You are on page 1of 129
DESIGN AND CONSTRUCTION ses STANDARD DRAWINGS CHULA VISTA | 2017 ® DEPARTMENT OF ENGINEERING AND CAPITAL PROJECTS perry Ranta =: atc Se eaeey ed SHEET INDEX ‘STO. SHT. TE PREV. STD. DRAINAGE — (DRN) DRN-O 2-YEAR, 6-HOUR PRECIPITATION CWO OROZ DRN=02 10—YEAR, 6-HOUR PRECIPITATION CVD DROS DRN-O8 50-YEAR, 6-HOUR PRECIPITATION CWO DROF DRN=04 100— YEAR, 6-HOUR PRECIPITATION CW DROS DRN-05 STREET DRAINAGE 36'-WIDE STREETS CVD OROB DRN=06 STREET DRAINAGE — 40° & 64° WDE STREETS CW DROS DRN-O7 INLET DESIGN — LENGTH OF INLET CWO DROS ORN=08 INLET DESIGN — PARTIAL INTERCEPTION OF GUTTER FLOW Cv ORO? DRN-09_[_1 | CURB INLET OPENING ves 45 DRN-09_| 2 [CURB INLET CURB HEIGHT AND PAVEMENT TRANSITION Mes 5 ‘DRN-70_[_1__| SIDEWALK UNDERORAIN CURB OUTLET DETAIL coves 17 DAN IT STORM DRAIN STENCIL oves 24 DRN=12_|_1_ [LANDSCAPE MEDIAN DRAIN owes 5 DRN-12 2 | LANDSCAPE MEDIAN DRAIN SECTIONS cves 5 GRADING — (GRD) GRO-OF VERTICAL SLOPE ROUNDING CW GROZ GRO-02 HORIZONTAL SLOPE ROUNDING CVO GROS RO~OS DRIVEWAYS VERTICAL DESIGN CWO GRO# GRD-04 DRIVEWAYS MINMUM GARAGE SETBACK CW OROS GRO-05__|_1_ | RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES ves 30 GRO-05 | 2 _| RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES OMeS 0 GRO-05__|_3_ [RETAINING WALL REQUIRENENTS PUBLICATION OUTLINES ves 30 GRO-05 | 4 _| RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES ves 30 GRO-05 | 5 | RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES ves 30 GRO-05 | 6 _| RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES ves 50 GRO~05_| 7 _| RETAINING WALL TYPE | owes 3H GRO-05_[_8 | RETAINING WALL TYPE Tt ves 32 GRO-05 | 9 | RETAINING WALL, CAP, KEY, & DRAINAGE DETALS ves 35 GRO-05 10 | RETAINING WALL STEP FOOTING & JOINT DETAILS cvs 34 GRO-05_|_11_|TABLE FOR VARIABLE HEEL, LEVEL BACKFIL, & 2 10 1 SLOPE ves 35 GRO~05_| 12 |TABLE FOR VAR. HEEL, 15-1 SLOPE, 250 PSF, & SURCHARGE Cvs 36 GRO-05_[13_|TABLE FOR 6-IN HEEL, LEVEL BACKFILL, & 2 TO 1 SLOPE coves 37 GRO-05 | 14 |TABLE FOR 6-IN HEEL, 1.5 70 1 SLOPE, 250 PSF, & SURCHARGE ves 38 GRO-05_| 15 |TABLE FOR 2-IN HEEL, LEVEL BACKFIL, & 2 TO 1 SLOPE eve 39 GRO-05 [16 |TABLE FOR 2-IN HEEL, 1.5 10 1 SLOPE, 250 PSF & SURCHARGE ves 40 RO~06 GRADED SLOPES CW ROT arate Biota SHEET INDEX ‘STD. ‘SHT. me PREV. STD. GENERAL SURFACE IMPROVEMENTS — (GSI) @s'-01 | _1_ [DRIVEWAY WITH MONOLITHIC CURE, GUTTER, AND SIDEWALK Cues 1 Gs-01 | 2 DRIVEWAY WITH NON-CONTIGUOUS SIDEWALK vest GS-01 _| 3 _|ORVEWAY NOTES west @5-02_| 1 [CROSS GUTTER owes 2 @s-02 | 2 [GROSS GUTTER DOWEL CONNECTIONS ves 2 5-03 | 1 [TRENCH BACKFLL TYPE | AND J owes 5 GS-03 | 2 [TRENCH BACKFLL NOTES Wes 4 @5=-05__|_3_ [MORATORIUM ROADWAY TRENCH RESURFACING 65-04 CURB d& SIDEWALK JOINT DETAILS cus 4 65-05 SIDEWALK THICK EDGE AT DRIVEWAY ves #2 65-06 MANHOLE ADJUSTMENT ves 48 O57 STAMPED CONCRETE CWS @5-08_[_1 [CURE RAMP TYPES A & B — NEW CONSTRUCTON ves 25 65-08_[ 2 _[CURG RAMP TYPE AT 61 — EXISTING SIDEWALK CWS 26 @si0a_| 3 _[cuRB RawP TYPE C CWS 27 @s-08_| 4 |cuRe RAMP TYPED VES 28 35-08 | 5 [CURB RAMP NOTES oves 29 @si-08__[ 6 [TRUNCATED DOWES Cvs 29 MISCELLANEOUS — (MSC) MSC-OT ‘SURVEY MONUMENT (LOCATED IN STREET) CVCS 15 WSC—02 POST & RAIL FENCE ves 16 WSC-03 GHAIN LINK TENNIS COURT FENCE Ces 15 MSC-04 BUS STOP & IRRIGATION PIPE SLEEVE owes #4 WSC=05 MAILBOX INSTALLATION CWS 46 ROADWAY — (RWY) RwY-01_|_1 _[6-LANE PRIME STREET SECTION WITH CONTIGUOUS SIDEWALK CWO S707 Rwe-01_|_2 | 4-LANE MAJOR AND COLLECTOR STREET WITH CONTIGUOUS SIDEWALK | CW STO2 Rwy-01_|_3_|2-1ANE COLLECTOR & RESIDENTIAL STREET WTH CONTIGUOUS SIDEWALK | CW STOS Rwr-01_|_4 | 2-LANE RESIDENTIAL & INDUSTRIAL STREET WITH CONTIGUOUS SIDEWALK | CVD STO# RuY-02_| 1 [MAUOR & COLLECTOR STREETS WITH NON-CONTIGUOUS SIDEWALK ovo S72 RWY-02_|_2 [COLLECTOR & RESIDENTIAL STREETS WITH NON-CONTIGUOUS SIDEWALK | CWO ST22 RWY-02 3 _| RESIDENTIAL & INDUSTRIAL STREETS WITH NON-CONTIGUOUS SIDEWALK CWO ST23 Ray=03_| _1_|OTAY RANCH ~ EXPRESSWAY, PRIME & MAJOR STREET SECTIONS CWO ST3I Rwy-03_|_2_|OTAY RANCH — VILLAGE ENTRY STREET SECTIONS CW STs RiY-03_| 3 _|OTAY RANCH ~ SECONDARY VILLAGE ENTRY STREET