Professional Documents
Culture Documents
Manufacturer:
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Table of contents
Table of contents
Section 1 Introduction.....................................................................11
Introduction to the application manual..............................................11
About the complete set of manuals for an IED............................11
About the application manual......................................................12
Intended audience.......................................................................12
Related documents......................................................................12
Revision notes.............................................................................13
Section 3 Requirements.................................................................35
Current transformer requirements....................................................35
Current transformer classification................................................35
Conditions....................................................................................36
Fault current................................................................................37
Application..............................................................................69
Setting guidelines...................................................................70
Setting parameters.................................................................70
Test mode functionality................................................................71
Application..............................................................................71
Setting guidelines...................................................................71
Setting parameters.................................................................71
IED identifiers..............................................................................71
Application..............................................................................71
Setting parameters.................................................................72
Rated system frequency (RFR)...................................................72
Application..............................................................................72
Setting guidelines...................................................................73
Setting parameters.................................................................73
Signal matrix for binary inputs (SMBI).........................................73
Application..............................................................................73
Setting guidelines...................................................................73
Setting parameters.................................................................73
Signal matrix for binary outputs (SMBO).....................................73
Application..............................................................................73
Setting guidelines...................................................................74
Setting parameters.................................................................74
Signal matrix for mA inputs (SMMI).............................................74
Application..............................................................................74
Setting guidelines...................................................................74
Setting parameters.................................................................74
Signal matrix for analog inputs (SMAI)........................................74
Application..............................................................................74
Setting guidelines...................................................................74
Setting parameters.................................................................75
Summation block 3 phase (SUM3Ph).........................................77
Application..............................................................................77
Setting guidelines...................................................................77
Setting parameters.................................................................78
Differential protection........................................................................78
High impedance differential protection (PDIF, 87).......................78
Application..............................................................................78
Setting guidelines...................................................................83
Connection examples.............................................................87
Setting parameters.................................................................90
Current protection.............................................................................90
Instantaneous phase overcurrent protection (PIOC, 50).............90
Application..............................................................................91
Setting guidelines...................................................................91
Setting parameters.................................................................95
Four step phase overcurrent protection (POCM, 51_67).............95
Application..............................................................................95
Setting guidelines...................................................................97
Setting parameters...............................................................105
Instantaneous residual overcurrent protection (PIOC, 50N)......111
Application............................................................................111
Setting guidelines.................................................................111
Setting parameters...............................................................113
Four step residual overcurrent protection (PEFM, 51N/
67N)...........................................................................................114
Application............................................................................114
Setting guidelines.................................................................115
Setting parameters...............................................................125
Thermal overload protection, one time constant (PTTR,
26).............................................................................................132
Application............................................................................132
Setting guideline...................................................................133
Setting parameters...............................................................134
Thermal overload protection, two time constants (PTTR,
49).............................................................................................134
Application............................................................................135
Setting guideline...................................................................136
Setting parameters...............................................................138
Breaker failure protection (RBRF, 50BF)...................................139
Application............................................................................139
Setting guidelines.................................................................140
Setting parameters...............................................................142
Stub protection (PTOC, 50STB)................................................143
Application............................................................................144
Setting guidelines.................................................................144
Setting parameters...............................................................145
Pole discordance protection (RPLD, 52PD)..............................145
Application............................................................................146
Setting guidelines.................................................................146
Setting parameters...............................................................147
Voltage protection...........................................................................147
Two step undervoltage protection (PUVM, 27)..........................147
Application............................................................................148
Setting guidelines.................................................................148
Setting parameters...............................................................151
Two step overvoltage protection (POVM, 59)............................154
Application............................................................................154
Setting guidelines.................................................................155
Setting parameters...............................................................157
Two step residual overvoltage protection (POVM, 59N)...........160
Application............................................................................160
Setting guidelines.................................................................160
Setting parameters...............................................................165
Frequency protection......................................................................167
Underfrequency protection (PTUF, 81).....................................167
Application............................................................................167
Setting guidelines.................................................................168
Setting parameters...............................................................169
Overfrequency protection (PTOF, 81).......................................169
Application............................................................................170
Setting guidelines.................................................................170
Setting parameters...............................................................171
Rate-of-change frequency protection (PFRC, 81).....................171
Application............................................................................171
Setting guidelines.................................................................172
Setting parameters...............................................................172
Multipurpose protection..................................................................173
General current and voltage protection (GAPC)........................173
Application............................................................................173
Setting guidelines.................................................................178
Setting parameters...............................................................187
Secondary system supervision.......................................................197
Current circuit supervision (RDIF).............................................197
Application............................................................................197
Setting guidelines.................................................................198
Setting parameters...............................................................198
Fuse failure supervision (RFUF)................................................198
Application............................................................................198
Setting guidelines.................................................................200
Setting parameters...............................................................202
Control............................................................................................203
Synchrocheck and energizing check (RSYN, 25)......................203
Application............................................................................203
Application examples...........................................................207
Setting guidelines ................................................................214
Setting parameters...............................................................218
Autorecloser (RREC, 79)...........................................................219
Application............................................................................220
Setting guidelines.................................................................231
Setting parameters...............................................................240
Setting guidelines.................................................................284
Setting parameters...............................................................293
Event counter (GGIO)................................................................307
Application............................................................................307
Setting guidelines.................................................................307
Setting parameters...............................................................307
Event function (EV)....................................................................308
Application............................................................................308
Setting guidelines.................................................................308
Setting parameters...............................................................309
Fault locator (RFLO)..................................................................311
Application............................................................................311
Setting guidelines.................................................................312
Setting parameters...............................................................313
Measured value expander block................................................314
Application............................................................................314
Setting guidelines.................................................................314
Disturbance report (RDRE).......................................................315
Application............................................................................315
Setting guidelines.................................................................316
Setting parameters...............................................................320
Event list (RDRE)......................................................................335
Application............................................................................335
Setting guidelines.................................................................335
Indications (RDRE)....................................................................335
Application............................................................................335
Setting guidelines.................................................................336
Event recorder (RDRE).............................................................336
Application............................................................................336
Setting guidelines.................................................................337
Trip value recorder (RDRE).......................................................337
Application............................................................................337
Setting guidelines.................................................................337
Disturbance recorder (RDRE)...................................................338
Application............................................................................338
Setting guidelines.................................................................338
Metering..........................................................................................339
Pulse counter logic (GGIO).......................................................339
Application............................................................................339
Setting guidelines.................................................................339
Setting parameters...............................................................340
Section 7 Configuration................................................................371
Introduction.....................................................................................371
Description of configuration REC 670............................................372
Introduction................................................................................372
Description of configuration A..............................................372
Description of configuration B..............................................375
Section 9 Glossary.......................................................................383
Glossary.........................................................................................383
Section 1 Introduction
en06000097.vsd
The Operator’s Manual (OM) contains instructions on how to operate the protection
IED during normal service once it has been commissioned. The operator’s manual
can be used to find out how to handle disturbances or how to view calculated and
measured network data in order to determine the cause of a fault.
The IED 670 engineering guide (EG) contains instructions on how to engineer the
IED 670 products. The manual guides to use the different tool components for IED
670 engineering. It also guides how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. The third
part is an introduction about the diagnostic tool components available for IED 670
products and the PCM 600 tool.
• The chapter “Engineering of the IED” describes the overall procedure regarding
the engineering process of an IED.
• The chapter “Requirements“ describes current and voltage transformer
requirements.
• The chapter “IED application” describes the use of the included software
functions in the IED. The chapter discuss application possibilities and gives
guidelines for calculating settings for a particular application.
• The chapter “Station communication“ describes the communication possibilities
in a SA-system.
• The chapter “Remote communication“ describes the remote end data
communication possibilities through binary signal transferring.
• The chapter “Configuration” describes the preconfiguration of the IED and its
complements.
• The chapter “Setting examples” describes different settings.
• The chapter “Glossary” is a list of terms, acronyms and abbreviations used in
ABB technical documentation.
Requirements
The system engineer/technical responsible must have a good knowledge about
protection systems, protection equipment, protection functions and the configured
functional logics in the protection.
2.1 Introduction
The IED 670 includes all the necessary functions to build any application.
The functions are available in a software library and there is a basic library of
functions always included in any supply that are sufficient for most applications.
For special applications there is a number of software options which must be ordered
separately.
The function library with available basic functions and options are shown in figure
below.
The cases can be mounted in 19” rack, flushed or wall mounted as preferred.
The engineering is done with use of the PCM 600 engineering toolbox.
Install the PCM 600 toolbox with the connectivity package for IED 670 series and
open it from the Start menu or from the short-cut on the desktop.
The Application configuration tool is used to set up the included hardware structure
and the software functions.
The hardware is set-up under the Edit/Function selector menu where for each location
the physical analog and digital IO is defined. The figure 2 shows an example from
this set-up.
The hardware also includes e.g. the configurable LEDs and the remote end line data
communication module LDCM. These are also important parts of the physical
interface and will be shown with the signal matrix tool.
Figure 3 shows an example for RET 670 of these function blocks configured for use
in the signal matrix tool.
en05000530.vsd
These function blocks will, as the graphical configuration has been compiled, show-
up in the signal matrix tool when this has been opened. The use of the Signal Matrix
tool is described below.
The fifteen configurable LEDs can be connected to virtual inputs or virtual outputs
only with the signal matrix tool This means that signals foreseen to be used on an
LED such as group signals must be connected through an OR function block to a
virtual output for use by the LED. Naturally the same signal can be connected to a
physical output e.g. for SCADA signaling. The six first LEDs are red and the
remaining nine are yellow.
This function block is vital for the IED 670 functionality. Interfaces both to local
analog inputs as well as remote analog inputs through the LDCM communication
module are connected through this function block. The signals from this block is
connected to the different applications. Some important comments for the
understanding of the function:
• The function block can be used for voltage inputs or current inputs. Which of the
two is defined as a setting parameter (TYPE input) on the function block.
• The output AI3P is a general output for all of the phases. It is normally connected
to the functions. The only difference is the Disturbance recorder block where the
individual channels are connected to individual channels. The four individual
outputs are the three phases and the neutral where the neutral is residually
summated from the phases if no physical connection is made to the fourth input
with the signal matrix tool. If the physical connection is made the physical input
is used instead. When e.g. a neutral overcurrent protection is connected to the
function block output AI3P it will measure the fourth neutral channel. For each
application it can then be decided if this is the residual sum or e.g. if a neutral
current transformer is connected there.
• The physical inputs can be connected phase-phase instead of phase to neutral.
This is acceptable and the setting of the pre-processing block (under
GeneralSettings/Powersystem/3PhAnalogueGrp) ConTypeGrpn must then be
set to Phase to phase. The pre-processing block will then use the physical values
as phase to phase values and calculate the phase to neutral values.
• The name of the pre-processing block and the names of the four inputs are the
names shown on the signal matrix tool and the function block name should be
selected for simple understanding what the input means.
en05000531.vsd
The analog pre-processing blocks shall also be configured to have the correct
frequency tracking. This is included in the SMAI function blocks. The first block in
each task time group is provided with a possibility to keep track of the frequency for
adjustment of the fouriers filter to the correct frequency. In principle the first function
block in the series should have the DFT ref setting for the group set to preferable L1
phase voltage input, typical input 7 which means setting of DFTRefGrp1 to be set to
Grp7AdDFTRef. The L1 voltage frequency will then be the frequency reference. If
SMAI block for other task times (e.g.13-24 resp 25-36) also are included they can be
given the same reference by connecting the output SYNCOUT to input DFTSPSC
on the function blocks SMAI 13 resp 25. These function blocks must then have setting
DFTRefGrp13=ExternalDFTRef.
The function block sending the signal must have the setting of the DFT reference
output set to DFTRefExtOut1= Grp7AdDFTRef.
There are four different software alternatives with which the IED can be managed.
The intention is that these configurations shall suit most applications with minor or
no changes.
The Multi breaker arrangement includes One- and a half, Double breaker and Ring
breaker arrangements.
The number of IO must be ordered to the application where more IO is foreseen for
the Single phase tripping arrangements respectively the Multi-breaker arrangement.
The basic ordering includes one Binary input module (16 inputs) and one Binary
Output module (24 outputs), sufficient for the default configured IO to trip and close
circuit breaker and with possible communication interface.
Optional functions and optional IO ordered will not be configured at delivery. As the
standard delivered hardware only includes one binary input and one binary output
module only the key functions such as tripping are connected to the outputs in the
signal matrix tool.
The required total IO must be calculated and specified at ordering and the IO adapted
with help of the Signal Matrix Tool (SMT).
The diagrams show an example of how to connect the primary apparatuses to the IED
when also the control functionality is required. It is intended as a reference for the
alternative applications. As there normally is two sub-systems and not always all
functions in both there is a need for exchange of data between the sub-systems. The
configurations are prepared to cover for the most common applications but not all
possibilities.
The Application configuration tool CAP 531, which is part of the PCM600
engineering platform, will further to the four arrangements above include also
alternatives for each of them with all of the software options configured. These can
then be used directly or as assistance where only minor adaptation will be necessary.
The configurations are as far as found necessary provided with application comments
to explain why the signals have been connected in the special way. This is of course
for the special application features created not standard functionality.
When the IED has been received, or before from the configuration templates, there
are two possibilities to adapt to the specific needs.
The signal matrix tool uses information from the compiled application configuration
performed with CAP 531. At saving the information will be sent to the SMT tool.
Open the Signal Matrix Tool by a right click on the IED in the Plant structure of PCM
600.
The physical IO will be shown up on the horizontal axis and the virtual IO on the
vertical IO. The user has then full freedom for each application to connect the virtual
signal from the graphical configuration to analog or digital IO. The physical IO is set
up under Application configuration tool in menu Edit/Function selector.
In this menu the included IO boards must be edited and must match the ordered
hardware. It is commonly required that this menu is edited, the configuration
compiled and downloaded and then the PST tool can be used to connect the physical
inputs with the virtual IO.
One virtual signal on the vertical axis can be connected to several physical binary IO.
One analog input may also be connected to several preprocessing elements for the
analog signals.
Figure 5: Example (RET 670) from signal matrix tool tabs for binary input defines the connection between
the physical and virtual IO.
This gives the user flexibility to connect any signal he needs to an IO without doing
any changes in the graphical configuration. To allow full flexibility a number of
logically prepared signals has also been generated.
Interface elements to make signals available in the signal matrix tool can also be
added so that in future applications the same configuration can be used and the
adaptation made with the signal matrix tool.
en05000532.vsd
It is advisable to start from one of the four basic configurations and delete and add
function blocks and connections in the selected configuration, closest to the
application. Refer to the “Help in CAP 531” for more information. For the basic
configuration available in the ordered IED and the alternative configurations available
as templates refer to the “configuration section” later in this manual.
The PCM 600 toolbox with the configuration tool CAP 531 shall be installed prior
to the below sequence.
Procedure
1. Open the configuration program CAP 531 under the PCM 600 platform by
opening Start/Programs/ABB/PCM 600.
The below view will show up.
2. Start the configuration tool under the menu or by clicking the wrench symbol.
In the configuration tool open the template to start from under Edit. Note that
the IED has default configuration as ordered, open the correct or a more suitable
alternative template.
Default password is ”abb”
Information how to log on as an administrators is available in “Operator's
manual”. Please refer to section "Related documents".
The template will be installed and you can see the worksheets used in the
template.
3. Open the worksheets to be adjusted. Check in the configuration diagrams and
verify what you need to change e.g. logic added or IO signals adjusted.
Following guidelines can be given.
New function blocks are added by selecting the function from the function
library. It is also possible to copy an existing by marking the existing and take
Ctrl+C.
The following view is shown.
The new function block is selected and added to the worksheet. Note that all
inputs needs to be connected either with a signal or with a True (On) or False
(Off) signal.
4. Click the input and take key “v” or click the “var” symbol to add a variable on
an input or output.
5. Type the name you want to use for the signal. Type True or False for fixed On
or Off.
6. If the input shall be connected to the output on a function close by, take the line
tool and connect the two.
All variables will be available and with the same variable name you connect
inputs and outputs. An output can be connected to several inputs, e.g. on IO
boards, on Trip function block, on an OR, AND or TIMER function block etc.
Inputs cannot be connected to several places without an OR gate.
When you select your function blocks e.g. logic elements to build a logic you
must, for high speed circuits, keep track of the processing order. The processing
number is shown on each function block. A sequence should have raising task
numbers not to loose one processor loop, e.g. 1, 3, 8 or even 100 ms.
You can copy and paste variables and function blocks/logic elements. You will
at pasting of e.g. an OR gate be requested to select the new one with the correct
sequence number.
7. When you are satisfied with the logic you have created, save, close and click on
the IED symbol and Compile the configuration.
You will then get warnings and errors for all mistakes. All errors must be
corrected, warnings can be checked to see if they are acceptable, mostly due to
connection of function blocks with different cycle times.
8. Click on the Errors and Warnings in the Error list to directly open the worksheet
where the problem is found. Correct all mistakes, save and compile again.
9. When no errors occur, download the configuration to the IED.
You must have the correct IP address and you must have either a straight
Ethernet cable with a HUB in between or a crossed Ethernet cable when you
are directly connected PC-IED.
The IED are set using the PCM 600 setting tool. The IED is delivered with a default
setting where many parameters are selected to be default suitable. However of course
all important settings such as currents, impedances and times always need to be set.
To simplify the use the tool has a normal user view and an advanced user view. The
normal user does not need to set parameters defined as parameters for the advanced
user. Switching is simply done from the symbols on the toolbar.
Setting can be done locally from the HMI or from the engineering tool. The settings
are always under password control and the user must log-in with an authority level
to match the settings to be changed.
The IED has the settings available in six setting groups and switching between these
setting groups can be performed either from physical IO or from a SA system or the
SCADA system over the communication link. The special function block
ACTGROUP is used for this purpose and this switching is not password controlled.
The function block includes a definition how many setting groups are used to prevent
switching to a not set group.
The local setting can be blocked after commissioning by activating a digital input or
from SA system as defined in the configuration. Default there is a software switch
which can be set to block the setting from the HMI.
• Control
• Advanced Control
• Administrator
The higher level will always include the rights of the lower level. Without logging in
giving the correct authority the user can only view the values.
The parameters are selected to belong to some of the authority levels. The higher
levels are always authorized to set lower level parameters.
The default administrator password is “abb” resp “ABB”. This shall be changed by
the administrator responsible for setting up the user names, the authority levels and
the passwords for the different users.
The IED does not have any password handling until users are set-up in the IED. This
is done from the front Local HMI to prevent access by mistake or purposely in from
a network.
Disconnectable terminal
or key-switch
+
ChangeLock
en05000754.vsd
Logic blocks of each type are available in different task times and task orders. This
allows the user to define own logic with all the logic elements and function in the
correct sequence. At creating the logic the elements sequence number and task times
should always be checked and logic components with the suitable values selected.
en05000537.vsd
Figure 11: It is important to ensure that the task numbers are in sequence to
have a fast processing of logic.
The advanced logic capabilities and the flexible functions give the user a possibility
to manage any type of application.
Examples are:
Line distance protection where the busbar is provided with three phase voltage
transformers and the lines with only single-phase sets for Synchrocheck reference.
Bus voltage protection e.g. Over- and Undervoltage, Over- and Underfrequency
protection functions in the bay.
Voltage reference for metering functions - where three phase voltage transformers
does not exist on the object.
A voltage selection can be created in IED 670 with a user defined logic where
positions of disconnectors (and breakers) are used to create the required voltage
selection.
An example is shown in figure 12 where the voltage transformers for a double bus
system are connected to the line protection function, which may be line distance relays
or voltage or frequency relays.
Supervision of the fuse/MCB failures can be fed through the same logic and connected
to e.g. block operation of undervoltage functions.
Its is also a possible to block functions when both disconnectors are open.
Figure 12: The voltage selection logic for busbar voltage transformers in a double bus arrangement.
The negative sequence part will detect one and two phase fuse failures and the positive
sequence part will detect three phase fuse failures. Due to the combination it can
detect failures of fuses as well as MCB’s.
The logic can include status supervision before the fault was tripped to ensure that
the sequence is only closing apparatuses already closed before the fault, information
about the fault to ensure it was a transformer fault, check that the disconnector is open
before the breaker/s is/are closed and verification that the new status has been reached
before next sequence is started.
Due to space restrictions examples cannot be shown here but contact your local ABB
for support on advanced special logic.
An advanced alternative exists for generating station where the unit transformer
supplies will need to synchronize at switching and this synchronizing is done on a
decaying bus voltage on voltage level as well as frequency level depending on the
available synchronous and asynchronous machines maintaining the bus voltage.
It shall be noticed that the exchange of information between the two transformers can
be with peer- to-peer communication across IEC61850-8-1 or over LON bus as
alternative to a hardwire connection. With the fast Goose IO transfer times are in the
level 4 ms which is sufficient also for this type of logic.
Due to space restrictions examples cannot be shown here but contact your local ABB
for support on advanced special logic.
The testing requirement is minimized with the use of an advanced internal self
supervision. This in, combination with the numerical design and the use of measured
values in the substation control, means that the need of scheduled maintenance testing
does not exist. However, during commissioning, changes in the system with setting
or configuration changes etc. there is a need of simple access to test the IED 670.
The test interface is preferable done with test switches from the COMBITEST test
system. The COMBITEST test switches and test handles provides a high amount of
IO allowing test of integrated IEDs such as the IED 670 family.
Test switch contacts should be provided on selected inputs and outputs to allow
verification of setting values such as current, voltage, impedance and set timers. Due
to the high amount of functionality some interfaces must be switched off in software.
It is then important to ensure that e.g. times to trip can be measured from other signals
with test switches. In the connection diagrams for the four configurations, the typical
location of test switch contacts is indicated. The outputs without test switches must
either be provided with a second test switch or blocked by software. This can be done
e.g. by blocking virtual outputs SMBO with “In test” condition. The “In test” is with
COMBTEST test switches RTXP24 provided by contact 29-30 (early closing)
activating a binary input and connected to the test function block.
2.11.1 How to use the IED in conjunction with PCM 600 toolbox
The below check list gives a short guideline of how to use the protection and control
IED with help of the PCM 600 toolbox. Uploading of disturbance record is not
included below but is available from PCM 600.
Procedure
6. Set the IED with use of the PCM 600 Parameter Setting Tool PST.
7. Adjust the setting to the values suitable for your application.
Remember to also do the general settings. General setting values have only one
set and are the basic parameters such as CT and VT ratios etc.
8. Download to the IED, you can download from any level in your structure but
ensure to download all parts.
setting will also decide how many setting groups are initiated in
the parameter setting menu.
9. Test the IED. Use the Debug tool in the CAP 531 configuration tool to se on-
line the status of digital signals.
This simplifies the evaluation. Note that faults need to be put on continuously
to follow a fault signal as the debug update time is on second level.
10. Check also Measurements/Functions where each function measured result can
be seen.
This shows mistakes in CT or VT settings, mistakes in setting function ON-OFF
etc. If values do not show up the most probably reason is that it is OFF, secondly
it can be incorrect configured. If the function is ON, open the CAP, not in debug
mode, and upload options from the relay.
11. Click the Red-Green Leaf and update the function block from the occurring list.
You will notice if e.g. the function has not been ordered as it will not show up
as available.
12. Save, Compile and download again.
If that does not take care of the problem, contact ABB SA-T Supportline.
Section 3 Requirements
The performance of a protection function will depend on the quality of the measured
current signal. Saturation of the current transformer (CT) will cause distortion of the
current signal and can result in a failure to operate or cause unwanted operations of
some functions. Consequently CT saturation can have an influence on both the
dependability and the security of the protection. This protection IED has been
designed to permit heavy CT saturation with maintained correct operation.
There are several different ways to specify CTs. Conventional magnetic core CTs are
usually specified and manufactured according to some international or national
standards, which specify different protection classes as well. There are many different
standards and a lot of classes but fundamentally there are three different types of CTs:
The high remanence type has no limit for the remanent flux. This CT has a magnetic
core without any airgap and a remanent flux might remain almost infinite time. In
this type of transformers the remanence can be up to around 80% of the saturation
flux. Typical examples of high remanence type CT are class P, PX, TPS, TPX
according to IEC, class P, X according to BS (old British Standard) and nongapped
class C, K according to ANSI/IEEE.
The low remanence type has a specified limit for the remanent flux. This CT is made
with a small airgap to reduce the remanence to a level that does not exceed 10% of
the saturation flux. The small airgap has only very limited influence on the other
properties of the CT. Class PR, TPY according to IEC are low remanence type CTs.
The non remanence type CT has practically negligible level of remanent flux. This
type of CT has relatively big airgaps in order to reduce the remanence to practically
zero level. In the same time, these airgaps reduce the influence of the DC-component
from the primary fault current. The airgaps will also decrease the measuring accuracy
in the non-saturated region of operation. Class TPZ according to IEC is a non
remanence type CT.
Different standards and classes specify the saturation e.m.f. in different ways but it
is possible to approximately compare values from different classes. The rated
equivalent limiting secondary e.m.f. Eal according to the IEC 60044 – 6 standard is
used to specify the CT requirements for IED 670. The requirements are also specified
according to other standards.
3.1.2 Conditions
The requirements are a result of investigations performed in our network simulator.
The current transformer models are representative for current transformers of high
remanence and low remanence type. The results may not always be valid for non
remanence type CTs (TPZ).
The performances of the protection functions have been checked in the range from
symmetrical to fully asymmetrical fault currents. Primary time constants of at least
120 ms have been considered at the tests. The current requirements below are thus
applicable both for symmetrical and asymmetrical fault currents.
The remanence in the current transformer core can cause unwanted operations or
minor additional time delays for some protection functions. As unwanted operations
are not acceptable at all maximum remanence has been considered for fault cases
critical for the security, e.g. faults in reverse direction and external faults. Because of
the almost negligible risk of additional time delays and the non-existent risk of failure
to operate the remanence have not been considered for the dependability cases. The
requirements below are therefore fully valid for all normal applications.
the network will occur when the voltage is between 40° and 90°. In addition fully
asymmetrical fault current will not exist in all phases at the same time.
When calculating the current transformer requirements, maximum fault current for
the relevant fault position should be used and therefore both fault types have to be
considered.
The conclusion is that the loop resistance, twice the resistance of the single secondary
wire, must be used in the calculation for phase-to-earth faults and the phase resistance,
the resistance of a single secondary wire, may normally be used in the calculation for
three-phase faults.
As the burden can be considerable different for three-phase faults and phase-to-earth
faults it is important to consider both cases. Even in a case where the phase-to-earth
fault current is smaller than the three-phase fault current the phase-to-earth fault can
be dimensioning for the CT depending on the higher burden.
In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case and therefore the resistance of the single secondary wire always
can be used in the calculation, for this case.
The current error of the current transformer can limit the possibility to use a very
sensitive setting of a sensitive residual overcurrent protection. If a very sensitive
setting of this function will be used it is recommended that the current transformer
should have an accuracy class which have an current error at rated primary current
that is less than ±1% (e.g. 5P). If current transformers with less accuracy are used it
is advisable to check the actual unwanted residual current during the commissioning.
The CT requirements for the different functions below are specified as a rated
equivalent limiting secondary e.m.f. Eal according to the IEC 60044-6 standard.
Requirements for CTs specified in different ways are given at the end of this section.
The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal
to the required secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = 5 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
(Equation 1)
where:
Iop The primary operate value (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing
the phase and neutral wires, must be used for faults in solidly earthed systems. The resistance
of a single secondary wire should be used for faults in high impedance earthed systems.
SR The burden of IED 670 a current input channel (VA). SR=0,25 VA/channel
The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal
to the required secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = 1, 5 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
(Equation 2)
where:
Iop The primary operate value (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing
the phase and neutral wires, must be used for faults in solidly earthed systems. The resistance
of a single secondary wire should be used for faults in high impedance earthed systems.
SR The burden of IED 670 a current input channel (VA). SR=0,25 VA/channel
The requirement according to Equation 3 and Equation 4 does not need to be fulfilled
if the high set instantaneous or definitive time stage is used. In this case Equation 2
is the only necessary requirement.
If the inverse time delayed function is the only used overcurrent protection function
the CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal
to the required secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = 20 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
(Equation 3)
where
Iop The primary current set value of the inverse time function (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance
containing the phase and neutral wires, must be used for faults in solidly earthed
systems. The resistance of a single secondary wire should be used for faults in
high impedance earthed systems.
SR The burden of IED 670 a current input channel (VA). SR=0,25 VA/channel
Independent of the value of Iop the maximum required Eal is specified according to
the following:
Isn æ S ö
E al ³ E alreq max = I k max × × ç R CT + R L + R2 ÷
I pn è Ir ø
(Equation 4)
where
Ikmax Maximum primary fundamental frequency current for close-in faults (A)
If the directional overcurrent function is used the CTs must have a rated equivalent
secondary e.m.f. Eal that is larger than or equal to the required equivalent secondary
e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = I k max × × ç R CT + R L + R2 ÷
I pn è Ir ø
(Equation 5)
where:
Ikmax Maximum primary fundamental frequency current for close-in forward and reverse faults (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing
the phase and neutral wires, must be used for faults in solidly earthed systems. The resistance
of a single secondary wire should be used for faults in high impedance earthed systems.
SR The burden of IED 670 a current input channel (VA). SR=0,25 VA/channel
All kinds of conventional magnetic core CTs are possible to use with REx 670 IEDs
if they fulfill the requirements corresponding to the above specified expressed as the
rated equivalent secondary e.m.f. Eal according to the IEC 60044-6 standard. From
different standards and available data for relaying applications it is possible to
approximately calculate a secondary e.m.f. of the CT comparable with Eal. By
comparing this with the required secondary e.m.f. Ealreq it is possible to judge if the
CT fulfills the requirements. The requirements according to some other standards are
specified below.
CTs according to these classes are specified approximately in the same way by a rated
knee-point e.m.f. Eknee (Ek for class PX, EkneeBS for class X and the limiting secondary
voltage Ual for TPS). The value of the Eknee is lower than the corresponding Eal
according to IEC 60044-6. It is not possible to give a general relation between the
Eknee and the Eal but normally the Eknee is approximately 80 % of the Eal. Therefore,
the CTs according to class PX, X and TPS must have a rated knee-point e.m.f.
Eknee that fulfills the following:
2 + j 20
ZC = = 0.0125 + j 0.125 pu = 0.126Ð84° pu
160 (Equation 7)
where:
ZbANSI The impedance (i.e. complex quantity) of the standard ANSI burden for the specific C class
(W)
UANSI The secondary terminal voltage for the specific C class (V)
The CTs according to class C must have a calculated rated equivalent limiting
secondary e.m.f. EalANSI that fulfills the following:
The performance of a protection function will depend on the quality of the measured
input signal. Transients caused by capacitive voltage transformers (CVTs) can affect
some protection functions.
The capacitive voltage transformers (CVTs) should fulfill the requirements according
to the IEC 60044–5 standard regarding ferro-resonance and transients. The ferro-
resonance requirements of the CVTs are specified in chapter 7.4 of the standard.
The transient responses for three different standard transient response classes, T1, T2
and T3 are specified in chapter 15.5 of the standard. CVTs according to all classes
can be used.
The protection IED has effective filters for these transients, which gives secure and
correct operation with CVTs.
The SNTP server to be used shall be connected to the local network, i.e. not more
than 4-5 switches/routers away from the IED. The SNTP server shall be dedicated
for its task, or at least equipped with at real-time operating system, i.e. not a PC with
SNTP server software. The SNTP server shall be stable, i.e. either synchronized from
a stable source like GPS, or local i.e. without synchronization. Using a local SNTP
server i.e. without synchronization as primary or secondary server in a redundant
configuration is not recommended.
The REC 670 IED is used for the control, protection and monitoring of different types
of bays in power networks. The IED is especially suitable for applications in
distributed control systems with high demands on reliability. The IED can be used
up to the highest voltage levels. It is suitable for the control of all apparatuses in any
type of switchgear arrangements.
A number of protection functions are available for flexibility in use for different
station types and busbar arrangements. The auto-reclose for single-, two-, and/or
three-phase reclose includes priority circuits for multi-breaker arrangements. It co-
operates with the synchrocheck function with quick or delayed reclosing. Several
breaker failure functions are included to provide a breaker failure function
independent from the protection IEDs, also for a complete one- and a half breaker
diameter.
High set instantaneous phase and earth overcurrent, 4 step directional or un-
directional delayed phase and earth overcurrent, thermal overload and two step under
and overvoltage functions are examples of the available functions allowing user to
fulfill any application requirement.
Disturbance recording and fault locator are available to allow independent post-fault
analysis after primary disturbances with a single failure in the protection system.
6 x 32 dual directional channels for intertrip and binary signals transfer is available
in the communication between selected IEDs inside the station or in a near-by station.
The advanced logic capability, where the user logic is prepared with a graphical tool,
allows special applications such as automatic opening of disconnectors in multi-
breaker arrangements, closing of breaker rings, load transfer logics etc. The graphical
configuration tool ensures simple and fast testing and commissioning.
The wide application flexibility makes this product an excellent choice for both new
installations and the refurbishment of existing installations.
4.2.1 Application
In order to get correct measurement results as well as correct protection operations
the analog input channels must be configured and properly set. It is necessary to define
a reference PhaseAngleRef for correct calculation of phase angles. For power
measuring and all directional and differential functions the directions of the input
currents must be properly defined. The measuring and protection algorithms in IED
670 are using primary system quantities and the set values are done in primary
quantities as well. Therefore it is extremely important to properly set the data about
the connected current and voltage transformers.
