Professional Documents
Culture Documents
User's Guide
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
Issued: 30.6.2004
Version: E/17.06.2008 User's Guide
Contents:
3
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
5
6
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
1.1. Copyrights
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any
errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB Oy
be liable for incidental or consequential damages arising from use of any software or
hardware described in this document.
This document and parts thereof must not be reproduced or copied without written per-
mission from ABB Oy, and the contents thereof must not be imparted to a third party
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
1.2. Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names men-
tioned in this document may be trademarks or registered trademarks of their respective
holders.
1.3. General
This manual provides thorough information on the OPC Client for IEC 60870-5-101
Slave protocol (later in this manual IEC101 Slave OPC Client) and the central concepts
related to it. You will find instructions on to take it into use. The basic operation proced-
ures are also discussed.
Information in this user’s guide is intended for application engineers who need to con-
figure IEC101 Slave OPC Client in order to establish communication to an OPC server.
As a prerequisite, you should understand IEC870-5-101 protocol and the basic procedures
in COM600 Communication Engineering Tool (CET).
7
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Introduction
This section gives an overview of the IEC101 Slave OPC Client and states the system
requirements to be met when using the client.
Configuration
In this section you will find an overview of the configuration tasks and instructions
on how to create and configure IEC101 Slave OPC Client related objects.
Operation
This section covers the basic operation procedures you can carry out when transferring
or activating the Communication Gateway COM610 computer or Station Computer
615 with new configurations.
You are also given instructions on how to monitor and control the IEC101 commu-
nication.
Technical reference
This section contains a list of status codes and information about the IEC 61850 data
modelling.
8
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
• You may be told to enter the string MIF349 in a field. The string is shown as follows
in the procedure:
MIF349
• Variables are shown using lowercase letters:
sequence name
1.5. Terminology
The following is a list of terms associated with the IEC101 Slave OPC Client that you
should be familiar with. The list contains terms that are unique to ABB or have a usage
or definition that is different from standard industry usage.
Term Description
9
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Term Description
1.6. Abbreviations
The following is a list of abbreviations associated with the IEC101 Slave OPC Client
that you should be familiar with. See also 1.5, Terminology.
Abbreviation Description
10
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Abbreviation Description
11
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
2. Introduction
The IEC101 Slave OPC Client is configured using the Communication Engineering Tool
(CET). Communication Engineering Tool (CET) can also be used for diagnosing and
controlling the operation of the IEC101 Slave OPC Client. COM610/615 has a web
server that can be used for remote diagnostic of the Gateway including the IEC101 Slave
OPC Client.
The IEC101 Slave OPC Client uses serial communication (RS232 interface). Before you
can start using the IEC101 OPC Client, at least one OPC server has to be configured to
provide access to the process devices. In this manual, the term “IEC101 Device” is used
for a virtual station in the COM610/615 representing the slave stations visible to the
IEC101 master system.
12
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
3. Configuration
First you need to start Communication Engineering Tool (CET) to open a project where
at least one OPC server has been configured. You can also open and name a new project,
where you configure at least one OPC server.
13
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
IEC101_configuration_overview.bmp
The configuration work can basically be divided into two separate tasks:
1. building an object tree, and
2. configuring object properties.
First, you need to build an object tree. This is done by adding objects to the object tree,
see 3.3.1, General about building object tree and 3.3.5, Adding data objects.
Figure 3.2-1 shows an example of how the object tree may look like after it has been
built. In the example tree you can see the IEC101 OPC Client object and its child objects
like channels, devices, and data objects. Indentation is used to indicate the parent-child
relationship between the objects.
After you have added the necessary objects to the object tree in the communication
structure, you need to configure them, see 3.4.1, General about configuring objects.
14
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Object Description
The object tree is built in the Communication structure of the COM600 Engineering
Tool, see Figure 3.2-1. It is built by adding objects in a logical order starting from the
IEC101 Slave OPC Client object.
Before the IEC101 Slave OPC Client can be taken into use, an OPC server has to be
configured for the process communication. For more information on this subject, refer
to the COM600 User's Guide
You have several possible ways to add objects to the object tree in the Communication
structure:
• You can right-click the object to which you want to add a child object.