SECTIONS CW STIS Riy-03_| 4 _|OTAY RANCH — PROMENADE STREET SECTIONS. vo STs arate Biota SHEET INDEX ‘STO. SHT. TE PREV. STD. ROADWAY CONTINUED — (RWY) Rwr-03 | 5 |OTAY RANCH — PKWY, RESIDENTIAL, & INDUSTRIAL ST SECTIONS CW S135 Ruy-04 [1 |6-LANE PRIME INTERSECTION STANDARDS ov ST12 Rwy-04 | 2 _[6-LANE MAJOR INTERSECTION STANDARDS ow STS RWY-04 | 3_|6-LANE MAJOR INTERSECTION STANDARDS 2 cv St14 Ruy-04 [4 _|4-LANE MAJOR INTERSECTION STANDARDS ov Sm15 Riy-04 [5 _[4-LANE MAJOR & COLLECTOR INTERSECTION STANDARDS CWO S116 RWY-04 6 | OTAY RANCH — VILLAGE INTERSECTION STANDARDS CVD ST36 Rin—05_|_1_| SIGHT DISTANCE REQUIREMENTS CW TRO? Rwr—05 [2 _| SIGHT DISTANCE REQUIREMENTS ADDITONAL NOTES CW TRO? Ruv-05_|_3_| SIGHT DISTANCE REQUIREMENTS FOR STREETS 40° OR LESS WD TROB Rwy-06 [1 _ [TURN LANE REQUIREMENTS Wo STi RWy-06_[~ 2 _[OTAY RANCH — TURN LANE REQUIREMENTS CW S137 RWY-O7 KNUCKLES TYPE 1 AND TYPE WO S705 RW—08 CUL-DE-SAC CW S706 Rwy09 LOCATION OF UNDERGROUND UTLITES IN STREET CW S107 SEWER — (SWR) ‘SWR-OT PEAK TO AVERAGE SEWER FLOW cv SHOT ‘SWR-02 DEEP SEWER CONNECTION ves 14 SWR-O5 DEEP CUT HOUSE CONNECTION SEWER LATERAL coves 18 ‘SWR-04 SEWER LATERAL IN LANDSCAPED AREAS ves 20 SUR=05 SEWER LATERAL IN PCC DRIVEWAY Cues 2 SWR—06 SEWER LATERAL IN LANDSCAPE SW & ORY UTLUTES IN ROW. ves 22 SWR-07 SEWER LATERAL IN PCC DWY ~ SW é ORY UTLITES IN ROM. ves 23 SWR—08 SEWER MAIN REPAIR DETAILS coves 49 TRAFFIC — (TRF) TRF-O1 TRAFFIC SIGNAL STANDARD LOCATIONS vO TROT TRF-02 TYPICAL SIGN POST PLACEMENT Cw TROZ TRF-05 STREET LIGHT LOCATIONS CW TRO4 TRF-04 TYPIGAL SIDEWALK AND CROSSWALK LOCATIONS CVD TROS TRF-05 ‘SIONAL HEAD MOUNTING BRACKET AND MAST ARM INSTALLATION coves 8 TRF-06 EVPE DETECTOR ves 12 TRE=07 | _1_| STREET NAME SIGNS CW TROBA TRE-07_|_2 _| STREET NAME SIGNS DETALS CV TROBE TRF-07 _|_3_| OVERHEAD STREET NAME SIGNS TRF-07_|_4 | OVERHEAD STREET NAME SION DETAILS TRe=07 _|_5 OVERHEAD STREET NAME SIGN ABBREVATIONS SHEET INDEX arate Biota STD. SHT. mE PREV. STD. TRAFFIC CONTINUED — (TRF) TRF-08 1 _ | STREET LIGHTING STANDARD cves 6 TRF-08 2 _| STREET LIGHT STANDARD FOUNDATION DETAIL cues 7 TRF-0B J _| STREET LIGHTING STANDARD ELECTRICAL DETAILS eves 9 TRF—09 PULL BOXES cues It TRE-09 STREET LIGHT & TRAFFIC SIGNAL CONDUIT TRENCH eves 10 TRF-10 1 | BREAK-AWAY SIGN POST CWO TROS TRF-10 2 | BREAKAWAY POST ON MEDIAN cves 47 TRF-11 LADDER CROSSWALK MARKINGS LAYOUTS AND NOTES cry STANDARD LEGEND DESCRIPTION DRAWING | proposep | FAISTING CONTROLLER oh TRAFFIC SIGNAL WITH MASTARM, SAFETY LIGHT; SIGNAL INDICATION, BACK PLATE AND INTERNALL ¥ ILLUMINATED ‘STREET NAME SIGN. FLASHING BEACON, ONE WAY INDUCTIVE LOOP DETECTOR ELECTRICAL CONDUIT EMERGENCY VEHICLE PRE-EMPTION EQUIPMENT (E.V.P.E.)| METER PEDESTAL SERVICE POINT STREET LIGHTS OVERHEAD CONDUCTOR PEDESTRIAN PUSH BUTTON ON SPECIAL PUSH BUTTON POST TRF-08 TRF-08 | _—IRF=08. “ELEC ~ (GIVE NO. WIRES) orP6 ppb OPP; POWER POLE OPP ‘ove POLE No.) PULL BOX Pao Pe INDUCTIVE LOOP DETECTOR PULL BOX AND STUB—OUT PaO O- TELEPHONE POLE or (ove neote) TRAFFIC SIGNAL WITH THREE LENS INDICATION AND BLACK PLATE (UNLESS OTHERWISE INDICATED) WALK—WAIT PEDESTRIAN SIGNAL «o | + 1-0 TRAFFIC SIGNAL WITH THREE INDICATION (GREEN ARROW) «tio ato INLESS OTHERMSE INDICATED) : c—o | m—o REVISION [BY [APPROVED|DATE] CITY OF CHULA VISTA ORIGINAL JARR| 775) ENGINEERING & CAPITAL PROJECTS 10/15 /02_| wil G. SWASON 17/95, STANDARD DRAWING TAM SALLE 11/21/2017 Laid fora we INT SyaBOLS FOR TRAFFIC SIGNAL a [ah Aah! | LIGHTING INSTALLATIONS Iv LEGEND (ook (REMARKS IN PARENTHESES ARE rs ee STANDARD | NY OY aoc age sul DESCRIPTION EXISTING CONSTRUCTION IS GHOSTED. BOUNDARIES & CE] IES: CITY BOUNDARY LINE COUNTY OF SAN DIEGO os ‘CITY OF CHULA VISTA (ony eoNDARES) | ‘SUBDIVISION & RECORD OF PARCEL & LOT SPLIT LINES EASEMENTS & SETBACK LINES y a) SURVEY SOUNDARIES Tau SENET RO) PROPERTY LINES ALONG SIREETS & ALLEYS ; : (vos rem LOT LINES BETWEEN LOTS, oe 9.99 Fe TZE, TYPE & © OF EASEMENTS) z CENTERLINES STREETS: GRADING OVERLAY USING A.C. SURFACING ONLY SHOWN SHADED GRADING USING A.B. & A.C. SURFACING SHOWN SHADED OVERLAY USING AB. & A.C. SURFACING SHOWN SHADED