Example
The setting PhaseAngleRef=7 shall be used if a phase-to-earth voltage (usually the
L1 phase-to-earth voltage connected to VT channel number 7 of the analogue card)
is selected to be the phase reference.
en05000456.vsd
Example 1
Two IEDs used for protection of two objects
Line
Ip
Transformer Ip Ip
Line
Reverse Forward
Definition of direction
for directional functions
Transformer
Is Is
protection Line protection
en05000753.vsd
The figure 15 shows the most normal case where the objects have their own CTs. The
settings for CT direction shall be done according to the figure. To protect the line the
direction of the directional functions of the line protection shall be set to Forward.
This means that the protection is looking towards the line.
Example 2
Two IEDs used for protection of two objects and sharing a CT
Transformer
Line
Reverse Forward
Definition of direction
for directional functions
Transformer
protection Line protection
en05000460.vsd
This example is similar to example 1 but the transformer is feeding just one line and
the line protection uses the same CT as the transformer protection does. The CT
direction is set with different reference objects for the two IEDs though it is the same
current from the same CT that is feeding two IEDs. With these settings the directional
functions of the line protection shall be set to Forward to look towards the line.
Example 3
One IED used to protect two objects
Transformer
Line
Forward Reverse
Definition of direction
for directional
Transformer and line functions
Line protection
en05000461.vsd
In this example one IED includes both transformer and line protection and the line
protection uses the same CT as the transformer protection does. For both current input
channels the CT direction is set with the transformer as reference object. This means
that the direction Forward for the line protection is towards the transformer. To look
towards the line the direction of the directional functions of the line protection must
be set to Reverse. The direction Forward/Reverse is related to the reference object
that is the transformer in this case.
When a function is set to Reverse and shall protect an object in reverse direction it
shall be noted that some directional functions are not symmetrical regarding the reach
in forward and reverse direction. It is in first hand the reach of the directional criteria
that can differ. Normally it is not any limitation but it is advisable to have it in mind
and check if it is acceptable for the application in question.
If the IED has a sufficient number of analog current inputs an alternative solution is
shown in figure 18. The same currents are fed to two separate groups of inputs and
the line and transformer protection functions are configured to the different inputs.
The CT direction for the current channels to the line protection is set with the line as
reference object and the directional functions of the line protection shall be set to
Forward to protect the line.
Transformer
Line
Reverse Forward
Definition of direction
for directional
Transformer and line functions
Line protection
Busbar
2
Busbar
Protection
2 1
en06000196.vsd
Figure 19: Example how to set CTStarPoint parameters for REB 670
For busbar protection it is possible to set the CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in figure 19, set CTStarPoint=ToObject, and for all CT inputs
marked with 2 in figure 19, set CTStarPoint=FromObject.
The second solution will be to use all connected bays as reference objects. In that
case for all CT inputs marked with 1 in figure 19, set CTStarPoint=FromObject, and
for all CT inputs marked with 2 in figure 19, set CTStarPoint=ToObject.
Regardless which one of the above two options is selected busbar differential
protection will behave correctly.
The main CT ratios must also be set. This is done by setting the two parameters
CTsec and CTprim for each current channel. For a 1000/1 A CT the following setting
shall be used: CTprim=1000 (value in A) CTsec=1 (value in A).
Example
Consider a VT with the following data:
132 kV 110 V
3 3
The following setting should be used: VTprim=132 (value in kV) VTsec=110 (value
in V)
has a four lines and the medium size LCD can display the single line diagram with
up to 15 objects.
The local human machine interface is equipped with an LCD that can display the
single line diagram with up to 15 objects.
The local human-machine interface is simple and easy to understand – the whole front
plate is divided into zones, each of them with a well-defined functionality:
4.3.2.1 Introduction
The adaptation of the LHMI to the application and user preferences is made with:
4.3.3.1 Introduction
The function block HLED (LEDMonitor) controls and supplies information about
the status of the indication LEDs. The input and output signals of HLED are
configured with the PCM 600 tool. The input signal for each LED is selected
individually with the PCM 600 Signal Matrix Tool (SMT). LEDs (number 1–6) for
trip indications are red and LEDs (number 7–15) for start indications are yellow.
Each indication LED on the LHMI can be set individually to operate in six different
sequences; two as follow type and four as latch type. Two of the latching types are
intended to be used as a protection indication system, either in collecting or restarting
mode, with reset functionality. The other two are intended to be used as signalling
system in collecting (coll) mode with an acknowledgment functionality. The light
from the LEDs can be steady (-S) or flickering (-F).
4.4.1.1 Application
The protection and control IEDs have a complex design with many included
functions. The included self-supervision function and the INTernal signals function
block provide good supervision of the IED. The fault signals make it easier to analyze
and locate a fault.
Both hardware and software supervision is included and it is also possible to indicate
possible faults through a hardware contact on the power supply module and/or
through the software communication.
Internal events are generated by the built-in supervisory functions. The supervisory
functions supervise the status of the various modules in the IED and, in case of failure,
a corresponding event is generated. Similarly, when the failure is corrected, a
corresponding event is generated.
Apart from the built-in supervision of the various modules, events are also generated
when the status changes for the:
The internal events are time tagged with a resolution of 1 ms and stored in a list. The
list can store up to 40 events. The list is based on the FIFO principle, that is, when it
is full, the oldest event is overwritten. The list cannot be cleared and its content cannot
be modified.
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The information can only be retrieved with the aid of a Station Monitoring System
(SMS). The PC can be connected either to the port at the front or at the rear of the
IED.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.4.2.1 Application
Use time synchronization to achieve a common time base for the IEDs in a protection
and control system. This makes comparison of events and disturbance data between
all IEDs in the system possible.
In the IED 670 IED, the internal time can be synchronized from a number of sources:
Out of these, LON and SPA contains two types of synchronization messages:
• Coarse time messages are sent every minute and contain complete date and time,
i.e. year, month, day, hour, minute, second and millisecond.
• Fine time messages are sent every second and comprises only seconds and
milliseconds.
The setting tells the IED which of these that shall be used to synchronize the IED.
It is possible to set several time-sources, i.e. for instance both SNTP and GPS, and
in that case the IED will automatically choose the time-source that will provide the
best accuracy. At a given point in time, only one time-source will be used.
System time
The time is set with years, month, day, hour, minute, second and millisecond.
Synchronization
The setting parameters for the real-time clock with external time synchronization
(TIME) are set via the local HMI or the PCM 600 tool.
TimeSynch
When the source of time synchronization is selected on the local HMI, the parameter
is called TimeSynch. The time synchronization source can also be set from the PCM
600 tool. The setting alternatives are:
• Off
• SPA
• LON
• BIN (Binary Minute Pulse)
• GPS
• GPS+SPA
• GPS+LON
• GPS+BIN
• SNTP
• GPS+SNTP
• Off
• SPA
• LON
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
4.4.3.1 Application
Six sets of settings are available to optimize IED operation for different system
conditions. By creating and switching between fine tuned setting sets, either from the
human-machine interface or configurable binary inputs, results in a highly adaptable
IED that can cope with a variety of system scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control units to best provide for dependability, security and selectivity
requirements. Protection units operate with a higher degree of availability, especially,
if the setting values of their parameters are continuously optimized according to the
conditions in the power system.
Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-
tested settings in advance for different protection functions. Six different groups of
setting parameters are available in the IED. Any of them can be activated
automatically through the different programmable binary inputs by means of external
or internal control signals.
A function block, SGC, (available in CAP 531) defines how many setting groups are
used. Setting is done with parameter MAXSETGR and shall be set to the required
value for each application. Only the number of setting groups set will be available in
PST and for activation with the ACGR function block.
The setting ActiveSetGrp, which is set via from the local HMI or from the PCM600
tool, is used to select which parameter group to be active. The active group can also
be selected with configured input to the function block SGC.
The length of the pulse, sent out by the output signal SETCHGD when an active group
has changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between.
4.4.4.1 Application
The protection and control IEDs have a complex configuration with many included
functions. To make the testing procedure easier, the IEDs include the feature to
individually block a single, several or all functions.
This means that it is possible to see when a function is activated or trips. It also enables
the user to follow the operation of several related functions to check correct
functionality and to check parts of the configuration etc.
Remember always that there are two possible ways to place the IED in the “Test
mode: On” state. If, at the end of one test, you took off the IED from the Test mode,
but the functions are still shown being in the test mode, check your configuration —
you might have the input on the TEST function block activated.
4.4.5.1 Application
The IED identifier function is divided into two parts. One part handles factory defined
settings and the other part handles customer specific settings.
• IEDType
• IEDVer
• SerialNo
• OrderingNo
• ProductionDate
• StationName
• StationNumber
• ObjectName
• ObjectNumber
• UnitName
• UnitNumber
4.4.6.1 Application
Set the system rated frequency. Refer to section "Signal matrix for analog inputs
(SMAI)" for description on frequency tracking.
4.4.7.1 Application
The SMBI function block is used within the CAP tool in direct relation with the Signal
Matrix Tool (see the overview of the engineering process in chapter "Engineering of
the IED"). It represents the way binary inputs are brought in for one IED 670
configuration.
There are no setting parameters for the SMBI available to the user in PST. However,
the user must give a name to the SMBI instance and the SMBI inputs, directly in the
CAP tool. These names will define the function block in the Signal Matrix Tool.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.4.8.1 Application
The SMBO function block is used within the CAP tool in direct relation with the
Signal Matrix Tool (see the overview of the engineering process in chapter
"Engineering of the IED"). It represents the way binary outputs are sent from one IED
670 configuration.
There are no setting parameters for the SMBO available to the user in PST. However,
the user must give a name to the SMBO instance and the SMBO outputs, directly in
the CAP tool. These names will define the function block in the Signal Matrix Tool.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.4.9.1 Application
The SMMI function block is used within the CAP tool in direct relation with the
Signal Matrix Tool (please see the overview of the engineering process in chapter
"Engineering of the IED"). It represents the way milliamp (mA) inputs are brought
in for one IED 670 configuration.
There are no setting parameters for the SMMI available to the user in PST. However,
the user must give a name to the SMMI instance and the SMMI inputs, directly in the
CAP tool.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.4.10.1 Application
The SMAI function block (or the pre-processing function block PreProc, as it is also
named) is used within the CAP tool in direct relation with the Signal Matrix Tool (see
the overview of the engineering process in chapter "Engineering of the IED"). It
represents the way analog inputs are brought in for one IED 670 configuration.
The parameters for the signal matrix for analog inputs (SMAI) functions are set via
the local HMI or Protection and Control Manager (PCM 600).
Every SMAI function block can receive four analog signals (three phases and one
neutral value), either voltage or current. The outputs of the SMAI are giving
information about every aspect of the 3ph analog signals acquired (phase angle, RMS
value, frequency and frequency derivates, etc. – 244 values in total). Besides the block
“group name”, the analog inputs type (voltage or current) and the analog input names
that can be set directly in CAP, the user has several settings available in PST:
DFTRefExtOut: Parameter valid for function block PR01, PR13, PR25 only.
Reference DFT block for external output (SYNCOUT function output).
DFTReference: Reference DFT block for that specific instance of the SMAI.
These DFT reference block settings decide which DFT block will be used as reference
in the calculation of frequency and other values (Internal DFTRef will use set system
frequency. GrpnAdDFTRef will use calculated frequency from the selected analog
input n on AIM1, ExternalDFTRef will use input DFTSYNC as frequency reference.)
ConnectionType: Connection type for that specific instance (n) of the SMAI (if it is
Ph-N or Ph-Ph). Depending on connection type setting the not connected Ph-N or
Ph-Ph outputs will be calculated.
Negation: If the user wants to negate the 3ph signal, it can choose to negate only the
phase signals Negate3Ph, only the neutral signal NegateN or both Negate3Ph+N;
negation means rotation with 180° of the vectors.
MinValFreqMeas: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBase (for each instance n).
4.4.11.1 Application
The analog summation block SUM3Ph function block is used in order to get the sum
of two sets of 3 ph analog signals (of the same type) for those IED functions that
might need it.
The summation block receives the 3ph signals from the SMAI blocks. The summation
block has several settings.
FreqMeasMinVal: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBase (for each instance n).
4.5.1.1 Application
The application will be dependent on the primary system arrangements and location
of breakers, available separate cores on CTs etc.
IdN
en05000164.vsd
Figure 23: The high impedance principle for one phase with three current
transformer inputs
For a through fault one current transformer might saturate when the other still will
feed current. For such a case a voltage can be achieved across the relay. The
calculations are made with the worst situations in mind and a minimum operating
voltage UR is calculated according to equation 11
where:
IFmax is the maximum through fault current at the secondary side,
Rct is the current transformer secondary resistance and
RI is the maximum loop resistance of the circuit at any CT.
The maximum operating voltage have to be calculated (all loops) and the relay is set
higher than the highest achieved value (setting U>Trip). As the loop resistance is the
value to the connection point from each CT it is advisable to do all the CT core
summations in the switchgear to have shortest possible loops. This will give lower
setting values and also a better balanced scheme. The connection in to the control
room can then be from the most central bay.
For an internal fault the circulation is not possible and due to the high impedance the
current transformers will immediately saturate and a rms voltage with the size of
current transformer saturation voltage will be achieved across the relay. Due to the
fast saturation very high top voltages can be achieved. To prevent the risk of flashover
in the circuit, a voltage limiter must be included. The voltage limiter is of type voltage
dependent resistor (Metrosil).
Based on the above calculated operating voltage the relay stabilizing resistor must be
selected. The external unit with stabilizing resistor and the voltage dependent resistor
has a 6800 respectively 2200 ohm resistor (depending on ordered alternative) with a
shorting link to allow adjustment to the required value. Select a suitable value of the
resistor based on the UR voltage calculated. A higher resistance value will give a
higher sensitivity and a lower value a lower sensitivity.
The function has an operating current range 20 mA to 1.0A for 1 A inputs and 100
mA to 5A for 5A inputs. This is together with the selected and set value used to
calculate the required value of current at the set U>Trip and SeriesResitor values.
The table below shows the operating voltages for different resistances and the related
operating current. Adjust as required based on this table or to values in between as
required for the application.
Normally the voltage can be increased to higher values than the calculated minimum
U>Trip with a minor change of total operating values as long as this is done by
adjusting the resistor to a higher value. Check the sensitivity calculation below for
reference.
When you have selected the R value and set the U>Trip value the sensitivity of the
scheme IP can be calculated. The relay sensitivity is decided by the total current in
the circuit according to equation 12.
IP = n × ( IR + Ires + å lmag
(Equation 12)
where:
n is the CT ratio
IP is the current through the relay,
Ires is the current through the voltage limiter and
ΣImag is the sum of the magnetizing currents from all CTs in the circuit (e.g. 4 for Restricted earth
fault protection, 2 for reactor differential protection, 3-4 for Autotransformer differential
protection etc.).
It should be remembered that the vectorial sum of the currents must be used (relays,
Metrosil and resistor currents are resistive). The current measurement shall be
insensitive to DC component in fault current to allow a use of only the AC components
of the fault current in the above calculations.
Rl Rl
Rct UR Rct
R
Rres
I>
Protected Object
UR
UR
c) Internal faults
UR
en05000427.vsd
Figure 24: The high impedance principle for one phase with two current
transformer inputs
The setting calculations are individual for each application. Refer to the different
application descriptions below.
Configuration
The configuration is done in CAP531 graphical configuration tool. Signals from e.g.
check criterias are connected to the inputs as required for the application.
BLOCK input is used to block the function e.g. from an external check criteria.
BLKTR input is used to block the function tripping e.g. from an external check
criteria. The alarm level will be operative.
U>Alarm: Set the alarm level. The sensitivity can roughly be calculated as a divider
from the calculated sensitivity of the differential level. A typical setting is 10% of
U>Trip
tAlarm: Set the time for the alarm. Mostly this output is also used to short-circuit the
differential circuit at the alarm. A typical setting is 2-3 seconds.
U>Trip: Set the trip level according to the calculations in the examples for each
application example. The level is selected with margin to the calculated required
voltage to achieve stability. Values can be 20-200 V dependent of the application.
Series resistor: Set the value of the stabilizing series resistor. Calculate the value
according to the examples for each application. Adjust the resistor as close as possible
to the calculated example. Measure the value achieved and set this value here. Note!
The value shall always be a high impedance. This means e.g. for 1A circuits say bigger
than 400 ohms (400 VA) and for 5 A circuits say bigger than 100 ohms (2500 VA).
This ensures that the current will circulate and not go through the differential circuit
at through faults.
T-feeder protection
In many busbar arrangements such as one-and a half breaker, ring breaker, mesh
corner etc there will be a T-feeder from the current transformer at the breakers up to
the current transformers in the transformer bushings. It is often required to separate
the zones so the zone up to the bushing is covered from one differential function and
the transformer from another. The high impedance differential function in REx670
allows this to be done efficiently, see figure 25.
Figure 25: The protection scheme utilizing the high impedance function for the
T-feeder and the transformer differential protection for the
transformer
Normally this scheme is set to achieve a sensitivity of around 20 percent of the rated
current so the a low value can be used on the resistor.
Setting example
Basic data:
Current transformer ratio: 2000/1 A
CT Class: 20 VA 5P20
Secondary resistance: 6.2 ohms
Cable loop resistance: <100 m 2.5mm2 (one way) gives 2*0,8 ohm at 75° C
Max fault current: Equal to switchgear rated fault current 40 kA
Calculation:
4000
UR > × ( 6.2 + 1.6 ) = 156V
2000
Check from the table of selected resistances the required series stabilizing resistor
value to use. As this application does not need to be so sensitive select
SeriesResistor= 2000 ohm which gives a relay current of 100 mA.
2000
IP = (100 0° + 20 0° + 3 ×10 -60° ) ×10 -3 £ approx.220 A
1 (Equation 15)
The magnetizing current is taken from the magnetizing curve for the current
transformer cores which should be available. The value at U>Trip is taken. For the
voltage dependent resistor current the top value of voltage 200*√2 is used and the
top current used. Then the rms current is calculated by dividing with √2. Use the
maximum value from the curve.
It can clearly be seen that the sensitivity is not so much influenced by the selected
voltage level so a sufficient margin should be used. The selection of the stabilizing
resistor and the level of the magnetizing current (mostly dependent of the number of
turns) are the most important factors.
3Id
en05000176.vsd
Setting example
Basic data:
Current transformer ratio: 100/5 A (Note: Must be the same at all locations)
CT Class: 10 VA 5P20
Secondary resistance: 0.26 ohms
Cable loop resistance: <50 m 2.5mm2 (one way) gives 1*0.4 ohm at 75° C
Note! Only one way as the system earthing is limiting the earth fault current.
If high earth fault currents exists use two way cable.
Max fault current: The maximum through fault current is limited by the reactor reactance and
the inrush will be the worst for a reactor e.g. 800 A.
Calculation:
800
UR > × ( 0.26 + 0.4 ) = 5.28V
1000
æ 10 ö
E 5P > ç + 0.26 ÷ × 20 × 5 = 66V
è 25 ø
Check from the table of selected resistances the required series stabilizing resistor
value to use. As this application it is required to be so sensitive so select
SeriesResistor= 200 ohm which gives a relay current of 100 mA.
100
IP = × (100 0° + 5 0° + 2 × 100 -60° ) £ approx.5 A
5 (Equation 18)
The magnetizing current is taken from the magnetizing curve for the current
transformer cores which should be available. The value at U>Trip is taken. For the
voltage dependent resistor current the top value of voltage 20*√2 is used and the top
current used. Then the rms current is calculated by dividing with √2. Use the
maximum value from the curve.
As seen in the setting examples above the sensitivity of the function is normally high
which means that the function will in many cases operate also for short circuits or
open current transformer secondary circuits. However the stabilizing resistor can be
selected to achieve a sensitivity higher than normal load current and/or a separate
criteria can be added to the operation, a check zone. This can be another IED with
the same high impedance differential function, it could be a check that the fault is
there with a earth overcurrent function or neutral point voltage function etc.
For such cases where operation is not expected during normal service the alarm output
should be used to activate an external shorting of the differential circuit avoiding
continuous high voltage in the circuit. A time delay of a few seconds is used before
the shorting and alarm is activated.
Figure 27: Current voltage characteristics for the non-linear resistors, in the
range 10-200 V, 50 Hz the average range of current is: 0.01–10 mA.
L1 L2 L3
(A) (B) (C) 8
7
1
N 4
L3 (C)
L2 (B)
CT 1200/1 L1 (A) 5
Star/Wye
Connected X1 11 12 13 14 1 2 3 4 5 6 7
2
1
3
3
R4
R5
R6
R1
R2
R3
2 U
2 U
2 U
4
X X
2
L1 L2 L3 6
(A) (B) (C) 3-Ph Plate with Metrosils and Resistors
• Number 1 shows the scheme earthing point. Note that it is of outmost importance
to insure that only one earthing point exist in such scheme.
• Number 2 shows the three-phase plate with setting resistors and metrosils.
• Number 3 shows the necessary connection for three-phase metrosil set. Shown
connections are applicable for both types of three-phase plate.
• Number 4 shows the position of optional test switch for secondary injection into
the high impedance differential relay.
• Number 5 shows the necessary connection for setting resistors. Shown
connections are applicable for both types of three-phase plate.
• Number 6 shows that the factory made star point on a three-phase setting resistor
set shall be removed for installations with 670 series. This star point is required
for RADHA schemes only!
• Number 7 shows how to connect three individual phase currents for high
impedance scheme to three CT inputs in IED 670.
• Number 8 shows a TRM module where these current inputs are located. Note
that the CT ratio for high impedance differential protection application must be
set as one! Thus for main CTs with 1A secondary rating the following setting
values shall be entered: CTprim=1A and CTsec=1A; while for main CTs with
5A secondary rating the following setting values shall be entered: CTprim=5A
and CTsec=5A. The parameter CTStarPoint shall be always left to the default
value ToObject.
• Number 9 shows three connections made in Signal Matrix Tool (i.e. SMT) which
connect these three current inputs to first three input channels of the
L1 L2 L3
IED 670
N
(A) (B) (C)
4
1
N
CT 1500/5
X1 4 5 1 2 3
2
3
5
1
1
3
R1
R2
2 U
4
2
• Number 1 shows the scheme earthing point. Note that it is of outmost importance
to insure that only one earthing point exist in such scheme.
• Number 2 shows the one-phase plate with setting resistor and metrosil.
• Number 3 shows the necessary connection for the metrosil. Shown connections
are applicable for both types of one-phase plate. • Number 4 shows the position
of optional test switch for secondary injection into the high impedance
differential relay.
• Number 4 shows the position of optional test switch for secondary injection into
the high impedance differential relay.
• Number 5 shows the necessary connection for setting resistor. Shown
connections are applicable for both types of one-phase plate.
• Number 6 shows how to connect the REF high impedance scheme to one CT
input in IED 670.
• Number 7 shows a TRM module where this current input is located. Note that
the CT ratio for high impedance differential protection application must be set
as one! Thus for main CTs with 1A secondary rating the following setting values
shall be entered: CTprim=1A and CTsec=1A; while for main CTs with 5A
secondary rating the following setting values shall be entered: CTprim=5A and
CTsec=5A. The parameter CTStarPoint shall be always left to the default value
ToObject.
• Number 8 shows a connection made in Signal Matrix Tool (i.e. SMT) which
connects this current input to first input channel of the preprocessing function
block (10). For high impedance differential protection preprocessing function
block in 3ms task shall be used.
• Number 9 shows the preprocessing block which has a task to digitally filter the
connected analogue inputs. Preprocessing block output AI1 shall be connected
to one instances of high impedance differential protection function block (e.g.
HZD1 function block in the configuration tool).
Table 24: Parameter group settings for the HZPDIF_87 (HZD1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
U>Alarm 2 - 500 1 10 V Alarm voltage level in
volts on CT
secondary side
tAlarm 0.000 - 60.000 0.001 5.000 s Time delay to activate
alarm
U>Trip 5 - 900 1 100 V Operate voltage level
in volts on CT
secondary side
SeriesResistor 10 - 20000 1 250 ohm Value of series
resistor in Ohms
4.6.1.1 Application
Long transmission lines often transfer great quantities of electric power from
production to consumption areas. The unbalance of the produced and consumed
electric power at each end of the transmission line is very large. This means that a
fault on the line can easily endanger the stability of a complete system.
The transient stability of a power system depends mostly on three parameters (at
constant amount of transmitted electric power):
• The type of the fault. Three-phase faults are the most dangerous, because no
power can be transmitted through the fault point during fault conditions.
• The magnitude of the fault current. A high fault current indicates that the decrease
of transmitted power is high.
• The total fault clearing time. The phase angles between the EMFs of the
generators on both sides of the transmission line increase over the permitted
stability limits if the total fault clearing time, which consists of the protection
operating time and the breaker opening time, is too long.
The fault current on long transmission lines depends mostly on the fault position and
decreases with the distance from the generation point. For this reason the protection
must operate very quickly for faults very close to the generation (and relay) point, for
which very high fault currents are characteristic.
For this reason instantaneous phase overcurrent protection (IOC), which can operate
in 10 ms for faults characterized by very high currents, is included in some of the
IED. Refer to the ordering information for more details.
The parameters for the phase overcurrent protection function (IOC) are set via the
local HMI or Protection and Control Manager (PCM 600).
This protection function must operate only in a selective way. So check all system
and transient conditions that could cause its unwanted operation.
Only detailed network studies can determine the operating conditions under which
the highest possible fault current is expected on the line. In most cases, this current
appears during three-phase fault conditions. But also examine single-phase-to-earth
and two-phase-to-earth conditions.
Also study transients that could cause a high increase of the line current for short
times. A typical example is a transmission line with a power transformer at the remote
end, which can cause high inrush current when connected to the network and can thus
also cause the operation of the built-in, instantaneous, overcurrent protection.
IBase: Base current in primary A. This current is used as reference for current setting.
If possible to find a suitable value the rated current of the protected object is chosen.
OpMode: This parameter can be set to “2 out of 3” or “1 out of 3”. The setting controls
the minimum number of phase currents that must be larger than the set operate current
IP>> for operation. Normally this parameter is set to “1 out of 3” and will thus detect
all fault types. If the protection is to be used mainly for multi phase faults, “2 out of
3” should be chosen.
StValMult: The operate current can be changed by activation of the binary input
ENMULT to the set factor StValMult.
I fB
A B
ZA ZL ZB
~ ~
Relay
Fault
99000474.vsd
Then a fault in A has to be applied and the through fault current IfA has to be calculated,
figure 31. In order to get the maximum through fault current, the minimum value for
ZB and the maximum value for ZA have to be considered.
I fA
A B
ZA ZL ZB
~ ~
Relay
Fault
99000475.vsd
The relay must not trip for any of the two trough fault currents. Hence the minimum
theoretical current setting (Imin) will be:
A safety margin of 5% for the maximum protection static inaccuracy and a safety
margin of 5% for the maximum possible transient overreach have to be introduced.
An additional 20% is suggested due to the inaccuracy of the instrument transformers
under transient conditions and inaccuracy in the system data.
The minimum primary setting (Is) for the instantaneous phase overcurrent protection
is then:
Is ³ 1, 3 × I min
(Equation 20)
The protection function can be used for the specific application only if this setting
value is equal to or less than the maximum fault current that the relay has to clear,
IF in figure 32.
IF
A B
ZA ZL ZB
~ ~
Relay
Fault
99000476.vsd
The relay setting value IP>> is given in percentage of the primary base current value,
IBase. The value for IP>> is given from this formula:
Is
I >>= x100
IBase (Equation 21)
A fault in C has to be applied, and then the maximum current seen from the relay
(IM ) on the healthy line (this applies for single-phase-to-earth and two-phase-to-earth
faults) is calculated.
Line 1
A C B
ZL1
ZA ZB
~ Fault M ~
ZL2
99000477.vsd
IM
Relay Line 2
Figure 33: Two parallel lines. Influence from parallel line to the through fault
current: IM
The minimum theoretical current setting for the overcurrent protection function
(Imin) will be:
Where IfA and IfB have been described in the previous paragraph. Considering the
safety margins mentioned previously, the minimum setting (Is) for the instantaneous
phase overcurrent protection is then:
The protection function can be used for the specific application only if this setting
value is equal or less than the maximum phase fault current that the relay has to clear.
The relay setting value IP>> is given in percentage of the primary base current value,
IBase. The value for IP>> is given from this formula:
Is
I >>= x100
IBase (Equation 24)
Table 25: Parameter group settings for the PHPIOC_50 (IOC1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
OpMode 2 out of 3 - 1 out of 3 - Select operation
1 out of 3 mode 2-out of 3 / 1-
out of 3
IP>> 1 - 2500 1 200 %IB Operate phase
current level in % of
IBase
StValMult 0.5 - 5.0 0.1 1.0 - Multiplier for operate
current level
4.6.2.1 Application
The phase overcurrent protection function is used in several applications in the power
system. Some applications are:
In many applications several steps with different current pick up levels and time
delays are needed. TOC can have up to four different, individual settable, steps. The
flexibility of each step of the TOC function is great. The following options are
possible:
Choice of delay time characteristics: There are several types of delay time
characteristics available such as definite time delay and different types of inverse time
delay characteristics. The selectivity between different overcurrent protections is
normally enabled by co-ordination between the function time delays of the different
protections. To enable optimal co-ordination all overcurrent relays, to be co-ordinated
against each other, should have the same time delay characteristic. Therefore a wide
range of standardised inverse time characteristics are available: IEC and ANSI. It is
also possible to tailor make the inverse time characteristic.
Normally it is required that the phase overcurrent function shall reset as fast as
possible when the current level gets lower than the operation level. In some cases
some sort of delayed reset is required. Therefore different kinds of reset characteristics
can be used.
For some protection applications there can be a need to change the current pick-up
level for some time. A typical case is when the protection will measure the current to
a large motor. At the start up sequence of a motor the start current can be significantly
larger then the rated current of the motor. Therefore there is a possibility to give a
setting of a multiplication factor to the current pick-up level. This multiplication factor
is activated from a binary input signal to the function.
Power transformers can have a large inrush current, when being energized. This
phenomenon is due to saturation of the transformer magnetic core during parts of the
period. There is a risk that inrush current will reach levels above the pick-up current
of the phase overcurrent protection. The inrush current has a large second harmonic
content. This can be used to avoid unwanted operation of the protection. Therefore
the TOC function have a possibility of second harmonic restrain if the level of this
harmonic current reaches a value above a set percentage of the fundamental current.
The phase overcurrent protection is often used as protection for two and three phase
short circuits. In some cases it is not wanted to detect single-phase earth faults by the
phase overcurrent protection. This fault type is detected and cleared after operation
of earth fault protection. Therefore it is possible to make a choice how many phases,
at minimum, that have to have current above the pick-up level, to enable operation.
If set “1 of 3” it is sufficient to have high current in one phase only. If set “2 of 3” or
“3 of 3” single-phase earth faults are not detected.
The parameters for the four step phase overcurrent protection function (TOC) are set
via the local HMI or Protection and Control IED Manager (PCM 600).
The following settings can be done for the four step phase overcurrent protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the current of
the protected object.
UBase: Base voltage level in kV. This voltage is give as a phase-to-phase voltage and
this is the reference for voltage related settings of the function. Normally the setting
should be chosen to the rated phase-to-phase voltage of the voltage transformer
feeding the protection IED.
AngleRCA: Protection characteristic angle set in degrees. If the angle of the fault loop
current has the angle RCA the direction to fault is forward.
maxFwdAng and minFwdAng: Angle value, given in degrees, to define the angle
sector of the directional function, see figure 34.
IminOpPhSel: Minimum current for phase selection set in % of IBase. This setting
should be less than the lowest step setting. Default setting is 7%.
StartPhSel: Number of phases, with high current, required for operation. The setting
possibilities are: 1 of 3, 2 of 3 and 3 of 3. Default setting is 1 of 3.
Reverse
Uref
RCA
ROA
ROA Forward
Idir
en05000745.vsd
Characteristx: Selection of time delay characteristic for step x. Definite time delay
and different types of inverse time delay characteristics are available according to
table 26.
tx: Definite time delay for step x. Used if definite time characteristic is chosen. Setting
range: 0.000-60.000 s in step of 0.001 s
InxMult: Multiplier for scaling of the current setting value. If a binary input signal
(enableMultiplier) is activated the current operation level is increase by this setting
constant. Setting range: 1.0-10.0
txMin: Minimum operation time for IEC inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting. Setting
range: 0.000-60.000 s in step of 0.001 s.
ResetTypeCrvx: The reset of the delay timer can be made in different ways. By
choosing setting the possibilities are according to table 27.
The delay characteristics are described in the “Technical reference manual”. There
are some restrictions regarding the choice of reset delay.
For the independent time delay characteristics (type 5 and 15) the possible delay time
settings are instantaneous (1) and IEC (2 = set constant time reset).
For ANSI inverse time delay characteristics (type 1-4 and 6-8) all three types of reset
time characteristics are available; instantaneous (1), IEC (2 = set constant time reset)
and ANSI (3 = current dependent reset time).
For IEC inverse time delay characteristics (type 9-14) the possible delay time settings
are instantaneous (1) and IEC (2 = set constant time reset).
For the customer tailor made inverse time delay characteristics (type 17) all three
types of reset time characteristics are available; instantaneous (1), IEC (2 = set
constant time reset) and ANSI (3 = current dependent reset time). If the current
dependent type is used settings pr, tr and cr must be given.
HarmRestrainx: Enable block of step x from the harmonic restrain function (2nd
harmonic). This function should be used when there is a risk if power transformer
inrush currents might cause unwanted trip. Can be set Off/On.
tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for customer creation of inverse time
characteristic curve (Curve type = 17). See equation 25 for the time characteristic
equation.