• You can copy the object.
15
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
To start building the object tree, add the IEC101 Slave OPC Client object in the Commu-
nication structure by selecting the Gateway object, right-click it and select New > IEC101
> IEC101 Slave OPC Client, Figure 3.3.2-1 .
AddingClient101.jpg
After the IEC101 Slave OPC Client object has been successfully added, you can continue
building the object tree by adding either the IEC101 Balanced Channel object or the
IEC101 Unbalanced Channel object.
16
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
After a channel object has been successfully added, you can continue building the
structure by adding the IEC101 Device object. All the data can be connected to one
device or divided to several slave devices. Before dividing data to several slave devices,
it must be checked that the current protocol mode and the master system support the
feature.
Data objects are added somewhat differently than the upper level objects. Basically, you
drag and drop the data objects you need from an OPC server to the IEC101 Slave OPC
Client.
17
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
CrossReferences101.jpg
In the Cross References window, you can use a filter file to leave out some of the data
objects to be connected to IEC101 Device. Select the filter file to be used from the drop-
down menu Active Filter (see Figure 3.3.5-1). If there are no filter files listed in the drop-
down menu, you can create your own filter file by clicking Modify Filter File. You can
also modify an existing filter file to meet your needs.
The Cross References table allows you to view the data objects by type. Use the tabs in
the upper part of the table to do this. Under the General tab, you can see all the data
objects and their property values. Here you can sort the data objects by clicking the
column heading (Object Name, Description, 61850-Type, etc.).
There is a possibility to export the cross references table to Microsoft Excel and to import
the table from Microsoft Excel.
Clicking Apply connects the data objects to the IEC101 Device. After clicking Apply,
you can change the data object values either in the Object Properties window or in the
Cross References window. For more detailed instructions on configuring the data object
properties in the Cross References window, see 3.4.5.1, General about configuring data
objects.
18
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
After the objects have been added, you need to configure the object properties. Fig-
ure 3.4.1-1 shows an example of how to use Communication Engineering Tool (CET)
to configure the object properties for IEC101 Slave OPC Client.
To configure an object:
1. Select an object in the object tree of the communication structure.
2. The object properties appear now in the Object Properties window. The properties
and their values can be viewed as shown in Figure 3.4.1-1.
ObjProp.jpg
19
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
The available properties for different objects are listed in the following subsections.
Table 3.4.2-1 lists the configurable IEC101 Client properties and value ranges for them.
The actual configuration by using the COM600 Communication Engineering Tool (CET)
is performed as described in 3.4.1, General about configuring objects.
Table 3.4.2-1 IEC101 Slave OPC Client properties
Property / Para- Value or Value range/ Default Description
meter
Basic
Maximum OPC 0...65535 Specifies the maximum time in seconds
Server Initialization that any connected (configured) OPC
Time Default: 5 Server requires to retrieve all its initial
data.
Prog ID AE Instance identification of diagnostic OPC
alarm and event server.
ProgID DA Instance identification of diagnostic OPC
data access server.
Time Zone Correc- -720...720 The value of this property in minutes is
tion added to the synchronization time received
Default: 0 from an IEC101 master.
Station/Remote
Switch
Station/Remote Do not check Station/Remote Specifies if a position check for the station
Switch switch position, command remote switch is going to be made.
always allowed.
20
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
The IEC101 Balanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.1-1. The actual configuration by using the COM600
Communication Engineering Tool (CET) is performed as described in 3.4.1, General
about configuring objects.
Table 3.4.3.1-1 IEC101 Balanced Channel properties
Property / Para- Value or Value range/ Default Description
meter
Basic
In Use In use Specifies whether the channel is initially
in use or not.
Not in use
Dafault: In use
Protocol IEC60870-5-101 Balanced Protocol
Slave
Communication
Port
Baud Rate 300 bits/s Transmission rate used on the channel.
600 bits/s
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
56000 bits/s
57600 bits/s
115200 bits/s
128000 bits/s
256000 bits/s
21
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Odd
Default: Even
Receiver Data Bit 5...8 Specifies the number of data bits in each
Count received character.