OVERLAY USING P.C.C. SURFACING GRADING USING P.C.C. SURFACING OVERLAY USING A.B. & P.C.C, SURFACING ERNE REA CURB & GUTTER ——— (WOEATE WHER BOR & & TNSTION Locanons) CURB OR BERM OR DIKE "AC BERM OR POC_CURB. (INDICATE TYPE & SIZE) | MONOLITHIC CURB, GUTTER, & SIDEWALK SIDEWALK REVISION [BY [APPROVED[DA TE] CITY OF CHULA VISTA ORIGINAL [ARR| 8/6] ENGINEERING & CAPITAL PROJECTS S\ STANDARD DRAWING Tay SWMLLE 11/05/01 [Cul 6. SWANSON [11/02 77TH] WE || PROPERTY AND STREET SYMBOLS LAN S. YALLE 11/21/0017 HY Boi b Vv DESCRIPTION CITY STANDARD DRAWING LEGEND (REMARKS IN PARENTHESES ARE EXPLANATORY ONLY.) NEW CONSTRUCTION SYMBOLS ARE_SOUD. EXISTING CONSTRUCTION IS GHOSTED. STREETS CONTINUED: DRIVEWAY APPROACH os-01 csi-o1 ALLEY APPROACH eae cross GUTTER os-02 EDGE OF PAVEMENT RALWAY TRACKS (40 SCALE OR SWALER) (eee TN 40 SCH) BARRICADE conTINuoUS. SINGLE STREET SIGNS 7 we uTILTES: HP cas wait = “SHOW DMIETER ee TE) GAS SERVICE CONNECTION (SHOW Sze IF OTHER THAN3/4°) (OAS VALVE ny ee POWER LINES, OVERHEAD = a wR (GHOW NO. OF WiRES. VOLTAGE, £70.) POWER LINES UNDERGROUND LUZ COND. 120, 6 (GHOW SIZE OF CONOUMT, VOLTAGE, ETC.) TELEPHONE LINES, UNDERGROUND POWER OR TELEPHONE. MANHOLE wae a POLE ANCHOR OR DEADNAN [res : TELEPHONE. UNES, OVERHEAD SHOW WO. OF WRES, ETC) eu. (GHOW SIZE, NO., CONDUIT, ETC.) REVISION [BY [APPROVED]DATE| [10/15/02 Jow & SwmnsON [11702 CITY OF CHULA VISTA ORIGINAL [ARR| 5/62| ENGINEERING & CAPITAL PROJECTS STANDARD DRAWING 11/21/2017 [-ii/ei/ir[oeuy WAL [1/17 STREET AND UTILITY SYMBOLS Vl ALAS VALLE cary ENGNER DESCRIPTION CITY STANDARD DRAWING LEGEND (REMARKS IN. PARENTHESES ARE EXPLANATORY ONLY.) NEW CONSTRUCTION SYMBOLS ARE_ SOLD, [EXISTING CONSTRUCTION IS GHOSTED. UTILITIES_CONTINUED: ‘SEWER MAIN Te (GHOW OUWETER & TYPE) ‘SEWER LATERALS (SHOW DIAMETER OTHER THIN 4") SEWER MANHOLE Owe wo, SEWER PLUG ECP eive SEWER MAIN CLEANOUT CONCRETE CRADLE I ohh crane _| CONCRETE ENCASEMENT Ton eNcaseMent| AG. WATER MAIN Grow thor ac, oy Ee. a Size) ———® WATER SERVICE (SHOW _OWNETER IF OTHER THAN 3/4") Ww WATER (GATE) VALVE —o¥—n WATER NETER. Com ; poe caneenere ray BLOW OFF (siiow siz) FIRE HYDRANT a DRAINAGE: ‘STORM ORAN OR CULVERT 36" ROP 20x CULVERT GHOW SE) DRAINAGE CHANNEL OR OmTCH ===> SS > HEADWALL OR ENOWALL (SHOW APPROXIMATE ——| sie) CURB INLET (WNOIGATE TYPE | { } “LENGTH & sHow ‘STORM ORAN CLEANOUT ORG AAT iter APPROK.SHAPE) 6] REVISION [BY [APPROVED DATE] CITY OF CHULA VISTA ORIGINAL [ARR] 8/63] ENGINEERING & CAPITAL PROJECTS 71/05/01 | CWu] SWANSON [11702 STANDARD DRAWING 1/2/17 [0a WE VALE [11/17 UTILITY AND DRAINAGE SYMBOLS DESCRIPTION CITY STANDARD DRAWING (REWARKS_IN. PARENTHESES ARE NEW CONSTRUCTION SYMBOLS ARE SOLID. {EXISTING CONSTRUCTION IS GHOSTED. LEG D EXPLANATORY” ONLY) DRAINAGE_CONTINUED: cura ouTlet ca PIPE COLLAR l cys MONUMENTS: BENCH MARK @an_) ‘SURVEY WELL MONUMENT & MISCELLANEOUS: Gia OMETER AY GROG = © & Seer aes FENCE (CHAN UN, RE) ee FRE SOR hh ERE BO wa ie ey waren te Shag iin WD FONE Wooo FENCE ieee nou eecan eeeneael GRADING _& LANOSCAPING ORIGINAL GROUND (PROFLE) Sr FINISH ELEVATION EXISTING ELEVATION EXISTING CONTOUR, FINISH GRADE CONTOUR DAYLIGHT LINE 'SWALES & DIRECTION OF FLOW wm | _SLOPE PLANTING wy a wv iM wv | TOP: SHADE | oe, ee, TTT REVISION | BY [APPROVED |DATE| CITY OF CHULA VISTA a ARR] i ee EEC EE ine iocemaas 7 VAL N/A 72017 Tare A SECT OE: ANS MISCELLANEOUS SYMBOLS VII DRAINAGE (DRN) DESIGN AND CONSTRUCTION NTP NSLP PANTS Leh) Reiners CHULA VISTA | 2017 DEPARTMENT OF ENGINEERING AND CAPITAL PROJECTS Isopluvials of 2 Year, 6 Hour Storm i é § \\ = ll of E S ee g ‘ a Go ee . > e gf z eB 8 2 rob ee haw 2 & ‘oie 3 82 rE 5 u,8, 58 om SSEbss 2 z% $8 gs £E bo S 2. SR S 5 8B 2 8s, ——r {Ho aon 0 ” - 0 $3'0-ONOD3S U3d 1334 18ND NI MOTs NoIsaa(°O) REVISION [BY [APPROVED[DATE| TY OF CHULA VISTA ORIGINAL [NH 10772 ENGINEERING & CAPITAL PROJECTS [|e Swmison 11/02] STANDARD DRAWING Rag SALE 1/07207 ENGNEER REWSION [OPA|WCVALE IIVI7! STREET DRAINAGE — 40° & 64 [2 ‘es WIDE STREETS ORN-O6 TO_DETERMINE LENGTH OF INLET TO INTERCEPT 100% OF GUTTER FLOW Tem [UNITS DESCRIPTION HOW DETERMINED AMOUNT OF FLOW IN. GUTTER (ON ONE SIE OF STREET. HYOROLOGY STUDY OF AREA. DEPTH OF FLOW AT FACE OF ‘SEE GVD-DROS OR CVD-DRO7 (INTERSECTION OF Oy ¢ | | cure Nor CONSIDERING LUNE AND GUTTER GRADE LINE WILL FALL | inet DEPRESSION) ETWEEN LINES, INTERPOLATE FOR VALUES.) vo |, | EMORLOF weer waco wus ‘CVD-DROB AND CVD-DRO7 (INTERSECTION OF Og INTERCEPT 100% OF Q, AT GIVEN GUTTER GRADE, UNE AND GUTTER GRADE UNE WILL FALL GETWEEN d LINES. INTERPOLATE FOR VALUES.) TO_DETERMINE LENGTH OF INLET TO INTERCEPT A PORTION OF GUTTER FLOW (THIS METHOD TRIES DIFFERENT LENGTHS OF INLETS TO DETERMINE HOW MUCH FLOW WILL BE INTERCEPTED BY EACH LENGTH INLET AND HOW MUCH FLOW WILL CONTINUE PAST INLET. FIRST DETERMINE G, , d AND La AS ABOVE.) mem [unis DESCRIPTION HOW DETERMINED. Le | Leneri oF PRoPoseD Inver ‘SELECT TRIAL LENGTH Va RATIO OF LT Lg DMOE L BY Ly a | | AMOUNT FLOW UNE OF GUTTER SSD. ONG. OF INLET BEING CONSIDERED |S DEPRESSED AT INLET. FOR USE. of RATIO OF @ TO 4 DMOE 0 BY 4 FLOW INTERCEPTED BY INLET CVD-DROS (INTERSECTION OF L/Lo LINE @ | ets. | oF LENGTH L ANO 0/4 LUNE WILL FALL BETWEEN 0/Q) LINE INTERPOLATE FOR VALUES @ =a, x 0/0, 5-0 | ets, | FLOW CONTINUING PAST INLET. SUBTRACT @ FROM Q, NOTE: DRN=07 OR DRN-O8 MAY ALSO BE USED BEGINNING WITH A SELECTED @ TO DETERMINE L. REVISION [BY [APPROVED[OATE| CITY OF CHULA VISTA ORIGINAL [08/74 ENGINEERING & CAPITAL PROJECTS ‘ol [SWANSON {11/02 STANDARD DRAWING CLANS PAL W VALE [11/17 CHT ENGINEER — INLET DESIGN — LENGTH OF INLET DRN—-O7 10 ag ob 0.7) ae “le NOTE: SEE Mil FOR IDENTIFICATION OF SYMBOLS INLET DESIGN — PARTIAL INTERCEPTION OF GUTTER FLOW REVISION [BY [APPROVED DATE] City OF CHULA VISTA i). ORIGINAL [JW] I 772| ENGINEERING & CAPITAL PROJECTS . EVEN PR We ATPase Wav DRN-O8 10" INLET MARKER: 3/8" WELD ms ee zo hb : gy st we A" WELD gs wt a2 : w 328 cy es 1/4" DIA. ANCHOR — PROTECTION ° WR BAR @ 3°0.C. MAX. BAR os “a . 1/2" RAD. IN 1” DIA. : ‘SUPPORT BOLT Seo ores 1. FACE ANGLE SILL BE CAST WTO STRUCTRE COUMHUOUS FOR THE FUL LENGTH 2. POSED METAL PARIS SHALL BE HOT-DIPPED G8LVAMZED AFTER FABRICATON. I WHEN CURB INLET OPENNG HEIGHT (H) EXGEDS @*, STAL 1” OIA. STEEL PROTECTON BAR STEEL PROTEOTON BAR SHALL BE EMBEDDED 6" NTO CURB WUE 4 INSTALL AoinowAL 24RS AT 3 $° CLEAR SPAONG ABOVE FST BAR MEW OPENING EXCEEDS e WHEN OUR RLET OPENING LENGTH EXCEEDS NTALL 1" DA, STEEL SUPPORT BOLTS, SPACED AT Nor ORE THAN 5” 06 SHEET 1 OF 2] RESON [ov] ORIGINAL [OPH [APPROVED[DATE| City OF CHULA VISTA WME [WAT] ENGINEERING & CAPITAL PROJECTS W Oye STANDARD DRAWING AALS ae T7277 a CURB INLET OPENING DRN-OS WET EXIST (URS PER PLAN 6’ MAXIMUM- 4,5" Noma, CROWN ane aa NORMAL, CROWN TYPICAL_SECTION (A-A) 6° MAXIMUM ~ 4,5" —_— Zs SEE SHEET 1 FoR CURB INLET OPENING MEET EXIST up OF GUTTER curr ce) LOCALIZED_DEPRESSION (8-8) © A 8 [GUTTER TRANSITION} |--sUTTER TRANSITION] 10 TOP oF a i LU oF GUTTER 1 = ayrreR ees er wor eS" sHowt or SNS G CURB PROFILE — INLET TRANSITION ee SET 2 F 2 REVISION [BY APPROVED DATE] CITY OF CHULA VISTA ORIGINAL [OPH|W. WE [1/17] ENGINEERING & CAPITAL PROJECTS Sst STANDARD DRAWING IAN s, VALLE “1/21/2007 CURB INLET CURB HEIGHT AND _ |2IVENGHEER PAVEMENT TRANSITION DRN-OS 8 24” MANHOLE FRAME AND COVER, LIGHT DUTY AS PER SDRSD, M=2. RAW OR TOE ] SLOPE on FOR REINFORCEMENT SEE ‘SORSD, 0-25 2 porno Hfg| = teen al LF |. 20x 14°: 4°R STATION AS me 8 PLAN NO SCALE TOP OF CURB Top oF cuRB 4 TRANSITION TRANSITION 24"8 MH . r= C—O re I ; Tonal CORE Tot. SMe FLOW LINE ‘ 8” CURB FACE PROFILE NO SCALE 24" MH COVER- 3 (MIN,) 24" MH COVER ‘SIDEWALK FINISH (SEE ANCHOR DETAIL 'SDRSD, D-25 “1” UP SEE DETAIL “A” SLOPE 1/4” PER FOOT SECTION "B-B” CURB OUTLET DETAIL NO SCALE SHEET | OF 2) REVISION | BY [APPROVED|DATE] CITY OF CHULA VISTA 7 ‘ORIGINAL ate SUNS " ENGINEERING & CAPITAL PROJECTS . REVS 7 ewson [OPA YALE SIDEWALK UNDERDRAIN cura [esis = V7" OUTLET DETAIL DRN-10 (#4 TE BARS) e 12" OC) #4 @ 16" OC {6 {6° 7 Seid tN a P fopnowal Key |coNsTRUCTION JOINTS. St “AA” 272k x ay 1 5 1/4" STL. PLATE es [\ [sear wenorre’. Ke E te tty cal Vee Ee 1 faa A 6) cf cg \ a] >} i > T MALL) 8 = "ITCH T| en WALL it TT TT Tere tt P laow cne} | ATE. L 1/2 CLEAR | | t-1/2 