Fire Dampers Manuals UVS120H 2 Blades LV
Fire Dampers Manuals UVS120H 2 Blades LV
LV
SATURS
1. UGUNSDROŠA VĀRSTA KONSTRUKCIJA UN IZMĒRI ................................................................................................................................3
2. MONTĀŽA ........................................................................................................................................................................................................................5
2.1. Montāža masīvā sienā .........................................................................................................................................................................................5
3. DROŠĪBAS PRASĪBAS.................................................................................................................................................................................................6
4. MONTĀŽA ........................................................................................................................................................................................................................7
4.1. Signāla ierīču (mikroslēdžu) montāžas instrukcija ugunsdrošības UVS-H vārstiem.................................................................. 11
5. PERIODISKĀS PĀRBAUDES ................................................................................................................................................................................. 13
Taisnstūra ugunsdrošais vārsts UVS120H vārst, kas novērš liesmas un dūmu izplatīšanos gaisavados, saglabajot
konstrukciju. Vārsts ar divām sinhronām lāpstiņām.
2
3
10
9
5
6
7
8
11
9
Rokturis atvertā
pozicijā
H1
Lāpstiņa atvertā
pozicijā
A A
166,4
L 400 L
B 54.2
Bnom Hnom
Hnom 1050 ÷ 1600 Bnom 200 ÷ 1000
115
+10
0
2
Enkurskrūves A
(atbilstoši sienas materiālam)
H+60mm
B+60mm
Atvēruma izmēri
Veicot montāžas, pieslēgšanas vai apkalpošanas darbus, ir jāievēro lokālas darba drošības un aizsardzības prasības.
Ir jāizmanto individuālie darba aizsardzības līdzekļi sekojošo darbu veikšanai: ugunsdroša vārsta elektroinstalācija,
ugunsdroša vārsta mehāniska pieslēgšana gaisa vadam, visu veidu apkalpošanas darbi.
Pirms montāžas uzsākšanas atbildīga persona pārbauda ugunsdroša vārsta tehnisko stāvokli (vai vārsts netika bo-
jāts transportēšanas procesā)!
1. Vairākas reizes nospiežot “Push” pogu pārliecinās, vai vārsta lāpstiņa atveras un aizveras bez aizķeršanās, pretējā ga-
dījumā ir nepieciešams ieeļļot rotācijas mezglus norādītājās vietās:
2. Pirms vārsta montāžas ir jāpārbauda, vai lāpstiņas iznesums netraucēs tā aizvēršanās un atvēršanās procesam gaisa
vadā:
H, mm L, mm
450 15
500 40
550 65
600 80
650 115
700 140
H
750 165
L L
800 190
850 215
900 240
950 265
1000 290
• Kūstošais elements ir
vienreizējas lietošanas
un tas ir jāaizvieto pēc tā
nostrādāšanas.
• Kūstošais elements ir viegli
Lāpstiņa atvērta
pieejams aizvietošanai,
izskrūvējot “Push” pogas
skrūvi un izvelkot ārā
termālās iedarbības
mehānismu.
4. Pamatmehānisms ir jānosedz pirms montāžas darbu uzsākšanas, lai pasargātu no celtniecības putekļu un citu vielu
iedarbības.
+30
0
B+60
Masīvajās sienās
Vārstu ugunsdrošā šķērslī ir jāiemontē tādā veidā, lai pilnībā izslēgtu slodzes ietekmi uz vārstu no norobežojošām konstrukcijām vai
gaisa vadiem!
6. Attālums starp ugunsdrošiem vārstiem, kas iemontēti vienā norobežojošā konstrukcijā, nevar būt mazāks par
200 mm, bet attālums līdz blakus esošai sienai vai pārsegumam nedrīkst būt mazāks par 75 mm. Rekomendē-
jams attālums starp norobežojošo konstrukciju un pamatmehānismu ir 300 mm, lai nodrošinātu piekļuvi apkal-
pošanas darbiem. Vārsta lāpstiņas ass var būt izvietota tikai horizontāli!
≥75
≥200
≥75
8 ... 10 mm
Ir ieteicams izvēlēties ugunsdroša vārsta stiprinājumus, ņemot vērā vārsta svaru, kg:
Bnom
Hnom 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600
200 21.1 21.9 22.5 23.3 23.9 24.7 25.3 26.1 26.7 27.5 28.1 28.8
250 23.1 23.9 24.6 25.3 26.1 27.1 27.7 28.5 29.3 30.0 30.8 31.6
300 25.0 25.9 26.6 27.3 28.3 29.5 30.0 32.9 33.8 34.6 35.4 36.2
350 27.0 27.9 28.7 31.9 32.8 33.7 34.6 35.4 36.3 37.2 38.1 39.0
400 31.1 32.1 33.0 34.0 34.9 36.0 36.9 37.9 38.8 39.8 40.7 41.7
450 33.1 34.2 35.1 36.2 37.2 38.3 39.3 40.3 41.3 42.4 43.3 44.4
500 35.0 36.2 37.2 38.4 39.4 40.5 41.6 42.7 43.8 44.9 45.9 47.1
550 37.0 38.2 39.3 40.5 41.6 42.8 43.9 45.0 46.2 50.6 51.8 52.9
600 38.9 40.1 41.3 42.6 43.7 45.0 49.4 50.7 51.8 53.1 54.3 55.5
650 40.9 42.1 43.4 44.8 49.7 51.0 51.7 53.1 54.3 55.6 56.9 58.1
700 42.8 44.1 48.7 50.1 51.4 52.8 54.0 55.5 56.7 58.1 59.4 60.8
750 44.8 49.3 50.7 52.1 53.5 54.9 56.3 57.8 59.2 60.6 62.0 63.4
800 49.8 51.3 52.7 54.2 55.7 57.2 58.6 60.2 61.6 63.1 64.5 66.0
850 51.5 53.1 54.7 56.2 57.8 59.2 60.9 62.6 64.1 65.6 67.1 68.7
900 53.2 54.9 56.5 58.1 59.8 61.2 63.2 65.0 66.5 68.1 69.6 71.3
950 55.0 56.7 58.4 60.2 61.9 63.3 65.5 67.3 69.0 70.6 72.2 74.0
1000 56.7 58.6 60.4 62.2 64.0 65.4 67.8 69.7 71.4 73.1 74.7 76.6
Tā kā pēc ugunsdroša vārsta montāžas ir nepieciešams veikt periodiskās pārbaudes, ir nepieciešams nodrošināt piekļuvi tā
pamatmehānismam un paredzēt vismaz vienu revīzijas lūku.