æ ö
ç A
÷
t [s] = ç + B ÷ × IxMult
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø (Equation 25)
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset time
characteristic curve (Reset Curve type = 3). Further description can be found in the
“Technical reference manual”.
The settings for the 2nd harmonic restrain are described below.
2ndHarmStab: The rate of second harmonic current content for activation of the
2nd harmonic restrain signal, to block chosen steps. The setting is given in % of the
fundamental frequency residual current. The setting range is 5-100% in step of 1%.
The default setting is 20%.
HarmRestrainx: This parameter can be set Off/On, disable or enable the 2nd harmonic
restrain.
The four-step phase overcurrent protection can be used in different ways, depending
on the application where the protection is used. A general description is given below.
The pick up current setting inverse time protection or the lowest current step constant
inverse time protection must be given a current setting so that the highest possible
load current does not cause protection operation. Here consideration also has to be
taken to the protection reset current, so that a short peak of overcurrent does not cause
operation of the protection even when the overcurrent has ceased. This phenomenon
is described in figure 35.
Current I
Pick-up current
Reset current
Time t
en05000203.vsd
I max
I pu ³ 1.2 ×
k
(Equation 26)
where:
1.2 is a safety factor,
k is the resetting ratio of the protection, and
Imax is the maximum load current.
The maximum load current on the line has to be estimated. From operation statistics
the load current up to the present situation can be found. The current setting must be
valid also for some years ahead. It is, in most cases, realistic that the setting values
are updated not more often than once every five years. In many cases this time interval
is still longer. Investigate the maximum load current that different equipment on the
line can withstand. Study components such as line conductors, current transformers,
circuit breakers, and disconnectors. The manufacturer of the equipment normally
gives the maximum thermal load current of the equipment.
There is also a demand that all faults, within the zone that the protection shall cover,
must be detected by the phase overcurrent protection. The minimum fault current
Iscmin, to be detected by the protection, must be calculated. Taking this value as a
base, the highest pick up current setting can be written according to equation 27.
I pu £ 0.7 × I sc min
(Equation 27)
where:
0.7 is a safety factor and
Iscmin is the smallest fault current to be detected by the overcurrent protection.
As a summary the pick up current shall be chosen within the interval stated in
equation 28.
I max
1.2 × £ I pu £ 0.7 × I sc min
k (Equation 28)
The high current function of the overcurrent protection, which only has a short delay
of the operation, must be given a current setting so that the protection is selective to
other protection in the power system. It is desirable to have a rapid tripping of faults
within as large portion as possible of the part of the power system to be protected by
the protection (primary protected zone). A fault current calculation gives the largest
current of faults, Iscmax, at the most remote part of the primary protected zone.
Considerations have to be made to the risk of transient overreach, due to a possible
DC component of the short circuit current. The lowest current setting of the most
rapid stage, of the phase overcurrent protection, can be written according to
where:
1.2 is a safety factor,
kt is a factor that takes care of the transient overreach due to the DC component of the fault current
and can be considered to be less than 1.1
Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.
The operate times of the phase overcurrent protection has to be chosen so that the
fault time is so short so that equipment will not be destroyed due to thermal overload,
at the same time as selectivity is assured. For overcurrent protection, in a radial fed
network, the time setting can be chosen in a graphical way. This is mostly used in the
case of inverse time overcurrent protection. In the figure below is shown how the
time-versus-current curves are plotted in a diagram. The time setting is chosen to get
the shortest fault time with maintained selectivity. Selectivity is assured if the time
difference between the curves is larger than a critical time difference.
en05000204.wmf
The operation time can be set individually for each overcurrent protection. To assure
selectivity between different protective protections, in the radial network, there have
to be a minimum time difference Dt between the time delays of two protections. The
minimum time difference can be determined for different cases. To determine the
shortest possible time difference between we must have knowledge about operation
time of protections, breaker opening time and protection resetting time. These time
delays can vary significantly between different pieces of equipment. The following
time delays can be estimated:
Example
Assume two substations A and B directly connected to each other via one line, as
shown in the figure below. We study a fault located at another line from the station
B. The fault current to the overcurrent protection of IED B1 has a magnitude so that
the protection will have instantaneous function. The overcurrent protection of IED
A1 must have a delayed function. The sequence of events during the fault can be
described using a time axis, see figure 37.
A1 B1
Feeder
I> I>
Time axis
where:
t=0 is the fault occurs,
t=t1 is the trip signal from the overcurrent protection at IED B1 is sent. Operation time of this
protection is t1,
t=t2 is the circuit breaker at IED B1 opens. The circuit breaker opening time is t2 - t1 and
t=t3 is the overcurrent protection at IED A1 resets. The protection resetting time is t3 - t2.
To ensure that the overcurrent protection at IED A1, is selective to the overcurrent
protection at IED B1, the minimum time difference must be larger that the time t3.
There are uncertainties in the values of protection operation time, breaker opening
time and protection resetting time. Therefor a safety margin has to be included. With
normal values the needed time difference can be calculated according to
equation 30.
Dt ³ 40 ms + 100 ms + 40 ms + 40 ms = 220 ms
(Equation 30)
Table 28: Parameter group settings for the PH4POCM_51_67 (TOC1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 - Base setting for
current values
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage levels in kV
MaxFwdAng 40.0 - 70.0 0.1 50.0 Deg Maximum forward
angle
MinFwdAng 75.0 - 90.0 0.1 80.0 Deg Minimum forward
angle
AngleRCA -70.0 - -50.0 1.0 -65.0 Deg Relay characteristic
angle (RCA)
IMinOpPhSel 1 - 100 1 7 %IB Minimum current for
phase selection in %
of IBase
StartPhSel Not Used - 1 out of 3 - Number of phases
1 out of 3 required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3)
3 out of 3
2ndHarmStab 5 - 100 1 20 %IB Operate level of 2nd
harm restrain op in %
of Fundamental
DirMode1 Off - Non-directional - Directional mode of
Non-directional step 1 (off, nodir,
Forward forward, reverse)
Reverse
Characterist1 ANSI Ext. inv. - ANSI Def. Time - Selection of time
ANSI Very inv. delay curve type for
ANSI Norm. inv. step 1
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continued on next page
4.6.3.1 Application
In many application, when fault current is limited to a defined value by the object
impedance, an instantaneous earth fault protection can provide fast and selective
tripping.
The parameters for the instantaneous residual overcurrent protection function (IEF)
are set via the local HMI or Protection and Control Manager (PCM 600).
Some guidelines for the choice of setting parameter for the instantaneous residual
overcurrent protection (IEF) function is given.
The setting of the function is limited to the operation residual current to the protection
(IN>>).
The basic requirement is to assure selectivity, i.e. the IEF function shall not be allowed
to operate for faults at other objects than the protected object (line).
For a normal line in a meshed system single phase to earth faults and phase to phase
to earth faults shall be calculated as shown in figure 38 and figure 39. The residual
currents (3I0) to the protection are calculated. For the fault at the remote line end this
fault current is IfB. In this calculation the operational state with high source impedance
ZA and low source impedance ZB should be used. For the fault at the home busbar
this fault current is IfA. In this calculation the operational state with low source
impedance ZA and high source impedance ZB should be used.
I fB
A B
ZA ZL ZB
~ ~
Relay
Fault
99000474.vsd
I fA
A B
ZA ZL ZB
~ ~
Relay
Fault
99000475.vsd
The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20%
is suggested due to inaccuracy of instrument transformers under transient conditions
and inaccuracy in the system data.
In case of parallel lines with zero sequence mutual coupling a fault on the parallel
line, as shown in figure 40, should be calculated.
Line 1
A C B
ZL1
ZA ZB
~ Fault M ~
ZL2
99000477.vsd
IM
Relay Line 2
Figure 40: Two parallel lines. Influence from parallel line to the through fault
current: IM
The minimum theoretical current setting (Imin) will in this case be:
I m in ³ M A X ( IfA, I fB, I M )
(Equation 33)
Where:
IfA and IfB have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
Is ³ 1, 3 × Imin
(Equation 34)
The setting of the protection is set as a percentage of the base current (IBase).
IBase: Base current in primary A. This current is used as reference for current setting.
If possible to find a suitable value the rated current of the protected object is chosen.
StValMult: The operate current can be changed by activation of the binary input
ENMULT to the set factor StValMult.
Table 29: Parameter group settings for the EFPIOC_50N (IEF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
IN>> 1 - 2500 1 200 %IB Operate residual
current level in % of
IBase
StValMult 0.5 - 5.0 0.1 1.0 - Multiplier for operate
current level
4.6.4.1 Application
In many applications several steps with different current pick up levels and time
delays are needed.TEF can have up to four different, individual settable, steps. The
flexibility of each step of the TEF function is great. The following options are
possible:
Choice of delay time characteristics: There are several types of delay time
characteristics available such as definite time delay and different types of inverse time
delay characteristics. The selectivity between different overcurrent protections is
normally enabled by co-ordination between the function time delays of the different
protections. To enable optimal co-ordination all overcurrent relays, to be co-ordinated
against each other, should have the same time delay characteristic. Therefore a wide
range of standardized inverse time characteristics are available: IEC and ANSI. It is
also possible to tailor make the inverse time characteristic.
Normally it is required that the residual overcurrent function shall reset as fast as
possible when the current level gets lower than the operation level. In some cases
some sort of delayed reset is required. Therefore different kinds of reset characteristics
can be used.
For some protection applications there can be a need to change the current pick-up
level for some time. Therefore there is a possibility to give a setting of a multiplication
factor INnMULTEN to the residual current pick-up level. This multiplication factor
is activated from a binary input signal ENMULTn to the function.
Power transformers can have a large inrush current, when being energized. This
inrush current can have residual current components. The phenomenon is due to
saturation of the transformer magnetic core during parts of the cycle. There is a risk
that inrush current will give a residual current that reaches level above the pick-up
current of the residual overcurrent protection. The inrush current has a large second
harmonic content. This can be used to avoid unwanted operation of the protection.
Therefore the TEF function has a possibility of second harmonic restrain
HarmRestrainn if the level of this harmonic current reaches a value above a set
percentage of the fundamental current.
The parameters for the four step residual overcurrent protection function (TEF) are
set via the local HMI or Protection and Control Manager (PCM 600).
The following settings can be done for the four step residual overcurrent protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the current
transformer where the current measurement is made.
Ubase: Base voltage level in kV. This voltage is give as a phase-to-phase voltage and
this is the reference for voltage related settings of the function. The residual voltage
is used as reference voltage for the directional function. Normally the setting should
be chosen to the rated phase-to-phase voltage of the voltage transformer feeding the
protection terminal.
Characteristn: Selection of time delay characteristic for step n. Definite time delay
and different types of inverse time delay characteristics are available.
Inverse time characteristic enables fast fault clearance of high current faults at the
same time as selectivity to other inverse time phase overcurrent protections can be
assured. This is mainly used in radial fed networks but can also be used in meshed
networks. In meshed networks the settings must be based on network fault
calculations.
The different characteristics are described in the Technical Reference Manual (TRM).
tn: Definite time delay for step n. Used if definite time characteristic is chosen.
INnMult: Multiplier for scaling of the current setting value. If a binary input signal
(enableMultiplier) is activated the current operation level is increase by this setting
constant.
tnMin: Minimum operation time for IEC inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting.
ResetTypeCrvn: The reset of the delay timer can be made in different ways. By
choosing setting, the possibilities are described in the Technical Reference Manual
(TRM).
HarmRestrainx: Enable block of step x from the harmonic restrain function (2nd
harmonic). This function should be used when there is a risk if power transformer
inrush currents might cause unwanted trip. Can be set Off orOn.
tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for customer creation of inverse time
characteristic curve (Curve type = 17). The time characteristic equation is according
to equation 35:
æ ö
ç A
÷
t[ s ] = ç + B÷×k
çæ i ö p
÷
çç ÷ -C ÷
è è in > ø ø (Equation 35)
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset time
characteristic curve (Reset Curve type = 3). Further description can be found in the
Technical Reference Manual (TRM).
Operation
IN>Dir
en05000135.vsd
In a normal transmission network a normal value of RCA is about 65°. The setting
range is -180° to +180°.
IN>DirComp: Operate residual current level for directional comparison scheme. The
setting is given in % of IBase. The setting range is 1 - 100% in step of 1%. The start
tDirComp: Time delay for independent trip from the forward current of the directional
comparison functions. The setting range is 0.000 - 60.000 s in step of 0.001 s.
Below the settings for the 2nd harmonic restrain are described.
2ndHarmStab: The rate of second harmonic current content for activation of the
2nd harmonic restrain signal, to block chosen steps. The setting is given in % of the
fundamental frequency residual current. The setting range is 5 - 100% in step of 1%.
The default setting is 20%.
HarmRestrain: This parameter can be set Off/On, disable or enable the 2nd harmonic
restrain.
IN> IN>
Power System
en05000136.vsd
If the blkParTransf function is activated the 2nd harmonic restrain signal will latched
as long as the residual current measured by the relay is larger than a selected step
current level. Assume that step 4 is chosen to be the most sensitive step of the TEF
function. The harmonic restrain blocking is enabled for this step. Also the same
current setting as this step is chosen for the blocking at parallel transformer
energization.
Below the settings for the parallel transformer logic are described.
UseStartValue: Gives which current level that should be used for activation of the
blocking signal. This is given as one of the settings of the steps: Step 1/2/3/4. Normally
the step having the lowest operation current level should be set.
BlkParTransf: This parameter can be set Off/On, disable or enable the parallel
transformer logic.
The function can be used to fast trip again if one breaker pole does not close properly
at a manual or automatic closing.
SOTF and undertime are similar functions to achieve fast clearance at asymmetrical
closing based on requirements from different utilities.
The function is divided into two parts. The SOTF function will give operation from
step 2 or 3 during a set time after change in the position of the circuit breaker. The
SOTF function has a set time delay. The Under Time function, which have 2nd
harmonic restrain blocking, will give operation from step 4. The 2nd harmonic
restrain will prevent unwanted function in case of transformer inrush current. The
Under Time function has a set time delay.
ActivationSOTF: This setting will select the signal to activate SOTF function; CB
position open/CB position closed/CB close command.
tSOTF: Time delay for operation of the SOTF function. The setting range is 0.000 -
60.000 s in step of 0.001 s. The default setting is 0.100 s
step3ForSOTF: If this parameter is set on the step 3 start signal will be used as current
set level. If set off step 2 start signal will be used as current set level.
t4U: Time interval when the SOTF function is active after breaker closing. The setting
range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 5.000 s.
ActUnderTime: Describes the mode to activate the sensitive undertime function. The
function can be activated by Circuit breaker position (change) or Circuit breaker
command.
tUnderTime: Time delay for operation of the sensitive undertime function. The setting
range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 0.300 s
The protection measures the residual current out on the protected line. The protection
function has a directional function where the residual voltage (zero sequence voltage)
is the polarizing quantity.
The residual voltage can be internally generated when a three phase set of voltage
transformers are used.
IN>
xx05000149.vsd
Step 1
This step has directional instantaneous function. In the setting the requirement is that
overreaching of the protected line is not allowed.
3I0
IN >
One- or two
phase earthfault
en05000150.vsd
The residual current out on the line is calculated at a fault on the adjacent busbar (one-
or two phase to earth fault). To assure selectivity it is required that step 1 shall not
give a trip at this fault. The requirement can be formulated according to
equation 36.
3I0
IN >
Figure 45: Step 1, second calculation. Adjacent busbar, one line taken out of
service
A special case occurs at double circuit lines, with mutual zero sequence impedance
between the parallel lines, see figure 46.
3I0
IN >
In this case the residual current out on the line can be larger than in the case of earth
fault on the adjacent busbar.
The current setting for step 1 is chosen as the largest of the above calculated residual
currents, measured by the protection.
Step 2
This step has directional function and a short time delay, often about 0.4 s. Step 2
shall securely detect all earthy faults on the line, not detected by step 1.
3I0
IN >
The residual current, out on the line, is calculated at an operational case with minimal
earth fault current. The requirement that the whole line shall be covered by step 2 can
be formulated according to equation 39.
To assure selectivity the current setting must be chosen so that step 2 does not operate
at step 2 operation on a line from the adjacent substation. Consider a fault as shown
in figure 48.
3I0 3I0x
IN > IN >
3I 0
Istep 2 ³ 1.2 * * Istep1x
3I 0 x (Equation 40)
where:
Istep1x is the current setting for step 1 on the faulted line.
Step 3
This step has directional function and a time delay slightly larger than step 2, often
0.8 s. Step 3 shall enable selective trip of earth faults having some fault resistance to
earth, so that step 2 is not activated. The requirement on step 3 is selectivity to other
earth fault protections in the network. One criterion for setting is shown in
figure 49.
3I0 3I0x
IN > IN >
One phase
earth fault
en05000156.vsd
3I 0
Istep 3 ³ 1.2 * * Istep 2 x
3I 0 x (Equation 41)
where:
Istep2x is the chosen current setting for step 2 on the faulted line.
Step 4
This step normally has non-directional function and a relatively long time delay. The
task for step 4 is to detect and initiate trip for earth faults with large fault resistance,
for example tree faults. Step 4 shall also detect series faults where one or two poles,
of a breaker or other switching device, are open while the other poles are closed.
Both high-resistance earth faults and series faults give zero sequence current flow in
the network. Such currents give disturbances on telecommunication systems and
current to earth. It is important to clear such faults both concerning personal security
as well as risk of fire.
The current setting for step 4 is often set down to about 100 A (primary 3I0). In many
applications definite time delay in the range 1.2 - 2.0 s is used. In other applications
a current dependent inverse time characteristic is used. This enables a higher degree
of selectivity also for sensitive earth fault current protection.
Table 30: Parameter group settings for the EF4PEFM_51N67N (TEF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation mode Off /
On On
IBase 1 - 99999 1 3000 A Base setting for
current values
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage level in kV
IMinOpFund 1 - 2500 1 3 %IB Minimum
fundamental
frequency current
level in % of IBase
AngleRCA -180 - 180 1 65 Deg Relay characteristic
angle (RCA)
3UO>Dir 1 - 100 1 5 %UB Minimum polarizing
quantity in % of
UBase
IN>DirCmp 1 - 100 1 3 %IB Operate residual
current level for
DirComp in % of
IBase
tDirCmp 0.000 - 60.000 0.001 10.000 s Time delay for
DirComp
2ndHarmStab 5 - 100 1 20 % Second harmonic
restrain operation in
% of INAMPL
UseStartValue IN1> - IN1> - Current level blk at
IN2> parallel transf (step1,
IN3> 2, 3 or 4)
IN4>
BlkParTransf Off - Off - Enable blocking at
On parallel transformers
Table continued on next page
4.6.5.1 Application
Lines and cables in the power system are constructed for a certain maximum load
current level. If the current exceeds this level the losses will be higher than expected.
As a consequence the temperature of the conductors will increase. If the temperature
of the lines and cables reaches too high values the equipment might be damaged:
In stressed situations in the power system it can be required to overload lines and
cables for limited time. This should be done without risk for the above-mentioned
risks.
If the temperature of the protected object reaches a set warning level AlarmTemp a
signal can be given to the operator. This enables actions in the power system to be
done before dangerous temperatures are reached. If the temperature continues to
increase to the trip value TripTemp, the protection initiates trip of the protected line.
The parameters for the thermal overload function (THL) are set via the local HMI or
Protection and Control IED Manager (PCM 600).
The following settings can be done for the thermal overload protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the protected
object.
Imult: If the protection measures one of a number of parallel line currents the number
of parallel circuits is given in this setting.
IRef: Reference, steady state current, given in % of IBase that will give a steady state
(end) temperature TRef. It is suggested to set this current to the maximum steady state
current allowed for the line/cable under emergency operation (a few hours per year).
Tau: The thermal time constant of the protected circuit given in minutes. Please refer
to manufacturers manuals for details.
TripTemp: Temperature value for trip of the protected circuit. For cables a maximum
allowed conductor temperature is often stated to be 90°C. For overhead lines the
critical temperature for aluminium conductor is about 90 - 100°C. For a copper
conductor a normal figure is 70°C.
AlarmTemp: Temperature value for alarm of the protected circuit. This signal can be
used as a warning before the circuit is tripped. Therefore the setting shall be lower
than the trip level. It shall at the same time be higher than the maximum conductor
temperature at normal operation. For cables this level is often given to 65°C. Similar
values are stated for overhead lines. A suitable setting can be about 15°C below the
trip value.
Table 31: Parameter group settings for the LPTTR_26 (THL1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
HystTemp 0 - 50 1 10 - Hysteresis for start
temperature
IBase 0 - 99999 1 3000 A Base current in A
IMult 1-5 1 1 - Current multiplier
when THOL is used
for two or more lines
IRef 0 - 400 1 100 %IB The load current (in
%of IBase) leading to
TRef temperature
TRef 0 - 400 1 90 Deg C End temperature of
the line when loaded
with IRef
Tau 0 - 1000 1 45 Min Time constant of the
line in minutes.
TripTemp 0 - 400 1 90 Deg C Temperature level for
trip
AlarmTemp 0 - 200 1 80 Deg C Temperature level for
start (alarm)
ReclTemp 0 - 400 1 75 Deg C Temperature for reset
of lockout after trip
4.6.6.1 Application
Transformers in the power system are constructed for a certain maximum load current
(power) level. If the current exceeds this level the losses are higher than expected. As
a consequence the temperature of the transformer will increase. If the temperature of
the transformer reaches too high values the equipment might be damaged:
• The insulation within the transformer will have forced ageing. As a consequence
of this the risk of internal phase to phase or phase to earth faults will increase.
• There might be hot spots within the transformer. This will degrade the quality of
the transformer oil.
The permissible load level of a power transformer is highly dependent on the cooling
system of the transformer. We have two main principles:
• ONAN: The air is naturally circulated to the coolers without fans and the oil is
naturally circulated without pumps.
• OFAF: The coolers have fans to force air for cooling and pumps to force the
circulation of the transformer oil.
The protection can have two sets of parameters, one for non-forced cooling and one
for forced cooling. Both the permissive steady state loading level as well as the
thermal time constant is influenced by the cooling system of the transformer. The
activation of the two parameter sets can be switched by activation of binary input
signals COOLING to the function. This can be used for transformers where forced
cooling can be taken out of operation, for example at fan or pump faults.
The thermal overload protection estimates the internal heat content of the transformer
(temperature) continuously. This estimation is made by using a thermal model of the
transformer, which is based on current measurement.
If the heat content of the protected transformer reaches a set warning level a signal
can be given to the operator. Two warning levels are available. This enables actions
in the power system to be done before dangerous temperatures are reached. If the
temperature continues to increase to the trip value, the protection initiates trip of the
protected transformer.
After trip from the thermal overload protection the transformer will be cooling. There
will be a time gap before the heat content (temperature) reaches a level so that the
transformer can be taken into service again. Therefore the protection will continue to
estimate the heat content using a set cooling time constant. Energizing of the
transformer can be blocked until the heat content is reduced to a set level.
The parameters for the thermal overload protection, two time constants function
(TTR) are set via the local HMI or Protection and Control IED Manager (PCM 600).
The following settings can be done for the thermal overload protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the transformer
winding where the current measurement is made.
IRef: Reference level of the current given in % of IBase. When the current is equal
to IRef the final (steady state) heat content is equal to 1. It is suggested to give a setting
corresponding to the rated power of the transformer winding.
IRefMult: If a binary input ENMULT is activated the reference current value can be
multiplied by the factor IRefMult. The activation could be used in case of deviating
ambient temperature from the reference value. In the standard for loading of a
transformer an ambient temperature of 20°C is used. For lower ambient temperatures
the load ability is increased and vice versa. IRefMult can be set within a range: 0.01
- 10.00.
IBase1: Base current for setting given as percentage of IBase. This setting shall be
related to the status Off of COOLING input. It is suggested to give a setting
corresponding to the rated power of the transformer with natural cooling (ONAN).
IBase2: Base current for setting given as percentage of IBase. This setting shall be
related to the status On of COOLING input. It is suggested to give a setting
corresponding to the rated power of the transformer with forced cooling (OFAF). If
the transformer has no forced cooling IBase2 can be set equal to IBase1.
Tau1: The thermal time constant of the protected transformer, related to IBase1 (input
Off) given in minutes.
Tau2: The thermal time constant of the protected transformer, related to IBase2 (input
On) given in minutes.
The thermal time constant can be obtained from the manufacturers manuals. The
thermal time constant is dependent on the cooling and the amount of oil. Normal time
constants for medium and large transformers (according to IEC 60354) are about 2.5
hours for naturally cooled transformers and 1.5 hours for forced cooled transformers.
The time constant can be estimated from measurements of the oil temperature during
a cooling sequence (described in IEC 60354). It is assumed that the transformer is
operated at a certain load level with a constant oil temperature (steady state operation).
The oil temperature above the ambient temperature is DQo0. The transformer is
disconnected from the grid (no load). After a time t of at least 30 minutes the
temperature of the oil is measured again. Now the oil temperature above the ambient
temperature is DQot. The thermal time constant can now be estimated as:
t
t=
ln DQo 0 - ln DQ ot
(Equation 42)
If the transformer has forced cooling (OFAF) the measurement should be made both
with and without the forced cooling in operation, giving Tau2 and Tau1.
The time constants can be changed if the current is higher than a set value or lower
than a set value. If the current is high it is assumed that the forced cooling is activated
while it in deactivated at low current. The setting of the parameters below enables
automatic adjustment of the time constant.
Tau1High: Multiplication factor to adjust the time constant Tau1 if the current is
higher than the set value IHighTau1. IHighTau1 is set in % of IBase1.
Tau1Low: Multiplication factor to adjust the time constant Tau1 if the current is lower
than the set value ILowTau1. ILowTau1 is set in % of IBase1.
Tau2High: Multiplication factor to adjust the time constant Tau2 if the current is
higher than the set value IHighTau2. IHighTau2 is set in % of IBase2.
Tau2Low: Multiplication factor to adjust the time constant Tau2 if the current is lower
than the set value ILowTau2. ILowTau2 is set in % of IBase2.
The possibility to change time constant with the current value as the base can be useful
in different applications. Below some examples are given:
• In case a total interruption (low current) of the protected device all cooling
possibilities will be inactive. This can result in a changed value of the time
constant.
• If other components (motors) are included in the thermal protection function,
there is a risk of overheating of that equipment in case of very high current. The
thermal time constant is often smaller for a motor than for the transformer.
ITrip: The steady state current that steady state continuous current that the transformer
can withstand. The setting is given in % of Ibasex.
Alarm1: Heat content level for activation of the signal Alarm1. Alarm1 is set in % of
the trip heat content level.
Alarm2: Heat content level for activation of the signal Alarm2. Alarm2 is set in % of
the trip heat content level.
ResLo: Lockout release level of heat content to release the lockout signal. When the
thermal overload protection trips a lock-out signal is activated. This signal is intended
to block switch in of the protected circuit (transformer) as long as the transformer
temperature is high. The signal is released when the estimated heat content is below
the set value. This temperature value should be chosen below the alarm temperature.
ResLo is set in % of the trip heat content level.
ThetaInit: Heat content before activation of the function. This setting can be set a
little below the alarm level. If the transformer is loaded before the activation of the
protection function, its temperature can be higher than the ambient temperature. The
start point given in the setting will prevent risk of no trip at overtemperature during
the first moments after activation. ThetaInit is set in % of the trip heat content level.
Warning: If the calculated time to trip factor is below the setting Warning a warning
signal is activated. The setting is given in minutes.
Table 32: Parameter group settings for the TRPTTR_49 (TTR1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base current in A
IRef 10.0 - 1000.0 1.0 100.0 %IB Reference current in
% of IBASE
IRefMult 0.01 - 10.00 0.01 1.00 - Multiplication Factor
for reference current
IBase1 30.0 - 250.0 1.0 100.0 %IB Base current,IBase1
without Cooling
inpout in % of IBASE
IBase2 30.0 - 250.0 1.0 100.0 %IB Base Current,IBase2,
with Cooling input ON
in % of IBASE
Tau1 1.0 - 500.0 1.0 60.0 Min Time constant without
cooling input in min,
with IBase1
Tau2 1.0 - 500.0 1.0 60.0 Min Time constant with
cooling input in min,
with IBase2
IHighTau1 30.0 - 250.0 1.0 100.0 %IB1 Current Sett, in % of
IBase1 for rescaling
TC1 by TC1-IHIGH
Tau1High 5 - 2000 1 100 %tC1 Multiplier in % to TC1
when current is >
IHIGH-TC1
ILowTau1 30.0 - 250.0 1.0 100.0 %IB1 Current Set, in % of
IBase1 for rescaling
TC1 by TC1-ILOW
Tau1Low 5 - 2000 1 100 %tC1 Multiplier in % to TC1
when current is <
ILOW-TC1
IHighTau2 30.0 - 250.0 1.0 100.0 %IB2 Current Set, in % of
IBase2 for rescaling
TC2 by TC2-IHIGH
Tau2High 5 - 2000 1 100 %tC2 Multiplier in % to TC2
when current is
>IHIGH-TC2
Table continued on next page
4.6.7.1 Application
In the design of the fault clearance system the N-1 criterion is often used. This means
that a fault shall be cleared even if any component in the fault clearance system is
faulty. One necessary component in the fault clearance system is the circuit breaker.
It is from practical and economical reason not feasible to duplicate the circuit breaker
for the protected component. Instead a breaker failure protection is used.
The breaker protection function will issue a back-up trip command to adjacent circuit
breakers in case of failure to trip of the “normal” circuit breaker for the protected
component. The detection of failure to break the current through the breaker is made
by means of current measurement or as detection of remaining trip signal
(unconditional).
The breaker failure protection can also give a re-trip. This means that a second trip
signal is sent to the protected circuit breaker. The re-trip function can be used to
increase the probability of operation of the breaker, or it can be used to avoid back-
up trip of many breakers in case of mistakes during relay maintenance and test.
The parameters for the breaker failure protection function (BFP) are set via the local
HMI or Protection and Control IED Manager (PCM 600).
The following settings can be done for the breaker failure protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the current
transformer where the current measurement is made.
FunctionMode: This parameter can be set Current/Contact. This states the way the
detection of failure of the breaker is performed. In the mode current the current
measurement is used for the detection. In the mode Contact the long duration of start
signal (trip) is used as indicator of failure of the breaker. The mode Current and
Contact means that both ways of detections are activated. Contact mode can be usable
in applications where the fault current through the circuit breaker is small. This can
be the case for some generator protection application (for example reverse power
protection) or in case of line ends with weak end infeed.
BuTripMode: Back-up trip mode is given to state sufficient current criteria to detect
failure to break. 2 out of 4 means that at least 2 currents, of the three phase currents
and the residual current, shall be high to indicate breaker failure. 1 out of 3 means
that at least 1 current of the three phase currents shall be high to indicate breaker
failure. 1 out of 4 means that at least 1 current of the three phase currents or the residual
current shall be high to indicate breaker failure. In most applications 1 out of 3 is
sufficient.
RetripMode: This setting states how the re-trip function shall operate. Retrip Off
means that the re-trip function is not activated. I> check means that a phase current
must be larger than the operate level to allow re-trip. No I> check means re-trip is
done without current check.
IP>: Current level for detection of breaker failure, set in % of IBase. This parameter
should be set so that faults with small fault current can be detected. The setting can
be chosen in accordance with the most sensitive protection function to start the breaker
failure protection. Typical setting is 10% of IBase.
I>BlkCont: If any contact based detection of breaker failure is used this function can
be blocked if any phase current is larger than this setting level. If the
FunctionMode is set Current and Contact breaker failure for high current faults are
safely detected by the current measurement function. To increase security the contact
based function should be disabled for high currents. The setting can be given within
the range 5 – 200% of IBase.
IN>: Residual current level for detection of breaker failure set in % of IBase. In high
impedance earthed systems the residual current at phase to earth faults are normally
much smaller than the short circuit currents. In order to detect breaker failure at single-
phase earth faults in these systems it is necessary to measure the residual current
separately. Also in effectively earthed systems the setting of the earth fault current
protection can be chosen to relatively low current level. The BuTripMode is set 1 out
of 4. The current setting should be chosen in accordance to the setting of the sensitive
earth fault protection. The setting can be given within he range 2 – 200 % of IBase.
t1: Time delay of the re-trip. The setting can be given within the range 0 – 60 s in
steps of 0.001 s. Typical setting is 0 – 50 ms.
t2: Time delay of the back-up trip. The choice of this setting is made as short as
possible at the same time as unwanted operation must be avoided. Typical setting i
90 – 150 ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
where:
tcbopen is the maximum opening time for the circuit breaker
tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (the current
criteria reset)
tmargin is a safety margin
It is often required that the total fault clearance time shall be less than a given critical
time. This time is often dependent of the ability to maintain transient stability in case
of a fault close to a power plant.
Protection
operate time
Normal tcbopen
Time
en05000479.vsd
t2MPh: Time delay of the back-up trip at multi-phase start. The critical fault clearance
time is often shorter in case of multi-phase faults, compared to single phase to earth
faults. Therefore there is a possibility to reduce the back-up trip delay for multi-phase
faults. Typical setting is 90 – 150 ms.
t3: Additional time delay to t2 for a second back-up trip TRBU2. In some applications
there might be a requirement to have separated back-up trip functions, tripping
different back-up circuit breakers.
tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker. There
is a binary input CBFLT from the circuit breaker. This signal is activated when
internal supervision in the circuit breaker detect that the circuit breaker is unable to
clear fault. This could be the case when gas pressure is low in a SF6 circuit breaker,
of others. After the set time an alarm is given, so that actions can be done to repair
the circuit breaker. The time delay for back-up trip is bypassed when the CBFLT is
active. Typical setting is 2.0 seconds.
tPulse: Trip pulse duration. This setting must be larger than the critical impulse time
of circuit breakers to be tripped from the breaker failure protection. Typical setting
is 200 ms.