Default: 8
Stop Bits 1 stopbit Specifies the number of data bits in each
transmitted character.
2 stopbits
Default: 1 stopbit
Transmitter Data Bit 5...8 Specifies the number of stop bits attached
Count to each transmitted character.
Default: 8
Communication
Control
Carrier Blocking Carrier detect signal is ignored Determines whether the Carrier Detect
signal of the serial port must be set in
Carrier detect signal must be order for the IEC station to receive mes-
set sages
22
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Link Type RTS activated during transmis- The type of the data link connection used
sion (Unbalanced slave) on the channel.
The IEC101 Unbalanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.2-1. The actual configuration by using the COM610
Communication Engineering Tool (CET) is performed as described in 3.4.1, General
about configuring objects.
Table 3.4.3.2-1 IEC101 Unbalanced Channel properties
Property / Para- Value or Value range/ Default Description
meter
Basic
23
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Default: In use
Protocol IEC60870-5-101 Unbalanced Protocol
Slave
Communication
Port
Baud Rate 300 bits/s Transmission rate used on the channel.
600 bits/s
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
56000 bits/s
57600 bits/s
115200 bits/s
128000 bits/s
256000 bits/s
Odd
Default: Even
Receiver Data Bit 5...8 Specifies the number of data bits in each
Count received character.
Default: 8
24
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Default: 1 stopbit
Transmitter Data Bit 5...8 Specifies the number of stop bits attached
Count to each transmitted character.
Default: 8
Communication
Control
Carrier Blocking Carrier detect signal is ignored Determines whether the Carrier Detect
signal of the serial port must be set in
Carrier detect signal must be order for the IEC station to receive mes-
set sages
slave)
25
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Operating Mode Handshaking messages not Specifies whether the handshaking mes-
restarted sages (request, status of link, reset of
remote link) are restarted when a ‘request
Handshaking messages status of link’ message is received from
restarted the remote end.
Table 3.4.4.1-1 lists the configurable properties for IEC101 Device and value ranges for
these properties. The actual configuration by using the COM600 Communication
Engineering Tool (CET) is performed as described in 3.4.1, General about configuring
objects.
Table 3.4.4.1-1 IEC101 Device properties
Name Value/Value range Description
Basic
Diagnostics Enabled True Specifies whether diagnostic
AE events are sent for the sta-
False tion or not.
Default: False
Has Redundant Line True Specifies whether redundant
channel is used or not.
False
Default: False
26
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Default: In use
Addresses
Polling Address 0...255 or The link address of the IEC
60870-5-101 slave station
0...65535
Default: 1
27
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Default: Disabled
Command Handling
Command Address 0...65535 The object address of the bit-
stream process object in the
Default: 32000 OPC Client, where an unrecog-
nized message is handled.
Confirmation Messages Placed True Place confirmation messages
To Class 2 Queue to class 2 queue instead of
False class 1 queue.
Default: True
Disable Select-execute Validity True Disable select-execute validity
Check check.
False
Default: True
Execute time-out 0...65 The maximum time an execute
command is waited after a
Default: 30 select command.
Lengths
Cause of Transmission Length 1...2 The length of the cause of
transmission field in an IEC
Default: 1 60870-5-101 message
Information Address Length 1...3 The length of the information
object address in octets.
Default: 2
Information address maximum
value will be as follows:
28
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Default: True
Disable Hour Change Clock True Disable sending of hour change
Message clock synchronization mes-
False sage.
Default: True
Summer Time Summer time is not used States whether summer time is
used or not.
Summer time is used
29
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Transparent SPA Mapping 01 [IEC Address], [OPC Path], Defines IEC address for
[OPC Server object name] e.g. receiving Transparent SPA
Transparent SPA Mapping 02 25001, Line1.RACK.SPA6, messages and OPC path to the
SPA OPC Server IED where the message is for-
Transparent SPA Mapping 03 warded.
Transparent SPA Mapping 30
30
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
You can configure data objects either in the Object Properties window or in the Cross
References window.