1/4" STL. PLATE 1. \ tptrale 11 3 @ 3" 00 —Hfel 1-14" STAINLESS STL. BOL’ E le ee NUT AND LW (1/2' 3) . STEEL GRATE DETAIL EMBED 3” (MIN) 6 NO SCALE ah, 2 GRATE TO BE HOT DIPPED GALVANIZED AFTER FABRICATION PETA re 5’ TRANSITION BROW DITCH TRANSITION DETAIL NO SCALE SHEET 2 OF 2 REVISION [BY [APPROVED]DATE] CITY OF CHULA VISTA ORIGINAL 112/90] ENGINEERING & CAPITAL PROJECTS [Revision [ol c. Swmnson [11/0 STANDARD DRAWING. TS VAL sewsion [opi we “IHV7ISIDEWALK UNDERDRAIN BROW DITCH|AIY eohite TRANSITION DETAIL DRN-10 = 3 q 3 Le & 3 z 7 = Po Y ah % i @ a g2 3 el \ ao eH |Z w Ll 3 Ore oO y a = ion) i ia Z eae) Go > ong| & Bg stall SB a Ww Oy i vie Sp ke | OZ) iG ge8] Zags ; wel ae a é xo aS| 5 Sze] 35 Ba5| 22 IZ Oo] 20 SOR) S= hea 33] = 3 eee Ze) x oF” = & wa w |= gle 5 |5 g a Fees al is 3} (Bly) | =| al= eles i= | (Bs 3318/5 Bese alee MASONRY RETAINING WALLS The City of Chula Vista requires 9 permit for the construction of retaining walls, except those less than three feet in height and not supporting surcharge. This publication outlines the city’s requirements for retaining walls with level backfil, with sloping backfill and with vehicular surcharge. If construction does not involve grading, contact the Building Division of the Planning & Building Department for information on how to obtain a permit for a retaining wall (619-691-5272). If construction does involve grading, contact the Engineering Division of the Public Works Department (619-691-5024). 1. INSPECTIONS You must call the City for inspections ofter several specific phases of construction. To schedule an inspection for_a retaining wall permit having a permit number starting with a "” call the Building Division at (619) 691-5009. For permit ‘numbers starting with "PG" call the Engineering Division ot (619) 585-5737. Please call for these inspections at the following times, and do not proceed to the next phase of construction until the City inspector has given you written approval to proceed: A. Call for @ footing inspection after you have made the excavation for the footing, tied the steel securely in its final position, and made the site ready for concrete placement. Do not place concrete until the City inspector has given you written ‘approval to proceed. B. Call for a masonry pre-grout inspection after you have laid the block and have set the reinforcing steel in place, but before you place the grout. Do not lay blocks higher than 6 feet without @ pre-grout inspection. 1. If cleanout holes are required, lay the block to the full height of the grout pour before you call for the pre-grout inspection. Place grout in a continuous pour in grout lifts not more than 4 feet in height. 2. If cleanout holes gce_net required, call for a masonry pre-grout inspection rir levee rout pau LD elnot aio higher than the grout pour. Note that cleanouts are required for all ©. Call for a backfil/drainage inspection after grouting is completed and rock or rubble wall drains are in place, but before earth backfill is placed. D. Call for a final inspection after you have completed the construction and, if the City has required one, after a jicensed professional has prepared a compaction report. (See Section Vi) SHEET 1 OF 16] REVISION [BY [APPROVED [DATE] CITY OF CHULA VISTA ‘ORIGINAL [CVM[C. SWANSON [12/01] ENGINEERING & CAPITAL PROJECTS REVISION [DPH]W VALE [11/17 STANDARD DRAWING RETAINING WALL REQUIREMENTS PUBLICATION OUTLINES i. DESIGN TABLES The design tables, found towards the end of this publication, address a variety of different loading conditions and footing configurations. If you have a loading condition that is not shown in this publication, you must have a licensed pro~ fessional engineer or architect design the wall specifically for conditions existing on the site, Examples of loading conditions not covered in this publication include walls supporting building foundations and walls subjected to truck traffic surcharge greater than 250 psf, unless those loads are applied away from the wall a distance at least equal to the height of the wall. Retaining wall height is measured from the top of the footing