You are on page 1of 10
APPENDIX D Appendix D. Wiring D Introduction (A)General. This part contains wiring design examples to illustrate the application of some of the provisions of this Code. The examples illustrated herein, although not exhaustive, cover several scenarios which are typically encountered by the practitioners, The examples illustrate how to determine the size of branch circuits, feeders and services. Typical Single- Family and Multi-Family Dwelling units of different demand load are presented consid: and three-phase service systems. Single and multiple ‘motor examples illustrate how to size the branch eircuit ing the single phase conductors and overload protection. Several overload protection schemes are presented. Examples on system with fire pump to illustrate its special requirement and a system with a voltage regulator are also included. (B) Branch Circuits Required. For small single-family dwelling unit having a floor area of not more than 50 square meters with load not exceeding 3 680 volt- amperes, the code permits the use of only one circuit as illustrated in Example D1 [See Section 2.10.1.11(D)]. For the minimum number of branch circuit required, ction 2.10.1.11(A) to (C). see S (C) Feeder or Service Load Calculation, Feeder or service load calculation in the examples follows the method provided in Part 2.20.2. The optional calculations method of Part 2.20.3 is also illustrated [See Example D4] (D) Selection of Conductors. For conductor types and sizes, refer to 0 through 2000 volt (V) ampacity tables of Article 3.10 and Section 3.10.2.6 that pertains to such tables. For the minimum size of service entrance conductor, see Section 2.30.4.3. Conductor ampacities given in these examples for copper wires are based on ambient air temperature of 300C except specified otherwise. In the examples given, conductors are selected such that their ampacities are at least 125% of the continueus current through the conductor. Voltage drops, however, have not been considered in the selection, (E) Selection of Overcurrent Protection. Standard ratings for {uses and inverse time circuit breakers are listed in Section 2.40.1.6. Maximum rating or setting of motor branch circuit short-circuit and ground-fault protective devices are given in Table 4.30.14.6. (F) Voltage. For uniform application of the provisions of Articles 2.10, 2.15 and 2.20, a nominal voltage 230 volts is used in computing the ampere load on the conductor, n Examples Grounding. In conformance to the provisions of the code on ounding, illustrations herein show partial grounding requirements. Feeder and circuit wires indicated in the examples are for phase wires only For sizes of grounding conductors and electrodes, see Tables 2,50.3.17 and 2.50.6.13 respectively. (H) Allowance for Future Exp: Itis advisable to use larger service conductors and the corresponding overcurrent protective devices to accommodate future loads depending on the anticipated expansion. EXAMPLE D1 Single Family Dwelling Unit, Up to 50 Square Meters Floor Area with Load not Exceeding 3 680 Volt-Amperes.* The dwelling has a floor area of 50 square meters with typical small appliance loads for small residential units 1.1 Total Load: (A) General Lighting and Convenience Receptacle Load: [See Table 2.20.2.3] 50m? x 24 volt-amperes per m? 1200 volt-amperes (B) Typical Appliance Load: One electric flat iron 1200 volt-amperes 80 volt-amperes One television set One electric fan 75 volt-amperes One radio 20 volt-amperes Total Load 2575 volt-amperes 5 VA+230V= 11 Total Computed Current: 2 Amperes 1.2 Circuit Requirement: Use one 20-ampere 2-wire circuit. [See Sections 2.10.2.5(A) and 2.10.1.11(D)} 1.3 Service Entrance Conductors: Use two 3.5 mm2 (2.0 mm dia.) TW copper wires (minimum). [See Section 2.30.2.3(B) Exception]. 