The actual configuration in Object Properties window by using the COM600 Commu-
nication Engineering Tool (CET) is performed as described in 3.4.1, General about
configuring objects.
The parameters are stored in Object properties in the COM600 Communication Engin-
eering Tool (CET) (see the tables for each data object type).
Clicking Apply connects the data objects to the IEC101 Device. After clicking Apply
the connected data objects will appear as child objects for the IEC101 Device. The cross
reference information can then be also modified by selecting the data object and using
the object properties window.
Note that if you make changes in the object names or structuring of objects of OPC
Server, which are connected to the IEC101 Device, you must re-open the cross reference
tool and verify that the changes are correctly handled and then click Apply to update
the IEC101 configuration accordingly.
IEC101 Slave OPC Client supports data objects for status, measurements, controllable
status and controllable analog information. The following subsections list the configurable
data object properties for the IEC101 Slave OPC Client.
Information in the table below applies also to the Internal SPS data object.
Table 3.4.5.2-1 Configurable SPS properties for OPC client
Property/ Para- Value or Value range/ Default Description
meter
Basic
Common Data SPS Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC address for indication
Default: 0
Common
31
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Default: False
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is paced in the class
End of queue = 0 1 and class 2 queues.
Middle of queue = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send as Double True = 1 Specifies if a value of indication signal is
Point sent as double point value.
False= 0
Default: False
Send as Inverse True = 1 Specifies if a value of indication signal is
Value sent as inverse value.
False = 0
Default: False
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
32
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Basic
Common Data DPS Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC address for indication.
Default: 0
Common
Class 1 = Class 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
2 = Class 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: 1 = Class 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write 1 = True Defines whether a new indication value
overwrites an older one in the queue.
0 = False
Default: 0 = False
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send as Inverse True = 1 Specifies if a value of indication signal is
Value sent as inverse value.
False = 0
Default: False
Send as Single True = 1 Specifies if a value of indication signal is
Point sent as single point value.
False = 0
Default: False
33
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Information in the table below applies also to the Internal INS data object.
Table 3.4.5.4-1 Configurable INS properties for OPC client
Property/ Para- Value or Value range/ Default Description
meter
Basic
Common Data INS Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC address for indication.
Default: 0
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
34
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Basic
Common Data ACT Common data class according to IEC
Class 61850.
Addresses
General Address 0...16777215 IEC address for general indication.
Neutral Address 0...16777215 IEC address for neutral indication
Phase A Address 0...16777215 IEC address for phase A.
0 = Not in use
Phase B Address 0...16777215 IEC address for phase B.
0 = Not in use
Phase C Address 0...16777215 IEC address for phase C.
0 = Not in use
Common
35
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send as Double True = 1 Specifies if the value of indication signal
Point is sent as double point.
False = 0
Send as Inverse True = 1 Specifies the value of indication signal is
Value sent as inverse value.
False = 0
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Basic
36
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
0 = Not in use
Phase B Address 0...16777215 IEC address for phase B
0 = Not in use
Phase C Address 0...16777215 IEC address for phase C
0 = Not in use
Common
Class 1 = Class 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
2 = Class 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: 1 = Class 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send as Double True = 1 Specifies if a value of indication signal is
Point sent as double point.
False = 0
Send as Inverse True = 1 Specifies if a value of indication signal is
Point sent as inverse value.
False = 0
37
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Basic
Common Data BCR Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC Address for indication.
Default:0
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
38
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Basic
Common Data MV Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC Address for indication.
Default:0
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 2 = 2 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: True = 1
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
39
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Basic
Common Data CMV Common data class according to IEC
Class 61850.
Addresses
Indication Address 0...16777215 IEC Address for indication.
Default:0
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 2 = 2 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
40
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Default: True = 1
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send As Measurand Send with normalized value = Specifies the type of the indication signal
As Value Type 0 value. Long timestamp format cannot be
used with a scaled value.
Send with scaled value = 1
3.4.5.10. WYE
Basic
Common Data WYE Common data class according to IEC
Class 61850.
Addresses
Neutral Address 0...16777215 IEC address for neutral.
