You are on page 1of 24

Rev. No.

0
Si210 Control Panel Doc. No. 04-695-119
Page 1/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

DI1(Si210) E/L N-PLEX


Installation/Adjustment Manual
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 2/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

Index
1. Summary ------------------------------------------------------------------3

2. System ---------------------------------------------------------------------3

3. SYSTEM structure -----------------------------------------------------4

4. Function of each operation (Definition of Terms)------------5

5. Testing procedures ----------------------------------------------------6

6. N-PLEX MODULE structure -----------------------------------------7

7. N-PLEX MODULE Connection -------------------------------------10

8. N-PLEX NETWORK ----------------------------------------------------11


8.1 4 Unit N-Plex
8.2 3 Unit N-Plex
8.3 DHG-161 PCB Installation
8.4 Terminal Resistor
8.4.1 4 Unit N-Plex
8.4.2 3 Unit N-Plex

9. SPEC DATA --------------------------------------------------------------18


9.1 Additional Spec Data of N-Plex Module
9.2 Additional Spec Data of Sigma E/L

10. Annunciator ------------------------------------------------------------18


10.1 Annunciator of Sigma E/L
10.2 Annunciator of N-Plex Module(Check Initial Status,Time Setting)

11. Trouble Code and adjustment (Additional TCD) -----------20


11.1 Sigma E/L의 Trouble Code

12. Appendix ----------------------------------------------------------------21


12.1 Each lift operation mode when system is down
12.2 Floor ID Setting
12.3 Application of N-PLEX Operation
12.4 Function of SPEC1 & SPEC2
12.5 Trouble Shooting
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 3/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

1. Summary
This manual describes about N-Plex operation system structure that control 3 or 4 Sigma(Si210)
E/L with parallel operation, network wiring and the function of operation mode

Model DI 1 (Passenger Standard, C.P Type: SI210)


Speed 105 m/min more less
Parallel E/L max. 4 Unit/group
Floor/Stop max. 32floor / 32stop
Hall line max. 2 line

2. System
N-PLEX MODULE : N-PLEX operation control a device Supervisory Network
Group Network
24VDC

Supervisory Network
Inside No.1 E/L

Elevator Elevator Elevator Elevator


N-PLEX MODULE
No. 1 No. 2 No. 3 No. 4

24Vdc 24Vdc 24Vdc 24Vdc

DOC-211

GSL1

GSL2
DON-100
GSL3

GSM1 GSM2 GSL4


Group Group
Network (1) Network (2)

DHG-161 DHG-161
(32 FL) (32FL)

CRT
Supervisory
DHG-161 DHG-161
(1 FL) (1FL)
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 4/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

3. SYSTEM structure
P5V 1
2

P24V GSL1 MG1 3


1 GND 4
2 EARTH 5

3 COM+ MB1 RLY-16 6


GSL2 1
GND MOLEX
4 2
5 COM- 3
RLY-8
AMP GSL3
DON-100 MC1
4
MOLEX

GSL4
G SM 1+ 1
1
EARTH G SM 1- 2
2 GSM1 G S L 1 ,2 +
COM+ 3
3 G S L 1 ,2 - 4
4 G SM 2+ 5
GSM2
5 COM- G SM 2- 6
G S L 3 ,4 + 7
AMP G S L 3 ,4 - 8
M OLEX

DON-100 PCB
3Φ Transformer
110Vac 5Vdc DOC-120
EMI 24Vdc
SMPS
SH AC SM
FFB 380Vac GSL1
XHA
Surge N-PLEX MODULE
Absorber
CRT Supervisory
5Vdc
GSL1 MG MG
SW
DOC-211

GSL2
DON-100 MB MB
GSL3
GSL4 GSM1 MC MC
No.1 Control Panel

3Φ Transformer
110Vac 5Vdc DOC-120
EMI SMPS
24Vdc
SH SM
FFB 380Vac GSL2
XHA
Surge
Absorber
DHG-161 DHG-161
No.2 Control Panel
3Φ Transformer
DOC-120 DHG-161 DHG-161
110Vac 5Vdc
EMI SMPS
24Vdc
SH SM
GSL3 DHG-161 DHG-161
FFB 380Vac XHA
Surge
Absorber DHG-161 DHG-161

No.3 Control Panel


3Φ Transformer DOC-120
110Vac 5Vdc
EMI 24Vdc
SMPS
Elevator No.4 SH SM
GSL4
FFB 380Vac XHA

Surge
Absorber
DHG-161 DHG-161
No.4 Control Panel
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 5/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

4. Function of each operation (Definition of Terms)


SPEC
Item Operation control Stan-
Description
dard Option

It controls disposition of lift units, door open time and reference priority at
Office attendance
mode control ● reference floor as estimating the up direction congestion in office
attendance time.
Zone separation &
It controls lifts that are operated for each assigned low zone and high zone to
Quick operation ◎ maximize their transporting capacity by new grouping in office attendance time.
control
Control operation of
According to customer requirement, it can be operated to serve only odd or
grouping Odd and ◎ even floor by new elevator grouping which are under N-PLEX Module
Even floor
Stand by control
at reference floor ● It controls system that one lift stand by at reference floor at least.