1.4 Service Equipmen Use one 30-ampere, IPST, 250-volt safety switch with cone 20-ampere fuse; or use one 20-ampere trip, -pole, 240-volt enclosed molded case circuit breaker (see tion 2,40.2.3). *Note: For loads exceeding 3680 volt-amperes, see Section 2.10.1.11(A) to (C) and succeeding examples 1045 APPENDIX D 15 Diagrams. 2.8 m(29 mma Wwe oat) oe | Ln ering let ai’ Tt (eran tea) Example D2 jingle Family Dwelling Unit, Up to 150 Square Meters Floor Area. (Not More than Six Circuits) The dwelling has a floor area of 145 sq.m. It has the typical household appliances including one 1.5-Hp room air-conditioning unit. 2.1 Total Load: (A) General Lighting and Convenience Receptacle Load: [See Table 2.20.2.3] Note: Table 2.20.1. includes the receptacle outlets of 20 amperes or less. 145 m? x 24 volt-amperes per m? The computed load is 3480/230 One branch circuit of 20-ampere would be theoretically adequate, however for flexibility and to allow for future needs provide two 20-ampere branch circuits for lighting and convenience outlets. (B) Small Appliance Load: [See Sections 2,10.1.11(C)(1) and 2.20,3.13(A)] One 20-ampere @ 1500 VA. = 1500 VA Provide one 20-ampere small appliance circuit. (©) Laundry Circuit: [See Sections 2.10.1.11(C)(2) and 2.20.3.13(B)] One 20-ampere @ 1500 VA. = 1500 VA, Provide one 20-ampere laundry circuit. Sub-Total (6480 VA Application of Demand Factors: (See Table 2.20.3.3) First 3 000 volt-amperes @ 100% D.F. = 3000 VA Remainder @ 35% D.F. (3.480 VA.x 0.35) =1218 VA (D) Other Load: One 1.5-Hp room acu, 10 Ax 230V @ 100% ae = 2300 VA Provide one 20-ampere room acu circuit Total Net Computed Load = 6518 VA 2.2 Circuit Requirement: Use five 20-ampere 2-wire branch circuits. 1046 2.3 Service Entrance Conductors: Total Full Load Current: (See Sections 4.30.24 and: 4.40.17) Use two 14 mm? TW wires. Note 1: See Section 2.20.3.11 forthe conductor and overcurrent protection ampere rating. Note 2: See Section 2.30.2.3(B) for minimum service entranse conductor. 2.4 Service Equipment: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse. [3 000 VA + 1 218 VA + 300% (2 300 VA) = 230 V= 48 Amperes (2) Inverse Time Circuit Breaker. [3 000 VA + 1 218 VA + 250% (2 300 VA)] = 230 V=43 Amperes (B) Service Equipment Rating, Use one 60-ampere, IPST, 250-volt safety switch with ‘one 60-ampere fuse; or use one 50-ampere trip, 1-pole, 240-volt molded case circuit breaker (see Section 2.40.16). Note: See Section 2.40.14 for protection of conductors. 2.5 Diagrams: APPENDIX D Example D3 Single Family Dwelling Unit, Up to 150 Square Meters Floor Area. (More than Six Circuits) The dwelling has a floor area of 145 sq.m. It has the typical household appliances including one 8-kW electric range, two 1-Hp room air-conditioning unit, one 1.5-Hp room air-conditioning unit, and one 1-Hp water pump. 3.1 Total Load: (A) General Lighting and Convenience Receptacle Load: [See Table 2.20.2.3] Note: Table 220.13 inches the receptacle outlets of 2 amperes or less. 145 m? x 24 volt-amperes per m? = 3480 VA ‘The computed load is 3480/230 n ISA. One branch circuit of 20-ampere would be theoretically adequate, however