0 = Not in use
41
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
0 = Not in use
Phase B Address 0...16777215 IEC address for phase B.
0 = Not in use
Phase C Address 0...16777215 IEC address for phase C.
0 = Not in use
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 2 = 2 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: True = 1
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 1000 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send As Measurand Send with normalized value = Specifies the type of the indication signal
As Value Type 0 value. Long timestamp format cannot be
used with a scaled value.
Send with scaled value = 1
42
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Default:
Basic
Common Data DEL Common data class according to IEC
Class 61850.
Phase AB Address 0...16777215 IEC address for phase AB.
0 = Not in use
Phase BC Address 0...16777215 IEC address for phase BC.
0 = Not in use
Phase CA Address 0...16777215 IEC address for phase CA.
0 = Not in use
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 2 = 2 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: True = 1
43
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 1000 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send As Measurand Send with normalized value = Specifies the type of the indication signal
As Value Type 0 value. Long timestamp format cannot be
used with a scaled value.
Send with scaled value = 1
Information in the table below applies also to the Internal SPC data object.
Table 3.4.5.12-1 Configurable SPC properties for OPC client
Property/ Para- Value or Value range/ Default Description
meter
Basic
Common Data SPC Common data class according to IEC
Class 61850.
Addresses
Command Address 0...16777215 IEC address for command.
Default: 0
Indication Address 0...16777215 IEC address for indication.
Default: 0
44
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Receive As Inverse True = 1 Specifies if a value of indication signal is
Value sent as inverse value.
False = 0
Send as Double True = 1 Specifies if a value of indication signal is
Point Value sent as double point.
False = 0
Send As Inverse True Specifies the format of timestamp if one
Value is used: none, short or long. Long time tag
False format cannot be used with a scaled value.
Time Tag Handling Do not Send Time Tag = 0
45
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Basic
Common Data DPC Common data class according to IEC
Class 61850.
Addresses
Command Address 0...16777215 IEC address for command.
Indication Address 0...16777215 IEC address for indication.
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Direct Operate True = 1 If the value of this attribute is True, then
no select is required.
False = 0
Receive As Inverse True = 1 Specifies if the received open / close
Value commands are handled inversely.
False = 0
Send as Inverse True = 1 Specifies if a value of indication signal is
Value sent as inverse value.
False = 0
46
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Basic
Common Data INC Common data class according to IEC
Class 61850
Addresses
Command Address 0...16777215 IEC address for command.
Default: 0
Indication Address 0...16777215 IEC address for indication.
Default: 0
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
Interrogation Group 1...16 (general) or 1...4 (coun- Interrogation group. 1 - 16 general or 1 -
ters) 4 counter interrogation.
Over Write True = 1 Defines whether a new indication value
overwrites an older one in the queue.
False = 0
Default: False = 0
47
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send Indication As Send with normalized value = Send value of indication signal as normal-
Value Type 0 ized or scaled. Long timestamp format
cannot be used with a scaled value.
Send with scaled value = 1
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Basic
Common Data BSC Common data class according to IEC
Class 61850.
Addresses
Command Address 0...16777215 IEC address for command.
Position Address 0...16777215 IEC address for position.
Common
Class Class 1 = 1 Class of ASDU. Data sent from the slave
to the master can be assigned to two
Class 2 = 2 classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
Default: Class 1 = 1 class 2.
48
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send Indication As Send with normalized value = Specifies if the value of indication signal
Value Type 0 is sent as normalized or scaled. Long
timestamp format cannot be used with a
Send with scaled value = 1 scaled value.
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
Basic
Common Data ISC Common data class according to IEC
Class 61850.
Addresses
Command Address 0...16777215 IEC address for command.
49
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Default: False = 0
Priority 0...3 Priority of ASDU. This property defines
how the ASDU sent is placed in the class
End of queue = 0 1 and class 2 queues.
Middle = 1, 2
Beginning of queue = 3
Update Rate 0...60000 Maximum update rate of indication
changes between OPC server and client
Default: 0 in milliseconds. 0 means that server sends
all the changes to the client.