to the top of the wall. You must not build higher than the design height of the wall WM. BLOCK All block must be Type 'N’, grouted solid. (Design f IV, CONCRETE MIX REQUIREMENTS Note: Use of plastic cement is not permitted in retaining walls located in this Seismic Zone. 1,500 psi) A. The concrete mix footings must have a compressive strength of at least f= 2,500 psi in 28 days. You may use a mix containing the following proportions by volume, 1 part Portland cement 21/2 parts sand 3 1/2 parts 3/4-inch maximum-size gravel 7 gallons of water maximum per sack of cement Note: Hand mixed concrete and grout are not permitted on projects subject to the "Standard Specifications for Public Works Construction” (“Green Book”.) B. The mortar mix must have a compressive strength of at least 1,800 psi. You may use a mix containing the following proportions by volume: 1 part Portland cement 31/2 parts sand 1/4 part hydrated lime or lime putty ©. Grout must have a compressive strength of at least 2,000 psi in 28 days. -You may use a mix containing the following proportions by volume: 1 part Portland cement 3 parts sand 2 parts pea gravel (5/8-inch aggregate) SHEET 2 OF 16| REVISION | BY [APPROVED |DATE] CITY OF CHULA VISTA ORIGINAL [owe Sma [2/01] ENGINEERING é& CAPITAL PROJECTS RWG | REVISION [OPH[W. VALLE [11/17 STANDARD DRAWING. SMUD SVALLE 11/21/0007 tN ul + RETAINING WALL REQUIREMENTS VGHEER PUBLICATION OUTLINES GRD-O5 Note: Hand mixed concrete and grout are not permitted on projects subject to the "Standard Specifications for Public Works Construction” ("Green Book™.) Add water until you achieve pouring consistency without segregating the grout components. Rod or vibrate immediately. Re-rod or re-vibrate the grout about 10 minutes after pouring to ensure proper consolidation. When the grouting of a second lift is to be continued at later time, stop the grout placement 2 inches from the top of the masonry units. Note: All cells must be filled solid with grout. \. MORTAR KEY To obtain proper bonding between the footing and the first course of block, form @ mortar key by embedding a flat 2 x 4 flush with, and at the top of, the freshly placed footing concrete (See Drawing CVCS 33). Remove the 2 x 4 after the concrete has started to harden (about 1 hour). You may omit a mortar key if you set the first course of block into the freshly placed concrete footing. Vi. WALL DRAINS Provide wall drains (4~inch—diameter) at 6-foot intervals along the length of the wall and located just above the level of the soil or paving on the front face of the wall (See Drawing CVCS 33). Alternatively, form the drains by placing a block on its side at 6-foot intervals, by leaving out the mortar in the vertical spaces between all the blocks in the first course above the soil, by paving (head joint) on the front face of the wall, or by some other equivalent method acceptable to the City, Backfill behind wall drains or open head joints must be 12 inches wide filled with gravel and must extend from the top of the footing to above the top of the drain or open joint, Vi. SOW Wail design, footing sizes and reinforcing steel are all based on an active earth pressure with an equivalent fluid pressure of 56 psf and a weight of 120 pounds per cubic foot (pef). Extend all footings at least 12 inches into undisturbed natural soil or into fill that has been compacted to at least 90 percent density. Dampen soil prior to placing concrete in footings. Where the ground slopes away from the base of the wall, you must have a horizontal distance of at least 7 feet from the toe of the footing to “daylight” (See Drawing CVCS 33). The City may require a soils report, prepared by a licensed civil engineer specialized in soil mechanics or @ licensed geotechnical engineer, depending on soil conditions at the site. Footing sizes in the attached tables are based on a 1,000 psf maximum soil bearing value. If you wish to take advantage of a higher bearing value, you must have a licensed architect (a licensed architect may not design Public Works walls that are SHEET 3 OF 16 REVISION [SY [APPROVED|DATE| CITY OF CHULA