for flexibility and to allow for future needs provide two 20-ampere branch circuits for lighting and convenience outlets. (B) Small Appliance Load: {See Sections 2.10.1.11(C)(1) and 2.20.3.13(A)] ‘One 20-ampere @ 1500 VA 1500 VA Provide one 20-ampere small appliance circuit. (©) Laundry Circuit: [See Sections 2.10.1.11(C)(2) and 2.20.3.13(B)] One 20-ampere @ 1500 VA = 1500 VA Provide one 20-ampere laundry circuit. Sub-Total (6480 VA Application of Demand Factors: (See Table 2.20.3.3) First 3 000 volt-amperes @ 100% D.F. = 3000 VA Remainder @ 35% DF. GB 480 VA x 0.35) @) Other Load: One 8-kW electric range @ 80% D.F. (See Table 2.20.3.16) Provide one 40-ampere electric range sircuit. Two I-Hp room acu, 8 Ax 230 V x2 @ 100% DF. Provide two 20-ampere room acu circuits. One 1.5-Hp room acu, 10 A x 230 V @ 100% DF. = 1218 VA = 6400 VA. = 3680 VA = 2300 VA Provide one 20-ampere room acu circuit One 1-Hp water pump, 8 A x 230 V = 1840 VA @ 100% DF. Provide one 20-ampere water pump circuit Total Net Computed Load 18438 VA 3.2 Circuit Requirement: Use eight 20-ampere 2-wire branch circuits and one 40-ampere 2-wire branch circuit 3.3 Service Entrance Conductors: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.17) [18438 VA + 25% (2 300 VA)] +230 V = 83 Amperes Use two 38. mm? THW wires. 3.3 Service Entrance Conduetors: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7) [18438 VA + 25% (2 300 VA)] = 230°V = 83 Amperes Use two 38 mm? THW wires Note I: See Section 2.40.14 forthe conductor and overcurrent protection ampere rain Note 2: See Section 2.30.2.3 for minimum service entrance conductor, 3.4 Service Equipment: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse [3 000 VA + 1 218 VA +6 400 VA +3 680 VA. + 300% (2 300 VA) + 1 840 VA] +230 V= 100 Amperes (2) Inverse Time Circuit Breaker. [3.000 VA + 1 218 VA + 6 400 VA +3 680 VA % (2 300 VA) + 1 840 VA] + 230 V = 95 Amperes (B) Service Equipment Rating, Use one 200-ampere, IPST, 250-volt safety switch with one 125-ampere fuse (renewable); or (b) use one 125-ampere trip, I-pole, 240-volt molded case circuit breaker (see Section 2.40.1. 6). 1047 APPENDIX D 35 Diagrams: tt coer eens —— » _ 7 Lorna ener stim_] Example D4 Single Family Dwelling Unit, Up to 150 Square Meters Floor Area, Optional Calculation. ‘Same conditions as Example D3 4.1 Air Conditioning Load: 1¢ Section 2.20.4.3) ‘Two I-Hp room air-conditioning unit, 8Ax230Vx2 pete One 1.5-Hp room air-conditioning unit, _ 5, 10Ax230Vx1 aroma 4.2 Other Loads: General lighting and convenience receptacle load, = 3480.VA 145 mx 24 VA? One 20-ampere small appliance circuit _ @ 1500 volt-amperes ee One 20-ampere laundry circuit ule @ 1500 volt-amperes 1500 va One 8-KW electric range 8000 VA One 1-Hp water pump, er 8Ax230V oe Total Other Loads 16320 V Application of Demand Factors: [See Section 2.20.4.3(C)]" First 10 000 volt-amperes @ 100% D.F. 10000 V. Remainder @ 40% D-F. (6 320 VAx 0.40) 2528 V. Total Net Computed Load TsS08 VA 4.3 Cireuit Requirement: Use eight 20-ampere 2-wire branch circuits and one 40-ampere 2-wire branch circuit 1048, 4.4 Service Entrance Conducto: Total Full Load Current: 18508 volt-amperes + 230 V = 80 Amperes Use two 38 mm2 THW wires. [Note I: See Seetion 2.40.14 forthe conductor and overcurrent protection ampere rating Note 2: Se Section 2.30.23 for minimum service entrance conductor, 4.5 Service Equipment: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse. [3680 VA + 300% (2300 VA) + 10000 VA +2 528 VA] + 230 V = 100 Amperes (2) Inverse Time Circuit Breaker. [3 680 VA + 250% (2 300 VA) + 10000 VA +2 528 VA] +230 V = 95 Amperes (B) Service Equipment Rating. Use one 200-ampere, IPST, 250-volt safety switch with one 125-ampere fuse (renewable); or use one 125-ampere trip, I-pole, 240-volt molded case circuit breaker (see Section 2.40.1. 