Data Class Spe-
cific
Send Indication As Send with normalized value = Specifies if the value of indication signal
Value Type 0 is sent as normalized or scaled. Long
timestamp format cannot be used with a
Send with scaled value = 1 scaled value.
Time Tag Handling Do not Send Time Tag = 0 Specifies the format of timestamp if one
is used: none, short or long. Long time tag
Send Short Format Time Tag format cannot be used with a scaled value.
=1
50
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Basic
Common Data APC Common data class according to IEC
Class 61850.
Addresses
Command Address 0...16777215 IEC address for command.
51
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
4. Operation
After this, you can, for example, monitor and control the condition of connections in
network. This is done by using the Online diagnostics function in Communication
Engineering Tool (CET).
IEC101_Slave_OPC_Client_Online_diagnostics.jpg
52
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Event_Log101.jpg
You can also take a channel into use or out of use as described in this section.
53
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
IEC101_Channel _Online_Diagnostics.jpg
In the Diagnostic counters field, you can monitor the channel activity. The available
attributes can be seen in Figure 4.4-1. To reset Diagnostic counters, click Reset counters.
You can take an IEC101 Channel into use by marking the In use check box. If you
unmark the check box, the channel is taken out of use. To manually update diagnostic
counters, click Refresh.
In the Status information field, you can monitor the device status.
54
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
The Diagnostic counters field provides information on device activity. To reset diagnostic
counters, click Reset counters.
You can take an IEC101 Device into use by marking the In use check box. If you unmark
the check box, the device is taken out of use. To manually update diagnostic counters,
click Refresh.
IEC101_Diagnostic_AE_Client.jpg
Detailed information about field values (ASDU types, qualifier values etc.) can be found
in the IEC 60870-5-101 standard documentation.
55
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
5. Technical reference
The relationship between the IEC 61850 data modeling and IEC101 OPC Client is
described in this section.
For each data class, there is a table giving a detailed description about the relation between
the IEC101 data and IEC 61850 data object attributes and services. The tables also
describe how the data is presented on the OPC Server name space.
Name Type Value/Value range Mandat- Protocol informa- OPC data types
ory/Optional tion element
CP56Time2a
d Description Text O VT_BSTR
56
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
off (1)
on (2)
bad-state (3)
q Quality M BL, SB, NT, IV VT_I4
t TimeStamp M CP24Time2a VT_DATE
CP56Time2a
d Description Text O VT_BSTR
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
57
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
forward
backward
phsA BOOLEAN O SPI VT_BOOL
dirPhsA ENUMERATED unknown O VT_I4
forward
backward
phsB BOOLEAN O SPI VT_BOOL
dirPhsB ENUMERATED unknown O VT_I4
forward
backward
phsC BOOLEAN O SPI VT_BOOL
dirPhsC ENUMERATED unknown O VT_I4
forward
backward
neut BOOLEAN O SPI VT_BOOL
dirNeut ENUMERATED unknown O VT_I4
forward
backward
q Quality M EI, BL, SB, NT, IV
t TimeStamp M CP24Time2a, VT_DATE
CP56Time2a
d Description Text O VT_BSTR
58
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
CP56Time2a
d Description Text O VT_BSTR
Name Type Value/ Value Mandat- Protection inform- OPC data types
range ory/Optional ation element
<none> | Time of
occurence
hhLim REAL O VT_R4
hLim REAL O VT_R4
lLim REAL O VT_R4
llLim REAL O VT_R4
min REAL O VT_R4
max REAL O VT_R4
unit SiUnit O Config VT I4
d Description Text O VT_BSTR
CMV is configured in the same way as MV. The only difference is that instead of a
‘mag’ item, there is a ‘cVal’ node containing a ‘mag’ item.