Reference floor It make lifts that are to stop at reference floor always for quick passenger
stop control ◎
transportation. If they go through reference floor.

Function The special lift is separated from N-PLEX system, being operated
VIP operation ◎
of independently according to VIP call
Service
operation Dispersion stand by It disperses elevators in force to each low, middle and high zone to reduce
control ●
passenger’s waiting time as soon as they finished all call service.

Auto parking control ◎ In case there is no call from hall and car in designated time, all lifts will park.

The disable call makes that the disable lift to be assigned for this call. Then it
Disable call control ◎
provides convenience to disabled person by adjusting door open time.
Attendance
operation ● It serves for hall call under N-PLEX, operating by lift operator.

Independent
operation ● It is separated from N-PLEX, being operated by car call

In case normal hall call service is impossible due to hall call network down
Back-Up operation ●
or button breakdown, Each lift will serve to each odd or even floor.

Normal operation by N-PLEX Module.( all lifts under N-PLEX Module will
Auto operation ●
respond to ordinary hall and car call. )

As soon as hall call is registered ,It indicates a lift that will be serve
Service reservation ◎
against the call.

Detecting of hall If hall button is pressed over designated time, the call input is
button jam ●
detected and ignored.

It indicates one that will be run first among elevators that are stand
Displaying reference lift●
Function by at reference floor.
of
Pass announcement It announces to passengers who are waiting at hall that the lift passes
Control
due to full ◎
the floor without stop due to full load.
Service
Elevator monitoring It monitors the status of elevators operation. And it can be control the N-PLEX
system ◎
operation mode change, setting and emergency operation by computer

It can be checked the N-PLEX module status and changed SPEC data
Annunciator ●
by 4 by 16 cell annunciator that is mounted on N-PLEX Module

Operation mode setting According to customer needs, it can be change to other operation mode
function for each time ●
without traffic
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 6/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

5. Testing procedures
Note: In case of replacement of ROM of DOC-211 PCB,
perform the replacement after taking out DOC-211
Install & test each lift according to the PCB from N-PLEX MODULE.
Manual (Keep safety regulation)

See if N-PLEX Module is mounted on


N-PLEX Module will be mounted on control panel of #1 lift
control panel of lift #1

Inspect if switch setting of DOC-211


Refer item #5 (Page 7)
PCB in N-PLEX Module is correct

Connect 24Vdc of each control panel by


Refer item #7 (Page 10)
using cable ASY. supplied

Connect communication between each Refer item #7 (Page 10)


control panel & N-PLEX Module and inspect Refer item #8.1, 8.2 (Page 11,12)

Inspect if terminal resistor is connected


Refer item #8.4 (Page 16)
correctly

Switch off main switch of control panel &


N-PLEX Module according to safety regulation

Inspect if LEDs of DOC-211 PCB are


Refer item #6 (Page 7)
operated according to their function

N-PLEX Module: Refer to DGS-700 Spec Edition


Check if Spec Data for N-PLEX operation is
Switch on pin #5 of SW5 of DOC-211 PCB
correct Control panel: Refer item #9.2 (Page18)

Inspect if hall call of N-PLEX is functioned


correctly
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 7/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

6. N-PLEX MODULE structure


6.1 DOC-211 & DON-100 PCB Communication(Green)
Normal : Flicking
FAILURE : On or Off
LED4 : GSM1, GSM2 (G/A) Supervisory
RS-232 PORT LED5 : GSL1, GSL2 (G/A) Group #1
FLASH MEMORY UART - B LED6 : GSL3, GSL4 (G/A) Group #2
(2MB = 1,024kB * 2) (Dummy Terminal, PCB Drive Power LED7 : GNL (LON) NOT USED
(OS + Control Program) PC Connection) (+5V, GND) LED8 : CNL (LON) NOT USED

DIP SW setting is same


SYSTEM LED(Red) with DGS-700
Normal : Off In case of N-Plex, 6 Pin
FAILURE : On of SW5 is on
LED1 : CPU Failure
LED2 : M-WDTE
LED3 : ALARM
SPEC
EEPROM
Size : 32kB

SW2:SCG(G/A)
Terminal Resistor
G1 : GSM1, GSM2
DOC-211
(CRT,Supervisory)
G2 : GSL1, GSL2
(Lift Group #1)
G3 : GSL3, GSL4
(Lift Group #2)