6), 4.6 Diagrams: Same as Example D3. Example DS Single Family Dwelling Unit, More than 150 Square Meters Floor Area, 230 Volts Single Phase Service The dwelling has a floor area of 250 square meters. Ithas the typical houschold appliances including two 6-kVA package type air-conditioning units, six 1.5-Hp room air-condition units, two 4-kW wall mounted ovens, one 1.5-kW microwave oven, one 12-kW electric range, one 8-kW electric rang W clothes dryer, four 5-kW water heaters, and one 1.5-Hp water pump, 5.1 Air Conditioning Load: (See Section 2.20.3.23) ‘Two 6-KVA package type air- Ate conditioning units a Provide two 70-ampere package type acu circuits Six 2-Hp room air-conditioning units, 14Ax230Vx6 = 19320 VA. Provide six 30-ampere room acu circuits APPENDIX D 5.2 Lighting and Convenience Receptacle Load: (See Section 2.20.3, 250 m? x 24 VA/mi Provide at least two 20-ampere lighting and convenience receptacle cireuits. = 6000 VA Note: Actual computed lighting load shall be used if the total volt-ampere exceeds that obtained from the 24 volt-amperes Per square meter method. 5.3 Cooking Load: (See Section 2.20.3.16) ‘Two 4-kW wall mounted ovens, ODUNAR? = 8000 VA, Provide two 30-ampere wall mounted oven circuits. One 8-kW electric range = 8000 VA, Provide one 40-ampere electric range circuit Subtotal Load 16000 VA Application of Demand Factor: (See Table 2.20.3.16 Column C) 16000 volt-amperes x 0.55 One 1.5 kW microwave oven (See Table 2.20.3.16 Column B) Provide one 20-ampere microwave oven circuit One 12-kW electric range (See Table 2.20.3.16 Column A) Provide one 60-ampere electric range circuit = 8800 VA = 1200 VA = 8000 VA. Total Load 18000 VA 54 Other Loads: One 20-ampere small appliance circuit @ 1500 volt-amperes [See Section 2.20.1.11(C)(1)] Provide one 20-ampere small appliance circuit = 15000 VA. One laundry washing machine @ 1500 volt-amperes [See Section 2,20.1.11(C)(2)] Provide one 20-ampere laundry circuit. One 5-kW ¢lothes dryer Provide one 30-ampere clothes dryer circuit Four 5-kW water heaters Provide four 30-ampere water heater circuits One 1.5-Hp water pump, 10x 230 V_ = 2300 VA = 1500 VA. 5000 VA = 20000 VA Provide one 20-ampere water pump cireuit 31500 VA Application of Demand Factor: (See Section 2.20.3.23) 31500 volt-amperes x 0.40 Total Net Computed Load Total Other Loads 12120 VA (66240 VA 5.5 Circuit Requirement: Use six 20-ampere 2-wire branch circuits, thirteen 30-ampere 2-wire branch circuits, one 40-ampere 2ewire branch circuit, one 60-ampere 2-wire branch circuit and two 70-ampere 2-wire branch circuits, 5.6 Service Entrance Conductors: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7) [67 440 VA + 25% (6 000 VA)] +230 V = 300 Amperes Use two 325 mm? THW wires. Note: See Section 2.40.1.4 for conductor and overcurrent protection ampere rating, 8.1 Service Equipment: (A) Maximum Current Rating of Protective Device, with: (See Section 4,30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse. [300% (6000 VA) + 6000 VA + 19320 VA + 6000 VA + 18000 VA + 12 120 VA] + 230 V = 345 Amperes (2) Inverse Time Circuit Breaker. [250% (6000 VA) + 6000 VA + 19 320 VA + 6000 ‘VA + 18 000 VA + 12 120 VA] + 230 V = 332 Amperes (B) Service Equipment Rating, Use one 400-ampere, IPST, 250-volt safety switch with one 400-ampere fuse; oF use one 400-amper trip, L-pole, 240-volt molded case circuit breaker (see Section 2.40. 