59
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
5.2.10. WYE
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
60
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
off (1)
on (2)
bad-state (3)
q Quality M BL, SB, NT, IV VT_I4
t TimeStamp M CP24TIME2A VT_DATE
ctlCan BOOLEAN FALSE | TRUE O SCO VT_BOOL
stSeld BOOLEAN FALSE | TRUE O SPI VT_BOOL
d Description Text O VT_BSTR
61
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
lower (1)
higher (2)
reserved (3)
valWTr ValWithTrans M VTI VT_I4
q Quality M BL, SB, NT, IV VT_I4
t TimeStamp M CP24Time2a VT_DATE
d Description Text O VT_BSTR
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
62
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Name Type Value/ Value Mandat- Protocol informa- OPC data types
range ory/Optional tion element
5.3.1. Introduction
The following status codes are defined for the IEC 60870-5-101 slave protocol. Some
typical reasons for some of the status codes are also given.
63
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
64
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
5.4. Attributes
In addition to item tags for process data (indications and commands), the OPC servers
and clients also provide some item tags for controlling the devices and retrieving status
information from them.These item tags are called attributes.
There are three categories of attributes: IEC101 Slave OPC Client attributes, IEC101
Channel attributes and IEC101 Device attributes. These attributes are described in the
subsections below.
Protocol Stack Ver- Value: Version information The version information of the Protocol
sion Stack.
Basic
In use 0 = Not in use, the channel The state of the channel - whether it is in
communication is stopped. use or not. When a channel is not in use,
no data can be transmitted on it, and no
1 = In use. data is received from it. The channel
attributes can be read as usual. Generally,
a channel must be taken out of use by
setting this attribute to 0 before the chan-
nel attributes can be written.
65
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Clear To Send 0 = Passive signal Indicates the state of the Clear To Send
(CTS) (CTS) signal.
1 = Active signal
Data Carrier Detect 0 = Passive signal Indicates the state of Data Carrier Detect
(DCD) (DCD) signal.
1 = Active signal
Diagnostic Coun-
ters
Transmitted Mes- The number of transmitted data messages.
sages
Failed Transmis- The number of failed transmissions.
sions
Transmitted Com- The number of transmitted commands.
mands
Transmitted Replies The number of transmitted replies.
Received Messages The number of received data messages.
Parity Errors The number of times a parity error has
occurred.
Overrun Errors The number of times an overrun error has
occurred.
Check Sum Errors The number of times a redundancy error
has occurred.
Framing Errors The number of times a framing error has
occurred.
Buffer Overflow The number of times there as been a buf-
Errors fer overflow.
66
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
67
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
68
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Appendix 1
Not supported
Supported
Supported, may need additional configuring
Interoperability
This companion standard presents sets of parameters and alternatives from which subsets
have to be selected to implement particular telecontrol systems. Certain parameter values,
such as the number of octets in the common address of ASDUs represent mutually
exclusive alternatives. This means that only one value of the defined parameters is
admitted per system. Other parameters, such as the listed set of different process
information in command and in monitor direction allow the specification of the complete
set or subsets, as appropriate for the applications. This clause summarizes the parameters
of the previous clauses to facilitate a suitable selection for a specific application. If a
system is composed of equipment stemming from different manufacturers, it is necessary
that all the partners agree on the selected parameters.
69
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Frame format FT 1.2, single character 1 and the fixed time-out interval are used exclus-
ively in this companion standard.