G/A Communication
PORT (MC)
G1 : GSM1,GSM2 (CRT,
Supervisory)Pin1,2 Pin5,6
G2 : GSL1, GSL2
(Lift Group #1) Pin3,4
G3 : GSL3, GSL4
(Lift Group #2) Pin7,8
Each E/L 24V Power
source LED

DC 5V Power supply Switch

GSL 3, GSL 4 :
Group #2 Communication
24V Power source(No.3,4) GSM 1, GSM 2
CRT , Supervisory
Connection

GSL 1, GSL 2 :
Group #1 Communication
24V Power source(No.1,2) Each E/L CRT Port

No.1 24V line & No.3 24V line &


Communication Communication
line line
CRT ,Supervisory

No.2 24V line & No.4 24V line &


Communication Communication
line line
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 8/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

6.2 N-PLEX MODULE Position

N-PLEX MODULE
Note: In case of replacement of ROM of DOC-211 PCB,
perform the replacement after taking out DOC-211
PCB from N-PLEX MODULE.

DON-100

DOC-211

6.3 Dip SW5 of DOC-211

SW Function Setting

SW1 Address Map Change Standard Pin1 & Pin2 : Off (Job site : Not used)

G1 : GSM1, GSM2 (CRT, Supervisory)


SW2 GA Terminal Resistor G2 : GSL1, GSL2 ( Group #1) ※Refer to 8.4
G3 : GSL3, GSL4 ( Group #2)

SW3 Not used *


Standard Pin1(Flash Memory) & Pin2(EEPRom) : Off
SW4 Protection Switch
Spec Write Pin1 : Off, Pin2 : On

Standard In case of N-
N-Plex, Pin 6 should be ON
1 2 3 4 5 6 7 8
SW5
Spec Write When Spec Write, Pin 3 should be On with Pin 2 of SW4
1 2 3 4 5 6 7 8

SW6 Not used *

SW7 FLASH Write Protect/Write Standard Pin1 & Pin2 : Off (Job site : Not used)
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 9/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

6.4 LED Condition of DOC-211 PCB

No. Function Color Function Condition

LED1 Failure Red Check Operation CPU working status Normal : OFF

LED2 M-WDTE Red Watch Dog Timer Error Signal Detection Normal : OFF

LED3 ALM Red Operation CPU Address Error Detection Normal : OFF

LED4 SCG1-TXRUN Green SCG1 Communication Check(Supervisory) Normal : Flickering

LED5 SCG2-TXRUN Green SCG2 Communication Check(GSL 1,2) Normal : Flickering

LED6 SCG3-TRRUN Green SCG3 Communication Check(GSL 3,4) Normal : Flickering

LED7 GNL-WDT Green GNL Working Check N/A

LED8 CNL-WDT Green CNL Working Check N/A

6.5 LED Condition of DON-100 PCB

No. Function Color Condition

No.1 E/L Main No.1 E/L Main Power On --> LED1 ON


LED1 Red
Power Checking No.1 E/L Main Power Off --> LED1 OFF

No.2 E/L Main No.2 E/L Main Power On --> LED2 ON


LED1 Red
Power Checking No.2 E/L Main Power Off --> LED2 OFF

No.3 E/L Main No.3 E/L Main Power On --> LED3 ON


LED1 Red
Power Checking No.3 E/L Main Power Off --> LED3 OFF

No.4 E/L Main No.4 E/L Main Power On --> LED4 ON


LED1 Red
Power Checking No.4 E/L Main Power Off --> LED4 OFF
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 10/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

7. N-PLEX MODULE Connection


N-PLEX MODULE

GND
GND
CableAsy. ( AEG07C441*A )

P5V
Gray : Factory Wiring

1
2
3
4
5
6
Black : Field Wiring
MG
1 F-ROM
F-ROM
MB

2
3
4
DOC-211 PCB
i960
MC
8
7
6
5
4
3
2
1
GSL3,4+

GSL1,2+

GSM 1+
GSM 2+
GSL3,4-

GSL1,2-
GSM 2-

GSM 1-
CableAsy. ( AEG07C441*B )