Table 33: Parameter group settings for the CCRBRF_50BF (BFP1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current level settings
FunctionMode Current - Current - Detection for back-up
Contact trip Current/Cont/
Current&Contact Current and Cont
BuTripMode 2 out of 4 - 1 out of 3 - Back-up trip mode, 2
1 out of 3 out of 4, 1 out of 3 or
1 out of 4 1 out of 4
RetripMode Retrip Off - Retrip Off - Operation mode of re-
I> Check trip logic: OFF/I>
No I> Check check/No I> check
IP> 5 - 200 1 10 %IB Operate level in % of
IBase
I>BlkCont 5 - 200 1 20 %IB Current for blocking of
CB contact operation
in % of IBase
IN> 2 - 200 1 10 %IB Operate residual level
in % of IBase
t1 0.000 - 60.000 0.001 0.000 s Time delay of re-trip
t2 0.000 - 60.000 0.001 0.150 s Time delay of back-up
trip
t2MPh 0.000 - 60.000 0.001 0.150 s Time delay of back-up
trip at multi-phase
start
t3 0.000 - 60.000 0.001 0.030 s Additional time delay
to t2 for a second
back-up trip
tCBAlarm 0.000 - 60.000 0.001 5.000 s Time delay for CB
faulty signal
tPulse 0.000 - 60.000 0.001 0.200 s Trip pulse duration
4.6.8.1 Application
In a 1½-breaker switchyard the line protection and the busbar protection normally
have overlap when a connected object is in service. When an object is taken out of
service it is normally required to keep the diagonal of the 1½-breaker switchyard in
operation. This is done by opening the disconnector to the protected object. This will,
however, disable the normal object protection (for example the distance protection)
of the energized part between the circuit breakers and the open disconnector.
The stub protection is a simple phase overcurrent protection, fed from the two current
transformer groups feeding the object taken out of service. The Stub protection is
only activated when the disconnector of the object is open. The stub protection enables
fast fault clearance of faults at the section between the CT:s and the open disconnector.
Open
Disconnector
REx
670
en05000465.vsd
Figure 51: Typical connection for stub protection in 1 1/2 breaker arrangement.
The parameters for the stub protection function (STB) are set via the local HMI or
Protection and Control IED Manager (PCM 600).
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the current
transformer where the current measurement is made.
ReleaseMode: This parameter can be set Release or Continuous. With the Release
setting the function is only active when a binary release signal RELEASE into the
function is activated. This signal is normally taken from an auxiliary contact
(normally closed) of the line disconnector and connected to a binary input RELEASE
of the IED. With the setting Continuous the function is activated independent of
presence of any external release signal.
I>: Current level for the Stub protection, set in % of IBase. This parameter should be
set so that all faults on the stub can be detected. The setting should thus be based on
fault calculations.
Table 34: Parameter group settings for the STBPTOC_50STB (STB1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
ReleaseMode Release - Release - Release of stub
Continuous protection
I> 1 - 2500 1 200 %IB Operate current level
in % of IBase
t 0.000 - 60.000 0.001 0.000 s Time delay
4.6.9.1 Application
There is a risk that a circuit breaker will get discordance between the poles at circuit
breaker operation: closing or opening. One pole can be open and the other two closed,
or two poles can be open and one closed. Pole discordance of a circuit breaker will
case unsymmetrical currents in the power system. The consequence of this can be:
The pole discordance protection will detect situation with deviating positions of the
poles of the protected circuit breaker. The protection has two different options to
make this detection:
The parameters for the pole-discordance protection function (PDx) are set via the
local HMI or Protection and Control IED Manager (PCM 600).
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the protected
object where the current measurement is made.
ContSel: Operation of the contact based pole discordance function. Can be set: Off/
PD signal fromCB/Pole pos aux. cont. If PD signal fromCB is chosen the logic to
detect pole discordance is made close to the breaker auxiliary contacts and only one
signal is connected to the IED. If the CB/Pole pos aux cont. alternative is chosen each
open close signal is connected to the IED and the logic to detect pole discordance is
realised within the function itself.
CurrSel: Operation of the current based pole discordance function. Can be set: Off/
CB open monitor/Continuous monitor. In the alternative CB open monitor the
function is activated only directly in connection to breaker open or close command
(during 200 ms). In the alternative Continuous monitor function is continuously
activated.
CurrRelLevel: Current level of the largest phase current to allow operation of the
current.
Table 35: Parameter group settings for the CCRPLD_52PD (PD01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current levels
TimeDelayTrip 0.000 - 60.000 0.001 0.300 s Time delay between
trip condition and trip
signal
ContSel Off - Off - Contact function
PD signal from CB selection
Pole pos aux cont.
CurrSel Off - Off - Current function
CB oper monitor selection
Continuous
monitor
CurrUnsymLevel 0 - 100 1 80 % Unsym magn of
lowest phase current
compared to the
highest.
CurrRelLevel 0 - 100 1 10 %IB Current magnitude for
release of the function
in % of IBase
4.7.1.1 Application
The parameters for the two-step undervoltage protection function (TUV) are set via
the local HMI or Protection and Control IED Manager (PCM 600).
All the voltage conditions in the system where the TUV performs its functions should
be considered. The same also applies to the associated equipment, its voltage and
time characteristic.
There is a very wide application area where general undervoltage functions are used.
All voltage related settings are made as a percentage of a settable base voltage, which
normally is set to the primary nominal voltage level (phase-phase) of the power
system or the high voltage equipment under consideration.
The for the TUV function is normally not critical, since there must be enough time
available for the main protection to clear short-circuits and earth-faults.
Below, some applications and related setting guidelines for the voltage level are
given:
The following settings can be done for the two step undervoltage
protection.
Operation: Off/On
UBase: Base voltage phase to phase in primary kV. This voltage is used as reference
for voltage setting. It can be suitable to set this parameter to the rated primary voltage
of the voltage transformer where the current measurement is made. The undervoltage
protection function measures the phase to earth voltages, if the voltage transformer
is connected phase to earth to the analogue voltage inputs. The setting of the analogue
inputs are given as primary phase to phase voltage and secondary phase to phase
voltage. The function will operate if the phase to earth voltage gets lover than the set
percentage of the phase to earth voltage corresponding to the set base voltage
UBase. This means operation for phase to earth voltage under:
The below described setting parameters are identical for the two steps. Therefore the
setting parameters are described only once.
Characteristicn: This parameter gives the type of time delay to be used. The setting
can be. Definite time/Inverse Curve A/Inverse Curve B/Prog. inv. curve. The choice
is highly dependent of the protection application.
OpModen: This parameter describes how many of the three measured voltages that
should be below the set level to give operation. The setting can be. 1 out of 3/2 out
of 3/3 out of 3. In most applications it is sufficient that one phase voltage is low to
give operation. If the function shall be insensitive for single phase to earth faults 2
out of 3 can be chosen
Un<: Set operate undervoltage operation value for step n, given as % of Ubase. The
setting is highly dependent of the protection application. Here it is essential to
consider the minimum voltage at non-faulted situations. Normally this voltage is
larger than 90% of nominal voltage.
tn: time delay of step n, given in s. The setting is highly dependent of the protection
application. In many applications the protection function shall not directly trip in case
of short circuits or earth faults in the system. The time delay must be co-ordinated to
the short circuit protections.
tResetn: Reset time for step n if definite time delay is used, given in s. The default
value is 25 ms.
tnMin: Minimum operation time for inverse time characteristic for step n, given in s.
For very low voltages the undervoltage function, using inverse time characteristic,
can give very short operation time. This might lead to unselective trip. By setting
t1Min longer than the operation time for other protections such unselective tripping
can be avoided.
tIResetn: Reset time for step n if inverse time delay is used, given in s. The default
value is 25 ms.
kn: Time multiplier for inverse time characteristic. This parameter is used for co-
ordination between different inverse time delayed undervoltage protections.
CrvSatn: When the denominator in the expression of the programmable curve is equal
to zero the time delay will be infinity. There will be an undesired discontinuity.
Therefore a tuning parameter CrvSatn is set to compensate for this phenomenon. In
the voltage interval U> up to U> *(1.0 - CrvSatn/100) the used voltage will be: U>
*(1.0 - CrvSatn/100). If the programmable curve is used this parameter must be
calculated so that:
CrvSatn
B× -C > 0
100 (Equation 45)
IntBlkSeln: This parameter can be set: Off/Block of trip/Block all. In case of a low
voltage the undervoltage function can be blocked. This function can be used to prevent
function when the protected object is switched off. If the parameter is set Block of
trip or Block all this unwanted trip is prevented.
tBlkUVn: Time delay the undervoltage step n when the voltage level is below
IntBlkStValn, given in s. It is important that this delay is shorter than the operate time
delay of the undervoltage protection step.
Table 36: Basic parameter group settings for the PH2PUVM_27 (TUV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A characteristic
Inverse curve B selection, step 1
Prog. inv. curve
OpMode1 1 out of 3 - 1 out of 3 - Operation Mode, 1
2 out of 3 out of 3 / 2 out of 3 / 3
3 out of 3 out of 3, step 1
U1< 1 - 100 1 70 %UB Voltage setting/start
val (DT & IDMT) in %
of UBase, step 1
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
k1 0.05 0.01 0.05 - 1.10 - Time multiplier in
IDMT mode, step 1
Table continued on next page
Table 37: Advanced parameter group settings for the PH2PUVM_27 (TUV1-) function
Parameter Range Step Default Unit Description
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
ACrv1 1.000 0.001 0.005 - 200.000 - Setting A for
programmable under
voltage IDMT curve,
step 1
BCrv1 1.00 0.01 0.50 - 100.00 - Setting B for
programmable under
voltage IDMT curve,
step 1
CCrv1 0.0 0.1 0.0 - 1.0 - Setting C for
programmable under
voltage IDMT curve,
step 1
DCrv1 0.000 0.001 0.000 - 60.000 - Setting D for
programmable under
voltage IDMT curve,
step 1
PCrv1 1.000 0.001 0.000 - 3.000 - Setting P for
programmable under
voltage IDMT curve,
step 1
CrvSat1 0 - 100 1 0 % Tuning param for
prog. under voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 2
ResetTypeCrv2 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 2
Linearly
decreased
tIReset2 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 2
ACrv2 1.000 0.001 0.005 - 200.000 - Setting A for
programmable under
voltage IDMT curve,
step 2
BCrv2 1.00 0.01 0.50 - 100.00 - Setting B for
programmable under
voltage IDMT curve,
step 2
CCrv2 0.0 0.1 0.0 - 1.0 - Setting C for
programmable under
voltage IDMT curve,
step 2
Table continued on next page
4.7.2.1 Application
High voltage conditions are caused by abnormal situations in the power system. The
overvoltage protection is applied to power system elements, such as generators,
transformers, motors and power lines in order to detect high voltage conditions. The
overvoltage protection can be used in combination with low current signals, to
identify a transmission line, open in the remote end. The overvoltage protection is
also used to initiate voltage correction measures, like insertion of shunt reactors, to
compensate for low load, and thereby decreasing the voltage. The overvoltage
protection can be used to disconnect, from the network, apparatuses, like electric
motors, which will be damaged when subject to service under high voltage conditions.
TOV deals with high voltage conditions at power system frequency, which can be
caused by:
1. Different kinds of faults, where a too high voltage appears in a certain power
system, like metallic connection to a higher voltage level (broken conductor
falling down to a crossing overhead line, transformer flash over fault from the
high voltage winding to the low voltage winding, etc.).
2. Malfunctioning of a voltage regulator or wrong settings under manual control
(symmetrical voltage decrease).
3. Low load compared to the reactive power generation (symmetrical voltage
decrease).
4. Earth-faults in high impedance earthed systems causes, beside the high voltage
in the neutral, high voltages in the two non-faulted phases, (unsymmetrical
voltage increase).
The parameters for the two-step overvoltage protection function (TOV) are set via
the local HMI or Protection and Control IED Manager (PCM600).
All the voltage conditions in the system where TOV performs its functions should be
considered. The same also applies to the associated equipment, its voltage and time
characteristic.
There is a very wide application area where general overvoltage functions are used.
All voltage related settings are made as a percentage of a settable base primary
voltage, which normally is set to the nominal voltage level (phase-phase) of the power
system or the high voltage equipment under consideration.
The time delay for the TOV function can sometimes be critical and related to the size
of the overvoltage - a power system or a high voltage component can withstand
smaller overvoltages for some time, but in case of large overvoltages the related
equipment should be disconnected more rapidly.
Below, some applications and related setting guidelines for the voltage level are
given:
The following settings can be done for the two step overvoltage
protection
Operation: Off/On
UBase: Base voltage phase to phase in primary kV. This voltage is used as reference
for voltage setting. It can be suitable to set this parameter to the rated primary voltage
of the voltage transformer where the current measurement is made. The overvoltage
protection function measures the phase to earth voltages, if the voltage transformer
is connected phase to earth to the analogue voltage inputs. The setting of the analogue
inputs are given as primary phase to phase voltage and secondary phase to phase
voltage. The function will operate if the phase to earth voltage gets lover than the set
percentage of the phase to earth voltage corresponding to the set base voltage
UBase. This means operation for phase to earth voltage over:
The below described setting parameters are identical for the two steps. Therefore the
setting parameters are described only once.
Characteristicn: This parameter gives the type of time delay to be used. The setting
can be. Definite time/Inverse Curve A/Inverse Curve B/Inverse Curve C/Prog. inv.
curve. The choice is highly dependent of the protection application.
OpModen: This parameter describes how many of the three measured voltages that
should be above the set level to give operation. The setting can be. 1 out of 3/2 out of
3/3 out of 3. In most applications it is sufficient that one phase voltage is high to give
operation. If the function shall be insensitive for single phase to earth faults 1 out of
3 can be chosen, because the voltage will normally rise in the non-faulted phases at
single phase to earth faults.
Un>: Set operate overvoltage operation value for step n, given as % of Ubase. The
setting is highly dependent of the protection application. Here it is essential to
consider the Maximum voltage at non-faulted situations. Normally this voltage is less
than 110% of nominal voltage.
tn: time delay of step n, given in s. The setting is highly dependent of the protection
application. In many applications the protection function has the task to prevent
damages to the protected object. The speed might be important for example in case
of protection of transformer that might be overexcited. The time delay must be co-
ordinated with other automated actions in the system.
tResetn: Reset time for step n if definite time delay is used, given in s. The default
value is 25 ms.
tnMin: Minimum operation time for inverse time characteristic for step n, given in s.
For very high voltages the overvoltage function, using inverse time characteristic,
can give very short operation time. This might lead to unselective trip. By setting
t1Min longer than the operation time for other protections such unselective tripping
can be avoided.
tIResetn: Reset time for step n if inverse time delay is used, given in s. The default
value is 25 ms.
kn: Time multiplier for inverse time characteristic. This parameter is used for co-
ordination between different inverse time delayed undervoltage protections.
CrvSatn: When the denominator in the expression of the programmable curve is equal
to zero the time delay will be infinity. There will be an undesired discontinuity.
Therefore a tuning parameter CrvSatn is set to compensate for this phenomenon. In
the voltage interval U> up to U>·(1.0 + CrvSatn/100) the used voltage will be:
U>·(1.0 + CrvSatn/100). If the programmable curve is used this parameter must be
calculated so that:
CrvSatn
B× -C > 0
100 (Equation 47)
Table 38: Parameter group settings for the PH2POVM_59 (TOV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A charcteristic
Inverse curve B selection, step 1
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - 1 out of 3 - Operation mode, 1
2 out of 3 out of 3 / 2 out of 3 / 3
3 out of 3 out of 3, step 1
U1> 1 - 200 1 120 %UB Voltage setting/start
val (DT & IDMT) in %
of UBase, step 1
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
k1 0.05 - 1.10 0.01 0.05 - Time multiplier in
IDMT mode, step 1
ACrv1 0.005 - 200.000 0.001 1.000 - Setting A for
programmable over
voltage IDMT curve,
step 1
BCrv1 0.50 - 100.00 0.01 1.00 - Setting B for
programmable over
voltage IDMT curve,
step 1
CCrv1 0.0 - 1.0 0.1 0.0 - Setting C for
programmable over
voltage IDMT curve,
step 1
DCrv1 0.000 - 60.000 0.001 0.000 - Setting D for
programmable over
voltage IDMT curve,
step 1
PCrv1 0.000 - 3.000 0.001 1.000 - Setting P for
programmable over
voltage IDMT curve,
step 1
Table continued on next page
4.7.3.1 Application
The two-step residual overvoltage protection function (TRV) is primarily used in high
impedance earthed distribution networks, mainly as a backup for the primary earth-
fault protection of the feeders and the transformer. To increase the security for
different earth-fault related functions, the residual overvoltage signal can be used as
a release signal. The residual voltage can be measured either at the transformer neutral
or from a voltage transformer open delta connection. The residual voltage can also
be calculated internally, based on measurement of the three phase-voltages.
In high impedance earthed systems the system neutral voltage, i.e. the residual
voltage, will increase in case of any fault connected to earth. Depending on the type
of fault and fault resistance the residual voltage will reach different values. The
highest residual voltage, equal to the phase-earth voltage, is achieved for a single
phase-earth fault. The residual voltage will increase approximately the same amount
in the whole system and does not provide any guidance in finding the faulted
component. Therefore TRV is often used as a backup protection or as a release signal
for the feeder earth-fault protection.
The parameters for the two-step residual overvoltage protection function (TRV) are
set via the local HMI or Protection and Control IED Manager (PCM 600).
All the voltage conditions in the system where the TRV performs its functions should
be considered. The same also applies to the associated equipment, its voltage and
time characteristic.
There is a very wide application area where general single input or residual
overvoltage functions are used. All voltage related settings are made as a percentage
of a settable base voltage, which can be set to the primary nominal voltage (phase-
phase) level of the power system or the high voltage equipment under consideration.
The time delay for the TRV function are seldom critical, since residual voltage is
related to earth-faults in a high impedance earthed system, and enough time must
normally be give single input for the primary protection to clear the fault. In some
more specific situations, where the single overvoltage protection is used to protect
some specific equipment the time delay can be shorter.
Below, some applications and related setting guidelines for the residual voltage level
are given.
The voltage transformers measuring the phase to earth voltages will then measure
zero voltage in the faulty phase. The two healthy phases will measure full phase to
phase voltage, as the earth is available on the faulty phase and the neutral has a full
phase to earth voltage. The residual overvoltage will be three time the phase to earth
voltage. See figure "".
The following settings can be done for the two step residual overvoltage
protection
Operation: Off/On
UBase: This voltage is used as reference for the voltage setting. We have different
possibilities to feed the IED for this protection function.
1.The IED is fed from a normal voltage transformer group where the residual voltage
is created from the phase to earth voltages within the protection software. The setting
of the analogue input is given as:
2.The IED is fed from a broken delta connection normal voltage transformer group.
In a open delta connection the protection is fed by the voltage 3U0 (single input). The
setting of the analogue input is given as the ratio of the voltage transformer e.g 230/
√3/110 or 20/√3 /(110/3).
3.The IED is fed from a single voltage transformer connected to the neutral point of
a power transformer in the power system. In this connection the protection is fed by
the voltage UN (single input). The setting of the analogue input is given as primary
phase to earth voltage and secondary phase to earth voltage. The protection function
will measure the residual voltage corresponding nominal phase to earth voltage. The
measurement will be based on the neutral voltage displacement.
The below described setting parameters are identical for the two steps. Therefore the
setting parameters are described only once.
Characteristicn: This parameter gives the type of time delay to be used. The setting
can be. Definite time/Inverse Curve A/Inverse Curve B/Inverse Curve C/Prog. inv.
curve. The choice is highly dependent of the protection application.
Un>: Set operate overvoltage operation value for step n, given as % of residual
voltage corresponding to UBase:
U > (%)*UBase(kV)
The setting is dependent of the required sensitivity of the protection and the system
earthing. In non-effectively earthed systems the residual voltage can be maximum
the rated phase to earth voltage, which should correspond to 100%.
In effectively earthed systems this value is dependent of the ratio Z0/Z1. The required
setting to detect high resistive earth faults must be based on network calculations.
tn: time delay of step n, given in s. The setting is highly dependent of the protection
application. In many applications the protection function has the task to prevent
damages to the protected object. The speed might be important for example in case
of protection of transformer that might be overexcited. The time delay must be co-
ordinated with other automated actions in the system.
tResetn: Reset time for step n if definite time delay is used, given in s. The default
value is 25 ms.
tnMin: Minimum operation time for inverse time characteristic for step n, given in s.
For very high voltages the overvoltage function, using inverse time characteristic,
can give very short operation time. This might lead to unselective trip. By setting
t1Min longer than the operation time for other protections such unselective tripping
can be avoided.
tIResetn: Reset time for step n if inverse time delay is used, given in s. The default
value is 25 ms.
kn: Time multiplier for inverse time characteristic. This parameter is used for co-
ordination between different inverse time delayed undervoltage protections.
CrvSatn: When the denominator in the expression of the programmable curve is equal
to zero the time delay will be infinity. There will be an undesired discontinuity.
Therefore a tuning parameter CrvSatn is set to compensate for this phenomenon. In
the voltage interval U> up to U>·(1.0 + CrvSatn/100) the used voltage will be:
CrvSatn
B× -C > 0
100 (Equation 48)
Table 39: Parameter group settings for the R2POVM_59N (TRV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A characteristic
Inverse curve B selection, step 1
Inverse curve C
Prog. inv. curve
U1> 1 - 200 1 30 %UB Voltage setting/start
val (DT & IDMT), step
1 in % of UBase
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
k1 0.05 - 1.10 0.01 0.05 - Time multiplier in
IDMT mode, step 1
ACrv1 0.005 - 200.000 0.001 1.000 - Setting A for
programmable over
voltage IDMT curve,
step 1
BCrv1 0.50 - 100.00 0.01 1.00 - Setting B for
programmable over
voltage IDMT curve,
step 1
Table continued on next page
4.8.1.1 Application
The parameters for the underfrequency (TUF) function are set via the local HMI or
Protection and Control IED Manager (PCM 600).
All the frequency and voltage magnitude conditions in the system where the
underfrequency protection performs its functions should be considered. The same
also applies to the associated equipment, its frequency and time characteristic.
The underfrequency start value is set in[Hz. All voltage magnitude related settings
are made as a percentage of a settable base voltage, which normally is set to the
nominal primary voltage level (phase-phase) of the power system or the high voltage
equipment under consideration.
Below, some applications and related setting guidelines for the frequency level are
given:
The voltage related time delay is used for load shedding. The settings of the
underfrequency function could be the same all over the power system. The load
shedding is then performed firstly in areas with low voltage magnitude, which
normally are the most problematic areas, where the load shedding also is most
efficient.
Table 40: Basic parameter group settings for the SAPTUF_81 (TUF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV.
StartFrequency 35.00 - 75.00 0.01 48.80 Hz Frequency setting/
start value.
tTrip 0.000 - 60.000 0.001 0.200 s Operate time delay.
TimeDlyRestore 0.000 - 60.000 0.001 0.000 s Restore time delay.
RestoreFreq 45.00 - 65.00 0.01 50.10 Hz Restore frequency
level after operation.
TimerOperation Definite timer - Definite timer - Setting for choosing
Volt based timer timer mode.
UNom 50 - 150 1 100 %UB Nominal voltage in %
of UBase for voltage
based timer.
UMin 50 - 150 1 90 %UB Lower operation limit
in % of UBase for
voltage based timer.
Exponent 1.0 0.1 0.0 - 5.0 - For calculation of the
curve form for voltage
based timer.
tMax 0.010 - 60.000 0.001 1.000 s Maximum time
operation limit for
voltage based timer.
tMin 0.010 - 60.000 0.001 1.000 s Minimum time
operation limit for
voltage based timer.
Table 41: Advanced parameter group settings for the SAPTUF_81 (TUF1-) function
Parameter Range Step Default Unit Description
IntBlkStVal 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
tReset 0.000 - 60.000 0.001 0.000 s Time delay for reset.
4.8.2.1 Application
The parameters for the overfrequency (TOF) function are set via the local HMI or
Protection and Control IED Manager (PCM 600).
All the frequency and voltage magnitude conditions in the system where the
overfrequency protection performs its functions should be considered. The same also
applies to the associated equipment, its frequency and time characteristic.
The overfrequency start value is set in Hz. All voltage magnitude related settings are
made as a percentage of a settable base voltage, which normally is set to the nominal
voltage level (phase-phase) of the power system or the high voltage equipment under
consideration.
Below, some applications and related setting guidelines for the frequency level are
given.
setting level, the number of levels and the distance between two levels (in time and/
or in frequency) depend very much on the characteristics of the power system under
consideration. The size of the "largest loss of load" compared to "the size of the power
system" is a critical parameter. In large systems, the generator shedding can be set at
a fairly low frequency level, and the time delay is normally not critical. In smaller
systems the frequency start level has to be set at a higher value, and the time delay
must be rather short.
Table 42: Parameter group settings for the SAPTOF_81 (TOF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV.
StartFrequency 35.00 - 75.00 0.01 51.20 Hz Frequency setting/
start value.
IntBlkStVall 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
tTrip 0.000 - 60.000 0.001 0.000 s Operate time delay.
tReset 0.000 - 60.000 0.001 0.000 s Time delay for reset.
4.8.3.1 Application
The parameters for the rate-of-change of frequency (RCF) function are set via the
local HMI or Protection and Control IED Manager (PCM 600).
All the frequency and voltage magnitude conditions in the system where the rate-of-
change of frequency protection performs its functions should be considered. The same
also applies to the associated equipment, its frequency and time characteristic.
There are especially two application areas for rate-of-change of frequency protection:
The rate-of-change of frequency start value is set in Hz/s. All voltage magnitude
related settings are made as a percentage of a settable base voltage, which normally
is set to the primary nominal voltage level (phase-phase) of the power system or the
high voltage equipment under consideration.
Table 43: Parameter group settings for the SAPFRC_81 (RCF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV
StartFreqGrad -10.00 - 10.00 0.01 0.50 Hz/s Frequency gradient
start value. Sign
defines direction.
IntBlockLevel 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
tTrip 0.000 - 60.000 0.001 0.200 s Operate time delay in
pos./neg. frequency
gradient mode.
RestoreFreq 45.00 - 65.00 0.01 49.90 Hz Restore frequency if
frequency is above
frequency value (Hz)
tRestore 0.000 - 60.000 0.001 0.000 s Restore time delay.
tReset 0.000 - 60.000 0.001 0.000 s Time delay for reset.
I< I>
U< U>
4.9.1.1 Application
The IED can be provided with multiple function (GF) protection modules. The
function is always connected to three-phase current and three-phase voltage input in
the configuration tool, but it will always measure only one current and one voltage
quantity selected by the end user in the setting tool.
Each general current and voltage protection function module has got four independent
protection elements built into it.
All these four protection elements within one general protection function works
independently from each other and they can be individually enabled or disabled.
However it shall be once more noted that all these four protection elements measure
one selected current quantity and one selected voltage quantity (see table 44 and
table 45). It is possible to simultaneously use all four-protection elements and their
individual stages. Sometimes in order to obtain desired application functionality it is
necessary to provide interaction between two or more protection elements/stages
within one GF function by appropriate IED configuration (e.g. dead machine
protection for generators).
The user can select, by a setting parameter CurrentInput, to measure one of the
following current quantities shown in table 44.
The user can select, by a setting parameter VoltageInput, to measure one of the
following voltage quantities shown in table 45.
It is important to notice that the voltage selection from table 45 is always applicable
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-ground voltages UL1, UL2 & UL3 or three
phase-to-phase voltages UL1L2, UL2L3 & UL3L1. This information about actual VT
connection is entered as a setting parameter for the pre-processing block, which will
then take automatic care about it.
1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 44.
2. rated phase current of the protected object in primary amperes multiplied by √3
(i.e. 1,732 x Iphase), when the measured Current Quantity is selected from 10 to
15, as shown in table 44.
1. rated phase-to-ground voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 45.
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 45.
Application possibilities
Due to its flexibility the GF can be used, with appropriate settings and configuration
in many different applications. Some of possible examples are given below:
The parameters for the general current and voltage protection function (GF) are set
via the local HMI or Protection and Control IED Manager (PCM 600).
This functionality can be achieved by using one GF function. The following shall be
done in order to ensure proper operation of the function:
1. Connect three-phase power line currents and three-phase power line voltages to
one GF instance (e.g. GF04)
2. Set parameter CurrentInput to NegSeq (please note that function measures I2
current and NOT 3I2 current; this is essential for proper OC pickup level setting)
3. Set parameter VoltageInput to -NegSeq (please note that the negative sequence
voltage phasor is intentionally inverted in order to simplify directionality
4. Set base current value equal to the rated primary current of power line CTs
5. Set base voltage value equal to the rated power line phase-to-phase voltage in
kV
6. Set parameter RCA_DIR to value +65 degrees (i.e. NegSeq current typically lags
the inverted NegSeq voltage for this angle during the fault)
7. Set parameter ROA_DIR to value 90 degree
8. Set parameter LowVolt_VM to value 2% (NegSeq voltage level above which
the directional element will be enabled)
9. Enable one overcurrent stage (e.g. OC1)
10. By parameter CurveType_OC1 select appropriate IDMT or definite time delayed
curve in accordance with your network protection philosophy
11. Set parameter StartCurr_OC1 to value between 3-10% (typical values)
12. Set parameter tDef_OC1 or parameter “k” when IDMT curves are used to insure
proper time coordination with other ground fault protections installed in the
vicinity of this power line
13. Set parameter DirMode_OC1 to Forward
14. Set parameter DirPrinc_OC1 to IcosΦ&U
15. Set parameter ActLowVolt1_VM to Block
• In order to insure proper restraining of this element for CT saturations
during three-phase faults it is possible to use current restraint feature and
enable this element to operate only when NegSeq current is bigger than a
certain percentage (i.e. 10% is typical value) of measured PosSeq current
in the power line. To do this the following settings within the same function
shall be done:
16. Set parameter EnRestrainCurr to On
17. Set parameter RestrCurrInput to PosSeq
18. Set parameter RestrCurrCoeff to value 0,10
If required this function can be used in directional comparison protection scheme for
the power line protection if communication channels to the remote end of this power
line are available. In that case typically two NegSeq overcurrent steps are required.
One for forward and one for reverse direction. As explained before the OC1 stage
can be used to detect faults in forward direction. The built-in OC2 stage can be used
to detect faults in reverse direction.
• the set values for RCA_Dir and ROA_Dir setting parameters will be as well
applicable for OC2 stage
• setting parameter DirMode_OC2 shall be set to Reverse
• setting parameter StartCurr_OC2 shall be made more sensitive than pickup value
of forward OC1 element (i.e. typically 60% of OC1 set pickup level) in order to
insure proper operation of the directional comparison scheme during current
reversal situations
• start signals from OC1 and OC2 elements shall be used to send forward and
reverse signals to the remote end of the power line
• the available scheme communications function block within REx670 IED shall
be used between multipurpose protection function and the communication
equipment in order to insure proper conditioning of the above two start signals
Furthermore the other build-in UC, OV and UV protection elements can be used for
other protection and alarming purposes.
The capability curve for a generator negative sequence overcurrent protection, often
used world-wide, is defined by the ANSI standard in accordance with the following
formula:
k
top = 2
æ I NS ö
ç ÷
è Ir ø (Equation 49)
where:
top is the operating time in seconds of the negative sequence overcurrent relay
x = 7% = 0, 07 pu (Equation 50)
Equation 49 can be re-written in the following way without changing the value for
the operate time of the negative sequence inverse overcurrent relay:
1
k×
top = x2
2
æ I NS ö
ç ÷
è x × Ir ø (Equation 51)
In order to achieve such protection functionality with one GF functions the following
must be done:
æ A ö
top = k × ç P + B÷
è M -C ø (Equation 52)
where:
top is the operating time in seconds of the IDMT algorithm
k is time multiplier (parameter setting)
M is ratio between measured current magnitude and set pickup current level
A, B, C and P are user settable coefficients which determine the curve used for IDMT calculation
When the equation 49 is compared with the equation 51 for the inverse time
characteristic of the OC1 step in it is obvious that if the following rules are followed:
then the OC1 step of the GF function can be used for generator negative sequence
inverse overcurrent protection.
For this particular example the following settings shall be entered to insure proper
function operation:
Proper timing of the GF function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. If required delayed time
reset for OC1 step can be set in order to ensure proper function operation in case of
repetitive unbalance conditions.
Furthermore the other build-in protection elements can be used for other protection
and alarming purposes (e.g. use OC2 for negative sequence overcurrent alarm and
OV1 for negative sequence overvoltage alarm).
The generator stator overload protection is defined by IEC or ANSI standard for turbo
generators in accordance with the following formula:
k
top = 2
æ Im ö
ç ÷ -1
è Ir ø (Equation 53)
where:
top is the operating time of the generator stator overload relay
k is the generator capability constant in accordance with the relevant standard (k = 37.5 for the
IEC standard or k = 41.4 for the ANSI standard)
Im is the magnitude of the measured current
This formula is applicable only when measured current (e.g. positive sequence
current) exceeds a pre-set value (typically in the range from 105 to 125% of the
generator rated current).
By defining parameter x equal to the per unit value for the desired pickup for the
overload relay in accordance with the following formula:
formula 3.5can be re-written in the following way without changing the value for the
operate time of the generator stator overload relay:
1
k×
top = x2
2
æ Im ö 1
ç ÷ - 2
è x × Ir ø x (Equation 55)
In order to achieve such protection functionality with one GF functions the following
must be done:
æ A ö
top = k × ç P + B÷
è M -C ø (Equation 56)
where:
top is the operating time in seconds of the IDMT algorithm
When the equation 55 is compared with the equation 56 for the inverse time
characteristic of the OC1 step in it is obvious that if the following rules are followed:
then the OC1 step of the GF function can be used for generator negative sequence
inverse overcurrent protection.