Application layer
70
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Mode 1 (The least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is
used exclusively in this companion standard
71
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
72
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Remote initialization
73
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
Clock synchronization
No additional definition
Short pulse duration (duration determined by a system parameter in the outstation
Long pulse duration (duration determined by a system parameter in the outstation
Persistent output
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
74
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
75
76
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
Index
A
adding
channel object ................................................................................................ 16
data object ..................................................................................................... 17
device object .................................................................................................. 17
OPC client ...................................................................................................... 16
Analogue set point (APC)
IEC 61850 data modeling ................................................................................ 63
properties ....................................................................................................... 51
attributes
channel .......................................................................................................... 65
client .............................................................................................................. 65
device ............................................................................................................ 66
B
Balanced channel
properties ....................................................................................................... 21
Binary controlled step position information (BSC)
IEC 61850 data modeling ................................................................................ 62
properties ....................................................................................................... 48
Binary counter reading (BCR)
IEC 61850 data modeling ................................................................................ 59
properties ....................................................................................................... 38
C
channel
attributes ........................................................................................................ 65
diagnostics ..................................................................................................... 53
channel object
adding ........................................................................................................... 16
client
attributes ........................................................................................................ 65
Complex measured value (CMV)
IEC 61850 data modeling ................................................................................ 59
properties ....................................................................................................... 40
configuring
data object ..................................................................................................... 31
object ............................................................................................................. 19
Controllable double point (DPC)
IEC 61850 data modeling ................................................................................ 61
properties ....................................................................................................... 46
Controllable integer status (INC)
IEC 61850 data modeling ................................................................................ 62
77
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
properties ....................................................................................................... 47
Controllable single point (SPC)
IEC 61850 data modeling ................................................................................ 61
properties ....................................................................................................... 44
D
data object
adding ........................................................................................................... 17
configuring ..................................................................................................... 31
Delta (DEL)
IEC 61850 data modeling ............................................................................... 60
properties ....................................................................................................... 43
device
attributes ........................................................................................................ 66
diagnostics ..................................................................................................... 54
device object
adding ........................................................................................................... 17
diagnostics
channel .......................................................................................................... 53
device ............................................................................................................ 54
OPC client ...................................................................................................... 52
signal ............................................................................................................. 55
Directional protection activation information (ACD)
IEC 61850 data modeling ................................................................................ 58
properties ....................................................................................................... 36
Double point status (DPS)
IEC61860 data modeling ................................................................................. 57
properties ....................................................................................................... 33
F
Filter File
Active Filter .................................................................................................... 18
I
IEC 61850 data modeling
Analogue set point (APC) ................................................................................ 63
Binary counter reading (BCR) .......................................................................... 59
Complex measured value (CMV) ..................................................................... 59
Controllable double point (DPC) ...................................................................... 61
Controllable integer status (INC) ...................................................................... 62
Controllable single point (SPC) ........................................................................ 61
Delta (DEL) .................................................................................................... 60
Directional protection activation information (ACD) ............................................ 58
Double point status (DPS) ............................................................................... 57
Integer controlled step position information (ISC) .............................................. 62
Integer status (INS) ......................................................................................... 57
Measured value (MV) ...................................................................................... 59
78
1MRS755382 COM600 Station Automation Series IEC 60870-5-101
Slave (OPC) 3.2
User's Guide
M
Measured value (MV)
IEC 61850 data modeling ................................................................................ 59
properties ....................................................................................................... 39
O
object
configuring ..................................................................................................... 19
OPC client
adding ........................................................................................................... 16
diagnostics ..................................................................................................... 52
features ......................................................................................................... 12
properties ....................................................................................................... 20
P
properties
Analogue set point (APC) ................................................................................ 51
Balanced channel .......................................................................................... 21
Binary controlled step position information (BSC) .............................................. 48
Binary counter reading (BCR) .......................................................................... 38
Complex measured value (CMV) ..................................................................... 40
Controllable double point (DPC) ...................................................................... 46
Controllable integer status (INC) ...................................................................... 47
Controllable single point (SPC) ........................................................................ 44
Delta (DEL) .................................................................................................... 43
Directional protection activation information (ACD) ............................................ 36
Double point status (DPS) ............................................................................... 33
IEC101 device ................................................................................................ 26
Integer controlled step position information (ISC) .............................................. 49
Integer status (INS) ......................................................................................... 34
Measured value (MV) ...................................................................................... 39
OPC client ...................................................................................................... 20
Protection activation (ACT) .............................................................................. 35
Single point status (SPS) ................................................................................ 31
Unbalanced channel ....................................................................................... 23
79
IEC 60870-5-101 COM600 Station Automation Series 1MRS755382
WYE .............................................................................................................. 41
Protection activation information (ACT)
IEC 61850 data modeling ................................................................................ 57
properties ....................................................................................................... 35
S
signal
diagnostics ..................................................................................................... 55
Single point status (SPS)
IEC 61850 data modeling ................................................................................ 56
properties ....................................................................................................... 31
U
Unbalanced channel
properties ....................................................................................................... 23
W
WYE
IEC 61850 data modeling ................................................................................ 60
properties ....................................................................................................... 41
80
1MRS755382 E/17.06.2008