1
1 P5V
2
2 P5V

MG 1
GSM 1

3
3
4
4 GND
COM+ 5
5 GND
COM- 6
EARTH 7

1
2
DON-100 PCB 1
2
GSM 1+
GSM 1-

(AEG07C390*A) 3 GSL1,2+
GSM 2

3
4 GSL1,2-
MC 1

4
5 GSM 2+
COM+ 5
CableAsy. ( AEG07C441*C ) 6 GSM 2-
COM- 6
7 GSL3,4+
EARTH 7
8 GSL3,4-
MB

GSL 1 GSL 2 GSL 3 GSL 4


EARTH 7

1
1
2
3
4
5
6

1
2
3
4
5
6
EARTH 7

1
2
3

5
COM- 6
EARTH 7

2
3
4
5
6
EARTH 7
COM+

COM+

COM+

COM+
COM-

COM-
COM-
P24V

P24V

P24V

P24V
GND

GND

GND

GND

GSL1 GSL2 GSL3 GSL4 GLS1: AEG07C358*A


GLS2: AEG07C358*B,C,D
GLS3: AEG07C358*E,F,G
Np.1 DOC-120

GSL1 GSL2 GSL3 GSL4 GLS4: AEG07C358*H,I,J


AC-05

GSL1 GSL2 GSL3 GSL4

CRT
SH SH SH SH AEG07C357*A
SH SH SH SH
DOC-120 DOC-120 DOC-120 DOC-120
5 6 5 6 5 6 5 6
TML3 TML3 TML3 TML3
SH
SH

SH
SH

SH
SH

SH
SH

DOP-116 DOP-116 DOP-116 DOP-116


SVP

SVP

SVP

SVP

No.1 No.2 No.3 No.4


Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 11/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8. N-PLEX NETWORK
8.1 4 Unit N-PLEX (When Hall Line is connected No.2 and No.4)
Communication N-PLEX Terminal resistor establishment method refer to 8.4
MG
24VDC MODULE
DOC-211 Hall line can be change to No.1 instead of No.2
Terminal MC Hall line can be change to No.3 instead of No.4
Resistor
DON-100
No.4 24 Vdc Pin 1(24V),Pin 4(G) Pin 3, Pin 5
GSL4
No.3 24 Vdc Pin 1(24V),Pin 4(G) Pin 3, Pin 5
GSL3
No.2 24 Vdc Pin 1(24V),Pin 4(G) Pin 3, Pin 5
GSL2
No.1 24 Vdc Pin 1(24V),Pin 4(G) Pin 3, Pin 5
GSL1

No.1 No.2 No.3 No.4


N-PLEX
DOC-120 DOC-120 DOC-120 DOC-120

SL SH SL SH SL SH SL SH

DOP-116 DOP-116 DOP-116 DOP-116


SH SH SH SH
XHA XHA XHA XHA

DHP-100 DHP-100
HP2 DCM-10X HP2 DCM-10X
DCM-10X HP1 DCM-10X HP1
HIP2 HI HIP2 HI
HI HIP1 HI HIP1
HAP HAP

32F DHG-161 32F DHG-161


HA HA

HI1 HI2 HI1 HI2

DHF-121 DHF-121

LANTERN LANTERN LANTERN LANTERN

DHP-100 DHP-100
HP2 DCM-10X HP2 DCM-10X
DCM-10X HP1 DCM-10X HP1
HIP2 HI HIP2 HI
HI HIP1 HI HIP1
HAP HAP

1F DHG-161 1F DHG-161
HA HA

HI1 HI2 HI1 HI2

DHF-121 DHF-121
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 12/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.2 3 Unit N-PLEX (When Hall Line is connected No.2 and No.3)

Communication N-PLEX
MG Terminal resistor establishment method refer to 8.4
MODULE
24VDC DOC-211 Hall line can be change to No.1 instead of No.2
Terminal MC
Resistor
DON-100
Pin 1(24V),Pin 4(G)
No.4 24 Vdc GSL4
Pin 1(24V),Pin 4(G) Pin 3, Pin 5
No.3 24 Vdc GSL3
Pin 1(24V),Pin 4(G) Pin 3, Pin 5
No.2 24 Vdc GSL2
Pin 1(24V),Pin 4(G) Pin 3, Pin 5
No.1 24 Vdc GSL1

No.1 No.2 No.3


N-PLEX
DOC-120 DOC-120 DOC-120

SL SH SL SH SL SH

DOP-116 DOP-116 DOP-116


SH SH SH
XHA XHA XHA

DHP-100 DHP-100
HP2 DCM-10X HP2

DCM-10X HP1 DCM-10X HP1


HIP2 HI HIP2
HI HIP1 HI HIP1
HAP HAP

32F DHG-161 32F DHG-161


HA HA

HI1 HI2 HI1 HI2

DHF-121 DHF-120

LANTERN LANTERN LANTERN

DHP-100 DHP-100
HP2 DCM-10X HP2

DCM-10X HP1 DCM-10X HP1


HIP2 HI HIP2
HI HIP1 HI HIP1
HAP HAP

1F DHG-161 1F DHG-161
HA HA

HI1 HI2 HI1 HI2

DHF-121 DHF-120
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 13/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.3 DHG-161 PCB