Proper timing of the GF function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. If required delayed time
reset for OC1 step can be set in order to insure proper function operation in case of
repetitive overload conditions.
Furthermore the other build-in protection elements can be used for other protection
and alarming purposes.
In the similar way rotor overload protection in accordance with ANSI standard can
be achieved.
1. Connect three-phase currents from the protected object to one GF instance (e.g.
GF03)
2. Set parameter CurrentInput to value "UnbalancePh"
3. Set parameter EnRestrainCurr to "On"
4. Set parameter RestrCurrInput to "MaxPh"
5. Set parameter RestrCurrCoeff to value 0.97
6. Set base current value to the rated current of the protected object in primary
amperes
7. Enable one overcurrent step (e.g. OC1)
8. Select parameter CurveType_OC1 to value "IEC Def. Time"
9. Set parameter StartCurr_OC1 to value 5%
10. Set parameter tDef_OC1 to desired time delay (e.g. 2.0s)
Proper operation of the GF function made in this way can easily be verified by
secondary injection. All other settings can be left at the default values. However it
shall be noted that set values for restrain current and its coefficient will as well be
applicable for OC2 step as soon as it is enabled.
Furthermore the other build-in protection elements can be used for other protection
and alarming purposes. For example in case of generator application by enabling OC2
step with set pickup to 200% and time delay to 0,1s simple but effective protection
against circuit breaker head flashover protection is achieved.
This functionality can be achieved by using one GF function. The following shall be
done in order to insure proper operation of the function:
Proper operation of the GF function made in this way can easily be verified by
secondary injection. All other settings can be left at the default values. Furthermore
the other build-in protection elements can be used for other protection and alarming
purposes.
This functionality can be achieved by using one GF function. The following shall be
done in order to insure proper operation of the function:
1. Connect three-phase generator currents from the star point and three-phase
generator voltages to one GF instance (e.g. GF02)
2. Set parameter CurrentInput to "PosSeq"
3. Set parameter VoltageInput to "PosSeq"
4. Set base current value to the rated generator current primary amperes
5. Set base voltage value to the rated generator phase-to-phase voltage in kV
6. Set parameter RCA_DIR to value -84 degree (i.e. current lead voltage for this
angle)
7. Set parameter ROA_DIR to value 90 degree
8. Set parameter LowVolt_VM to value 5%
9. Enable one overcurrent step (e.g. OC1)
10. Select parameter CurveType_OC1 to value "IEC Def. Time"
11. Set parameter StartCurr_OC1 to value 38%
12. Set parameter tDef_OC1 to value 2,0s (typical setting)
13. Set parameter DirMode_OC1 to "Forward"
14. Set parameter DirPrinc_OC1 to "IcosF&U"
15. Set parameter ActLowVolt1_VM to "Block"
Proper operation of the GF function made in this way can easily be verified by
secondary injection. All other settings can be left at the default values. However it
shall be noted that set values for RCA & ROA angles will be applicable for OC2 step
if directional feature is enabled for this step as well. Figure 54 shows overall
protection characteristic
Furthermore the other build-in protection elements can be used for other protection
and alarming purposes.
Q [pu]
Operating region
A
0.8
ILowSet
0.6 B
IPS
0.4
rca
0.2
0
0.2 0.4 0.6 0.8 1 1.2 1.4 P [pu]
-rca
UPS
-0.2
C
-0.4 ILowSet
D
-0.8
en05000535.vsd
Table 46: Basic parameter group settings for the CVGAPC (GF01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
CurrentInput phase1 - MaxPh - Select current signal
phase2 which will be
phase3 measured inside
PosSeq function
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
IBase 1 - 99999 1 3000 A Base Current
Table continued on next page
Table 47: Advanced parameter group settings for the CVGAPC (GF01-) function
Parameter Range Step Default Unit Description
CurrMult_OC1 2.0 0.1 1.0 - 10.0 - Multiplier for scaling
the current setting
value for OC1
ResCrvType_OC1 Instantaneous - Instantaneous - Selection of reset
IEC Reset curve type for OC1
ANSI reset
tResetDef_OC1 0.00 - 6000.00 0.01 0.00 s Reset time delay used
in IEC Definite Time
curve OC1
P_OC1 0.020 0.001 0.001 - 10.000 - Parameter P for
customer
programmable curve
for OC1
A_OC1 0.140 0.001 0.000 - 999.000 - Parameter A for
customer
programmable curve
for OC1
B_OC1 0.000 0.001 0.000 - 99.000 - Parameter B for
customer
programmable curve
for OC1
C_OC1 1.000 0.001 0.000 - 1.000 - Parameter C for
customer
programmable curve
for OC1
PR_OC1 0.500 0.001 0.005 - 3.000 - Parameter PR for
customer
programmable curve
for OC1
Table continued on next page
4.10.1.1 Application
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth fault current and negative
sequence current functions. When currents from two independent 3-phase sets of
CT’s, or CT cores, measuring the same primary currents are available, reliable current
circuit supervision can be arranged by comparing the currents from the two sets. If
an error in any CT circuit is detected, the protection functions concerned can be
blocked and an alarm given.
The supervision function must be sensitive and have short operate time in order to
prevent unwanted tripping from fast-acting, sensitive numerical protections in case
of faulty CT secondary circuits.
The CCS function compares the residual current from a three phase set of current
transformer cores with the neutral point current on a separate input taken from another
set of cores on the same current transformer.
The minimum operate current, IMinOp, should as a minimum be set to twice the
residual current in the supervised CT circuits under normal service conditions and
rated primary current.
The parameter Ip>Block is normally set at 150% in order to block the function during
transient conditions.
The FAIL output is connected in the CAP configuration to the blocking input of the
protection function to be blocked at faulty CT secondary circuits.
Table 48: Parameter group settings for the CCSRDIF (CCS1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A IBase value for
current level
detectors
Ip>Block 5 - 500 1 150 %IB Block of the function
at high phase current,
in % of IBase
IMinOp 5 - 200 1 20 %IB Minimum operate
current differential
level in % of IBase
4.10.2.1 Application
Different protection functions within the protection IED, operates on the basis of the
measured voltage in the relay point. Examples are:
These functions can operate unnecessarily if a fault occurs in the secondary circuits
between the voltage instrument transformers and the IED.
The fuse-failure supervision function as built into the IED670 products can operate
on the basis of external binary signals from the miniature circuit breaker or from the
line disconnector. The first case influences the operation of all voltage-dependent
functions while the second one does not affect the impedance measuring functions.
The zero sequence detection algorithm, based on the zero sequence measuring
quantities, a high value of voltage 3 U0 without the presence of the residual current
3 I0, is recommended for use in directly or low impedance earthed networks. A
criterion based on delta current and delta voltage measurements can be added to the
fuse failure supervision function in order to detect a three phase fuse failure, which
in practice is more associated with voltage transformer switching during station
operations. In cases where the line can have a weak-infeed of zero sequence current
this function shall be avoided.
A separate operation mode selector OpMode has been introduced for better adaptation
to system requirements. The mode selector makes it possible to select interactions
between the negative sequence and zero sequence algorithm. In normal applications
the OpMode is set to either UNsINs for selecting negative sequence algorithm or
UZsIZs for zero sequence based algorithm. If system studies or field experiences
shows that there is a risk that the fuse failure function will not be activated due to the
system conditions, the dependability of the fuse failure function can be increased if
the OpMode is set to UZsIZs OR UNsINs or OptimZsNs. In mode UZsIZs OR
UNsINs both the negative and zero sequence based algorithm is activated and working
in an OR-condition. Also in mode OptimZsNs both the negative and zero sequence
algorithm are activated and the one that has the highest magnitude of measured
negative sequence current will operate.
General
The negative and zero sequence voltages and currents always exist due to different
non-symmetries in the primary system and differences in the current and voltage
instrument transformers. The minimum value for the operation of the current and
voltage measuring elements must always be set with a safety margin of 10 to 20%,
depending on the system operating conditions.
Pay special attention to the dissymmetry of the measuring quantities when the
function is used on longer untransposed lines, on multicircuit lines and so on.
The voltage threshold UPh> is used to identify low voltage condition in the system.
Set UPh> below the minimum operating voltage that might occur during emergency
conditions. We propose a setting of approximately 70% of UBase.
ΔU2
3U2 > = ×100
UBase (Equation 57)
where:
DU2 is maximal negative sequence voltage during normal operation condition
UBase is setting of base voltage for the function
The setting of the current limit 3I2> is done in percentage of IBase. The setting of
3I2> must be higher than the normal unbalance current that might exist in the system.
The setting can be calculated according to equation 58.
DI2
3I2 > = ×100
IBase (Equation 58)
where:
DI2 is maximal negative sequence current during normal operating condition
IBase is setting of base current for the function
100
3U0 > = ΔU0 ×
UBase (Equation 59)
where:
DU0 is maximal zero sequence voltage during normal operation condition
UBase is setting of base voltage for the function
The setting of the current limit 3I0> is done in percentage of IBase, where IBase is
the primary base current, normally the rated current of the primary current transformer
winding. The setting of 3I2> must be higher than the normal unbalance current that
might exist in the system. The setting can be calculated according to equation 60.
DI0
3I0 > = s × ×100
IBase (Equation 60)
where:
DI0 is maximal negative sequence current during normal operating condition
IBase is setting of base current for the function
USetprim
DU > = × 100
UBase (Equation 61)
ISetprim
DI > = ×100
IBase (Equation 62)
Set the operation mode selector OperationDUDI to On if the delta function shall be
in operation.
The current threshold IPh> shall be set lower than the IMinOp for the distance
protection function. A 5-10% lower value is recommended.
Set the IDLD< with a sufficient margin below the minimum expected load current.
A safety margin of at least 15-20% is recommended. The operate value must however
exceed the maximum charging current of an overhead line, when only one phase is
disconnected (mutual coupling to the other phases).
Set the UDLD< with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.
Table 49: Parameter group settings for the SDDRFUF (FSD1-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base value for current
settings in A
UBase 0.05 - 2000.00 0.05 400.00 kV Base value for voltage
settings in kV
OpMode Off - UZsIZs - Operating mode
UNsINs selection
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 1 30 %UB Operate level of
residual overvoltage
element in % of
UBase
3I0< 1 - 100 1 10 %IB Operate level of
residual undercurrent
element in % of IBase
3U2> 1 - 100 1 30 %UB Operate level of neg
seq overvoltage
element in % of
UBase
3I2< 1 - 100 1 10 %IB Operate level of neg
seq undercurrent
element in % of IBase
OperationDUDI Off - Off - Operation of change
On based function Off/On
Table continued on next page
4.11 Control
4.11.1.1 Application
Synchrocheck
The main purpose of the synchrocheck function is to provide control over the closing
of circuit breakers in power networks in order to prevent closing if conditions for
synchronism are not detected. It is also used to prevent the re-connection of two
systems, which are divided after islanding and after a three pole reclosing.
The synchrocheck function block includes both the sychronism check function and
the energizing function to allow closing when one side of the breaker is dead. The
synchrocheck function also includes a built in voltage selection scheme which allows
simple application in all types of busbar arrangements.
~ ~
en04000179.vsd
Figure 55 shows two interconnected power systems. The cloud means that the
interconnection can be further away, i.e. a weak connection through other stations.
The need for a synchronization check increases as the meshed system decreases since
the risk of the two networks being out of synchronization at manual or automatic
closing is greater.
The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. Output is only generated when all measured conditions
are within their set limits simultaneously. The check consists of:
A time delay is available to ensure that the conditions are fulfilled for a minimum
period of time.
In very stable power systems the frequency difference is insignificant or zero for
manually initiated closing or closing by automatic restoration. In steady conditions a
bigger phase angle difference can be allowed as this is sometimes the case in a long
and loaded parallel power line. For this application we accept a synchrocheck with a
long operation time and high sensitivity regarding the frequency difference (3 mHz)
and a relatively low phase angle difference setting.
Another example, is when the operation of the power net is disturbed and high-speed
auto-reclosing after fault clearance takes place. This can cause a power swing in the
net and the phase angle difference may begin to oscillate. Generally, the frequency
difference is the time derivative of the phase angle difference and will, typically
oscillate between positive and negative values. When the circuit breaker needs to be
en04000174.vsd
Energizing check
The main purpose of the energizing check function is to facilitate the controlled re-
connection of disconnected lines and busses to energized lines and busses.
The energizing check function measures the bus and line voltages and compares them
to both high and low threshold values. The output is only given when the actual
measured conditions match the set conditions. Figure 57 shows two power systems,
where one (1) is energized and the other (2) is not energized. Power system 2 is
energized (DLLB) from system 1 via the circuit breaker A.
1 2
A B
~
EnergizingCheck
voltageHighLimitBus > 50 - 120 % of Ub
voltageHighLimitLine > 50 - 120 % of Ub
voltageLowLimitBus < 10 - 80 % of Ub
voltageLowLimitLine < 10 - 80 % of Ub
maxVoltageForEnergizing < 80 - 140 % of Ub
en04000173.vsd
The energizing operation can operate in the dead line live bus (DLLB) direction, dead
bus live line (DBLL) direction or in both directions over the circuit breaker.
Energizing from different directions can be different for automatic reclosing and
manual closing of the circuit breaker. For manual closing it is also possible to allow
closing when both sides of the breaker are dead, Dead Bus Dead Line (DBDL).
The equipment is considered energized if the voltage is above a set value, e.g. 80%
of the base voltage, and non-energized if it is below a set value, e.g. 30% of the base
voltage. A disconnected line can have a considerable potential because of factors such
as induction from a line running in parallel, or feeding via extinguishing capacitors
in the circuit breakers. This voltage can be as high as 50% or more of the base voltage
of the line. Normally for breakers with single breaking elements (<330kV) the level
is well below 30%.
When the energizing direction corresponds to the settings, the situation has to remain
constant for a certain period of time before the close signal is permitted. The purpose
of the delayed operate time is to ensure that the dead side remains de-energized and
that the condition is not due to temporary interference.
Voltage selection
The voltage selection function is used for the connection of appropriate voltages to
the synchrocheck and energizing check functions. For example, when the IED is used
in a double bus arrangement, the voltage that should be selected depends on the status
of the breakers and/or disconnectors. By checking the status of the disconnectors
auxiliary contacts, the right voltages for the synchrocheck and energizing check
functions can be selected. Available voltage selection types are for single circuit
breaker with double busbars and the 1 1/2 circuit breaker arrangement. A double
circuit breaker arrangement and single circuit breaker with a single busbar do not
need any voltage selection function. Neither does a single circuit breaker with double
busbars using external voltage selection need any internal voltage selection.
The voltages from busbars and lines must be physically connected to the voltage
inputs in the IED and connected, using the control software, to each of the maximum
two synchrocheck functions available in the IED.
The synchrocheck function block can also be used in some switchyard arrangements,
but with different parameter settings. Below are some examples of how different
arrangements are connected to the IED analogue inputs and to the function block
(SYN). One function block is used per circuit breaker. The IED can be provided with
one or two function blocks.
Bus 1 SYN1-
SYN
B1QOPEN B1SEL
QB1 B1QCLD B2SEL
B2QOPEN LN1SEL
Fuse B2QCLD LN2SEL
VT LN1QOPEN USELFAIL
LN1QCLD AUTOENOK
bus1Voltage QA1 LN2QOPEN MANENOK
AIM1-UREF1 LN2QCLD TSTENOK
UB1OK SYNOK
UB1FF TSTSYNOK
UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
ULN1FF PHDIFF
AIM1- lineVoltage/1/2/3 ULN2OK PHDIFF2
UL1/UL2/UL3 Fuse
ULN2FF UDIFFME
VT TSTENERG FRDIFFME
TSTSYNC PHDIFFME
Line BLKENERG UOK
BLKSYNC
BLOCK
en04000177.vsd
Figure 58: Connection of the Synchrocheck function block in a single busbar arrangement
Line
en04000175.vsd
Figure 59: Connection of the Synchrocheck function block in a single breaker, double busbar arrangement
with external voltage selection.
Bus 1 SYN1-
Bus 2 SYN
B1QOPEN B1SEL
B1QCLD B2SEL
Fuse B2QOPEN LN1SEL
Fuse VT B2QCLD LN2SEL
VT
LN1QOPEN USELFAIL
bus1Voltage LN1QCLD AUTOENOK
AIM1-UREF1 LN2QOPEN MANENOK
bus2Voltage LN2QCLD TSTENOK
AIM2-UREF2 UB1OK SYNOK
UB1FF TSTSYNOK
QB1 UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
QB2 ULN1FF PHDIFF
ULN2OK PHDIFF2
ULN2FF UDIFFME
TSTENERG FRDIFFME
TSTSYNC PHDIFFME
QA1 BLKENERG UOK
BLKSYNC
BLOCK
AIM1- lineVoltage/1/2/3
UL1/UL2/UL3 Fuse
VT
Line
en04000178.vsd
Figure 60: Connection of the Synchrocheck function block in a single breaker, double busbar arrangement
with internal voltage selection.
When internal voltage selection is needed, two analog input modules AIM1 (TRM
+ADM) and AIM2 (TRM+ADM) are required. The voltage transformer circuit
connections are made according to figure 60. The voltages from the busbar VTs are
connected to the single phase analog input UREF1 (CH10) on the analog input module
AIM1 and to the single phase analog input UREF2 (CH09) on the analog input module
AIM2. The line voltage is connected as a three-phase voltage to the analog inputs
UL1 (CH06), UL2 (CH07), UL3 (CH08) on the module AIM1. Inputs and outputs
not used in the function block (SYN) are dimmed in the figure. The voltage selection
parameter selectCBConfig is set to “1” to indicate a selection (single CB, double bus).
QA2
en04000176.vsd
SYN1 and SYN2. All voltages for the whole diameter must be connected to both
IEDs in the diameter respectively.
Bus 1
Bus 2 SYN1-
QB1 QB1 SYN
QA1 QA1 B1QOPEN B1SEL
B1QCLD B2SEL
B2QOPEN LN1SEL
Fuse QB2 QB2 B2QCLD LN2SEL
VT
bus1Voltage LN1QOPEN USELFAIL
AIM1-UREF1 LN1QCLD AUTOENOK
LN2QOPEN MANENOK
Fuse LN2QCLD TSTENOK
VT UB1OK
bus2Voltage SYNOK
AIM2-UREF2 UB1FF TSTSYNOK
UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
ULN1FF PHDIFF
ULN2OK PHDIFF2
QA1 ULN2FF UDIFFME
TSTENERG FRDIFFME
QB61 QB62 TSTSYNC PHDIFFME
BLKENERG UOK
QB9 QB9 BLKSYNC
BLOCK
line1Voltage Fuse
VT Bus 1 CB
AIM1- 1/2/3
UL1/UL2/UL3
SYN2-
Fuse
line2Voltage VT SYN
AIM2-UREF3 B1QOPEN B1SEL
B1QCLD B2SEL
B2QOPEN LN1SEL
B2QCLD LN2SEL
Line 1 Line 2 LN1QOPEN USELFAIL
LN1QCLD AUTOENOK
LN2QOPEN MANENOK
LN2QCLD TSTENOK
UB1OK SYNOK
UB1FF TSTSYNOK
UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
ULN1FF PHDIFF
ULN2OK PHDIFF2
ULN2FF UDIFFME
TSTENERG FRDIFFME
TSTSYNC PHDIFFME
BLKENERG UOK
BLKSYNC
BLOCK
Tie CB
en04000172.vsd
Figure 62: Voltage connections in a 1 ½ breaker arrangement for the line 1 IED
Bus 1
Bus 2
SYN1-
QB1 QB1
SYN
QA1 QA1 B1QOPEN B1SEL
B1QCLD B2SEL
B2QOPEN LN1SEL
Fuse QB2 QB2 B2QCLD LN2SEL
bus1Voltage VT LN1QOPEN USELFAIL
AIM2-UREF2 LN1QCLD AUTOENOK
LN2QOPEN MANENOK
Fuse LN2QCLD TSTENOK
VT UB1OK SYNOK
bus2Voltage
AIM1-UREF1 UB1FF TSTSYNOK
UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
ULN1FF PHDIFF
ULN2OK PHDIFF2
QA1 ULN2FF UDIFFME
TSTENERG FRDIFFME
TSTSYNC PHDIFFME
QB61 QB62 BLKENERG UOK
BLKSYNC
QB9 QB9
BLOCK
Fuse Bus 2 CB
VT
line1Voltage
AIM2-UREF3
line2Voltage Fuse
SYN2-
VT
AIM1- 1/2/3 SYN
UL1/UL2/UL3 B1QOPEN B1SEL
B1QCLD B2SEL
B2QOPEN LN1SEL
B2QCLD LN2SEL
LN1QOPEN USELFAIL
LN1QCLD AUTOENOK
Line 1 Line 2
LN2QOPEN MANENOK
LN2QCLD TSTENOK
UB1OK SYNOK
UB1FF TSTSYNOK
UB2OK UDIFF
UB2FF FRDIFF
ULN1OK FRDIFF2
ULN1FF PHDIFF
ULN2OK PHDIFF2
ULN2FF UDIFFME
TSTENERG FRDIFFME
TSTSYNC PHDIFFME
BLKENERG UOK
BLKSYNC
BLOCK
Tie CB
en04000171.vsd
Figure 63: Voltage connections in a 1 ½ breaker arrangement for the line 2 IED
The example shows the use of the Synchrocheck function for the Tie
Circuit breaker in both Line IEDs. This depends on the arrangement
of Auto-reclose and manual closing and might often not be required.
Connecting and configuring is done according to figure 62 and figure 63. The
connections are similar in both IEDs, apart from the line voltages and the bus voltages,
which are crossed. This means that the three-phase line voltages UL1, UL2 and UL3
for line 1and F3 for line 2 in the line 1 IED are crossed in the line 2 IED. Also, the
bus voltage connections to both the IEDs are crossed. The physical analog
connections of voltages and the connection to the SYN1 and SYN2 function blocks
must be carefully checked in the PCM. In both IEDs the connections and
configurations must abide by the following rules: Normally apparatus position is
connected with contacts showing both open (b-type) and closed positions (a-type).
Bus CB:
Tie CB:
The setting parameters for the synchrocheck and energizing check function (SYN)
are set via the local HMI, or Protection and Control IED Manager (PCM 600) in the
PCM. Refer to the Setting parameters table in the next section of this chapter.
Operation
The operation mode can be set On/Off from the PST. The setting OFF disables the
whole function.
Configuration parameters for selection of measuring phase of the voltage for busbar
1 and 2 respectively, which can be a single-phase (phase-neutral) or two-phase (phase-
phase) voltage.
Configuration parameters for selection of measuring phase of the voltage for line 1
and 2 respectively, which can be a single-phase (phase-neutral) or two-phase (phase-
phase) voltage.
CBConfig
This configuration setting is used to define type of voltage selection. Type of voltage
selection can be selected as:
• no voltage selection
• single circuit breaker with double bus
• 1 1/2 circuit breaker arrangement with the breaker connected to busbar 1
• 1 1/2 circuit breaker arrangement with the breaker connected to busbar 2
• 1 1/2 circuit breaker arrangement with the breaker connected to line 1 and 2 (tie
breaker)
UBase
OperationSync
The OperationSync setting OFF disables the synchrocheck function and sets the
outputs SYNOK and TSTSYNOK to low.
With the setting ON, the function is in service and the output signal depends on the
input conditions.
Release means that the output signal SYNOK is set fixed high and normally used at
commissioning. If the function is in test mode and OperationSync is set in release
mode, the output TSTSYNOK is set fixed high.
PhaseShift
This setting is used to compensate for a phase shift caused by a line transformer
between the two measurement points for bus voltage and line voltage. The set value
is added to the measured line phase angle. The bus voltage is reference voltage.
URatio
The URatio is defined as URatio=bus voltage/line voltage. A typical use of the setting
is to compensate for the voltage difference caused if one wishes to connect the bus
voltage phase-phase and line voltage phase-neutral. The SelPhaseBusx setting should
then be set to phase-phase and the URatio setting to sqr3=1.73. This setting scales
up the line voltage to equal level with the bus voltage.
The voltage level settings shall be chosen in relation to the bus/line network voltage.
The threshold voltages UHighBusSync and UHighLineSync have to be set lower than
the value at which the breaker is expected to be closed with synchronism check. A
typical value may be 80% of the base voltage.
UDiff
The frequency difference level settings, FreqDiffM and FreqDiffA, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the FreqDiffM setting is used. Four auto-reclosing
a bigger frequency difference setting is preferable, where the FreqDiffA setting is
used. A typical value for the FreqDiffM can 10 mHz and a typical value for the
FreqDiffA can be 100-200 mHz.
The phase angle difference level settings, PhaseDiffM and PhaseDiffA, shall also be
chosen depending on conditions in the network. The phase angle setting must be
chosen to allow closing under maximum load condition. A typical maximum value
in heavy loaded networks can be 45 degrees whereas in most networks the maximum
occurring angle is below 25 degrees.
The purpose of the timer delay settings, tSyncM and tSyncA, is to ensure that the
synchro check conditions remains constant and that the situation is not due to a
temporary interference. Should the conditions not persist for the specified time, the
delay timer is reset and the procedure is restarted when the conditions are fulfilled
again. Circuit breaker closing is thus not permitted until the synchro check situation
has remained constant throughout the set delay setting time. Under stable conditions
a longer operation time delay setting is needed, where the tSyncM setting is used.
During auto-reclosing a shorter operation time delay setting is preferable, where the
tSyncA setting is used. A typical value for the tSyncM may be 1 second and a typical
value for the tSyncA may be 0.1 second.
OperationEnerg
The setting OFF disables the energizing check function and sets the outputs
AUTOENOK, MANENOK and TSTENOK to low.
With the setting ON, the function is in service and the output signal depends on the
input conditions.
Release means that the output signals AUTOENOK and MANENOK are set fixed
high and normally used when commissioning. If the function is in test mode and
OperationEnerg is set in release mode, the output TSTENOK is set fixed high.
The voltage level settings shall be chosen in relation to the bus/line network voltage.
The threshold voltages UHighBusEnerg and UHighLineEnerg, have to be set lower
than the value at which the network is considered to be energized. A typical value
may be 80 % of the base voltage.
In the same way, the threshold voltages ULowBusEnerg and ULowLineEnerg, have
to be set greater than the value where the network is considered not to be energized.
A typical value may be 30% of the base voltage. Note that a disconnected line can
have a considerable potential due to, for instance, induction from a line running in
parallel, or by being fed via the extinguishing capacitors in the circuit breakers. This
voltage can be as high as 30% or more of the base line voltage.
Two different settings can be used for automatic and manual closing of the circuit
breaker. The settings for each of them are:
The purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure that
the dead side remains de-energized and that the condition is not due to a temporary
interference. Should the conditions not persist for the specified time, the delay timer
is reset and the procedure is restarted when the conditions are fulfilled again. Circuit
breaker closing is thus not permitted until the energizing condition has remained
constant throughout the set delay setting time.
ManEnergDBDL
If the parameter is set to On, manual closing is enabled when both line voltage and
bus voltage are below ULowLineEnerg and ULowBusEnerg respectively and
ManEnerg is set to DLLB, DBLL or Both.
UMaxEnerg
This setting is used to block the closing when the voltage on the live side is above
the set value of UMaxEnerg.
Table 50: Parameter group settings for the SECRSYN_25 (SYN1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
SelPhaseBus1 phase1 - phase2 - Select phase for bus1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseBus2 phase1 - phase2 - Select phase for bus2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine1 phase1 - phase2 - Select phase for line1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine2 phase1 - phase2 - Select phase for line2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
CBConfig No voltage sel. - No voltage sel. - Select CB
Double bus configuration
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
UHighBusEnerg 50.0 - 120.0 1.0 80.0 %UB Voltage high limit bus
for energizing check
in % of UBase
UHighLineEnerg 50.0 - 120.0 1.0 80.0 %UB Voltage high limit line
for energizing check
in % of UBase
ULowBusEnerg 10.0 - 80.0 1.0 40.0 %UB Voltage low limit bus
for energizing check
in % of UBase
ULowLineEnerg 10.0 - 80.0 1.0 40.0 %UB Voltage low limit line
for energizing check
in % of UBase
AutoEnerg Off - DLLB - Automatic energizing
DLLB check mode
DBLL
Both
ManEnerg Off - DLLB - Manual energizing
DLLB check mode
DBLL
Both
Table continued on next page
4.11.2.1 Application
Instant of fault
Operates
Operates
Line
Resets
Resets
Fault
protection
Closed
Circuit
breaker
Open
Contact closed
Close command
Are extinguishers
Trip command
function
Start AR
AR reset
en04000146.vsd
A somewhat longer dead time may be required for single-phase reclosing compared
to high-speed three-phase reclosing. This is due to the influence on the fault arc from
the voltage and the current in the non-tripped phases.
To maximize the availability of the power system it is possible to choose single pole
tripping and automatic reclosing during single-phase faults and three pole tripping
and automatic reclosing during multi-phase faults. Three-phase automatic reclosing
can be performed with or without the use of a synchronicity check, and an energizing
check, such as dead line or dead busbar check.
During the single-pole open time there is an equivalent "series"-fault in the system
resulting in a flow of zero sequence current. It is therefore necessary to coordinate
the residual current protections (earth fault protection) with the single pole tripping
and the auto-reclosing function. Attention shall also be paid to “pole
discrepancy” (pole discordance) that arises when circuit breakers are provided with
single pole operating devices. These breakers need pole discrepancy protection. They
must also be coordinated with the single pole auto-recloser and blocked during the
dead time when a normal discrepancy occurs. Alternatively they should use a trip
time longer than the set single phase dead time.
For the individual line breakers and auto-reclosing equipment, the ”auto-reclosing
open time” expression is used. This is the dead time setting for the Auto-Recloser.
During simultaneous tripping and reclosing at the two line ends, auto-reclosing open
time is approximately equal to the line dead time. Otherwise these two times may
differ as one line end might have a slower trip than the other end which means that
the line will not be dead until both ends have opened.
If the fault is permanent, the line protection will trip again when reclosing is attempted
in order to clear the fault.
It is common to use one automatic reclosing function per line circuit-breaker (CB).
When one CB per line end is used, then there is one auto-reclosing function per line
end. If auto-reclosing functions are included in duplicated line protection, which
means two auto-reclosing functions per CB, one should take measures to avoid
uncoordinated reclosing commands. In one and a half breaker, double-breaker and
ring bus arrangements, two CBs per line end are operated. One auto-reclosing
function per CB is recommended. Arranged in such a way, sequential reclosing of
the two CBs can be arranged with a priority circuit available in the auto-reclose
function. In case of a permanent fault and unsuccessful reclosing of the first CB,
reclosing of the second CB is cancelled and thus the stress on the power system is
limited. Another advantage with the breaker connected auto-recloser is that checking
that the breaker closed before the sequence, breaker prepared for an autoreclose
sequence etc. is much simpler.
Transmission protection systems are usually sub-divided and provided with two
redundant protection relays. In such systems it is common to provide auto-reclosing
in only one of the sub-systems as the requirement is for fault clearance and a failure
to reclose because of the auto-recloser being out of service is not considered a major
disturbance. If two auto-reclosers are provided on the same breaker, the application
must be carefully checked and normally one must be the master and be connected to
inhibit the other auto-recloser if it has started. This inhibit can for example be done
from AR In progress.
When Single and/or three phase auto-reclosing is used there are a number of cases
where the tripping shall be three phase anyway. Some examples are:·
• Evolving fault where the fault during the dead-time spreads to another phase.
The other two phases must then be tripped and a three phase dead-time and auto-
reclose initiated
• Permanent fault
• Fault during three phase dead-time
• Auto-reclose out of service or CB not ready for an auto-reclosing cycle
“Prepare three phase tripping” is then used to switch the tripping to three phase. This
signal is generated by the auto-recloser and connected to the trip function block and
also connected outside the IED through IO when a common auto-recloser is provided
for two sub-systems. An alternative signal “Prepare 1 Phase tripping” is also provided
and can be used as an alternative when the autorecloser is shared with another
subsystem. This provides a fail safe connection so that even a failure in the IED with
the auto-recloser will mean that the other sub-system will start a three-phase trip.
A permanent fault will cause the line protection to trip again when it recloses in an
attempt to clear the fault.
Some examples:
When the function is set ON and operative (other conditions such as CB closed and
CB Ready are also fulfilled), the output SETON is activated (high). When the function
is ready to accept a reclosing start.
A number of conditions need to be fulfilled for the start to be accepted and a new
auto-reclosing cycle to be started. They are linked to dedicated inputs. The inputs are:
a) CBREADY, CB ready for a reclosing cycle, e.g. charged operating gear, b) CBPOS
to ensure that the CB was closed when the line fault occurred and start was applied,
c) No signal at input INHIBIT, i.e. no blocking or inhibit signal present. After the
start has been accepted, it is latched in and an internal signal “Started” is set. It can
be interrupted by certain events, like an “Inhibit” signal.
Depending of the starting principle (General Trip or only Instantaneous trip) adopted
above the delayed and back-up zones might not be required. Breaker failure local and
remote must however always be connected.
An auto-reclosing open time extension delay, tExtended t1, can be added to the normal
shot 1 delay. It is intended to come into use if the communication channel for
permissive line protection is lost. In such a case there can be a significant time
difference in fault clearance at the two ends of the line. A longer “auto-reclosing open
time” can then be useful. This extension time is controlled by setting parameter
Extended t1=On and the input PLCLOST.