1.6). Example D6 Single Family Dwelling Unit, More than 150 Square Meters Floor Area,400/230 Volts Three-Phase 4-Wire Service Same conditions as Example DS except that the two 6-KVA package 3-phase supply. ype air-conditioning units require 1049 APPENDIX D 6.1 Branch Circuit Arrangement: ‘A 3-phase fusible or circuit breaker type panelboard shall be provided for balanced distribution of single phase loads. 6.2 rcuit Requirement: Use two 40-ampere 3-wire branch circuits, six 20-ampere 2-wire branch circuits, thirteen 30-ampere 2-wire branch circuit, one 40-ampere 2-wire branch circuit, and one 60-ampere 2-wire branch circuit. 6.3 Service Entrance Conductors: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7) [66 190 VA + 25% (6 000 VA)] + (400 V)(1.732) = 98 Amperes Use three 50 mm2 + one $0 mm 2 (neutral) THW wires 6.4 Service Equipment: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse. [300% (6000 VA) + 6 000 VA + 19 320 VA + 6000 VA + 16 750 VA + 12 120 VA] ~ (400 V) (1.732) = 112 Amperes (2) Inverse Time Circuit Breaker. [250% (6 000 VA) + 6 000 VA + 19 320 VA + 6 000 VA + 16 750 VA + 12 120 VA] + (400 V) (1.732) = 109 Amperes (B) Service Equipment Rating, Use one 200-ampere, 3-pole, 415-volt safety switch with three 125-ampere fuse (renewable); or use one 125-ampere trip, 3-pole, 415-volt molded case circuit breaker, Example D7 Multifamily Dwelling Unit, 230 Volts Single Phase Service Multifamily dwelling having 12 dwelling units with individual feeder to each dwelling unit, Each dwelling unit has floor area of 90 square meters and with typical household appliances including one 8-kW electric range and one 1-Hp room air-conditioning unit 7.1 Total Load for Each Dwelling Unit: (A) General Lighting and Convenience Receptacle Load: [See Table 2.20.2.3] 1050 Note: Table 2.20.1.3 inches the receptacle outlets of 20-ampere of less 90 mi x 24 VA‘? Provide two 20-ampere lighting and convenience receptacle circuits. (B) Small Appliance Load: (See Sections 2.10.1.11(C)(1) and 2.203.13(A)] One 20-ampere @ 1500 volt-amperes = 1500 VA Provide one 20-ampere small appliance cireuit (©) Laundry Cireuit Load: [See Sections 2.10.1.11(C) Q)and 2.20.3.13(B)) One 20-ampere @ 1500 volt-amperes = 1500 VA Provide one 20-ampere laundry circuit Subtotal 3160 VA Application of Demand Factors: (See Table 2.20.3.3) First 3 000 volt-amperes @ 100% DF, = 3000 VA Remainder @ 35% DF. (60 VAx035) miei (D) Other Loads: One 8-KW electric range @ 80% D.F. (Gee Table 2.20.3.16) Provide one 40-ampere electric range circuit. One I-Hp room acu, 8 Ax 230V @ 100% DE. Provide one 20-ampere room acu cireuit, Total Net Computed Load (For Each Dwelling Unit) =2160 VA = 6400 VA = 1840 VA = 11996 VA 7.2 Circuit Requirement for Each Dwelling Unit: Use five 20-ampere 2-wire branch circuits and one 40-ampere 2-wire branch circuit. 