8.3.1 Floor ID & Button Type Setting

SW1-8P
Hall Button Type
A Type (First Hall line) : 7 Pin OFF
1 2 3 4 5 6 7 8 B Type (Second Hall line) : 7 Pin ON

Floor ID

8.3.2. Installation procedure of DHG-161 PCB

Connect HU, HD connector of


DHG-161 (For button interface)
Start

Disconnect XHA connector of


Connect HUC, HDC connector of
control panel
DHG-161 for disabled type

Get on car top according to safe


Connect HF1 connector of
procedure of car top access
DHG-161 for hall lantern

Operate lift on car top by


Connect HC1 connector of
maintenance mode (15m/min)
DHG-161 for hall chime

Set floor ID by DIP SW (SW1)


of DHG-161 Perform prior procedures
repeatedly for the other floors

Connect HA connector of DHG-161 Switch off main switch after completing


above procedures & perform lock secure
according to safety regulation
Connect HI1 connector of DHG-161
to DCM-1XX for indicator
No need HI2 connector Connect XHA connector after
returning main switch

These procedures are in order to prevent from End


damage of PCB
during connection work in hoistway.
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 14/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.3.3 Button Type Setting(4 Unit N-Plex)

Duplex setting between No.1 and No.2 Duplex setting between No.3 and No.4

SPEC1 Dip SW SPEC1 Dip SW SPEC1 Dip SW SPEC1 Dip SW


(DOC-120) (DOC-120) (DOC-120) (DOC-120)

1 2 1 2 1 2 1 2

No.1 No.2 No.3 No.4


N-PLEX
DOC-120 DOC-120 DOC-120 DOC-120

SL SH SL SH SL SH SL SH

DOP-116 DOP-116 DOP-116 DOP-116


SH SH SH SH
XHA XHA XHA XHA

DHG-161 DHG-161

DHG-161 DHG-161

Floor ID Floor ID

DHG-161 DHG-161
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
A Type : 7 Pin OFF B Type : 7 Pin ON

A Type Spec B Type Spec


Address No1 Data No2 Data Address No3 Data No4 Data

1D04 “00” “00” 1D04 “01” “01”

DHG-161 DHG-161
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 15/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.3.4 Button Type Setting(3 Unit N-Plex)

Duplex setting between No.1 and No.2 Simplex setting No.3

SPEC1 Dip SW SPEC1 Dip SW SPEC1 Dip SW


(DOC-120 PCB) (DOC-120 PCB) (DOC-120 PCB)

1 2 1 2 1 2

No.1 No.2 No.3


N-PLEX
DOC-120 DOC-120 DOC-120

SL SH SL SH SL SH

DOP-116 DOP-116 DOP-116


SH SH SH
XHA XHA XHA

DHG-161 DHG-161

DHG-161 DHG-161

Floor ID Floor ID

DHG-161 DHG-161
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
A Type : 7 Pin OFF B Type : 7 Pin ON

A Type Spec B Type Spec


Address No1 Data No2 Data Address No3 Data

1D04 “00” “00” 1D04 “01”

DHG-161 DHG-161
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 16/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.4 Terminal Resistor setting


8.4.1 4 Unit N-PLEX (When Hall Line is connected No.2 and No.4)

N-PLEX MODULE
GSL4
GSL3
GSL2
GSL1

Terminal
Resistor Terminal
Resistor

No.1 No.2 No.3 No.4

DOC-120 DOC-120
32F 32F

SH SH

SM 2F SM 2F

SL 1F Terminal SL 1F Terminal
Resistor Resistor

8.4.2 3 Unit N-PLEX (When Hall Line is connected No.2 and No.3)

SW2 N-PLEX
G1
ON DOC-211 MODULE Terminal
G2 Resistor
G3
MC GSL3
GSL2
GSL1

Terminal 1호기 2호기 3호기


Resistor

DOC-120
32F 32F

SH

SM 2F 2F

SL 1F Terminal 1F Terminal
Resistor Resistor
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 17/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

8.4.3 4 Unit N-PLEX (When Hall Line is connected No.1 and No.3)

N-PLEX MODULE GSL4


GSL3
GSL2
GSL1 Terminal
Terminal Resistor
Resistor

No.1 No.2 No.3 No.4

32F DOC-120 32F DOC-120

SH SH

2F 2F SM
SM

1F SL 1F Terminal SL
Resistor

Terminal
Resistor

8.4.4 3 Unit N-PLEX (When Hall Line is connected No.1 and No.3)

SW2 N-PLEX
ON
G1 DOC-211 MODULE Terminal
G2
Resistor
G3
MC GSL3
GSL2
GSL1

Terminal
1호기 2호기 Resistor 3호기

32F DOC-120 32F

SH

2F 2F
SM

1F SL
1F

Terminal Terminal
Resistor Resistor
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 18/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