Reclosing programs
The maximum number of reclosing shots in an auto-reclosing cycle is selected by the
parameter NoOfShots from 1 to 5. The type of reclosing used at the first reclosing
shot is set by parameter FirstShot. The first alternative is three-phase reclosing. The
The decision is also made in the tripping function block (TR) where the setting 3Ph,
1/3Ph (or1/2/3Ph) is selected.
FirstShot=1/2/3ph (normal setting for a 1/3 phase Auto reclose with Trip
modules (TR) in 1/3Phase trip)
1-phase, 2-phase or 3-phase reclosing first shot, followed by 3-phase reclosing shots,
if selected. Here, the auto-reclosing function is assumed to be "On" and "Ready". The
breaker is closed and the operation gear ready (operating energy stored). Input
START (or STARTHS) is received and sealed-in. The output READY is reset (set
to false). Output ACTIVE is set.
• If TR2P is low and TR3P is low (1-phase trip): The timer for 1-phase reclosing
open time is started and the output 1PT1 (1-phase reclosing in progress) is
activated. It can be used to suppress pole disagreement trip and earth-fault
protection during the 1-phase open interval.
• If TR2P is high and TR3P is low (2-phase trip): The timer for 2-phase reclosing
open time is started and the output 2PT1 (2-phase reclosing in progress) is
activated.
• If TR3P is high (3-phase trip): The timer for 3-phase auto-reclosing open time,
t1 3Ph or t1 3PhHS is started and output 3PT1 (3-phase auto-reclosing shot 1 in
progress) is set.
While any of the auto-reclosing open time timers are running, the output INPROGR
is activated. When the "open time" timer runs out, the respective internal signal is
transmitted to the output module for further checks and to issue a closing command
to the circuit breaker.
When a CB closing command is issued the output prepare 3-phase trip is set. When
issuing a CB closing command a “reclaim” timer tReclaim is started. If no tripping
takes place during that time the auto-reclosing function resets to the “Ready” state
and the signal ACTIVE resets. If the first reclosing shot fails, a 3-phase trip will be
initiated and 3-phase reclosing can follow, if selected.
A start of a new reclosing cycle is blocked during the set “reclaim time” after the
selected number of reclosing shots have been made.
Transient fault
After the Reclosing command the reclaim timer keeps running for the set time. If no
tripping occurs within this time, tReclaim, the Auto-Reclosing will reset. The CB
remains closed and the operating gear recharges. The input signals CBPOS and
CBREADY will be set
onto a persistent fault. It can also be used to generate a Lock-out of manual closing
until the operator has reset the lock-out, see separate section.
Lock-Out initiation
In many cases there is a requirement that a Lock-out is generated when the Auto-
Reclosing attempt fails. This is done with logic connected to the in- and outputs of
the Auto-Reclose function and connected to Binary IO as required. Many alternative
ways of performing the logic exist depending on whether manual closing is
interlocked in the IED, whether an external physical Lock-out relay exists and
whether the reset is hardwired, or carried out by means of communication. There are
also different alternatives regarding what shall generate Lock-out. Examples of
questions are:
In figures 65 and 66 the logic shows how a closing Lock-out logic can be designed
with the Lock-out relay as an external relay alternatively with the lock-out created
internally with the Manual closing going through the Synchro-check function. An
example of Lock-out logic.
OR AR
BJ-TRIP
SOTF-TRIP INHIBIT
UNSUCCL OR
SMBO
Lock-out
BFP RXMD1
11
TRBU 21
12
en05000315.vsd
OR AR
BJ-TRIP
SOTF-TRIP INHIBIT
UNSUCCL
OR
TR
SETLKOUT
CLLOUT
BFP SOFTWARE RESET LOCK-OUT RSTLOUT
OR IO RESET
BJTRIP
OR AND
MAN CLOSE SMBO
AR CLOSE
SYNC OR
AUTO STOP
CLOSE COMMAND
MAN ENOK
en05000316.vsd
Figure 66: Lock-out arranged with internal logic with manual closing going
through in IED
Evolving fault
An evolving fault starts as a single-phase fault which leads to single-phase tripping
and then the fault spreads to another phase. The second fault is then cleared by three-
phase tripping.
The Auto-Reclosing function will first receive a trip and start signal (START) without
any three-phase signal (TR3P). The Auto-Reclosing function will start a single-phase
reclosing, if programmed to do so. At the evolving fault clearance there will be a new
signal START and three-phase trip information, TR3P. The single-phase reclosing
sequence will then be stopped, and instead the timer, t1 3Ph, for three-phase reclosing
will be started from zero. The sequence will continue as a three-phase reclosing
sequence, if it is a selected alternative reclosing mode.
The second fault which can be single phase is tripped three phase because trip module
(TR) in the IED has an evolving fault timer which ensures that second fault is always
tripped three phase. For other types of relays where the relays do not include this
function the output PREP3PH (or the inverted PERMIT1PH) is used to prepare the
other sub-system for three phase tripping. This signal will, for evolving fault
situations be activated a short time after the first trip has reset and will thus ensure
that new trips will be three phase.
Configuration
The PCM configuration tool is used to configure signals.
Automatic-recloser function parameters are set via the local HMI panel or the
Parameter Setting Tool (PST) is a part of the PCM 600 tool and is installed on a PC
and connected to the front panel of the IED with an ordinary ethernet cable. Please
refer to the Application Manual (AM) for a list of the setting parameters and the local
HMI path.
ON and OFF
These inputs can be connected to binary inputs or to a communication interface block
for external control.
START
It should be connected to the trip output protection function, which starts the auto-
reclosing function. It can also be connected to a binary input for start from an external
contact. A logical OR-gate can be used to combine the number of start sources.
INHIBIT
To this input shall be connected signals that interrupt a reclosing cycle or prevent a
start from being accepted. Such signals can come from protection for a line connected
shunt reactor, from transfer trip receive, from back-up protection functions, busbar
protection trip or from breaker failure protection. When the CB open position is set
to start the Auto-Recloser, then manual opening must also be connected here. The
inhibit is often a combination of signals from external IED’s via the IO and internal
functions. An OR gate is then used for the combination.
SYNC
This is connected to the internal synchronism check function when required. It can
also be connected to a binary input for synchronization from an external device. If
neither internal nor external synchronism or energizing check is required, it can be
connected to a permanently high source, TRUE. The signal is required for three phase
shots 1-5 to proceed (Note! Not the HS step)
PLCLOST
This is intended for line protection permissive signal channel lost (fail) (e.g. PLC=
Power Line Carrier fail). It can be connected, when required to prolong the AR time
when communication is not working, i.e. one line end might trip with a zone 2 delay.
When the function is not used it is set to FALSE.
TRSOTF
This is the signal “Trip by Switch Onto Fault”. It is usually connected to the “switch
onto fault” output of line protection if multi-shot Auto-Reclose attempts are used.
The input will start the shots 2-5. For single shot applications the input is set to
FALSE.
THOLHOLD
Signal “Thermal overload protection holding back Auto-Reclosing”. It is normally
set to FALSE. It can be connected to a thermal overload protection trip signal which
resets only when the thermal content has gone down to an acceptable level, e.g. 70%.
As long as the signal is high, indicating that the line is hot, the Auto-Reclosing is held
back. When the signal resets, a reclosing cycle will continue. Please observe that this
have a considerable delay! Input can also be used for other purposes if for some reason
the Auto-Reclose shot is halted.
WAIT
Used to hold back reclosing of the “low priority unit” during sequential reclosing.
See “Recommendation for multi-breaker arrangement” below! The signal is activated
from output AR-WFMASTER on the second breaker Auto-Recloser in multi-breaker
arrangements.
BLKON
Used to block the Auto-Reclosing function e.g. when certain special service
conditions arise. Input is normally set to FALSE. When used, blocking must be reset
with AR-BLOCKOFF.
BLOCKOFF
Used to Unblock the Auto-Reclosing function when it has gone to Block due to
activating input AR-BLKON or by an unsuccessful Auto-Reclose attempt if the
setting BlockUnsuc is set to On. Input is normally set to FALSE.
RESET
Used to Reset the Auto-Recloser to start condition. Possible Thermal overload Hold
etc. will be reset. Positions, setting On-Off etc. will be started and checked with set
times. Input is normally set to FALSE.
SETON
Can be used to indicate that the auto-reclose function is switched On and operative.
BLOCKED
Indicates that the auto-reclose function is temporarily or permanently blocked.
ACTIVE
Indicates that the AR is active, from start until end of reclaim time.
INPROGR
Indicates that a sequence is in progress, from start until reclosing command.
UNSUCCL
Indicates unsuccessful reclosing.
CLOSECB
Connect to a binary output for circuit-breaker closing command.
READY
Indicates that the Auto-reclosing function is ready for a new and complete reclosing
sequence. It can be connected to the zone extension of a line protection should
extended zone reach before automatic reclosing be necessary.
PREP3P
Prepare 3-phase trip is usually connected to the trip block to force a coming trip to
be a 3-phase one. If the function cannot make a single- or two-phase reclosing, the
tripping should be three-phase.
PERMIT1P
Permit 1-phase trip is the inverse of AR-PREP1P. It can be connected to a binary
output relay for connection to external protection or trip relays. In case of a total loss
of auxiliary power, the output relay drops and does not allow 1-phase trip. If needed,
the signal can be inverted by a contact of the output relay breaking.
WFMASTER
Wait from master is used in high priority units to hold back reclosing of the low
priority unit during sequential reclosing. Refer to the recommendation for multi-
breaker arrangements in figure 69.
Other outputs
The other outputs can be connected for indication, disturbance recording etc. as
required.
IOM IOM
INPUT AR OUTPUT
xx ON BLOCKED xx
xx OFF SETON xx
xx F BLKON xx
INPROGR
xx T xx
BLOCKOFF ACTIVE
xx INHIBIT UNSUCCL xx
xx SUCCL xx
xx CBREADY xx
xx CBPOS xx
xx PLCLOST CLOSECB xx
xx xx
F RESET PERMIT1P
PREP3P
PROTECTION READY
xxxx-TRIP >1 START
F STARTHS 1PT1
F 2PT1
SKIPHS
SOTF-TRIP 3PT1
ZM1--TRIP >1 TRSOTF
3PT2
F 3PT3
THOLHOLD
F 3PT4
TR2P
T 3PT5
TR3P
SYN-AUTOOK
SYNC
F WAIT
F
RSTCOUNT
WFMASTER
en04000135.vsd
While the reclosing of the master is in progress, it issues the signal WFMASTER. A
reset delay of one second ensures that the WAIT signal is kept high for the duration
of the breaker closing time. After an unsuccessful reclosing it is also maintained by
the signal UNSUCCL. In the slave unit, the signal WAIT holds back a reclosing
operation. When the Wait signal is reset at the time of a successful reclosing of the
first CB, the slave unit is released to continue the reclosing sequence. A parameter
tWait sets a maximum waiting time for the reset of the WAIT. At time-out it interrupts
the reclosing cycle of the slave unit. If reclosing of the first breaker is unsuccessful,
the output signal UNSUCCL connected to the input INHIBIT of the slave unit
interrupts the reclosing sequence of the latter.
IOM IOM
INPUT AR- OUTPUT
xx ON BLOCKED xx
xx OFF SETON xx
xx F xx
BLKON INPROGR
T
xx BLOCKOFF ACTIVE xx
xx INHIBIT UNSUCCL xx
xx SUCCL xx
xx CBREADY xx
xx CBPOS xx
xx PLCLOST CLOSECB xx
xx PERMIT1P xx
F
RESET
PREP3P TRIP-P3PTR
PROTECTION START READY
xxxx-TRIP >1 1PT1 TEF-BLOCK
>1
2PT1
F
STARTHS 3PT1
F 3PT2
SKIPHS
3PT3
SOTF-TRIP TRSOTF
>1 3PT4
ZM1--TRIP
3PT5
F
THOLHOLD
TRIP-TR2P
TR2P
TRIP-TR3P TR3P
SYN-AUTOOK
SYNC
F
WAIT
F
RSTCOUNT
WFMASTER
en04000136.vsd
Terminal ‘‘ Master ”
Priority = High
AR
ON BLOCKED
OFF SETON
BLKON INPROGR
BLOCKOFF ACTIVE
INHIBIT UNSUCCL
RESET SUCCL
PLCLOST READY
START CLOSECB CB1
x
STARTHS
PERMIT1P
SKIPHS
PREP3P
THOLHOLD
TRSOTF 1PT1
2PT1
CBREADY 3PT1
CBPOS 3PT2
SYNC 3PT3
3PT4
WAIT 3PT5
RSTCOUNT
WFMASTER
Terminal ‘‘ Slave ”
Priority = Low
AR
ON BLOCKED
OFF SETON
BLKON INPROGR
BLOCKOFF ACTIVE
INHIBIT
UNSUCCL
RESET
SUCCL
PLCLOST READY
START x
CLOSECB CB2
STARTHS
SKIPHS PERMIT1P
PREP3P
TRSOTF
THOLHOLD 1PT1
2PT1
CBREADY
3PT1
CBPOS
3PT2
SYNC 3PT3
WAIT 3PT4
3PT5
WFMASTER
Operation
The operation of the Auto-reclose function can be switched on and off. The setting
“external control” makes it possible to switch it on or off using an external switch via
IO or communication ports.
Extended t1 and tExtended t1, Extended auto-reclosing open time for shot 1.
The communication link in a permissive (not strict) line protection scheme, for
instance a power line carrier (PLC) link, may not always be available. If lost, it can
result in delayed tripping at one end of a line. There is a possibility to extend the auto-
reclosing open time in such a case by use of an input to PLCLOST, and the setting
parameters. Typical setting in such a case: Extended t1 = ON and tExtended t1 = 0.8
s.
of a power swing when reclosing after a line fault. Too short a time may prevent a
potentially successful reclosing. A typical setting may be 2.0 s.
StartByCBOpen = Off, On
The normal setting is Off. It is used when the function is started by protection trip
signals Follow CB = Off, On The usual setting is Follow CB = Off. The setting “ON”
can be used for delayed reclosing with long delay, to cover the case when a CB is
being manually closed during the “auto-reclosing open time” before the auto-
reclosing function has issued its CB closing command.
tCBClosedMin
A typical setting is 5.0 s. If the CB has not been closed for at least this minimum time,
a reclosing start will not be accepted.
to ensure that the CB is ready for a C-O sequence at shot 2 and further shots. During
single-shot reclosing, the “OCO” selection can be used. A breaker shall according to
its duty cycle always have storing energy for a CO operation after the first trip. (IEC
56 duty cycle is O-0.3secCO-3minCO).
BlockUnsuc
Setting of whether an Unsuccessful Auto-Reclose attempt shall set the Auto-Reclose
in Block. If used the inputs BLOCKOFF must be configured to unblock the function
after an unsuccessful Reclosing attempt.Normal setting is Off.
Table 52: Parameter group settings for the SMBRREC_79 (AR01-) function
Parameter Range Step Default Unit Description
Operation Off - External ctrl - 0 = Off, 1 =
External ctrl ExternalCtrl, 2 = On
On
NoOfShots 1 - 1 - Max number of
2 reclosing shots 1-5
3
4
5
FirstShot 3 phase - 1/2/3ph - Restriction of fault
1/2/3ph type for shot 1
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
StartByCBOpen Off - Off - To be set ON if AR is
On to be started by CB
open position
CBAuxContType NormClosed - NormOpen - Select the CB aux
NormOpen contact type NC/NO
for CBPOS input
CBReadyType CO - CO - Select type of circuit
OCO breaker ready signal
CO/OCO
t1 1Ph 0.000 - 60.000 0.001 1.000 s Open time for shot 1,
single-phase
t1 2Ph 0.000 - 60.000 0.001 1.000 s Open time for shot 1,
two-phase
t1 3Ph 0.000 - 60.000 0.001 6.000 s Open time for shot 1,
delayed reclosing 3ph
t1 3PhHS 0.000 - 60.000 0.001 0.400 s Open time for shot 1,
high speed reclosing
3ph
t2 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 2,
three-phase
t3 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 3,
three-phase
t4 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 4,
three-phase
t5 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 5,
three-phase
tReclaim 0.00 - 6000.00 0.01 60.00 s Duration of the
reclaim time
tSync 0.00 - 6000.00 0.01 30.00 s Maximum wait time
for synchrocheck OK
Extended t1 Off - Off - Extended open time
On for loss of permissive
channel
tExtended t1 0.000 - 60.000 0.001 0.400 s Open time extended
by this value if
Extended t1 is true
Table continued on next page
4.11.3.1 Application
The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck,
operator place selection and external or internal blockings.
Figure 70 gives an overview from what places the apparatus control function receive
commands. Commands to an apparatus can be initiated from the Control Center (CC),
the station HMI or the local HMI on the IED front.
cc
Station HMI
GW
Station bus
The three latter functions are logical nodes according to IEC 61850. The signal flow
between these function blocks appears in figure 71. To realize the reservation
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV)
also are included in the apparatus control function. The application description for
all these functions can be found below. The function SCILO in the figure below is
the logical node for interlocking.
Control operation can be performed from the LHMI. Ithe administrator has defined
users with the UM tool, then the local/remote switch is under authority control. If not,
the default (factory) user is the SuperUser, that can perform control operations from
the LHMI without LogOn. The default position of the local/remote switch is on
remote.
IEC 61850
SCILO
en05000116.vsd
The bay control function also provides blocking functions that can be distributed to
different apparatuses within the bay. There are four different blocking alternatives:
The function does not have a corresponding functionality defined in the IEC 61850
standard, which means that this function is included as a vendor specific logical node.
After the selection of an apparatus and before the execution, the switch controller
performs the following checks and actions:
In the case when there are three one-phase switches (SXCBR) connected to the switch
controller function, the switch controller will "merge" the position of the three
switches to the resulting three-phase position. In case of a pole discordance situation,
i.e. the positions of the one-phase switches are not equal for a time longer than a
settable time; an error signal will be given. The mid position of apparatuses can be
suppressed at the (SCSWI) by setting the tIntermediate at (SXCBR/SXSWI) to an
appropriate value.
The switch controller is not dependent on the type of switching device SXCBR or
SXSWI. The switch controller represents the content of the CSWI logical node
(according to IEC 61850) with mandatory functionality.
Switch (SXCBR/SXSWI)
The Switch is a function used to close and interrupt an ac power circuit under normal
conditions or to interrupt the circuit under fault or emergency conditions. The
intention with this function is to represent the lowest level of a power-switching
device with or without short circuit breaking capability, e.g. circuit breakers,
disconnectors, earthing switches etc.
The purpose of this function is to provide the actual status of positions and to perform
the control operations, i.e. pass all the commands to the primary apparatus via output
boards and to supervise the switching operation and position.
The content of this function is represented by the IEC 61850 definitions for the logical
nodes XCBR and XSWI with mandatory functionality.
To ensure that the interlocking information is correct at the time of operation, a unique
reservation method is available in the IEDs. With this reservation method the
operation will temporarily be blocked for all switching devices in other bays, which
switching states are used for evaluation of permission to operate. Actual position
indications from these bays are then transferred over the serial bus for evaluation in
the IED. After the evaluation the operation can be executed with high security.
This functionality is realized over the station bus by means of the function blocks
QCRSV and RESIN. The application principle appears from figure 72.
The function block QCRSV handles the reservation. It sends out either the reservation
request to other bays or the acknowledgement if the bay has received a request from
another bay.
The other function block RESIN receives the reservation information from other bays.
The number of instances is the same as the number of involved bays (up to 60
instances are available). The received signals are either the request for reservation
from another bay or the acknowledgment from each bay respectively, which have
received a request from this bay. Also the information of valid transmission over the
station bus must be received.
REx670 REx670
SCSWI
RES_GRT
RES_RQ
3 RESIN
EXCH_IN
QCRSV
EXCH_OUT
RES_RQ1
From other ..
...
SCSWI in RES_RQ8
...
the bay
RES_GRT1 To other
RESIN ..
SCSWI
EXCH_IN RES_GRT8
in the
EXCH_OUT RES_DATA bay
3 2
...
Station bus
en05000117.vsd
Figure 72: Application principles for reservation over the station bus
The reservation can also be realized with external wiring according to the application
example in figure 73. This solution is realized with external auxiliary relays and extra
binary inputs and outputs in each IED, but without use of function blocks QCRSV
and RESIN.
REx670 REx670
SCSWI
RES_EXT
SELECTED
OR
Other SCSWI in the bay
BI BO BI BO
en05000118.vsd
The solution in figure 73 can also be realized over the station bus according to the
application example in figure 74. The solutions in figure 73 and figure 74 do not have
the same high security compared to the solution in figure 72, but have instead a higher
availability. This because no acknowledgment is required.
REx670 REx670
IntlReceive SCSWI
RESGRANT RES_EXT
SELECTED
. . .
. . .
IntlReceive SPGGIO
RESGRANT Other SCWI in OR IN
the bay
...
Station bus
en05000178.vsd
• The Switch controller, SCSWI, initializes all operations for one apparatus and
performs the actual switching and is more or less the interface to the drive of one
apparatus. It includes the position handling as well as the control of the position.
• The Circuit breaker, SXCBR, is the process interface to the circuit breaker for
the apparatus control function.
• The Circuit switch, SXSWI, is the process interface to the disconnector or the
earthing switch for the apparatus control function.
• The Bay Control, QCBAY, fulfils the bay-level functions for the apparatuses,
such as operator place selection and blockings for the complete bay.
• The Reservation, QCRSV, deals with the reservation function.
• The Residual overcurrent protection, EF4PEFM, trips the breaker in case of
ZMQPIDS.
• The Protection trip conditioning, SMPPTRC, connects the "operate" outputs of
one or more protection functions to a common "trip" to be transmitted to SXCBR.
• The Autoreclosing, SMBRREC, consists of the facilities to automatically close
a tripped breaker with respect to a number of configurable conditions.
• The logical node Interlocking, SCILO, provides the information to the switching
controller SCSWI weather it is permitted to operate due to the switchyard
topology. The interlocking conditions are evaluated with separate logic and
connected to SCILO.
• The Synchronism-check, SECRSYN calculates and compares the voltage phasor
difference from both sides of an open breaker with predefined switching
conditions (synchrocheck). Also the case that one side is dead (energizing-check)
is included.
• The logical node Generic Automatic Process Control, GAPC, is an automatic
function that reduces the interaction between the operator and the system. With
one command, the operator can start a sequence that will end with a connection
of a process object (e.g. line) to one of the possible busbars.
The overview of the interaction between these functions is shown in figure 75 below.
Trip
Synchrocheck
OK
Close cmd
Res. req. SCSWI SXCBR
Res. granted (Switching control) (Circuit breaker)
QCRSV
(Reservation) Res. req.
Close CB
SMBRREC
Enable
Enable
open
(Auto- close
Position
reclosure)
I/O
SCILO
(Interlocking)
other bays
Pos. from
Open rel.
Interlocking Close rel.
function Open rel.
block Close rel. SCILO
(Not a LN) Position (Interlocking)
Enable Enable
open close
GAPC Res.
granted Open cmd
(Generic
Close cmd
Automatic SCSWI SXSWI
Process Open/Close (Switching control) (Disconnector)
Control) Open/Close
Position
I/O
en05000120.vsd
The setting parameters for the apparatus control function are set via the local HMI or
Protection and Control IED Manager (PCM 600). Refer to the setting parameter
tables.
When the operation shall be performed in one step, the model direct control with
normal security is used.
At control with enhanced security there is an additional supervision of the status value
by the control object, which means that each command sequence must be terminated
by a termination command.
tSelect is the maximum time between the select and the execute command signal, i.e.
the time the operator has to perform the command execution after the selection of the
object to operate. When the time has expired, the selected output signal is set to false
and a cause-code is given over IEC 61850.
The time parameter tResResponse is the allowed time from reservation request to the
feedback reservation granted from all bays involved in the reservation function. When
the time has expired, the control function is reset.
tSynchrocheck is the allowed time for the synchrocheck function to fulfil the close
conditions. When the time has expired, the control function is reset.
tExecutionFB is the maximum time between the execute command signal and the
command termination. When the time has expired, the control function is reset.
tPoleDiscord is the allowed time to have discrepancy between the poles at control of
three one-phase breakers. At discrepancy an output signal is activated to be used for
trip or alarm.
Switch (SXCBR/SXSWI)
tStartMove is the supervision time for the apparatus to start moving after a command
execution. When the time has expired, the switch function is reset.
If the parameter AdaptivePulse is set to Adaptive the command output pulse resets
when a new correct end position is reached. If the parameter is set to Not adaptive
the command output pulse remains active until the timer tClose(Open)Pulse has
elapsed.
tOpenPulse is the output pulse length for an open command. The default length is set
to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. The default length is set
to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
When the parameter ParamRequestx (x=1-8) is set to Only own bay res. individually
for each apparatus (x) in the bay, only the own bay is reserved, i.e. the output for
reservation request of other bays (RES_BAYS) will not be activated at selection of
apparatus x.
4.11.4 Interlocking
The main purpose of switchgear interlocking is:
This document only deals with the first point, and only with restrictions caused by
switching devices other than the one to be controlled. This means that switch
interlock, because of device alarms, is not included in this document.
• With basically zero current. The circuit is open on one side and has a small
extension. The capacitive current is small (for example < 5A) and power
transformers with inrush current are not allowed.
• To connect or disconnect a parallel circuit carrying load current. The switching
voltage across the open contacts is thus virtually zero, thanks to the parallel circuit
(for example < 1% of rated voltage). Paralleling of power transformers is not
allowed.
Earthing switches are allowed to connect and disconnect earthing of isolated points.
Due to capacitive or inductive coupling there may be some voltage (for example <
40% of rated voltage) before earthing and some current (for example < 100A) after
earthing of a line.
Circuit breakers are usually not interlocked. Closing is only interlocked against
running disconnectors in the same bay, and the bus-coupler opening is interlocked
during a busbar transfer.
The positions of all switching devices in a bay and from some other bays determine
the conditions for operational interlocking. Conditions from other stations are usually
not available. Therefore, a line earthing switch is usually not fully interlocked. The
operator must be convinced that the line is not energized from the other side before
closing the earthing switch. As an option, a voltage indication can be used for
interlocking. Take care to avoid a dangerous enable condition at the loss of a VT
secondary voltage, for example, because of a blown fuse.
The switch positions used by the operational interlocking logic are obtained from
auxiliary contacts or position sensors. For each end position (open or closed) a true
indication is needed - thus forming a double indication. The apparatus control function
continuously checks its consistency. If neither condition is high (1 or TRUE), the
switch may be in an intermediate position, for example, moving. This dynamic state
may continue for some time, which in the case of disconnectors may be up to 10
seconds. Should both indications stay low for a longer period, the position indication
will be interpreted as unknown. If both indications stay high, something is wrong, and
the state is again treated as unknown. In both cases an alarm is sent to the operator.
Indications from position sensors shall be self-checked and system faults indicated
by a fault signal. In the interlocking logic, the signals are used to avoid dangerous
enable or release conditions. When the switching state of a switching device cannot
be determined operation is not permitted.
For switches with an individual operation gear per phase, the evaluation must consider
possible phase discrepancies. This is done with the aid of an AND-function for all
three phases in each apparatus for both open and close indications. Phase
discrepancies will result in an unknown double indication state.
The following sections describe how the interlocking for a certain switchgear
configuration can be realized in the IED by using standard interlocking modules and
their interconnections. They also describe the configuration settings. The inputs for
delivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except
in the following cases:
The interlocking module ABC_LINE is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 76. The module can also be
used for a double busbar arrangement without transfer busbar or a single busbar
arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1
QA1
QC2
QB9
QC9
en04000478.vsd
The signals from other bays connected to the module ABC_LINE are described
below.
These signals from each line bay (ABC_LINE) except that of the own bay are needed:
Signal
QB7OPTR Q7 is open
VPQB7TR The switch status for QB7 is valid.
EXDU_BPB No transmission error from the bay that contains the above information.
QB7OPTR (bay 1)
QB7OPTR (bay 2) & BB7_D_OP
. . .
. . .
QB7OPTR (bay n-1)
VPQB7TR (bay 1)
VPQB7TR (bay 2) & VP_BB7_D
. . .
. . .
VPQB7TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2) & EXDU_BPB
. . .
. . .
EXDU_BPB (bay n-1)
en04000477.vsd
Section 1 Section 2
(WA1)A1 A2
(WA2)B1 B2
(WA7)C C
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE ABC_BC ABC_LINE ABC_BC
en04000479.vsd
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR The bus-section disconnector is open.
DCCLTR The bus-section disconnector is closed.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-
section coupler bay (A1A2_BS), rather than the bus-section disconnector bay
(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B are
used. The same type of module (A1A2_BS) is used for different busbars, that is, for
both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.
S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay that contains the above information.
BC12CLTR (sect.1)
BC_12_CL
DCCLTR (A1A2) >1
DCCLTR (B1B2) &
BC12CLTR (sect.2)
VPBC12TR (sect.1)
VPDCTR (A1A2) & VP_BC_12
VPDCTR (B1B2)
VPBC12TR (sect.2)
BC17OPTR (sect.1)
BC_17_OP
&
DCOPTR (A1A2) >1
BC17OPTR (sect.2)
BC17CLTR (sect.1)
BC_17_CL
>1
DCCLTR (A1A2) &
BC17CLTR (sect.2)
VPBC17TR (sect.1)
VPDCTR (A1A2) & VP_BC_17
VPBC17TR (sect.2)
BC27OPTR (sect.1)
BC_27_OP
&
DCOPTR (B1B2) >1
BC27OPTR (sect.2)
BC27CLTR (sect.1)
BC_27_CL
>1
DCCLTR (B1B2) &
BC27CLTR (sect.2)
VPBC27TR (sect.1)
VPDCTR (B1B2) & VP_BC_27
VPBC27TR (sect.2)
EXDU_BC (sect.1)
EXDU_DC (A1A2) & EXDU_BC
EXDU_DC (B1B2)
EXDU_BC (sect.2)
en04000480.vsd
Figure 79: Signals to a line bay in section 1 from the bus-coupler bays in each
section
For a line bay in section 2, the same conditions as above are valid by changing section
1 to section 2 and vice versa.
Configuration setting
If there is no bypass busbar and therefore no QB7 disconnector, then the interlocking
for QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to
open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
• QB7_OP = 1
• QB7_CL = 0
• QC71_OP = 1
• QC71_CL = 0
• BB7_D_OP = 1
• BC_17_OP = 1
• BC_17_CL = 0
• BC_27_OP = 1
• BC_27_CL = 0
• EXDU_BPB = 1
• VP_BB7_D = 1
• VP_BC_17 = 1
• VP_BC_27 = 1
If there is no second busbar WA2 and therefore no QB2 disconnector, then the
interlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are set
to open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
• QB2_OP = 1
• QB2_CL = 0
• QC21_OP = 1
• QC21_CL = 0
• BC_12_CL = 0
• BC_27_OP = 1
• BC_27_CL = 0
• VP_BC_12 = 1
The interlocking module ABC_BC is used for a bus-coupler bay connected to a double
busbar arrangement according to figure 80. The module can also be used for a single
busbar arrangement with transfer busbar or double busbar arrangement without
transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1
QA1
QC2
en04000514.vsd
WA1 (A)
WA2 (B)
QB1 QB2
QC1
QA1
AB_TRAFO
QC2
QC3
QA2
QA2 and QC4 are not
QC4 used in this interlocking
QB3 QB4
en04000515.vsd
The interlocking module A1A2_BS is used for one bus-section circuit breaker
between section 1 and 2 according to figure 82. The module can be used for different
busbars, which includes a bus-section circuit breaker.
QA1
QC3 QC4
en04000516.vsd
A1A2_BS
The interlocking module A1A2_DC is used for one bus-section disconnector between
section 1 and 2 according to figure 83. The module can be used for different busbars,
which includes a bus-section disconnector.
QB
WA1 (A1) WA2 (A2)
QC1 QC2
A1A2_DC en04000492.vsd
The interlocking module BB_ES is used for one busbar earthing switch on any busbar
parts according to figure 84.
QC
en04000504.vsd
The signals from other bays connected to the module BB_ES are described below.
Section 1 Section 2
(WA1)A1 A2
(WA2)B1 B2
(WA7)C C
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES ABC_BC BB_ES
ABC_LINE AB_TRAFO ABC_LINE
en04000505.vsd
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and each bus-coupler bay (ABC_BC) are needed:
Signal
QB1OPTR QB1 is open.
QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)
QB220OTR QB2 and QB20 are open (ABC_BC)
QB7OPTR QB7 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
VQB220TR The switch status of QB2 and QB20 are valid.
VPQB7TR The switch status of QB7 is valid.
EXDU_BB No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Signal
DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-
section coupler bay (A1A2_BS) rather than the bus-section disconnector bay
(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B are
used. The same type of module (A1A2_BS) is used for different busbars, that is, for
both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
QB1OPTR QB1 is open.
QB2OPTR QB2 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains the
above information.
For a busbar earthing switch, these conditions from the A1 busbar section are valid:
Figure 86: Signals from any bays in section A1 to a busbar earthing switch in
the same section
For a busbar earthing switch, these conditions from the A2 busbar section are valid:
Figure 87: Signals from any bays in section A2 to a busbar earthing switch in
the same section
For a busbar earthing switch, these conditions from the B1 busbar section are valid:
QB2OPTR(QB220OTR)(bay 1/sect.B1)
... & BB_DC_OP
...
...
QB2OPTR (QB220OTR)(bay n/sect.B1)
DCOPTR (B1/B2)
VPQB2TR(VQB220TR)
. . .(bay 1/sect.B1) VP_BB_DC
&
...
