat-Release Apparatus Using
Polymethylmethacrylate and Gaseous Fuels. Fire Saf. J. 19 82 , 5 pp . 9 –2 0
[5 ] Tordella J . , & T wille y W.H. “Development o f a Calorimeter for Simultaneously Measuring
Heat Release and M as s Los s Rates ”, N B SI R 83 -2 70 8 . National B ureau of Standards , 19 8 3
[6] H uggett C. Estimation o f Rate o f Heat Release by Means o f Oxygen Consumption Measurements.
[8] B abrauskas V. “D evelopment of the C one C alorimeter — A B ench-S cale Heat Release Rate
[9] T wille y W. H . , & B abrauskas V. “Users Guide for the C one C alorimeter” N B S Sp ecial P ubl ication ,
SP745 . National B ureau of Standards , 19 8 8
[10] R ich ardson L . R. , & B rooks M.E. “Combustibility o f Building Materials”, pp 287-299, 16th
International Con ference on Fire Sa fety, San Francisco, 1991. Published by Interscience
C om munications Ltd . London, UK
[11] B abrauskus V. Nor th American E xp eriences in the Use of C one C alorimeter D ata for
Heat Release Rate. National Institute o f Standards and Technology, Gaithersburg, MD, 1991,
pp . 2 0 8 9 9.
[14] K aren C . , & J anssens M. Using Heat Release Rate to Assess Combustibility o f Building Products
in the C one C alorimeter. Fire Technol. 2 0 0 5 Novemb er
[17 ] G regory S . , G reen A. , Pas antes S . , , G rayson S . J . , Kum ar S . Use of C one C alorimeter for
Tes ting material s with Low Heat Release Rates . 1 3 th Fire & M aterial s con ference . Published by
I nterscience C ommunications Ltd, London, UK, 2 01 3 , pp . 2 63 .
board by large cone calorimeter” pp 171-172, Summaries o f Technical Papers o f Annual Meeting
of the Architec tural I ns titute of Jap an, S ep temb er 2 014 (in Jap anes e)
34
I n tern ati o n al Org an i z ati o n fo r S tan d ard i z ati o n
ISO/TS 5 660-4: 2 01 6(E)
[19] Yoshioka H., H ayakawa T., Yoshida K., N oguchi T. “Development of Large-Format Cone-
Calorimeter for Measuring Low Levels of Heat Release — Pertaining To Duct Flow Rates” 14th
f
Fi re & M ateria l s con erence . P ubl i she d b y I nters c ience C om mu n ic ation s Ltd, L ondon, U K, 2 01 5 ,
pp. 127–35.
ICS 1 3 .2 2 0.5 0