9. SPEC data for N-PLEX


9.1 Additional SPEC data of N-PLEX Module
Refer to DGS-700 SPEC. EDITION

9.2 Additional SPEC data of Sigma E/L


(Refer to SPEC Edition for the others of SPEC data)
Address Label Byte Data Default Description

1D00H Enable 1 00/01 00 In case N-PLEX function is applied, set ‘0x01’

1D02H Car_Id 1 *H 00 Lift ID under N-PLEX control ( 0x01 ~ 0x04 )


Standard type setting when one of DHG line is applied.
In case of one hall line and duplex system, hall line was
always set to A type(7th Dip S/W Off),
1D04H Default_Side 1 00/01 00 But it shall be set to B type sometimes according to
N-PLEX system control requirement (7th Dip S/W On)

So, In case of one hall line with B type, set ‘0x01’


Reserved Chime driving Spec
0x00 : No usage of reserved Chime driving.
0x01 : As a reserved announce sound, ‘Ping~’
1D06H Reserve_Chime 1 *H 00 0x02 : As a reserved announce sound ‘Ping Pong~’
0x03 : According to reserved call direction,
In case of ‘Up’ call registration, ‘Ping~’
Else if ‘Down’ call registration, ‘Ding Dong~’

10. Annunciator
10.1 Annunciator of Sigma E/L
Refer to Sigma E/L Manual

10.2 Annunciator of N-PLEX Module

10.2.1 Check Initial Status


Check that the screen below is displayed in the LCD (ANN) after power input.
(Note: Main screen below is pertinent to OpCode750)
Check the system initial status
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 19/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

System initial status


A01 : A03 : A05 : A07 : A09 : A11 A12 : A14 A15 A16

B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14

C01 C02 C03 C04 C05 C06 C07 C08 : C10 C11 C12 C13

O p c o d e : D10 D11 D12 / D14 D15 D16

ID Coordinates Description

1 A01 Operating system/Stand-by system initial status (0: operating system 1: wait system)

2 A03 Operating MICOM down (0: normal 1: error)

3 A05 Stand-by MICOM down (0: normal 1: error)

Operation mode saving (0: normal times 1: office-going 2: work-leaving 3: prior lunch time 4:
4 A07
uncrowded 5: post lunch time 6: usual overcrowdedness 7: overcrowdedness on a certain floor

5 A09 0(spec and clock write protected) 1(spec and clock write enabled)

6 A11,12 Bit information of incorporated elevator (hexadecimal)

7 A14,15,16 Total floor (decimal)

8 B01~06 Time recognized by the system (year, month, day)

9 B07,08 Time recognized by the system [day of the week : 0(Sunday) ~ 6(Saturday)] ex) 2(Tuesday)

10 B09~14 Time recognized by the system (hour, minute, second)

11 C01~08 System Status Flag Configuration

12 C10~13 External Device Connection Status Flag Configuration

13 D10~12 OpCode in process

14 D14~16 Displaying the number of screens registered in the OpCode in process

10.2.3 Local Time Setting


1)Setting time change enabled status (set Pin3 of SW5 to On)

2)Press 001 on the DOA-100 LCD.

3)Check that 001 is indicated in D10-D12 on DOA-100 LCD. (Refer to page11)


4)Press Enter key(C) on the main screen of DOA-100 LCD.

5)Check that LCD screen switches to the below screen.

A01 A02: A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14

Y Y M M D D W W H H M M S S

C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14

1 I n 2 S e t
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 20/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

6)Present time check


Note 1: Time is displayed in the way of the twenty-four hour system. (Ex: 04:00 PM = >16:00)
Note 2: Sunday is indicated as 0 and Saturday as 6.
Note 3: All data is input in the way of BCD. (Ex: 23:00 =>$23)
- Present time is displayed in A01~A14. (yymmddwwhhmmss)
- When the present time is Monday, Feb 17 1998 04:30:12 PM ($98021701160430)
7)Input current time (input 1)
Check that D00 switches from ‘1’ to ‘ * ’.
Check that ‘$’ is displayed in C01.
Input desired time in the form of data with fourteen digits by referring to the style written
on the second line.
When fourteen-digit time input is finished, D01 switches from ‘*’ to ‘1’.
8)Check that input time is correct.
9)Present time change request (input 2)
-If data is not normally recorded, ‘Time Set Error’ is indicated on C01~C16.
If so, check that switch status and time of STEP 1 are logically correct values.
(Ex: If time is 25, it is an error)
-If data is recorded normally, input time is indicated on A01~A14.

10)Input D to switch from data setting mode to OpCode input mode.