VISTA t ‘ORIGINAL [Cum] ¢. SWANSON [12/01] ENGINEERING & CAPITAL PROJECTS Wy REVISION [DPH|W-VALE [11/17 ‘STANDARD DRAWING aa RETAINING WALL REQUIREMENTS, PUBLICATION OUTLINES CCAM S VALE 1172172007 CHT ENGREER GRD-05 in the right-of-way) or civil/structural engineer design the wali(s) specifically for the existing site conditions. Again, the City may require a soils report, prepared by a licensed civil engineer specialized in soil mechanics or a licensed geotechnical engineer, depending on soil conditions at the site. Vil. REINFORCING STEEL Use reinforcing steel bars which conform to ASTM specification A615-85, Grade 40 or 60. When you can’t use one continuous bar, you must lop or splice bars @ distance of at least 40-bar diameters (ie, 15” for #3 bars, 20” for #4 bars, 25" for #5 bars, 50" for #6 bars). The required minimum lop splice for bars of different size to be based on the diameter of the larger size bar. Bends in the reinforcing steel must conform to the Manual of Standard Practice, American Concrete Institute. Backing for hooks must be at least a distance equal to four bar diameters. All required bar embedment dimensions are clear distances to outside of bar. Spacing for parallel bars is center to center of bars. Place two or more bars longitudinally in the footing (See Tables for number of bars needed). For 6-inch or 8inch blocks, place one #3 bar longitudinally in the center of the wall in a bond beam block every 16 inches of wall height as the blocks are laid up. For 12-inch blocks, place ‘one #4 bar longitudinally in the center of the wail in a bond beam block every 16 inches of wall height as the blocks are laid up. IX, JOINTS Vertical control joints are needed at intervals of not more than 32 feet. Joints must resist shear and other lateral forces and still permit longitudinal movement. Vertical expansion joints are needed at intervals of not more than 96 feet (See Drawing CVCS 54). X. STEP FOOTINGS Base the footing dimensions and the amount of reinforcing steel on the maximum height of the wall on either side of a step in the footing elevation. The construction of the step must follow the details on Drawing CVCS 34. Xi. BACKEIL Do not place backfill material against @ masonry retaining wall until the grout has either reached design strength or has cured for a minimum of 28 days. Compaction of backfil material by either jetting or ponding with water is not permitted, Each layer of backfill must be moistened and thoroughly tamped, rolled or otherwise compacted until the relative compaction is not less than 90% If the wall is within the City right-of-way, subject to vehicular surcharge or SHEET 4 OF 16 REVISION [BY [APPROVED DATE] CITY OF CHULA VISTA ORIGINAL [Cw c. SHANSON [12/01] ENGINEERING & CAPITAL PROJECTS Ut | REWSION [OPH We VALE 11/17 STANDARD DRAWING RETAINING WALL REQUIREMENTS — [HIV ENGHEER CAMS VALLE: 1/21/07 T PUBLICATION OUTLINES GRD-—O5 subject to the "Standard Specifications for Public Works Construction” (Green Book"), the City will require a compaction test and certificate, from a soil engineer, showing that the entire fill has been compacted to at least 90% il, FENCING If @ pedestrian walkway is adjacent to the top of a retaining wall that is more than 30-inches in height, you must install safety fencing at the top of the wall If @ wall is greater thon 3O-inches in height and is adjacent to a street, driveway or parking area, you must install a vehicular guardrail at the top of the wail il, USE OF TABLES First, determine the height of wall you need to construct. Then determine the slope of retained earth or if the wall supports vehicular surcharge, Based on what distance you choose from the footing toe to the face of wall, use the table with the necessary wall height and slope of retained earth or surcharge. From the appropriate fable, copy the wall design information, including block width, reinforcing steel size and spacing, and footing and key dimensions, on to a copy of the City's typical wall section form (Drawings CVCS 31 or CVCS 32). Use a separate form for each different design of wall, (One wall design may be used