8. Nepieciešams pārbaudīt, vai ugunsdrošs vārsts ir stingri iemontēts norobežojošā konstrukcijā, vai kūstošais elements
un sviras nav deformētas un vārsta lāpstiņa aizveras bez aizķeršanās, vairākas reizes nospiežot pārbaudes “Push”
pogu. Lāpstiņai jābūt aizvērtai pilnībā.
9. Kad vārsts ir iemontēts un pārbaudīts, ir nepieciešams pārliecināties, ka tā lāpstiņa ir atstāta normālā darba pozīcijā
jeb ir atvērta.
10. Vārsta montāžas laikā ir jāievēro lokālās darba aizsardzības un ugunsdrošības likumdošanas prasības.
11. Vārsta pamatmehānismam ir iespējams pieslēgt mikroslēdžus, ar kuru palīdzību var attālināti kontrolēt lāpstiņas pozīcijas
stāvokli. Tikai vienas gala pozīcijas kontrolei (atvērta vai aizvērta lāpstiņa) ir nepieciešams viens mikroslēdzis, abu gala po-
zīciju identificēšanai ir nepieciešami divi mikroslēdži. Mikroslēdžu montāžai uz pamatmehānisma ir nepieciešams noņemt
rokturi un vāciņu ar “Komfovent” uzrakstu, izskrūvējot DIN 912 skrūvi. Zem vāciņa atrodas mikroslēdžu pozicionēšanas
ligzdas. Komplektā ar mikroslēdžiem nāk arī plastmasas izciļņripa, kuru nepieciešams uzstādīt lāpstiņas asī.
Montāža:
NC
2
DARBĪBAS GADĪJUMĀ, JA MIKROSLĒDŽU PLĀKSNES Normally Open
ATLOCĪTAS NEPIETIEKOŠI:
1 NO
3
COM
Common
parādīts attēlā:
3-5°
Instuments:
3-30 V 3-30 V
GADĪJUMĀ, JA TIEK PIEFIKSĒTA VISMAZ VIENA NO ZEMĀK MINĒTAM NEATBILSTĪBĀM, IR AIZLIEGTS EKSPLOTĒT,
LĪDZ TĀS NOVĒRŠANAI:
• REVĪZIJAS LŪKA NAV PIEEJAMA VAI NAV IERĪKOTA;
• VĀRSTA LĀPSTIŅA IR NOBLOĶĒTA ATVĒRTĀ POZĪCIJĀ;
• VĀRSTA KORPUSS TIKA DEFORMĒTS MONTĀŽAS PROCESĀ;
• VĀRSTS IR IEBŪVĒTS, NEIEVĒROJOT RAŽOTĀJA MONTĀŽAS NORĀDĪJUMUS;
• STIPRINĀJUMI, KURUS IZMANTOJA VĀRSTA MONTĀŽAI, BLOĶĒ LĀPSTIŅAS KUSTĪBU;
• SPRAUGAS STARP VĀRSTA KORPUSU UN NOROBEŽOJOŠO KONSTRUKCIJU ATSTĀTAS NEAIZPILDĪTAS;
• VĀRSTS IR IEMONTĒTS ĀRPUS SIENAS NO NOROBEŽOJOŠĀS KONSTRUKCIJAS, NEVIS TĀJĀ;
• BŪVNIECĪBAS PUTEKĻI VAI BŪVGRŪŽI NAV NOTĪRĪTI NO VĀRSTA IEKŠĒJĀM UN ĀRĒJĀM VIRSMĀM;
• PIEDZIŅA (KUR TIEK IZMANTOTA) NETURAS CIEŠI UZ STIPRINĀŠANAS KRONŠTEINA;
• GAISA VADĀ VAI CAUR UGUNSDROŠO VĀRSTU IEMONTĒTAS CITAS KOMUNIKĀCIJAS.
Saskaņā ar LVS EN 15650:2010 standarta prasībām vārsta apkalpošanu ir jāveic vismaz reizi pusgadā.
Zemāk ir atrodama Komfovent rekomendējamā ugunsdroša vārsta apkalpošanas veidlapa.
Periodiskās
1. gads 2. gads 3. gads 4. gads 5. gads
pārbaudes gads
Pārbaudes datums 01.01.21
Pārbaudes veicējs
Montāžas datums:
Pārbaudes veicējs/datums: UGUNSDROŠO VĀRSTU
Apliecināja: PERIODISKĀS PĀRBAUDES
Ugunsdrošā vārsta uzskaites Nr. FD25
Komentāri
SIA KOMFOVENT