11)Time input enabled status release
-Set the Pin3 of SW5 to Off

11. Trouble Code and adjustment (Additional TCD)


11.1 Trouble Code

● Operation CPU
TCD 209 ER_NPLEX_MASTER_COM Detection part Application SI210
○ Speed CPU
[Counteraction]
[Meaning] Communication error with N-PLEX Module
1.Check if N-PLEX is applied to system.
(N-PLEX is not applied but if related SPEC is set, It
[Explanation]
will detect error.)
None of received data from N-PLEX Module during <<Related N-PLEX SPEC DATA>>
3seconds.Fail of data transmitting to N-PLEX ADDR Label Description
Module over 4times. 0x1D00 Enable N-PLEX Function: 0x01, None: 0x00
0x1D02 Car_Id N-PLEX Lift ID(0x01~0x04)

2 Check the communication wiring of N-PLEX


(SH Connector)
Comm. Cable should be twisted shied cable only.
G_Signal_Wait_Counter == 0
TCD 209 3.Check the terminal resistor condition.
(HJP-SH jumper should be connected.)
Group_Fail_Count > 3 refer to ‘Terminal resistor setting method’

In case terminal resistor is not set properly,


- Communication error will happen frequently and
Hall Call registration is unable.
- Backup operation will be enabled.
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 21/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

12. Appendix
12.1 Each lift operation mode when system is down

N-PLEX Module is mounted on the control panel of Lift#1 to control 3 or 4 lifts for parallel operation.
When it works normally, it will assign calls of 2nd hall line to a lift that can serve with optimum condition.
But in case N-PLEX module is breakdown, it cannot assign calls to some lift anymore. Then each lift will change their
operation mode to simplex or duplex after designated time has passed. The master lift will assign hall calls to the another lift.
The following table shows the changed operation mode of each lift in case N-PLEX module is breakdown or each lift is breakdown.

12.1.1 4 Unit N-Plex


N-PLEX Module DHG-161(all floor)
Breakdown
No.1 Breakdown No.2 Breakdown No.3 Breakdown No.4 Breakdown
Breakdown

No1,2 : Duplex All Lift : No,2 : Simplex No,1 : Simplex No1,2 : Duplex No1,2 : Duplex
* No.3,4 : Duplex Back-Up Operation No.3,4 : Duplex No.4 : Simplex No.3 : Simplex
No.3,4 : Duplex

N-PLEX Module All Lift : No,2 : Simplex No,1 : Simplex No1,2 : Duplex No1,2 : Duplex
* Back-Up Operation No.3,4 : Duplex No.3,4 : Duplex No.4 : Simplex No.3 : Simplex
Breakdown

DHG-161(all floor) All Lift : No.2,3,4 : No.1,3,4 : No.1,2,4 : No.1,2,3 :


Back-Up Operation
* Back-Up Operation Back-Up Operation Back-Up Operation Back-Up Operation
Breakdown

No,2 : Simplex No.2,3,4 : No.2 : Simplex No.2 : Simplex


No.1 Breakdown No.3,4 : Duplex Back-Up Operation * No.3,4 : Duplex
No.4 : Simplex No.3 : Simplex

No,1 : Simplex No.1,3,4 : No.1 : Simplex No.1 : Simplex


No.2 Breakdown No.3,4 : Duplex Back-Up Operation
No.3,4 : Duplex * No.4 : Simplex No.3 : Simplex

No1,2 : Duplex No.1,2,4 : No.2 : Simplex No.1 : Simplex


No.3 Breakdown No.4 : Simplex Back-Up Operation No.4 : Simplex No.4 : Simplex
* No.1,2 : Duplex

No1,2 : Duplex No.1,2,3 : No.2 : Simplex No.1 : Simplex


No.4 Breakdown No.3 : Simplex Back-Up Operation No.3 : Simplex No.3 : Simplex
No.1,2 : Duplex *

12.1.1 3 Unit N-Plex


N-PLEX Module DHG-161(all floor)
Breakdown
No.1 Breakdown No.2 Breakdown No.3 Breakdown
Breakdown

No1,2 : Duplex All Lift : No.2 : Simplex No.1 : Simplex


* No.3 : Simplex Back-Up Operation No.3 : Simplex No.3 : Simplex
No.1,2 : Duplex

N-PLEX Module All Lift : No.2 : Simplex No.1 : Simplex


* Back-Up Operation No.3 : Simplex No.3 : Simplex
No.1,2 : Duplex
Breakdown

DHG-161(all floor) All Lift : No.2,3 : No.1,3 : No.1,2 :


Back-Up Operation
* Back-Up Operation Back-Up Operation Back-Up Operation
Breakdown

No.2 : Simplex No.2,3 :


No.1 Breakdown No.3 : Simplex Back-Up Operation
* No.3 : Simplex No.2 : Simplex

No.1 : Simplex No.1,3 :