7.3 Service Feeder Conductors for Each Dwelling Unit: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7) [11996 VA + 25% (1 840 VA)] + 230V = 54 Amperes: Use two 22 mm? THW wires. Note: See Section 2.20.2.3 for the conductor and overcurrent protection ampere rating, 74 Service Equipment for Each Dwelling Unit: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) OO APPENDIX D () Nontime Delay Fuse. [3000 VA + 756 VA + 6 400 VA + 300% (1 840 VA)] + 230V = 68 Amperes (2) Inverse Time Circuit Breaker. [3000 VA + 756 VA + 6400 VA + 250% (1840 VA)] =230V = 64 Amperes (B) Service Equipment Rating. Use one 100-ampere, IPST, 250-volt safety switch with one 100-ampere fuse; or use one 100-ampere trip, I-pole, 240-volt molded case circuit breaker (see Section 2.40.16) 7.5 Total Load for 12 Dwelling Units: [See Section 2.20.4.5(A)] General lighting and convenience receptacle load, 2160 VA x 12 ‘Small appliance load, 1500 VA x 12 = 25920 VA = 18000 VA, Laundry circuit load, 1500 VA x 12 8000 VA, oe S-kW electric range, 8000 VAx _ 4 16000 VA One I-Hp room acu, 1840. VAx 12 _= 22080 VA Total Computed Load 180000 VA Application of Demand Factors: (See Table 2.20.4.5) 180000 volt-amperes x 0.41 = 73800 VA 7.6 Main Service Entrance Conductors: Total Full Load Current: 73800 volt-amperes + 230 V = 321 Amperes Use two 325 mm! or two sets of two 100 mm? THW wires. Note: See Section 3.10.14 for conductors in parallel 7.7 Main Service Equipment: (A) Maximum Current Rating, 230 V=321 Amperes (B) Service Equipment Rating, 73800 volt-amperes (1) Use one 600-ampere, IPST, 250-volt safety switch with one 500-ampere fuse; or (2) Use one $00-ampere trip, 1-pole, 240-volt enclosed molded case circuit breaker (see Section Example D8 Multifamily Dwelling Unit, 400/230 Volts Three- Phase 4-Wire Service Same conditions as Example D7 except that it has 40 dwelling units and 3-phase 4-wire supply, 8.1 Total Load for Each Dwelling Unit: Total Net Computed Load: (Based on Example D7) 8.2 Circuit Requirement for Each Dwelling U = 11996 VA Use five 20-ampere 2-wire branch circuits and one 40-ampere 2-wire branch circuit. 8.3 Service Feeder Conductors for Each Dwelling Unit: Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7) [11996 VA + 25% (1 840 VA)] + 230 V = 54 Amperes Use two 22 mm? THW wires. 8.4 Service Equipment for Each Dwelling Unit: (A) Maximum Current Rating of Protective Device, with: (See Section 4.30.4.2 and Table 4.30.4.2) (1) Nontime Delay Fuse. [3000 VA + 756 VA + 6400 VA + 300% (1840 VA)] +230 V= 68 Amperes (2) Inverse Time Circuit Breaker, [3000 VA + 756 VA + 6400 VA + 250% (1840 VA)] + 230 V = 64 Amperes (B) Service Equipment Rating, Use one 100-ampere, IPST, 250-volt safety switch with one 100-ampere fuse, or use one 100-ampere trip, 1-pole, 240-volt molded case circuit breaker. 85 Total Load for 40 Dwelling Units: [See Section 2.204.5(A)] General lighting load, 2160 VA x 40 SRA Small appliance load i 1500 VA x 40 ee Laundry circuit load, zs 1500 VA x 40 OOO VA, One 8-KW electric range, atest 8000 VA x 40 APPENDIX D. One 1-Hp room acu, 1840 VA x 40 Total Computed Load (600000 VA Application of Demand Factor: (See Table 2.20.45) 600000 volt-amperes x 0.28 = 168000 VA = 73600 VA 8.6 Main Service Entrance Conductors: Total Full Load Current: 168 000 volt-amperes + (400 V)(1.732) = 242 Amperes Use three 200 mm? + one 200 mm? (neutral) THW wires, Note: See Section 3.10.14 for conductors in parallel. 8.7 Main Service Equipment: (A) Total Current: 168 000 volt-amperes (400 V)(1.732) = 242 Amperes (B) Seryice Equipment Rating. Use one 400-ampere, 3-pole, 415-volt safety switch with three 300-ampere fuses, or use one 250-ampere trip, 3-pole, 415-volt molded case circuit breaker. Example D9 Motors, Motor Circuits, and Controllers, Single Motor A three-phase, 460 volts, 60 Hz, 25-Hp squirrel cage induction motor is to be connected for full voltage starting, It has a full load current of 31.6 amperes, a service factor of 1.15 and a Code Letter "F" in its nameplate. The ambient temperature of the place of, installation is 40°C. 9.1 Total Load: (See Table 4.30.14.4) Full load current of 3-phase, 25-Hp motor= 34 Amperes Note:The fl load current value used o determine the ampacity ‘of conductors for motors shall be hased on Table 430. 