for all walls of a certain height and lower. However, there may be savings in material costs if a different, more economical, design is used for walls of lower height) Indicate on each form the locations on the property that the particular wall design will be used. See EXAMPLE at end of the attached forms. XIV, PLAN SUBMITTAI Prepare a land development plan (for Engineering Division permits) or plot plan (for Building Division permits) showing the location, type and height of each wall. Show all adjacent structures, driveways, parking areas and pedestrian walkwoys. ‘Attach a completed form for each proposed wall design, as well as a copy of this procedure with the (following) discalimer signed and dated. xv. LAIMER These design standards indicate 9 minimum acceptable design for retaining walls meeting very specific field conditions and construction procedures. Gity approval of retaining walls and any related improvements shall not constitute a representa~ tion of the adequacy of the design or engineering of such retaining walls or improvements, nor shall it constitute an implied representation as to its suitability or fitness for any particular purpose. The City assumes no lability or any responsibility for damage or failure. The owner should consult with an appropriate Registered Civil Engineer or licensed architect. ‘SHEET 5 0F 16 REVISION | BY |APPROVED|DATE} CITY OF CHULA VISTA Srren{oul ane | ENGINEERING de CAPITAL PROJECTS [IM| La C Ww REVISION [DPH| W. VALLE 111/17] STANDARD DRAWING imigiy.S, VALE 1172172007 |— RETAINING WALL REQUIREMENTS [ZIV ENGNEER pees PUBLICATION OUTLINES GRD-05 LOW. DES! © Based on the site conditions and retaining wall location, determine if the wall will have a variable heel size (no limitation on the size of the heel), a 6-in or 2-in heel size, then © Determine if the wall is retaining a level or sloping backfill, or level backfill with vehicular surcharge, then © Based on the conditions noted above, select the appropriate design table (for ex. Variable heel (Minimum toe), 1.5 to 1 slope), then © Move across the table and find the applicable retaining wall height (for ex. 6'-8"). Retaining wall height is measured from the top of the footing to to the top of the wall. The design data found under that column (for ex. column titled CVVI5-68) is what applies to the wall. Then, © From the design data under the applicable column, determine if the wall is TYPE I or il, in case of the example TYPE I, then © Tronsfer the design data to the appropriate drawing, CVCS 31 for TYPE | wall and CVCS 32 for TYPE I! wall, as shown on the attached example, then © Indicate on the plot plan the location and. extent of where each wall type (for ex. CWVI5-68) is to be built. ‘© Repeat the above steps for each wall with different height and/or conditions (for ex. heel size, backfill slope or vehicular surcharge). SHEET 6 OF 16 REVISION [BY [APPROVED[DATE] CITY OF CHULA VISTA : 0 GRIGNAL Tow c SMSO [12/01] ENGINEERING & CAPITAL PROJECTS v WW! REVISION [OPH] W ALE [11/17 ‘STANDARD ORAWING iULan SOME 11/1/0017 RETAINING WALL REQUIREMENTS [at alite PUBLICATION OUTLINES GRD—05 6" MAX. 2° MIN. 7 et (SEE SEC. vil) WALL _ORAIN (SEE SEC. V) LAP SPLICE (SEE SEC. vil) EDGE OF cone ~ TYP NO SCALE HORIZONTAL STEEL # BARS ©. ” WALL— 2172" TP. THICKNESS Le 70 FACE OF MASONRY H=WALL HEIGHT. MORTAR KEY ———} (sc SEC | 5" CLEAR ol | "A" VERTICAL REINF. #—— BARS @___ “oc "B” LOWER VERTICAL REINF. # pars @___ "00 To EXTEND UPWARDS FROM TOP OF FOOTING 2'-8" OR HEIGHT OF WALL, WHICHEVER IS THE LESSER 24/2" De, | _____— Face oF MASONRY GRAVEL BAOKFILL x 12" WOE "0" UPPER FOUNDATION REINF. é BARS @___"0C 12" MINIMUM CONCRETE DEPTH, 12" MIN. INTO NATURAL GROUND OR INTO APPROVED COMPACTED FILL, FOOTING HORIZONTAL BARS KEY TO TOE, - ae [= ——" NT KEY REINF. #_— Bars a_“oo [__ WHFOOTING WiTH=—— '——" | KEY- “WOTH x D&B TH SHEET 7 OF 16 REVISION [BY [APPROVED[DATE] CITY OF CHULA VISTA ORIGINAL [wil SWANSON [12/01] ENGINEERING & CAPITAL PROJECTS Wise Upee- 11/2172017 REVISION [OPH[W. VALE [11/17 STANDARD DRAWING RLS, IE ENGNEER RETAINING WALL TYPE | GRD—05

You might also like