No.2 Breakdown No.3 : Simplex Back-Up Operation
No.3 : Simplex * No.1 : Simplex

No.1,2 :
No.3 Breakdown No.1,2 : Duplex
Back-Up Operation
No.2 : Simplex No.1 : Simplex *
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 22/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

12.2 Floor ID Setting

ON DHG-16X ON
SW1-8P DHG-16X
(16 Floor) SW1-8P (32 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X DHG-16X
SW1-8P (31 Floor)
1 2 3 4 5 6 7 8 (15 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X DHG-16X
(14 Floor)
SW1-8P (30 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON DHG-16X ON
SW1-8P DHG-16X
(13 Floor) SW1-8P
(29 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (12 Floor) (28 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X DHG-16X
(11 Floor)
SW1-8P
1 2 3 4 5 6 7 8 (27 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (10 Floor) 1 2 3 4 5 6 7 8 (26 Floor)

ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (9 Floor) (25 Floor)
1 2 3 4 5 6 7 8
ON DHG-16X ON
SW1-8P SW1-8P DHG-16X
(8 Floor) (24 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON DHG-16X ON
SW1-8P DHG-16X
(7 Floor) SW1-8P
(23 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (6 Floor) (22 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X
(5 Floor)
SW1-8P DHG-16X
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (21 Floor)

ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (4 Floor) 1 2 3 4 5 6 7 8 (20 Floor)
ON ON
SW1-8P DHG-16X SW1-8P DHG-16X
1 2 3 4 5 6 7 8 (3 Floor) (19 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X DHG-16X
(2 Floor) SW1-8P
1 2 3 4 5 6 7 8 (18 Floor)
1 2 3 4 5 6 7 8
ON ON
SW1-8P DHG-16X DHG-16X
(1 Floor)
SW1-8P (17 Floor)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 23/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

12.3 Application of N-PLEX Operation


12.3.1 It is impossible to separate a lift for single from 4 unit N-PLEX operation.
12.3.2 Even the hall line service pattern is different, it can be applicable Max.
32 Hall Node (connection numbers).
12.3.3 Application condition of N-PLEX operation for each machine room layout

Case 1) 4 of CP are in One machine room Case 2) 3 of CP are in One machine room

Machine Room1 Machine Room1


Group 1 Group 2 Group 1 Group 2

No.1 No. 1
& &
No.2 No.3 No.4 No.2 No.3
N-plex N-plex
Module Module

Case 3) Machine room is separated.- 1 Case 4) Machine room is separated.- 2

Machine Room1 Machine Room2 Machine Room1 Machine Room2


Group 1 Group 2 Group 1 Group 2

No.1 No. 1
& &
No.2 No.3 No.4 No.2 No.3
N-plex N-plex
Module Module
Rev. No. 0
Si210 Control Panel Doc. No. 04-695-119
Page 24/24
FOD
Overseas Support Team
N-PLEX Date MAR. 2004

12.4 Function of SPEC1 & SPEC2


12.4.1 SPEC 1 DIP S/W

Bit ON OFF

1 With Duplex Operation With Simplex Operation

2 No.2 No.1

3 Not used Not used

4 Load detector Type : Potentiometer Load detector Type : Micro Switch

5 Setting to verification Mode Normal Position

6 With voice synthesizer(Auto-announcement) Without voice synthesizer

7 With emergency(fire) operation Without emergency(fire) operation

8 In factory checking Mode Normal Position

12.4.2 SPEC 2 DIP S/W


Bit ON OFF

1 Forcedly door closing is invalid Forcedly door closing is valid

2 Door time fixed(5 sec) Door time is flexible( SPEC data)

3 Not used Not used

4 Not used Not used

12.5 Trouble Shooting


No. Symptoms and Action to take
Symptoms

In case of N-PLEX operation system that controls 4 elevators with 2 Hall lines, if N-PLEX MODULE
is breakdown, Only car call can be registered normally but hall call after DSK mode change.

In case Lift #1 and 2 are operated by DSK mode In case Lift #3 and 24are operated by DSK mode
and hall station DIP(SW1-8P) 7th pin is turned on, and hall station DIP(SW1-8P) 7th pin is turned off,
1 Set the SPEC data as followings Set the SPEC data as followings
SPEC DATA SPEC DATA
Action to take

ADDR Description DATA ADDR Description DATA


Front normal call Front normal call
0x08E0 11000011B(0xC3) 0x08E0 10000011B(0x83)
service map service map
Front disable call Front disable call
0x08E4 00110011B(0x33) 0x08E4 00100011B(0x23)
service map service map

0x1D04 Default Side 0x01 0x1D04 Default Side 0x00