...
VPQB2TR(VQB220TR) (bay n/sect.B1)
VPDCTR (B1/B2)
Figure 88: Signals from any bays in section B1 to a busbar earthing switch in
the same section
For a busbar earthing switch, these conditions from the B2 busbar section are valid:
Figure 89: Signals from any bays in section B2 to a busbar earthing switch in
the same section
For a busbar earthing switch on bypass busbar C, these conditions are valid:
QB7OPTR (bay 1)
... & BB_DC_OP
...
...
QB7OPTR (bay n)
VPQB7TR (bay 1)
... & VP_BB_DC
...
...
VPQB7TR (bay n)
EXDU_BB (bay 1)
... & EXDU_BB
...
...
EXDU_BB (bay n) en04000510.vsd
Section 1 Section 2
(WA1)A1 A2
(WA2)B1 B2
A1A2_DC(BS)
BB_ES B1B2_DC(BS) BB_ES
DB_BUS DB_BUS
en04000511.vsd
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Signal
DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration described in section “Signals
in single breaker arrangement”.
Section 1 Section 2
(WA1)A1 A2
(WA2)B1 B2
A1A2_DC(BS)
BB_ES B1B2_DC(BS) BB_ES
BH_LINE BH_LINE
en04000512.vsd
The project-specific logic are the same as for the logic for the double busbar
configuration described in section “Signals in single breaker arrangement”.
Signal
BB_DC_OP All disconnectors on this part of the busbar are open.
VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB No transmission error from any bay that contains the above information.
The interlocking modules DB_BUS_A, DB_LINE and DB_BUS_B are used for a
line connected to a double circuit breaker arrangement according to figure 93.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4
QA1 QA2
DB_BUS_A DB_BUS_B
QC2 QC5
QB61 QB62
QC3
QB9
DB_LINE
QC9
en04000518.vsd
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are connected
to the busbars. DB_BUS_A and DB_BUS_B are the connections from the line to the
busbars.
Configuration setting
For application without QB9 and QC9, just set the appropriate inputs to open state
and disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
• QB9_OP = 1
• QB9_CL = 0
• QC9_OP = 1
• QC9_CL = 0
If, in this case, a line voltage supervision is added, then rather than setting QB9 to
open state, specify the state of the voltage supervision:
• QB9_OP = VOLT_OFF
• QB9_CL = VOLT_ON
• VOLT_OFF = 1
• VOLT_ON = 0
The interlocking modules BH_LINE_A, BH_CONN and BH_LINE_B are used for
lines connected to a breaker-and-a-half diameter according to figure 94.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1
QA1 QA1
QC2 QC2
QB6 QB6
QC3 QC3
BH_LINE_A BH_LINE_B
QB9 QB9
QC1 QC2
QC9 QC9
BH_CONN
en04000513.vsd
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the breaker and a half switchyard
layout.
4.11.5.1 Application
The SLGGIO function block (or the selector switch function block, as it is also
known) is used within the CAP configuration tool in order to get a selector switch
functionality similar with the one provided by a hardware selector switch. Hardware
selector switches are used extensively by utilities, in order to have different functions
operating on pre-set values. Hardware switches are however sources for maintenance
issues, lower system reliability and extended purchase portfolio. The virtual selector
switches eliminate all these problems.
The SLGGIO function block has two operating inputs (UP and DOWN), one blocking
input (BLOCK) and one operator position input (PSTO). The normal way a selector
switch is connected would be in accordance with fig.:
This is a minimal configuration, allowing for selector switch operation both from the
LHMI and from external sources (switches), via the IED binary inputs. It also allows
the operation from remote (like the station computer). The POS_NUM is an integer
value output, giving the actual output number. In this particular example, this is a
selector switch with 10 positions. Since the number of positions of the switch can be
established by settings (see below), one must be careful in coordinating the settings
with the configuration (if one sets the number of positions to x in settings – for
example, there will be only the first x outputs available from the block in the
configuration). Also the frequency of the (UP or DOWN) pulses should be lower than
the setting tPulse.
From the LHMI, there are two modes of operating the switch: from the menu and
from the SLD. An example of these two types of operation is given in this document:
The following settings are available for the Logic rotating switch for function
selection and LHMI presentation function:
noOfPositions: Sets the number of positions in the switch (max. 32)- this setting
influence the behaviour of the switch when changes from the last to the first position;
operatePulseLenght: In case of a pulsed output, it gives the length of the pulse (in
seconds);
timeDelay: The delay between the UP or DOWN activation signal positive front and
the output activation;
stopAtExtreme: Sets the behavior of the switch at the end positions – if set to 0, when
pressing UP while on first position, the switch will jump to the last position; when
pressing DOWN at the last position, the switch will jump to the first position; when
set to 1, no jump will be allowed;
Table 61: Parameter group settings for the SSGGIO (LRS1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off/On
On
NrPos 2 - 32 1 32 - Number of positions
in the switch
OutType Pulsed - Steady - Output type, steady
Steady (=1) or pulse (=0)
tPulse 0.000 - 60.000 0.001 0.200 s Operate pulse
duration, in [s]
tDelay 0.000 - 60000.000 0.010 0.000 s Time delay on the
output, in [s]
4.11.6.1 Application
The DPGGIO function block is used to send three logical outputs to other systems or
equipment in the substation. The three outputs are named “OPEN”, “CLOSE” and
“VALID”, since this function block is intended to be used as a position indicator
block in interlocking and reservation station-wide logics.
There are no settings available for the user for DPGGIO. However, to get the signals
sent by DPGGIO one must use the engineering tools described in chapter
"Engineering of the IED".
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.12 Logic
4.12.1.1 Application
All trip signals from the different protection functions shall be routed through the trip
logic. In its simplest alternative the logic will only link the trip signal and make sure
that it is long enough.
The tripping logic in IED 670 protection, control and monitoring IEDs offers three
different operating modes:
The three phase trip for all faults offers a simple solution and is often sufficient in
well meshed transmission systems and in sub-transmission systems. Since most
faults, especially at the highest voltage levels, are single phase to earth faults, single
phase tripping can be of great value. If only the faulty phase is tripped, power can
still be transferred on the line during the dead time that arises before reclosing. Single
phase tripping during single phase faults must be combined with single pole reclosing.
To meet the different double, one- and a half and other multiple circuit breaker
arrangements, two identical TR function blocks may be provided within the IED.
One TR function block should be used for each breaker, if the line is connected to
the substation via more than one breaker. Assume that single pole tripping and auto-
reclosing is used on the line. Both breakers are then normally set up for 1/3 phase
tripping and 1/3 phase auto-reclosing. As an alternative the breaker chosen as master
can have single pole tripping, while the slave breaker could have three pole tripping
and auto-reclosing. In the case of a permanent fault, only one of the breakers has to
be operated when the fault is energized a second time. In the event of a transient fault
the slave breaker performs a three pole reclosing onto the non-faulted line.
The same philosophy can be used for two-pole tripping and auto-reclosing.
To prevent closing of a circuit breaker after a trip the function can block the closing.
The two instances of the TR function are identical except for the name of the function
block (TRP1 and TRP2). References will therefore only be made to TRP1 in the
following description, but they also apply to TRP2.
TRP1
TRIP LOGIC
BLOCK TRIP
BLKLKOUT TRL1
TRIN TRL2
TRINL1 TRL3
TRINL2 TR1P
TRINL3 TR2P
PSL1 TR3P
PSL2 CLLKOUT
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
en05000543.vsd
This signal can also be used for other purposes internally in the IED. An example
could be the starting of Breaker failure protection. The three outputs TRL1, TRL2,
TRL3 will always be activated at every trip and can be utilized on individual trip
outputs if single pole operating devices are available on the circuit breaker even when
a Three phase tripping scheme is selected.
Set the function block to Program=3Ph and set the required length of the trip pulse
to e.g. tTripMin=150ms.
For special applications such as Lock-out refer to the separate section below. The
typical connection is shown below in figure 96. Signals that are not used are dimmed.
TRP1-
SMPPTRC_94
BLOCK TRIP
ZM1 TRIP
BLKLKOUT TRL1
ZM2 TRIP
³1 TRIN TRL2
ZM3 TRIP
DEF TRIP TRINL1 TRL3
TRINL2 TR1P
TRINL3 TR2P
PSL1 TR3P
PSL2 CLLKOUT
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
en05000544.vsd
Figure 96: The trip logic function TR is used for a simple three phase tripping
application.
The single phase tripping can include different options and the use of the different
inputs in the function block.
The inputs 1PTRZ and 1PTREF are used for single phase tripping for Distance
protection and Directional Earth fault protection function as required.
The inputs are combined with the phase selection logic and the start signals from the
phase selector must be connected to the inputs PSL1, PSL2 and PSL3 to achieve the
tripping on the respective single phase trip outputs TRL1, TRL2 and TRL3. The
Output TRIP is a General Trip and activated independent of which phase is involved.
Depending on which phases are involved the outputs TR1P,TR2P and TR3P will be
activated as well.
When single phase tripping schemes are used a single phase Auto Reclosing attempt
is expected to follow. For cases where the Auto-Reclosing is not in service or will
not follow for some reason, the input Prepare Three Phase Trip P3PTR must be
activated. This is normally connected to the respective output on the Auto-Recloser
but can also be connected to other signals, e.g. an external logic signal.If two breakers
are involved, one TR block instance and one Auto-Recloser instance is used for each
breaker. This will ensure correct operation and behavior of each breaker.
The output Trip 3 Phase TR3P must be connected to the respective input in the Auto-
Recloser to switch the Auto-Recloser to three phase Reclosing. If this signal is not
activated the Auto-Recloser will use single-phase Reclosing dead time. Note also that
if a second Line protection is utilizing the same Auto-Recloser the 3 Phase Trip signal
must be generated e.g. by using the three trip relays contacts in series and connecting
them in parallel to the TR3P output from the trip block.
The Trip Logic also has inputs TRINL1, TRINL2 and TRINL3 where phase selected
trip signals can be connected. Examples can be individual phase inter-trips from
remote end or internal/external phase selected trip signals which are routed through
the IED to achieve e.g. Auto-Reclose, Breaker failure etc.Other back-up functions
are connected to the input TRIN as described above. A typical connection for a single
phase tripping scheme is shown below in figure 97.
ZM2 TRIP
TRP1-
ZM3 TRIP SMPPTRC_94
³1
DEF TRIP
BLOCK TRIP
BLKLKOUT TRL1
ZM01
TRIN TRL2
Distance
TRIP
Function TRINL1 TRL3
PSL3 PSL3
TR3P 1PTRZ
AR01
1PTREF
Auto-Recloser
PREP3P P3PTR
SETLKOUT
TR3P RSTLKOUT
en05000545.vsd
Figure 97: The trip logic function TR used for Single phase tripping application.
The functionality is very similar to the single phase scheme described above. However
the Auto-Reclose must in addition to the connections for single phase above be
informed that the trip is two phase by connecting the Trip Logic output TR2P to the
respective input in the Auto-Recloser.
Lock-out
This function block is provided with possibilities to initiate lock-out. The lock-out
can be set to only activate the block closing output CLLKOUT or initiate the block
closing output and also maintain the trip signal (latched trip).
The Lock-out can then be manually reset after checking the primary fault by activating
the input reset Lock-Out RSTLKOUT.
If external conditions are required to initiate Lock-out but not initiate trip this can be
achieved by activating input SETLKOUT. The setting Auto-Lock = OFF will mean
that the internal trip is not activating lock-out so only initiation of the input
SETLKOUT will result in lock-out. This is normally the case for overhead line
protection where most faults are transient. Unsuccessful auto-reclose and back-up
zone tripping can in such cases be connected to initiate Lock-out by activating the
input.
The paramters for tripping logic are set via the local HMI or Protection and Control
IED Manager (PCM 600).
Operation: On or Off
Sets the mode of operation. Off switches the tripping off. The normal selection is:
Operation=On
Program: 3Ph,1/3Ph,1/2/3Ph
Set the required tripping scheme. Normally 3Ph or 1/2Ph are used.
TripLockout: On or Off
Set the scheme for lock-out. Off only activates lock-out output. On activates the lock-
out output and latching output contacts. The normal selection is: TripLockout=Off.
AutoLock: On or Off
Setting the scheme for lock-out. Off only activates lock-out through the input SET-
LOCKOUT. On also allows activation from trip function itself. The normal selection
is: AutoLock=Off.
tTripMin
Set the required minimum duration of the trip pulse. It should be set to ensure that
the breaker is tripped and if a signal is used to start the breaker failure protection
(BFP) function longer than the back-up trip timer in the BFP. Normal setting is:
tTripMin=0.150s
Table 62: Parameter group settings for the SMPPTRC_94 (TRP1-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
Program 3 phase - 1ph/3ph - Three ph; single or
1ph/3ph three ph; single, two
1ph/2ph/3ph or three ph trip
TripLockout Off - Off - On: activate output
On (CLLKOUT) and trip
latch, Off: only outp
AutoLock Off - Off - On: lockout from input
On (SETLKOUT) and
trip, Off: only inp
tTripMin 0.000 - 60.000 0.001 0.150 s Minimum duration of
trip output signal
4.12.2.1 Application
Twelve trip matrix logic blocks are included in the IED. The function blocks are used
in the configuration of the IED to route trip signals and/or other logical output signals
to the different output relays.
The matrix and the physical outputs will be seen in the PCM 600 engineering tool
and this allows the user to adapt the signals to the physical tripping outputs according
to the specific application needs.
Table 63: Parameter group settings for the TRMGGIO (TR01-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
PulseTime1 0.000 - 60.000 0.001 0.000 s Output pulse time for
output 1
OnDelayTime1 0.000 - 60.000 0.001 0.000 s Output on delay time
for output 1
OffDelayTime1 0.000 - 60.000 0.001 0.000 s Output off delay time
for output 1
PulseTime2 0.000 - 60.000 0.001 0.000 s Output pulse time for
output 2
OnDelayTime2 0.000 - 60.000 0.001 0.000 s Output on delay time
for output 2
OffDelayTime2 0.000 - 60.000 0.001 0.000 s Output off delay time
for output 2
PulseTime3 0.000 - 60.000 0.001 0.000 s Output pulse time for
output 3
OnDelayTime3 0.000 - 60.000 0.001 0.000 s Output on delay time
for output 3
OffDelayTime3 0.000 - 60.000 0.001 0.000 s Output off delay time
for output 3
4.12.3.1 Application
A high number of logic blocks and timers are available for user to adapt the
configuration to the specific application needs.
There are no settings for AND gates, OR gates, inverters or XOR gates.
For normal On/Off delay and pulse timers the time delays and pulse lengths are set
from the CAP configuration tool.
Both timers in the same logic block (the one delayed on pick-up and the one delayed
on drop-out) always have a common setting value. Pulse length settings are
independent of one another for all pulse circuits.
For controllable gates, settable timers and SR flip-flops with memory, the setting
parameters are accessible via the local HMI or Protection and Control IED Manager
(PCM 600).
Configuration
Logic is configured using the CAP configuration tool.
For each cycle time, the function block is given an serial execution number. This is
shown when using the CAP configuration tool with the designation of the function
block and the cycle time, for example, TMnn-(1044, 6). TMnn is the designation of
the function block, 1044 is the serial execution number and 6 is the cycle time.
The execution of different function blocks within the same cycle is determined by
the order of their serial execution numbers. Always remember this when connecting
two or more logical function blocks in series.
Table 66: Parameter group settings for the SRM (SM01-) function
Parameter Range Step Default Unit Description
Memory Off - Off - Operating mode of
On the memory function
Table 68: Parameter group settings for the TimerSet (TS01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off/On
On
t 0.000 - 90000.000 0.001 0.000 s Delay for settable
timer n
4.12.4.1 Application
The fixed signals function block generates a number of pre-set (fixed) signals that
can be used in the configuration of a IED, either for forcing the unused inputs in the
other function blocks to a certain level/value, or for creating a certain logic.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.13 Monitoring
4.13.1.1 Application
All measured values can be supervised with four settable limits, i.e. low-low limit,
low limit, high limit and high-high limit. A zero clamping reduction is also supported,
i.e the measured value below a settable limit is forced to zero which reduces the impact
of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure value
can also be based on periodic reporting.
The measuring function, SVR, provides the following power system quantities:
It is possible to calibrate the measuring function above to get class 0.5 presentation.
This is accomplished by angle and amplitude compensation at 5, 30 and 100% of
rated current and voltage.
The IED can be provided with up to 3 SVR-, 10 CP-, 5 VP-, 3 CSQ- and 3 VSQ-
measurement functions.
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM
600.
The parameters for the Measurement function (MMXU, MSQI) are set via the local
HMI or Protection and Control IED Manager (PCM 600).
Operation: Off/On. Every function instance (SVRx, CPxx, VP0x, CSQxx, VSQx)
can be taken in operation (On) or out of operation (Off). Default setting is Off.
The following general settings can be set for the Service Value functions (SVR).
PowAngComp: Angle compensation for phase shift between measured I & U. The
setting range is ±180 degrees. Default setting is 0 degree, which also is a typical
setting.
Mode: Selection of measured current and voltage. There are 9 different ways of
calculating monitored three-phase values depending on the available VT inputs
connected to the IED. See parameter group setting table. Default setting expects
complete VT information (L1,L2,L3).
k: Low pass filter coefficient for power measurement, U and I. The setting range is
0.0-1.0. Default setting is 0.0 i.e. no filtering, which also is a typical setting.
UBase: Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage supervised
object. The setting range is 0.05-2000 kV. Default setting is 400 kV.
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the supervised
object. The setting range is 1-99999 A. Default setting is 3000 A.
The following general settings can be set for the phase current monitoring
functions (CP).
The following general settings can be set for the phase-phase voltage monitoring
functions (VP).
The following general settings can be set for all monitored quantities included in
the functions (SVR, CP, VP, CSQ and VSQ).
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
The setting range is 0-100000 in steps of 0.001% related to measuring range. Default
setting is 0. Observe the related zero point clamping settings in Setting group N for
SVR (UGenZeroDb and IGenZeroDb). If measured value is below UGenZeroDb and/
or IGenZeroDb calculated S, P, Q and PF will be zero and these settings will override
XZeroDb.
XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and is
reporting interval in seconds. Amplitude deadband is the setting value in % of
measuring range. Integral deadband setting is the integral area, i.e. measured value
in % of measuring range multiplied by the time between two measured values. Default
setting is 10.
XHiHiLim: High-high limit. Set in applicable measuring unit. The setting range is
±10000000000 in steps of 0.001. Default setting is 900·106 (i.e 900 MW/MVar/
MVA).
XLimHyst: Hysteresis value in % of range and is common for all limits. The setting
range is 0-100 in steps of 0.001. Default setting is 5%.
All phase angles are presented in relation to defined reference channel. The parameter
PhaseAngleRef defines the reference, see section "Analog inputs".
Calibration curves
It is possible to calibrate the functions (SVR, CP and VP) to get class 0.5 presentations
of currents, voltages and powers. This is accomplished by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation curve
will have the characteristic for amplitude and angle compensation of currents as
shown in figure 98 (example). The first phase will be used as reference channel and
compared with the curve for calculation of factors. The factors will then be used for
all related channels.
Amplitude
% of Ir compensation
-10
IAmpComp5 Measured
IAmpComp30 current
IAmpComp100
5 30 100 % of Ir
0-5%: Constant
-10 5-30-100%: Linear
>100%: Constant
Degrees Angle
compensation
-10
IAngComp30 Measured
current
IAngComp5
IAngComp100
5 30 100 % of Ir
-10
en05000652.vsd
Setting examples
Three setting examples, in connection to service values (SVR), are provided:
For each of them detail explanation and final list of selected setting parameters values
will be provided.
400kV Busbar
800/1 A
400 0,1
/ kV
3 3
P Q
In order to monitor, supervise and calibrate the active and reactive power as indicated
in the above figure it is necessary to do the following:
Table 69: General settings parameters for the Service Value Report function
CAP & PST name Short Description (60 char) Selected Comments
value
Operation Operation Off/On On Function must be "On"
PowAmpFact Amplitude factor to scale power 1.000 It can be used during commissioning
calculations to achieve higher measurement
accuracy. Typically no scaling is
required
PowAngComp Angle compensation for phase 0.0 It can be used during commissioning
shift between measured I & U to achieve higher measurement
accuracy. Typically no angle
compensation is required. As well
here required direction of P & Q
measurement is towards protected
object (i.e. as per IED internal default
direction)
Mode Selection of measured current L1, L2, L3 All three phase to ground VT inputs
and voltage are available
k Low pass filter coefficient for 0.00 Typically no additional filtering is
power measurement, U and I required
Table continued on next page
CAP & PST name Short Description (60 char) Selected Comments
value
UGenZeroDb Zero point clamping in % of Ubase 25 Set minimum voltage level to 25%.
Voltage below 25% will force S, P and
Q to zero.
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%.
Current below 3% will force S, P and
Q to zero.
UBase Base setting for voltage level in kV 400.00 Set rated OHL phase-to-phase
voltage
IBase Base setting for current level in A 800 Set rated primary CT current used for
OHL
CAP & PST name Short Description (60 char) Selected Comments
value
IAngComp5 Angle calibration for current at 5% 0.00
of Ir
IAngComp30 Angle pre-calibration for current at 0.00
30% of Ir
IAngComp100 Angle pre-calibration for current at 0.00
100% of Ir
110kV Busbar
200/1
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
P Q
500/5
UL1L2
35 / 0,1kV
In order to measure the active and reactive power as indicated in the above figure, it
is necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see section "Analog inputs") data using the Parameter Setting Tool for analog
input channels
2. Connect in Application Configuration Tool measurement function to LV side
CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
CAP & PST name Short description (60 char) Selected Comment
value
Operation Operation Off/On On Function must be "On"
PowAmpFact Amplitude factor to scale power 1.000 Typically no scaling is required
calculations
PowAngComp Angle compensation for phase 180.0 Typically no angle compensation is
shift between measured I & U required. However here the required
direction of P & Q measurement is
towards busbar (i.e. Not per IED
internal default direction). Therefore
angle compensation have to be used
in order to get measurements in
aliment with the required direction.
Mode Selection of measured current L1L2 Only UL1L2 phase-to-phase voltage
and voltage is available
k Low pass filter coefficient for 0.00 Typically no additional filtering is
power measurement, U and I required
UGenZeroDb Zero point clamping in % of Ubase 25 Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase Base setting for voltage level in kV 35.00 Set LV side rated phase-to-phase
voltage
IBase Base setting for current level in A 495 Set transformer LV winding rated
current
220kV Busbar
300/1
100 MVA
242/15,65 kV
Yd5
15 / 0,1kV
UL1L2 , UL2L3
P Q
100MVA G
15,65kV
4000/5
en05000376.vsd
In order to measure the active and reactive power as indicated in the above figure, it
is necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef (see section "Analog inputs") using the Parameter Setting Tool
for analog input channels
2. Connect in Application Configuration Tool measurement function to the
generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
CAP & PST name Short description (60 char) Selected Comment
value
Operation Operation Off/On On Function must be “On"
PowAmpFact Amplitude factor to scale power 1.000 Typically no scaling is required
calculations
PowAngComp Angle compensation for phase 0.0 Typically no angle compensation is
shift between measured I & U required. As well here required
direction of P & Q measurement is
towards protected object (i.e. as per
IED internal default direction)
Mode Selection of measured current Arone Generator VTs are connected
and voltage between phases (i.e. V-connected)
Table continued on next page
CAP & PST name Short description (60 char) Selected Comment
value
k Low pass filter coefficient for 0.00 Typically no additional filtering is
power measurement, U and I required
UGenZeroDb Zero point clamping in % of Ubase 25% Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase Base setting for voltage level in kV 15,65 Set generator rated phase-to-phase
voltage
IBase Base setting for current level in A 3690 Set generator rated current
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM
600.
4.13.2.1 Application
This function has six counters which are used for storing the number of times each
counter has been activated. All six counters have a common blocking function used,
for example, when testing. All sex counters can be set on or off using a parameter
setting Operation on off. All sex counters has a common reset and a common function.
The setting parameters for the event counter function are set via the local HMI or
Protection and Control IED Manager (PCM 600). Refer to the setting parameter
tables.
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
4.13.3.1 Application
Analog and double indication values are also transferred through the event block.
The setting parameters for the event function are set from the PST parameter setting
tool, part of PCM 600.
EventMaskCh_1 - 16
The inputs can be set individually as:
• NoEvents
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect
LONChannelMask/SPAChannelMask
Definition of which part of the event function block that shall generate events:
• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16
MinInterval_1 - 16
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0.0 s to 1000.0 s in steps of 0.1 s. It should normally be set
to 0, i.e. no cyclic communication.
MaxEvPerSec
Three times this setting value gives the maximum burst quota per input channel. A
reasonable value as default should be 10 events/s which gives 30 events/s as a
maximum sustained event rate per channel.
4.13.4.1 Application
The main objective of line protection and monitoring terminals is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
distance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected lines and increases the total availability of a power system.
The fault locator is started with the input CALCDIST to which trip signals indicating
in-line faults are connected, typically distance protection zone 1 and accelerating zone
or the line differential protection. The disturbance report must also be started for the
same faults since the function uses pre- and post-fault information from the trip value
recorder function (TVR).
Beside this information the function must be informed about faulted phases for correct
loop selection (phase selective outputs from differential protection, distance
protection, directional OC protection etc). The following loops are used for different
types of faults:
The distance to the fault, which is calculated with a high accuracy, is stored together
with the recorded disturbances. This information can be read on the LHMI, uploaded
to PCM 600 and is available on the station bus according to IEC 61850 and according
to IEC 60870-5-103.
The distance to fault can be recalculated on the LHMI by using the measuring
algorithm for different fault loops or for changed system parameters.
The parameters for the fault locator function are set via the local HMI or Protection
and Control IED Manager (PCM 600).
The Fault Locator algorithm uses phase voltages, phase currents and residual current
in observed bay (protected line) and residual current from a parallel bay (line which
is mutual coupled to protected line).
The Fault Locator has close connection to the Disturbance Report function. All
external analog inputs (channel 1-30), connected to the Disturbance Report function,
are available to the Fault Locator and the function uses information calculated by the
Trip Value recorder. After allocation of analog inputs to the Disturbance Report
function, the user has to point out which analog inputs to be used by the Fault Locator.
According to the default settings the first four analog inputs are currents and next
three are voltages in the observed bay (no parallel line expected since chosen input
is set to zero). Use the Parameter Setting tool within PCM 600 for changing analog
configuration.
The list of parameters explains the meaning of the abbreviations. Figure 102 also
presents these system parameters graphically. Note, that all impedance values relate
to their primary values and to the total length of the protected line.
R0L+jX0L
R1L+jX1L
R1A+jX1A R1B+jX1B
Z0m=Z0m+jX0m
R0L+jX0L
R1L+jX1L en05000045.vsd
DRP
FL
Figure 102: Simplified network configuration with network data, required for set‐
tings of the fault location-measuring function.
For a single-circuit line (no parallel line), the figures for mutual zero-sequence
impedance (X0M, R0M) and analog input are set at zero.
Power system specific parameter settings shown in table 2 are not general settings
but specific setting included in the setting groups i.e. this makes it possible to change
conditions for the fault locator with short notice by changing setting group.
The source impedance is not constant in the network. However, this has a minor
influence on the accuracy of the distance-to-fault calculation, because only the phase
angle of the distribution factor has an influence on the accuracy. The phase angle of
the distribution factor is normally very low and practically constant, because the
positive-sequence line impedance, which has an angle close to 90°, dominates it.
Always set the source impedance resistance to values other than zero. If the actual
values are not known, the values that correspond to the source impedance
characteristic angle of 85° give satisfactory results.
Table 79: Parameter group settings for the LMBRFLO (FLO1-) function
Parameter Range Step Default Unit Description
R1A 0.001 - 1500.000 0.001 2.000 ohm/p Source resistance A
(near end)
X1A 0.001 - 1500.000 0.001 12.000 ohm/p Source reactance A
(near end)
R1B 0.001 - 1500.000 0.001 2.000 ohm/p Source resistance B
(far end)
X1B 0.001 - 1500.000 0.001 12.000 ohm/p Source reactance B
(far end)
R1L 0.001 - 1500.000 0.001 2.000 ohm/p Positive sequence
line resistance
X1L 0.001 - 1500.000 0.001 12.500 ohm/p Positive sequence
line reactance
R0L 0.001 - 1500.000 0.001 8.750 ohm/p Zero sequence line
resistance
X0L 0.001 - 1500.000 0.001 50.000 ohm/p Zero sequence line
reactance
R0M 0.000 - 1500.000 0.001 0.000 ohm/p Zero sequence
mutual resistance
X0M 0.000 - 1500.000 0.001 0.000 ohm/p Zero sequence
mutual reactance
LineLength 0.0 - 10000.0 0.1 40.0 km Length of line
4.13.5.1 Application
The functions MMXU (SVR, CP and VP), MSQI (CSQ and VSQ) and MVGGIO
(MV) are provided with measurement supervision functionality. All measured values
can be supervised with four settable limits, i.e. low-low limit, low limit, high limit
and high-high limit. The measure value expander block (XP) has been introduced to
be able to translate the integer output signal from the measuring functions to 5 binary
signals i.e. below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable
logic.
There are no settable parameters for the measured value expander block function.
Function block name: DRP--, DRA1- – DRA4-, IEC 60617 graphical symbol:
DRB1- – DRB6-
ANSI number:
IEC 61850 logical node name:
ABRDRE
4.13.6.1 Application
To get fast, complete and reliable information about disturbances in the primary and/
or in the secondary system it is very important to gather information on fault currents,
voltages and events. It is also important having a continuous event-logging to be able
to monitor in an overview perspective. These tasks are accomplished by the
Disturbance Report function and facilitate a better understanding of the power system
behavior and related primary and secondary equipment during and after a disturbance.
An analysis of the recorded data provides valuable information that can be used to
explain a disturbance, basis for change of relay setting plan, improve existing
equipment etc. This information can also be used in a longer perspective when
planning for and designing new installations, i.e. a disturbance recording could be a
part of Functional Analysis (FA).
The Disturbance Report (DRP), always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function blocks i.e.
maximum 30 external analog, 10 internal derived analog and 96 binary signals.
The Disturbance Report function is a common name for several functions i.e.
Indications (IND), Event recorder (ER), Event List (EL), Trip Value recorder (TVR),
Disturbance recorder (DR) and Fault Locator (FL).
Every disturbance report recording is saved in the IED. The same applies to all events,
which are continuously saved in a ring-buffer. The Local Human Machine Interface
(LHMI) is used to get information about the recordings, and the disturbance report
files may be uploaded to the PCM 600 (Protection and Control IED Manager) and
further analysis using the Disturbance Handling tool.
If the IED is connected to a station bus (IEC 61850-8-1), according to IEC 61850,
disturbance recorder and fault location information will be available on the bus. The
same information will be obtainable if IEC 60870-5-103 is used.
The setting parameters for the Disturbance Report function (DRP) are set via the
LHMI or the tool included in PCM 600.
User-defined names of binary and analog input signals can be set using the
configuration and parameter setting tool. The analog and binary signals appear with
their user-defined names. The name is used in all related functions (IND, EL, ER,
TVR and DR).
Figure 103Figure "" shows the relations among Disturbance Report, included
functions and function blocks. EL, ER and IND uses information from the binary
input function blocks (DRB1- 6). TVR uses analog information from the analog input
function blocks (DRA1-3) which is used by FL after estimation by TVR. The DR
function acquires information from both DRAx and DRBx.
DRP- - FL01
A4RADR RDRE FL
Analog signals
Trip Value Rec Fault Locator
DRB1-- 6- Disturbance
Recorder
Event Recorder
Indications
en05000124.vsd
For the Disturbance Report function there are a number of settings which also
influences the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED. The information:
Green LED:
Steady light In Service
Flashing light Internal failure
Dark No power supply
Yellow LED:
Steady light A Disturbance Report is triggered
Flashing light The IED is in test mode
Red LED:
Steady light Triggered on binary signal N with SetLEDN=ON
Operation
The operation of the Disturbance Report function has to be set On or Off. If Off is
selected, note that no disturbance report is registered, and none sub-function will
operate (the only general parameter that influences EL).
Operation=Off:
Operation=On:
• Disturbance report are stored, disturbance data can be read from the LHMI and
from a PC using PCM 600.
• LED information (yellow - start, red - trip) is stored.
• The disturbance summary is automatically scrolled on the LHMI for the two
latest registered disturbances, until cleared.
Every recording will get a number (1 to 65536) which is used as identifier (LHMI,
disturbance handling tool and IEC 61850). An alternative recording identification is
date, time and sequence number. The number is automatically increased by one for
each new recording and is reset to zero at midnight. The maximum number of
recordings stored in the IED is 100 and the oldest will be overwritten when a new
one arrives (FIFO).
Recording times
The different recording times for the disturbance report are set (the pre-fault time,
post-fault time, and limit time). These recording times affect all sub-functions more
or less but not the EL function.
Prefault recording time (PreFaultRecT) is the recording time before the starting point
of the disturbance. The setting should be at least 0.1 s to ensure enough samples for
the estimation of pre-fault values in the Trip Value Recorder function.
Postfault recording time (PostFaultRecT) is the maximum recording time after the
disappearance of the trig-signal (does not influence the TVR-function).
Recording time limit (TimeLimit) is the maximum recording time after trig. The
parameter limits the recording time if some trigging condition (fault-time) is very
long or permanently set (does not influence the TVR-function).
PostRetrig = Off
The function is insensitive for new trig signals during post fault time.
PostRetrig = On
The function completes current report and starts a new complete report i.e. the latter
will include:
If the IED is in test mode and OpModeTest=On. The Disturbance Report function
works in normal mode and the status is indicated in the saved recording.