14.4 9.2 Branch Circuit Conductors: [See Section 4.30.2.2(A)] 125% of Full Coad Current 34 Amperes x 1.25 = 42 Amperes Use three 14 mm? THW wires Note: Ampacity of 14 mm2 THW at 400C ambient is 65 Amperes x 0.88 = 572 Amperes. See Table 3.10.1.16 for ampacity correction faciors 1052 9.3 Motor and Branch Ci [See Section 4.30.3.2(A)] 125% of Rated Full Load Current: 31.6 Amperes x 1.25 =39 Amperes(Maximams 9.4 Branch Circuit Short-Circuit and Ground Protection: (See Section 4.30.4.2) é The branch circuit maybe protected by any of the: common types of protective devices, namely: delay fuse, Time delay fuse, Instantaneous trip: and Inverse time breaker. it Overload For the protection of a squirrel cage breaker with Letter "F" (See Table 4.30.4.2) the protective can be any of the following: (A) Nontime Delay (NTD) Fuses: (See Table 438-42) 300% of Full Load Current: : es 34 Amperes x 3 = 102 Amperes Use 100 Amperes NTD fuse. 4 Note: Ifthe 100-A fuse isnot sufficient forthe starting meme ‘of the motor, sce Section 4.30.4.2(C\1) Exception No. 28 (B) Time Delay (TD) Fuses: (See Table 4.304.2) 175% of Full Load Current: ‘ 34 Amperes x 1.75 = 59 Amperes Use 60 Amperes TD fuse (Sce Section 4.304210) Exception No. 2b). (©) Instantancous Trip (IT) Breaker: (See Table 4,30.4.2) 800% of Full Load Current 34 Amperes x 8 = 272 Amperes Use 300 Amperes IT circuit breaker (See Section 4,30.4.2(C) Exception No. I) (D) Inverse Time Delay (ITD) Breaker: (See Table 4.30.4.2) 250% of Full Load Current: 34 Amperes x 2.5 = 85 Amperes Use 100 Amperes ITD circuit breaker. I ns APPENDIX D 9.5 Diagram: Example D10 Motors, Motor Circuits, and Controllers, Multiple Motors Three squirrel cage induction motors: 25-Hp, 20-Hp and 10-Hp, all rated at 460 volts, 3-phase, 60 Hz are to be served by a feeder circuit, Ambient temperature does not exceed 30°C 10.1 Total Load: (See Table 4.30.14.4) One 3-phase, 460 volts, 25-Hp motor 34 Amperes One 3-phase, 460 volts, 20-Hp rT hie One phase, 450 VLD. 14 paper 25% of Lanes Molo (See Seton 43024) 34 Amperes x 0.25) Net Computed Current 8.5 Amper 83.5 Amperes 10.2 Feeder Conductors: [See Table 3.10.2.6(B)(16)] Use three 22 mm? THW wires. 10.3. Feeder Circuit Protection: 4.30.4.3(C)] [See Section Largest Protective Device: The 25-Hp motor being the largest motor, has the largest Protective device. For the values of the different device, see Example D9. (A) Nontime Delay (NTD) Fuses: Largest NTD fuse Full load current of 20-Hp motor Full load current of 10-Hp motor Total Computed Current Use 150 Amperes NTD fuse. (B) Time Delay (TD) Fuses: Largest TD fuse Full load current of 20-Hp motor Full load current of 10-Hp motor Total Computed Current Use 100 Amperes TD fuse (© Inverse Time Delay (ITD) Breaker Largest ITD fuse Full load current of 20-Hp motor Full load current of 10-Hp motor Total Computed Current Use 125 Amperes ITD fuse Note: Only fuses andor inverse time circuit breakers 14 Amperes = 141 Amperes 60 Amperes 27 Amperes 14 Amperes 101 Amperes 90 Amperes =27 Amperes = 14 Amperes = 131 Amperes fon fae ay my oy Note 1: For sin Note 2: (On F fire pumps, See 2.30.7.1(A) Exception No. 4, and Example Dit Voltage Regulators, Single Phase, 60 le motor taps, refer to Section 430.4.3(D), Pump Application) For installation including tions 2.30.6.3(A) Exception, 230.6.13(6), 2:30.75 Exception No. 4 Hz, 165. 80 Volts Input, 230 Volts Output VR Determine the size of input feeder wires and overcurrent Protection fora $ kVA, I-phase, 60 hertz 16: 280 volts. input, 230 volts output automatic voltage regulator. Sk ‘Ax 1000 16s V 30 Amperes Use 8.0 mm: (3.2 mm dia.) THW for feeder wire and (60-ampere fuse or 40-ampere trip molded case circuit breaker, 1os3 APPENDIX D. Example D12 Voltage Regulators, Three-Phase, 60 Hz, 350-530 Volts Input, 230 Volts Output VR Determine the size of input feeder wires and overcurrent protection fora 30 kVA, 3-phase, 60 hertz, 350-530 volts input, 230 volts output automatic voltage regulator. _ 30 KVA x 1000 nm 350 Vx 1.732 = 50 Amperes Use 14 mm? THW for feeder wire and 60-ampere fuse or 60-ampere trip molded case circuit breaker. Example D13 Available Short Circuit Current Calculate the maximum symmetrical fault current that would be supplied through a single phase distribution transformer rated at 100 KVA, 230 volts ifits impedance is 2.5%. Assuming that the primary source is of infinite capacity and neglecting all other impedances. transformer volt-amperes secondary voltage 100000 1 = 434.78 = 230 pe ff (fault current, ‘toed Zz symmetrical) 434.78 17; ais 391 amperes Example Did Simplified Fault Current Calculation A small factory is to be supplied at 230 volts, 3 ph, 60 hz by a bank of the distribution transformers rated at 100 KVA each with a bank impedance of 5%. This bank is connected to 34.5 kV Meralco line with a short circuit capacity of 1000 MVA. The power system is shown below. Determine the maximum symmetrical fault currents at points "a", "b" and "c” using the per-unit method. Determine the minimum symmetrical interrupting ratings of molded case circuit breakers A, B, and C. (Note, that or this example other impedance have been neglected. However, for actual design, consider all impedances of lines, busbars and other line devices.) Procedure using the Per-Unit Method 1. Draw system diagram 2, Draw impedance diagram 3. Obtain the Source Short Circuit level at the vicinity from the utility company. (1000000 kVA for Metro 1054 Ftcapaciy- 1000 MWA, mov se OA mn % conta m o0fDiene e 1OORVA mines Manila grid) 4, Select kVA base. (Any convenient value may do but preferably the transformer capacity. Use 300 kVA) 5. Compute PU value of utility source, (pu Zs) v KVA base 300 paz,” Gilly SCKVA 1000000 6, Compute PU for transformer, (pu Z) Impedance in percent __5 (given) _ 100 - 00 7. Compute PU value for feeder lines, 0.0003 pu: puZ, a, From Handbooks, obtain impedance of lines corresponding to size, type and number of conductors, in steel conduits or nonferrous conduits, ete. [For 3-250 mm: cable in stee! conduit, 100 ft (30.4 m) long, Z = 0.00546 ohm} b. Convert cable impedance from "ohm" to "pu (puZ,) ohm impedance _kVAbase LZ, = >}. : KV square 1000 0.00546 300, i =0031 0.230 x 0.230 1000 & 8. Compute PU value for motor contribution, (pu 20) kVA base 300 PLZ," “motor EVA/motOr ~~ yop 9354 = 0.75 BB ‘impedance *Average induction motor impedance per IEEE Sid 141 9. Compute for short circuit currents at designated points. 9.1 Draw impedance diagram. 9.2 Draw simplified diagram with values.

You might also like