For each of the 96 signals, it is also possible to select if the signal is to be used as a
trigger for the start of the disturbance report and if the trigger should be activated on
positive (1) or negative (0) slope.
OperationN: Disturbance Report may trig for binary input N (On) or not (Off).
TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary input
N.
Analog signals
Up to 40 analog signals can be selected among internal analog and analog input
signals. The configuration tool is used to configure the signals.
The analog trigger of the Disturbance report is not affected if analog input M is to be
included in the disturbance recording or not (OperationM= On/Off).
Sub-function parameters
All functions are in operation as long as the disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of
that particular input, will be fetched and shown in the disturbance summary on the
LHMI. If not set (Hide), status change will not be indicated.
SetLEDN: Set red “Trip” LED on LHMI in front of the IED if binary input N changes
status.
Disturbance recorder
OperationM: Analog channel M is to be recorded by the disturbance recorder (On)
or not (Off).
Event recorder
The ER function has no dedicated parameters.
Event List
The EL function has no dedicated parameters.
Consideration
The density of recording equipment in power systems is increasing, since the number
of modern IEDs, where recorders are included, is increasing. This leads to a vast
number of recordings at every single disturbance and a lot of information has to be
handled if the recording functions don"t have proper settings. The goal is to optimize
the settings in each IED to be able to capture just valuable disturbances and to
maximize the number that"s possible to save in the IED.
The recording time should not be longer than necessary (PostFaultrecT and
TimeLimit).
• Should the function record faults only for the protected object or cover more?
• How long is the longest expected fault clearing time?
• Is it necessary to include reclosure in the recording or should a persistent fault
generate a second recording (PostRetrig)?
• Binary signals: Use only relevant signals to start the recording i.e. protection trip,
carrier receive and/or start signals.
• Analog signals: The level triggering should be used with great care, since
unfortunate settings will cause enormously number of recordings. If nevertheless
analog input triggering is used, chose settings by a sufficient margin from normal
operation values. Phase voltages are not recommended for trigging.
Remember that values of parameters set elsewhere are linked to the information on
a report. Such parameters are, for example, station and object identifiers, CT and VT
ratios.
4.13.7.1 Application
The event list (EL), always included in the IED, logs all selected binary input signals
connected to the Disturbance report function. The list may contain of up to 1000 time-
tagged events stored in a ring-buffer where, if the buffer is full, the oldest event is
overwritten when a new event is logged.
The difference between the event list (EL) and the event recorder (ER) function is
that the list function continuously updates the log with time tagged events while the
recorder function is an extract of events during the disturbance report time window.
The event list information is available in the IED and the user can use the Local
Human Machine Interface (LHMI) to get the information. The list can also be
uploaded from the PCM 600 tool.
The setting parameters for the Event list function (EL) are a part of the Disturbance
report settings.
4.13.8.1 Application
Fast, condensed and reliable information about disturbances in the primary and/or in
the secondary system is important. Binary signals that have changed status during a
disturbance are an example of this. This information is used primarily in the short
term (e.g. immediate disturbance analysis, corrective actions) to get information via
the LHMI in a straightforward way without any knowledge of how to handle the IED.
There are three LED"s on the LHMI (green, yellow and red) which will display status
information about the IED (in service, internal failure etc.) and the Disturbance Report
function (trigged).
The Indication function (IND), always included in the IED, shows all selected binary
input signals connected to the Disturbance Report function that have been activated
during a disturbance. The status changes are logged during the entire recording time,
which depends on the set of recording times (pre-, post-fault and limit time) and the
actual fault time. The indications are not time-tagged.
The indication information is available for each of the recorded disturbances in the
IED and the user may use the Local Human Machine Interface (LHMI) to view the
information.
The setting parameters for LED"s and the Indication function (IND) are a part of the
Disturbance Report settings.
Available signals are identical with the binary signals recorded by the disturbance
report. It is possible to use all binary input signals for the Indication function on the
LHMI, but it is not recommended since the general view will be lost. The intention
is to point out some important signals, not to many, to be shown. If a more thorough
analysis is to be done information from the Event Recorder should be used.
SetLEDN: Set red LED on LHMI in front of the IED if binary input N changes status.
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of
that particular input, will be fetched and shown on the LHMI. If not set (Hide), status
change will not be indicated.
4.13.9.1 Application
Quick, complete and reliable information about disturbances in the primary and/or in
the secondary system is vital e.g. time tagged events logged during disturbances. This
information is used for different purposes in the short term (e.g. disturbance analysis,
corrective actions) and in the long term (e.g. disturbance analysis, statistics and
maintenance, i.e. Functional Analysis).
The event recorder (ER), always included in the IED, logs all selected binary input
signals connected to the Disturbance Report function. Each recording can contain up
to 150 time-tagged events. The events are logged during the total recording time,
which depends on the set of recording times (pre-, post-fault and limit time) and the
actual fault time. During this time, the first 150 events for all 96 binary signals are
logged and time-tagged.
The event recorder information is available for each of the recorded disturbances in
the IED and the user may use the Local Human Machine Interface (LHMI) to get the
information. The information is included in the disturbance recorder file, which may
be uploaded to the PCM 600 (Protection and Control IED Manager) and further
analyzed using the Disturbance Handling tool.
The setting parameters for the Event Recorder (ER) function are a part of the
Disturbance Report settings.
4.13.10.1 Application
Fast, complete and reliable information about disturbances such as fault currents and
voltage faults in the power system is vital. This information is used for different
purposes in the short perspective (e.g. fault location, disturbance analysis, corrective
actions) and the long term (e.g. disturbance analysis, statistics and maintenance, i.e.
Functional Analysis).
The trip value recorder (TVR), always included in the IED, calculates the values of
all selected external analog input signals (channel 1-30) connected to the Disturbance
Report function. The estimation is performed immediately after finalizing each
recording and available in the Disturbance Report. The result is magnitude and phase
angle before and during the fault for each analog input signal.
The information is used as input to the fault location function (FL), if included in the
IED and in operation.
The trip value recorder information is available for each of the recorded disturbances
in the IED and the user may use the Local Human Machine Interface (LHMI) to get
the information. The information is included in the disturbance recorder file, which
can be uploaded to the PCM 600 (Protection and Control IED Manager) and further
analyzed using the Disturbance Handling tool.
The trip value function (TVR) setting parameters are a part of the Disturbance Report
settings.
ZeroAngleRef: The parameter defines which analog signal to use as phase angle
reference for all other input signals. It is suggested to point out a sampled voltage
input signal e.g. a line or busbar phase voltage (channel 1-30).
4.13.11.1 Application
To get fast, complete and reliable information about fault current, voltage, binary
signal and other disturbances in the power system is very important. This is
accomplished by the Disturbance Recorder function and facilitates a better
understanding of the behavior of the power system and related primary and secondary
equipment during and after a disturbance. An analysis of the recorded data provides
valuable information that can be used to explain a disturbance, basis for change of
IED setting plan, improvement of existing equipment etc. This information can also
be used in a longer perspective when planning for and designing new installations,
i.e. a disturbance recording could be a part of Functional Analysis (FA).
The Disturbance Recorder (DR), always included in the IED, acquires sampled data
from all selected analog input and binary signals connected to the function blocks i.e.
maximum 30 external analog, 10 internal (derived) analog and 96 binary signals.
The disturbance recorder information is saved for each of the recorded disturbances
in the IED and the user may use the Local Human Machine Interface (LHMI) to get
some general information about the recordings. The disturbance recording
information is included in the disturbance recorder files, which may be uploaded to
the PCM 600 (Protection and Control IED Manager) for further analysis using the
Disturbance Handling tool. The information is also available on a station bus
according to IEC 61850 and according to IEC 60870-5-103.
The setting parameters for the Disturbance Recorder function (DR) is a part of the
Disturbance Report settings.
4.14 Metering
4.14.1.1 Application
The pulse counter logic function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIM), and
read by the pulse counter function. The number of pulses in the counter is then
reported via the station bus to the substation automation system or read via the station
monitoring system as a service value. When using IEC 61850, a scaled service value
is available over the station bus.
The normal use for this function is the counting of energy pulses from external energy
meters. An optional number of inputs from an arbitrary input module in IED 670 can
be used for this purpose with a frequency of up to 40 Hz. The pulse counter can also
be used as a general purpose counter.
From the Protection and Control IED Manager (PCM 600), these parameters can be
set individually for each pulse counter:
• Operation: Off/On
• tReporting: 0-3600s
• Event Mask: No Events/Report Events
The configuration of the inputs and outputs of the pulse counter function block is
made with the PCM 600 tool.
On the Binary Input Module, the debounce filter time is fixed set to 5 ms, that is, the
counter suppresses pulses with a pulse length less than 5 ms. The input oscillation
blocking frequency is preset to 40 Hz. That means that the counter finds the input
oscillating if the input frequency is greater than 40 Hz. The oscillation suppression
is released at 30 Hz. The values for blocking/release of the oscillation can be changed
in the local HMI and PCM 600 under:
Settings/General settings/I/O-modules
5.1 Overview
5.2.1 Application
IEC 61850–8–1 allows two or more intelligent electronic devices (IEDs) from one
or several vendors to exchange information and to use it in the performance of their
functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–
8–1 standard, allows the IEDs to communicate state and control information amongst
themselves, using a publish-subscribe mechanism. That is, upon detecting an event,
the IED(s) use a multi-cast transmission to notify those devices that have registered
to receive the data. An IED can, by publishing a GOOSE message, report it's status.
It can also request a control action to be directed at any device in the network.
This example shows the topology of an IEC 61850–8–1 configuration. IEC 61850–
8–1 specifies only the interface to the substation LAN. The LAN itself is left to the
system integrator.
Engineering
Station HSI
Workstation Gateway
Base System
SMS
CC
Printer
en06000195.vsd
Station HSI
MicroSCADA
Gateway
GOOSE
IEDName That specific IED name in the IEC 61850–8–1 system However, there are
specific settings for the network interface (Ethernet) that are directly related to the
IEC 61850–8–1 (but not only) in case this protocol is used.
IEC 61850–8–1 specific data (logical nodes etc.) per included function in an IED can
be found iin a separate document, refer to section "Related documents".
5.2.3.1 Application
The SPGGIO function block is used to send one single logical output to other systems
or equipment in the substation. It has one visible input, that should be connected in
CAP and one (invisible) output, that sends the information over IEC 61850–8–1.
There are no settings available for the user for SPGGIO. However, to get the signals
sent by SPGGIO one must use the engineering tools described in chapter
"Engineering of the IED".
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
5.2.4.1 Application
The MVGGIO function block is used to send the instantaneous value of an analog
output to other systems or equipment in the substation. It can also be used inside the
same IED, to attach a “RANGE” aspect to an analog value and to permit measurement
supervision on that value.
The settings available for the MVGGIO function allows the user to choose a deadband
and a zero deadband for the monitored signal. Values within the zero deadband are
considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low
and low-low ranges of the measured value. The actual range of the measured value
is shown on the range output of the MVGGIO function block. When a measured value
expander block (RANGE_XP) is connected to the range output, the logical outputs
of the RANGE_XP are changed accordingly.
5.3.1 Application
Gateway
Star coupler
RER 111
en05000663.vsd
An optical network can be used within the Substation Automation system. This
enables communication with the IED 670s through the LON bus from the operator’s
workplace, from the control center and also from other IEDs via bay-to-bay horizontal
communication.
The fiber optic LON bus is implemented using either glass core or plastic core fiber
optic cables.
The HV Control 670 software module is included in the LIB 520 high-voltage process
package, which is a part of the Application Software Library within MicroSCADA
applications.
The HV Control 670 software module is used for control functions in IED 670s. This
module contains the process picture, dialogues and a tool to generate the process
database for the control application in MicroSCADA.
Use the LNT, LON Network Tool to set the LON communication. This is a software
tool applied as one node on the LON bus. In order to communicate via LON, the IEDs
need to know which node addresses the other connected IEDs have, and which
network variable selectors should be used. This is organized by the LNT.
The node address is transferred to the LNT via the local HMI by setting the parameter
ServicePinMsg=YES. The node address is sent to the LNT via the LON bus, or the
LNT can scan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s.This
can be changed by the LNT.
5.4.1 Application
The communication protocol SPA is available for the IED 670 products as an option
and as an alternative to IEC 60870-5-103. The same communication port as for IEC
60870-5-103 is used.
SPA communication is applied when using the front communication port. For this
purpose, no serial communication module is required in the IED. Only the PCM 600
software in the PC and a crossed-over Ethernet cable for front connection is required.
When communicating with a PC see figure 107, using the rear SPA port on the serial
communication module (SLM), the only hardware required for a local monitoring
system is:
A remote monitoring system for communication over the public telephone network
also requires telephone modems and a remote PC.
The software required for a local monitoring system is PCM 600, and for a remote
monitoring system it is PCM 600 in the remote PC only.
Remote monitoring Local monitoring
system with system with
PCM600 PCM600
Teleph Teleph
one one
modem modem
Optical to electrical
converter, e.g. SPA-ZC 22
or Fiberdata modem en05000672.vsd
When communicating with a PC connected to the utility substation LAN, via WAN
and the utility office LAN (see figure 2), and using the rear Ethernet port on the optical
Ethernet module (OEM), the only hardware required for a station monitoring system
is:
Utility LAN
Remote
monitoring
system with
PCM600
WAN
Substation LAN
en05000715.vsd
Figure 108: SPA communication structure for a remote monitoring system via a
substation LAN, WAN and utility LAN.
The SPA communication is mainly used for the Station Monitoring System. It can
include different numerical relays/terminals/IEDs with remote communication
possibilities. Connection to a personal computer (PC) can be made directly (if the PC
is located in the substation) or by telephone modem through a telephone network with
ITU (former CCITT) characteristics or via a LAN/WAN connection.
Functionality
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The
communication is based on a master-slave principle, where the IED is a slave and the
PC is the master. Only one master can be applied on each fiber optic loop. A program
is required in the master computer for interpretation of the SPA-bus codes and for
translation of the data that should be sent to the IED.
The specification of the SPA protocol V2.5 is available as a separate document, SPA-
bus Communication Protocol V2.5, 1MRS 750076-MTD EN
The SPA and the IEC use the same rear communication port. To define the protocol
to be used, a setting is done on the local HMI. Refer to the ”Installation and
commissioning manual” for setting procedure.
When the communication protocol has been selected, the power to the IED must be
switched off and on.
The most important settings in the IED for SPA communication are the slave number
and baud rate (communication speed). These settings are absolutely essential for all
communication contact to the IED.
These settings can only be done on the local HMI for rear channel communication
and for front channel communication.
The slave number can be set to any value from 1 to 899, as long as the slave number
is unique within the used SPA loop.
The baud rate, which is the communication speed, can be set to between 300 and
38400 baud. The baud rate should be the same for the whole station, although different
baud rates in a loop are possible. If different baud rates in the same fibre optical loop
are used, consider this when making the communication setup in the communication
master, the PC.
For local fibre optic communication, 19200 or 38400 baud is the normal setting. If
telephone communication is used, the communication speed depends on the quality
of the connection and on the type of modem used. But remember that the IED does
not adapt its speed to the actual communication conditions, because the speed is set
on the HMI of the IED.
5.5.1 Application
The communication protocol IEC 60870-5-103 is available for the IED 670 products
as an option.
TCP/IP
Control Center
Station HSI
Gateway
Star coupler
RER 123
en05000660.vsd
The IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
Functionality
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology
a primary station is a master and a secondary station is a slave. The communication
is based on a point-to-point principle. The master must have software that can interpret
the IEC 60870-5-103 communication messages. For detailed information about IEC
60870-5-103, refer to the “IEC60870 standard” part 5: “Transmission protocols”,
and to the section 103: “Companion standard for the informative interface of
protection equipment”.
Design
General
The protocol implementation in IED 670 consists of the following functions:
• Event handling
• Report of analog service values (measurands)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization
Hardware
When communicating locally with a Personal Computer (PC) or a Remote Terminal
Unit (RTU) in the station, using the SPA/IEC port, the only hardware needed is:·
Optical fibres, glass/plastic· Opto/electrical converter for the PC/RTU· PC/RTU
Commands
The commands defined in the IEC 60870-5-103 protocol are represented in a
dedicated function blocks. These blocks have output signals for all available
commands according to the protocol.
Function block with defined IED functions in control direction, I103IEDCMD. This
block use PARAMETR as FUNCTION TYPE, and INFORMATION NUMBER
parameter is defined for each output signal.
Function block with pre defined functions in control direction, I103CMD. This block
includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER
parameter is defined for each output signal.
Function block with user defined functions in control direction, I103UserCMD. These
function blocks include the FUNCTION TYPE parameter for each block in the private
range, and the INFORMATION NUMBER parameter for each output signal.
Status
The events created in the IED available for the IEC 60870-5-103 protocol are based
on the:
Function block with defined IED functions in monitor direction, I103IED. This block
use PARAMETER as FUNCTION TYPE, and INFORMATION NUMBER
parameter is defined for each input signal.
Function blocks with user defined input signals in monitor direction, I103UserDef.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each input
signal.
Function block with defined functions for earth fault indications in monitor direction,
I103EF. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Function block with defined functions for fault indications in monitor direction,
I103FltDis. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal. This block
is suitable for distance protection function.
Function block with defined functions for fault indications in monitor direction,
I103FltStd. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal.
This block is suitable for line differential, transformer differential, over-current and
earth-fault protection functions.
Measurands
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to the
standard.
Function block that reports all valid measuring types depending on connected signals,
I103Meas.
Fault location
The fault location is expressed in reactive ohms. In relation to the line length in
reactive ohms, it gives the distance to the fault in percent. The data is available and
reported when the fault locator function is included in the IED.
Disturbance Recordings
• The transfer functionality is based on the Disturbance recorder function. The
analog and binary signals recorded will be reported to the master by polling. The
eight last disturbances that are recorded are available for transfer to the master.
A file that has been transferred and acknowledged by the master cannot be
transferred again.
• The binary signals that are reported by polling are those that are connected to the
disturbance function blocks DRB1 – DRB6. These function blocks include the
function type and the information number for each signal. See also the description
of the Disturbance report in the “Technical reference manua”l. The analog
channels, that are reported, are those connected to the disturbance function blocks
DRA1 – DRA4. The eight first ones belong to the public range and the remaining
ones to the private range.
Settings
When the communication protocols have been selected, the IED is automatically
restarted.
The settings for communication parameters slave number and baud rate can be found
on the local HMI at:
The baud rate, the communication speed, can be set either to 9600 bits/s or 19200
bits/s.
In addition there is a setting on each event block for function type. Refer to description
of the “Main Function type set on the local HMI”.
Commands
As for the commands defined in the protocol there is a dedicated function block with
eight output signals. Using the CAP 531 tool makes the configuration of these signals.
To realize the BlockOfInformation command, which is operated from the local HMI,
the output BLKINFO on the IEC command function block ICOM has to be connected
to an input on an event function block. This input shall have the information number
20 (monitor direction blocked) according to the standard.
Disturbance Recordings
For each input of the Disturbance recorder function there is a setting for the
information number of the connected signal. The information number can be set to
any value between 0 and 255.
Furthermore there is a setting on each input of the Disturbance recorder function for
the function type. Refer to description of ”Main Function type set on the local HMI”.
Please see the tables in the “Technical reference manual /Station communication”,
specifying the information types supported by the 670IED products with the
communication protocol IEC 60870-5-103 implemented.
EIA RS-485 is not supported. Glass or plastic fiber should be used. BFOC/2.5 is the
recommended interface to use (BFOC/2.5 is the same as ST connectors). ST
connectors are used with the optical power as specified in standard.
For more information please see the “IEC standard IEC 60870-5-103”.
5.6.1 Application
The single command, 16 signals (CD) is a common function and always included in
the IED.
The IEDs may be provided with a function to receive commands either from a
substation automation system or from the local human-machine interface, HMI. That
receiving function block has outputs that can be used, for example, to control high
voltage apparatuses in switchyards. For local control functions, the local HMI can
also be used. Together with the configuration logic circuits, the user can govern pulses
or steady output signals for control purposes within the IED or via binary outputs.
Figure 110 shows an application example of how the user can, in an easy way, connect
the command function via the configuration logic circuit to control a high-voltage
apparatus. This type of command control is normally carried out by sending a pulse
to the binary outputs of the IED. Figure 110 shows a close operation. An “open
breaker” operation is performed in a similar way but without the synchro-check
condition.
Single
command
function
CDxx Configuration logic circuits
SingleCmdFunc
OUTy
User- &
defined
conditions
Synchro-
check
en04000206.vsd
Figure 110: Application example showing a logic diagram for control of a circuit
breaker via configuration logic circuits.
Figure 111 and figure 112 show other ways to control functions, which require steady
On/Off signals. Here, the output is used to control built-in functions or external
devices.
Single
command
function
CDxx Function n
SingleCmdFunc
Function n CMDOUTy
OUTy
en04000207.vsd
Figure 111: Application example showing a logic diagram for control of built-in
functions.
Single
command
function
CDxx Configuration logic circuits
SingleCmdFunc
Device 1 CMDOUTy
OUTy
User- &
defined
conditions
en04000208.vsd
Figure 112: Application example showing a logic diagram for control of external
devices via configuration logic circuits.
Parameters to be set are MODE, common for the whole block, and CMDOUTy which
includes the user defined name for each output signal. The MODE input sets the
outputs to be one of the types Off, Steady, or Pulse.
• Off, sets all outputs to 0, independent of the values sent from the station level,
that is, the operator station or remote-control gateway.
• Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
• Pulse, gives a pulse with 100 ms duration, if a value sent from the station level
is changed from 0 to 1. That means that the configured logic connected to the
command function block may not have a cycle time longer than the cycle time
for the command function block.
5.7.1 Application
The IED may be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate with
other IEDs, these IEDs have a corresponding Multiple transmit function block with
16 outputs to send the information received by the command block.
5.7.2.1 Settings
The parameters for the multiple command function are set via the Protection and
Control IED Manager (PCM 600)..
The MODE input sets the outputs to be one of the types Off, Steady, or Pulse.
6.1.1 Application
IED 670s can be equipped with communication devices for line differential
communication and/or communication of binary signals between IEDs. The same
communication hardware is used for both purposes.
Sending of binary signals between two IEDs, one in each end of a power line is used
in teleprotection schemes and for direct transfer trips. In addition to this, there are
application possibilities like e.g. blocking/enabling functionality in the remote
substation, changing setting group in the remote IED depending on the switching
situation in the local substation etc.
The LDCM (Line Data Communication Module) has an optical connection such that
two IEDs can be connected over a direct fibre (multimode), as shown in figure 113 .
The protocol used is IEEE/ANSI C37.94. The maximum distance with this solution
is approximately 3 km.
M
CM C
LD
LD
M
CM DC
LD L
en05000526.vsd
Figure 113: Direct fibre optical connection between two IEDs with LDCM.
The LDCM can also be used together with an external optical to galvanic G.703
converter or with an alternative external optical to galvanic X.21 converter as shown
in figure 114. These solutions are aimed for connections to a multiplexer, which in
turn is connected to a telecommunications transmission network (e.g. SDH or PDH).
Multiplexer Multiplexer
Telecom. Network
*) *)
M CM
DC LD
L
M
CM DC
D L
L
When a modem G.703 or X21 is used, the connection between LDCM and the modem
is made with a multimode fibre of max. 3 km length. The IEEE/ANSI C37.94 protocol
is always used between LDCM and the modem.
TerminalNo: This setting assigns a number to the local IED. Up to 256 IEDs can be
assigned unique numbers. For a line differential protection, maximum 6 IEDs can be
included. The possibility to use the large number of IED designations is reserved for
the case where a high security against incorrect addressing in multiplexed systems is
desired.
DiffSync: Here the method of time synchronization, PingPong or GPS, for the line
differential function is selected.
OptoPower: The setting LowPower is used for fibres 0 – 1 km and HighPower for
fibres 1 – 3 km.
TransmCurr: This setting decides which of 2 possible local currents that shall be
transmitted, or if and how the sum of 2 local currents shall be transmitted, or finally
if the channel shall be used as a redundant channel.
In a 1½ breaker arrangement, there will be 2 local currents, and the earthing on the
CTs can be different for these. CT-SUM will transmit the sum of the 2 CT groups.
CT-DIFF1 will transmit CT group 1 minus CT group 2 and CT-DIFF2 will transmit
CT group 2 minus CT group 1.
CT-GRP1 or CT-GRP2 will transmit the respective CT group, and the setting
RedundantChannel makes the channel be used as a backup channel.
CompRange: The set value is the current peak value over which truncation will be
made. To set this value, knowledge of the fault current levels should be known. The
setting is not overly critical as it considers very high current values for which correct
operation normally still can be achieved.
Section 7 Configuration
7.1 Introduction
They show examples of how to connect the primary apparatuses to the IED physical
connections to the IED.
The IED is available to be ordered in three different alternatives with the configuration
suitable for the application. The control application will normally require adaptation
of interlocking signals, mimic adaptation to the specific arrangements etc. as e.g. the
availability of earthing switches varies.
The main protection functions are switched on and fully operative at delivery whereas
back-up functions, not generally used, will be set to Off.
The configuration is done for the complete control and measurement in the bays.
Interlocking is provided and configured to be default done across bays with GOOSE
messaging according to the IEC61850-8-1 standard.
Complete projects are provided with setting, signal matrix, mimic and the application
configuration prepared and for single breaker arrangements multiple feeders and the
bus coupler configurations are available and can simple be downloaded.
Disconnectors and Earthing switches are proposed and foreseen to be switched double
pole to have highest possible security against unnecessary operations due to e.g. a
single earth fault in the control circuit.
All IED’s can be reconfigured with help of the CAP 531 configuration tool, being
part of the PCM platform. This way the IED can be made suitable for special
applications and special logic can be developed i.e. logic for automatic opening of
disconnectors and closing ring bays, automatic load transfer from one busbar to the
other etc.
After calculating the IO need and ordering of the IED the number of IO must be
correctly set-up under the Application configuration tool menu Edit/Function
selector. Include the IO you have in the IED and Save-Compile before you leave CAP
531. This will mean that the available IO will be shown in the Signal matrix tool.
They show examples of how to connect the primary apparatuses to the IED physical
connections.
The configurations are as far as found necessary provided with application comments
to explain why the signals have been connected in the special way. This is of course
for the special application features created, not for “standard” functionality.
7.2.1 Introduction
Configuration 1MRK004500-90
This configuration is used in single breaker arrangements with single or double busbar
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases e.g. with full control of all apparatuses included more IO
cards are required. Our proposal for a full version with control is to use 2 Binary input
modules and 1 Binary output modules.
BUS WA1
BUS WA2
QB1-OPEN BIM:3
QB1-CLOSED BIM:4
QB2-OPEN BIM:5
AIM1:11
BIM:12 MCB-OK
AIM1:12
BIM:13 MCB-OK
-QA1
BOM:4 CLOSE QA1 C
C
BOM:21
S PARE
BOM:22 BOM:1
BOM:24 BOM:3
MAIN 2 TRIP T
C
BIM:1 QA1-OPEN
BIM:2 QA1-CLOSED
SPARE
BIM:15
BIM:16
-T1
P1
AIM1:1-4
BIM:7 QB9-OPEN
BIM:8 QB9-CLOSED
BIM:9 QC9-OPEN
BIM:10 QC9-CLOSED
MCB OR
FUSE
AIM1:7-9
en05000837.eps
Figure 115: Connection diagram for configuration A with the setting and signal
matrix defined.
Configuration 1MRK004500-91
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases e.g. with full control of all apparatuses included more IO
cards are required. Our proposal for a full version with control is to use 2 Binary input
modules and 1 or 2 Binary output modules. For systems without Substation
Automation a second binary output board might be required.
=1-QA1
AIM1:11
C
C
BIM:13 MCB-OK
T
BOM:4 CLOSE QA1 C
BIM:1 QA1-OPEN
BIM:2 QA1-CLOSED
AIM1:1-3
FAULT SIG NA LLING AND SPA RE OUTPUTS
-QB61
MCB OR
FUSE
AIM1:7-9
BOM:17 -QC9
BOM:18
BIM:11
QB9-OPEN -QB9
BIM:12 QB9-CLOSED
BOM:13
+ OPEN QB9
- BOM:23
BOM:14
CLOSE QB9
BOM:24
-T2
AND SPARE INPUTS
P1
FAULT SIG NA LS
BIM:16
AIM1:4-6 -QB62
=2-QA1
BOM:8 CLOSE =2-QA1 C
C
BOM:5
MAIN 2 TRIP T
BIM:6 =2-QA1-OPEN C
BIM:7 =2-QA2-CLOSED
MCB-OK
BIM:15
IRF
X11.1
X11.3
BUS WA2
X11.2 X11.4 5
en05000838.eps
Figure 116: Connection diagram for configuration B with the setting and signal
matrix defined.
Configuration 1MRK004500-92.
This configuration is used in one and a half breaker arrangements for a full bay. The
configuration can of course also be used for a section of the bay with a utilization of
a part of the apparatuses only.
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases e.g. with full control of all apparatuses included more IO
cards are required. Our proposal for a full version with control is to use 3 Binary input
modules and 2 Binary output modules. For systems without Substation Automation
a second binary output board might be required.
=1-QA1
C
AIM1:10 C
BIM:14
MCB-OK T
C
P1
-BI1
AIM1:1-3
=1-QB6
MCB OR
FUSE
AIM1:7-9
=1-QC9
BIM:10
1-QB9 OPEN
BIM:11 1-QB9 CLOSED
=1-QB9
BOM:13
+ OPEN 1-QB9
- BOM:21
BOM:14
CLOSE 1-QB9
BOM:22
-BI1
SIG NALLING
P1
FAULT
BOM:17
AIM1:4-6
BOM:18
3-QA1 OPEN T
BIM:4
C
BIM:5
3-QA1 CLOSED T
C
BIM:12
-QB62
2-QB9 OPEN
BIM:13 2-QB9 CLOSED
BOM:15
+ OPEN 2-QB9
-
BOM:23 =2-QB9
BOM:16 CLOSE 2-QB9 =2-QC9
BOM:24
MCB OR
=2-QB6
AIM1:11
FUSE
BOM:12 CLOSE =2-QA1
BOM:9
MCB OR
AIM1:12 FUSE
=2-BU1
IRF
-QB2
X11.1
X11.3
BIM:15 MCB-OK BUS WA2
X11.2 X11.4 5
en05000839.eps
Figure 117: Connection diagram for configuration C with the setting and signal
matrix defined.
The correct setting of the IED is of vital importance for the correct operation of the
protection function. The examples have been selected from an example power system
as per below figure.
Figure xx. Example network Note that all setting are based on primary values, either
in per unit (percent) of primary base values or as primary values direct, e.g. primary
ohms. The setting examples are typical and selected to show alternatives with
communication schemes, single- and three phase tripping and auto-reclosing, multi-
and single breaker arrangements.
- 400 kV long OH line with multi-breaker arrangement and single phase tripping.
Permissive underreach communication scheme.
Appendix 1
- 400 kV Short cable line with single breaker arrangement and single-phase tripping.
Permissive overreach communication scheme.
Appendix 2
- 132 kV long OH line with double-busbar, single breaker arrangements with three-
phase tripping. Permissive underreach communication scheme.
Appendix 3
The settings of IED670 are shown in examples from a traditional power system. The
following system structure has been defined for the examples.
G 400 kV
15000MVA
230 kV
Z1=0,9+j10.6
Z0=1.0+j12.0 132 kV
Station A
CTs 2000/1 CTs 2000/1A
CVT 400/0,11kV
Load
60 km
Transformers
25 km Sn=500MVA
415/230+/-9*1,67%kV
CTs 1200/1A ek=12%
CVT 230/0,11kV Z0=60ohm (415 base)
CTs 2000/1A Station C
Station E
CTs 1200/1A
CTs 600/1A CTs 1200/1A CVT 230/0,11kV
CVT 230/0,11kV 400 kV OHL data
35 km 80 km 0,014 +j 0,3 ohm/km
70 km 0,16 + j0,9 ohm/km
Transformer 0,09+ + j0,5 ohm/km
Sn=175MVA 300 km
242/132+/-9*1,67%kV
ek=10% Series Capacitor (mid line)
Z0=20ohm (230 base) -j 45 ohm
-j 45 ohm
en05000836.vsd
Figure 118: The typical power network with different objects are examples of how
to set the IED670.
The setting has been performed for the 400kV overhead power line between station
A and C (REL670), for the short 400 kV Cable feeder between station A and B
(RED670), for the Long 230 kV single power line between station A and E (REL670)
and for the short 132 kV power line between station F and G (REL670).
Setting of Transformers in Station C (400/230 kV) and station F 132/20 kV are also
calculated.
The complete setting examples for all IEDs as per above are available in separate
documents, refer to section "Related documents".
Section 9 Glossary
9.1 Glossary
AC Alternating current
A/D converter Analog to digital converter
ADBS Amplitude dead -band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CAP 531 Configuration and programming tool
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined mega pulses per second
CO cycle Close-open cycle
Co-directional Way of transmitting G.703 over a balanced line. Involves two
twisted pairs making it possible to transmit information in both
directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four
twisted pairs of with two are used for transmitting data in both
directions, and two pairs for transmitting clock signals
CPU Central processor unit
CR Carrier receive
CRC Cyclic redundancy check
CS Carrier send
CT Current transformer
CVT Capacitive voltage transformer
DAR Delayed auto-reclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFT Discrete Fourier transform
DIP-switch Small switch mounted on a printed circuit board
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE/ANSI Std.
1379-2000
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler